Strebel S-HQ, SHQ25s, SHQ38s, SHQ51s, SHQ60s Installation Instructions Manual

...
Installation Instructions Strebel Q-boiler range
2
Central heating on / off
Domestic hot water (DHW) on / off
Pump programme on / off
Reset key Unlocking the boiler
in case of error
display
Explanations of symbols and signs on the Control Tower display.
1 2
No heat requirement Ventilation phase Ignition phase Burner active on central heating Burner active on hot water Fan check Burner off when room thermostat is demanding Pump overrun phase for central heating Pump overrun phase for hot water Burner off because of to high flow water temperature Automatic venting programme
3 4 5
6 7 8 9 A
Water pressure is to low (<1,0 bar), flashing FILL will alternate with indication of water pressure, boiler power of 50% is possible. The installation needs to be
topped up.
Operation indication
(in the first display position by technical read out)
Mode key Selecting chapters
Water pressure is to high (>2,8 bar), if HIGH indication remains continuously visible, the boiler is taken out of operation. The installation pressure needs to be decreased by draining water.
Water pressure is to low (<0,7 bar), FILL indication remains continuously visible, the boiler is taken out of operation. The installation needs to be topped up.
0
From Good-read out to Technical read out (and vice versa):
- Press 5 sec. on the STEP key.
Installation Instructions Strebel Q-boiler range
3
Content
Declaration of conformity ............................................................................................................. 3
1 Introduction .................................................................................................................................. 4
2 Regulations .................................................................................................................................. 4
3 Scope of the supply...................................................................................................................... 6
4 Description of the boiler ............................................................................................................... 6
5 Mounting the boiler....................................................................................................................... 6
5.1 Dimensions ....................................................................................................................... 7
6 Connecting the boiler ................................................................................................................... 9
6.1 Central heating system ..................................................................................................... 9
6.2 Expansion vessel ............................................................................................................ 11
6.2.1 Expansion vessel module ............................................................................................... 12
6.3 Underfloor heating system (plastic pipes) ....................................................................... 13
6.4 Gas connection ...............................................................................................................13
6.5 Hot water supply .............................................................................................................13
6.6 Condensation drain pipe ................................................................................................. 14
6.7 Flue gas exhaust system and air supply system............................................................. 15
6.7.1 Dimensions of the flue gas and air intake duct................................................................ 18
7 External hot water cylinders ....................................................................................................... 19
8 Electrical connection .................................................................................................................. 20
9 Boiler controls ............................................................................................................................ 22
9.1 Explanation of the function keys ..................................................................................... 23
10 Filling and venting the boiler and installation.............................................................................. 24
10.1 Hot water supply ............................................................................................................. 24
11 Commissioning the boiler........................................................................................................... 25
11.1 Central heating system ................................................................................................... 25
11.2 Hot water supply ............................................................................................................. 25
11.3 Adjustments .................................................................................................................... 26
11.4 Activating factory settings (green key function)............................................................... 28
12 Isolating the boiler ..................................................................................................................... 29
13 Commissioning........................................................................................................................... 29
13.1 Checking for contamination............................................................................................. 29
13.2 Checking of the zero pressure control ............................................................................ 30
13.3 Checking the CO2............................................................................................................ 31
14 Maintenance............................................................................................................................... 32
14.1 Frequency of maintenance.............................................................................................. 32
14.2 Maintenance activities..................................................................................................... 33
14.3 Warranty ......................................................................................................................... 33
15 Technical specifications ............................................................................................................. 34
16 Parts of the boiler ....................................................................................................................... 35
17 Installation examples.................................................................................................................. 36
17.1 Radiator installation without thermostatic radiator valves................................................ 36
17.2 Radiator installation with underfloor heating zone........................................................... 37
18 Error indication ........................................................................................................................... 38
19 Declaration of conformity ........................................................................................................... 39
The appliance should only be installed by a Competent Gas Installer. Work on the boiler must be carried out by a competent person, (Ref: Gas Safety Installation and Use ) using correctly calibrated instruments with current test certification.
Installation Instructions Strebel Q-boiler range
4
1 Introduction
These instructions describe the functioning, installation, use and primary maintenance of STREBEL central heating units for the United Kingdom and Ireland. Where necessary the different regulations for each country are separately described.
These instructions are intended for the use by Corgi registered installers or registered Bord Gais installers in connection with the installation and putting into operation of STREBEL units. It is advisable to read these instructions thoroughly, well in advance of installation. Separate instructions for use are supplied with the unit for users of STREBEL central heating units. STREBEL is not liable for the consequences of mistakes or shortcomings which have found their way into the installation instructions or user’s manual. Further, STREBEL reserves the right to alter its products without prior notification.
When delivering the unit, give the customer clear instructions concerning its use; present the customer with the user’s manual and card.
Each unit is fitted with an identification plate. Consult the details on this plate to verify whether the unit is compliant with its intended location, e.g.: gas type, power source and exhaust classification.
Relevant Installation, Service and User manuals:
- BrainQ Digital room thermostat
- MadQ Cascade-/Zone controller
2 Regulations
The following regulations apply to installation of STREBEL central heating units: Legislation and Regulations.
Gas Safety (Installation and Use). All gas appliances must by law, be installed by a competent person, eg. Members of CORGI and in accordance with the current Gas Safety Regulation. Failure to install appliance correctly could lead to prosecution.
In addition to the above regulations this appliance must be installed in compliance with the current IEE Regulations, the Building Standards (Scotland Consolidation) Regulations. Regulations and bye laws of the Local Water Authority and the Current Health and Safety Regulation.
The current, Electricity at Work Regulation must be complied with and also be in accordance with the relevant and current editions of the British Standards.
The STREBEL S-HQ boiler is a certified appliance and must not be modified or installed in any way contrary to this Installation Manual. Manufacturers instructions must not be taken in any way as overriding statutory obligations.
Installation Instructions Strebel Q-boiler range
5
The STREBEL S-HQ is a central heating unit with an optional integrated hot water function. These units must be connected according to these instructions and all installation norms in respect of the part of the unit to be connected.
Observe the following rules of safety:
- All work on the unit must take place in a dry environment.
- STREBEL units may never be in operation without their housing, except in connection with maintenance or adjustments (see Chapter 13 and 14).
- Never allow electrical or electronic components to come into contact with water.
Carry out the following tasks in connection with maintenance, etc. to an already-
installed unit:
- Shut down all programmes
- Close the gas tap
- Remove the plug from the wall socket
- Close the stop cock of the unit’s intake connection
Take note of the following when maintenance or adjustments are needed:
- The unit must be able to function during these activities; for this reason, the unit’s supply voltage, gas pressure and water pressure must be maintained. Ensure that these is not a source of potential danger during these activities.
Following maintenance or other activities; always check the installation of all parts through which gas flows (using leak-search spray).
Following maintenance or other activities, always replace the housing and secure it with the screw behind the door at the front of the casing.
The following (safety) symbols may be encountered in these installation instructions and on the unit:
This symbol indicates that the unit must be stored away from frost.
This symbol indicates that the packaging and/or contents can be damaged as a result of insufficient care taken during transport.
This symbol indicates that, whilst still in its packaging, the unit must be protected from weather conditions during transport and storage.
KEY-symbol. This symbol indicates that assembly or dismantling, must be carried out.
ATTENTION symbol. This symbol indicates that extra attention must be paid in connection with a particular operation.
Useful tip or advice
Installation Instructions Strebel Q-boiler range
6
3 Scope of the supply
The boiler is supplied ready for use. The supply kit is composed as follows:
Boiler with casing; Template on the package wrapper;
Automatic vent (inside the boiler); Installation instructions
Safety valve (inside the boiler); Operating manual;
Suspension bracket Warranty card;
Draining valve with T-piece; Benchmark logbook.
Fixing material consisting of plugs and screws;
4 Description of the boiler
The STREBEL S-HQ boiler is a room sealed, condensing and modulating central heating boiler, with or without an integrated hot water facility.
The boiler is provided with a compact stainless steel heat exchanger with smooth tubes. A well thought out principal using durable materials. The boiler burns gas for supplying warmth. The heat is transferred in the heat exchanger to the water in the central heating system. By cooling down the flue gasses condensate is formed. This results in high efficiency. The condensate, which has no effect on the heat exchanger and the function of the boiler, is drained through an internal siphon.
The boiler is provided with an intelligent control system (CMS Control Management System). The boiler anticipates the heat demand of the central heating system or the hot water facility.
When an outside sensor is connected to the boiler works weather dependantly. This means that the boiler control measures the outside temperature and flow temperature. With this data the boiler calculates the optimal flow temperature for the installation.
Explanation of the type indication: STREBEL Q 51C
Q = Type 51 = Nominal load in kW C = Combi (S = Solo)
Room sealed boiler
The boiler retreives its combustion air from outside then discharges the flue gasses to the outside.
Condensing
Retrieves heat from the flue gasses. Water condensates on the heat exchanger.
Modulating
Higher or lower burning according to the heat demand.
Stainless Steel
Super solid kind of steel which keeps its quality for life. It will not rust or erode in con­trast to composition materials, like alumi­nium.
Installation Instructions Strebel Q-boiler range
7
5 Mounting the boiler
The room where the boiler will be placed must always be frost free. It is NOT necessary to have a purpose provided air vent in the room or internal space in
which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the extremely low surface temperature of the boiler casing during operation. Therefore the requirements of BS 6798, Clause 12, and BS5440:2 may be disregarded.
The boiler can be mounted practically to any wall with the suspension bracket and the enclosed fixing equipment. The wall must be flat and of sufficient strength in order to be able to carry the boiler weight with its water content. Above the boiler there must be at least 250 mm working space in order to be able to fit a coaxial flue system or a twin supply. On the left side of the boiler at least 50 mm and on the right side 10 mm must be reserved to allow fitting or removing of casing. The location of the boiler can be determined by using the template located inside the boiler packaging.
Lift the boiler only by the boilers rear wall
Installation Instructions Strebel Q-boiler range
10
6 Connecting the boiler
The boiler has the following connection pipes;
- The central heating pipes.
These can be connected to the installation by means of compression fittings;
- The gas pipe.
It is provided with a female thread into which the tail piece of the gas valve can be screwed;
- The condensation drain pipe.
It consists of an oval 24 mm plastic pipe. The drain pipe can be connected to this by means of an open connection. If the open connection is fitted in a different location, then the pipe can be lengthened by means of a 32 mm PVC sleeve;
- The flue gas exhaust system and air supply system.
It consists of a concentric connection 80/125 mm.
- Cold and hot water pipes. Only Combi boilers: These consist of 15 mm copper pipe and can be connected to the installation by means of compression fittings.
It is recommended that isolation valves are fitted to all heating and hot water connections to facilitate ease of future maintenace.
It is advisable to spray-clean all of the unit’s connecting pipes and/or to spray-clean/blow-clean the installation before connecting it to the unit.
6.1 Central heating system
Connect the central heating system according to the actual regulations. The boiler pipes can be connected to the installation by means of compression fittings.
Reducers should be used for connecting to thick-walled pipe (welded or threaded).
When removing the plastic sealing caps from the pipes, contaminated testing water can be released.
The boiler has a self-adjusting and self-protecting control system for the load and the pump capacity. By this means the temperature difference between the flow and return water is checked. Table 3 shows the water displacement which supplies th e circulation pump at certain installation resistance.
A low velocity header must be connected to the Q51C, Q51S and Q60S to prevent flow problems over the boiler.
STREBEL supplies the AA1OV09U Low velocity header for 1 boiler. This can be connected directly under the boiler on the flow and return pipe.
Boiler type pump type water flow rate permissible installation
resistance
UPER l/min l/h kPa mbar
Combi
Q25C
20-60 16,2 972 29 290
Q38C
20-70 24,6 1478 20 200
Q51C
20-70 30,1 1803
Solo
Q25S
20-60 9,7 583 47 470
Q25S
20-60 1 6,2 972 32 320
Q38S
20-70 24,6 1478 22 220
Q51S
20-7030,11803
Q60S
20-70 38,9 2333
Installation resistance table 3
Installation Instructions Strebel Q-boiler range
12
6.2 Expansion vessel
The central heating system must be provided with an expansion vessel. The expansion vessel which is used should be geared to the water content of the installation. The pre­charge pressure depends on the installation height above the mounted expansion vessel. See table 4.
All Combi boilers are provided with an expansion vessel connection. This pipe is connected with the three way valve and boiler pump. This prevent the expanding water, during hot water production, is being closed off from the expansion vessel, when the thermostatic radiator valves are fully closed. A second expansion vessel in the installation is not a problem.
In connection with correct functioning of the boiler it is necessary for the expansion vessel to be connected to the expansion vessel pipe of the boiler.
The Solo boilers are not provided with an expansion vessel connection. When one of these Solo boilers is combined with a cylinder then one has to take into account that the expansion vessel should be connected between the three-way valve and the boiler circulation pump.
choice of expansion vessel table 4
insta lla tio n height a bove
the expansion vessel
pre-charge pressure
of the expansion vessel
5 m 0,5 bar 10 m 1,0 bar 15 m 1,5 bar
Installation Instructions Strebel Q-boiler range
13
side view of the module with boiler (dimensions in mm) figure 5
540
wall
155
385
front view of the module with boiler (dimensions in mm) figure 6
660
105
6.2 Expansion vessel module
The STREBEL Q25S and Q38S boilers can be provided with an expansion vessel module. By this means the external expansion vessel is not required. This expansion vessel module is placed behind the STREBEL S-HQ boiler, by which means the expansion vessel is not noticeable. The content of the two expansion vessels is 20 litres. The pre-charge pressure is 1 bar.
The expansion vessel module can be supplied with the necessary pipes to connect with the STREBEL S-HQ boiler. The connecting pipes for the installation correspond with those of the boiler and have the same centre-to-centre distance to the wall. When checking the expansion vessels these are accessible via the left, right and upper sides. From these sides the tanks are also removable and the boiler does not have to be dismantled. The space which is required for mounting the expansion vessel module corresponds with the required space for mounting an STREBEL S-HQ boiler. They included template and mounting strip for the boiler which can be used for the expansion vessel module. The boiler is fitted on to this after the expansion vessel module has been mounted. The necessary mounting strip for the boiler is present on the module. Article numbers:
- the expansion vessel module without pipe connections AEM0209U
- pipe connections for expansion vessel module ALE0004U
480
expansion vessel module
figure 4
Loading...
+ 30 hidden pages