STREBEL CIS
ASSEMBLY INSTRUCTIONS FOR: STREBEL CIS
Page 16
V.1-03.08
Before start-up check whether:
1. There is sufficient water in the boiler and the heating system;
the pointer on the altitude (pressure) gauge is in the green
sector.
2. All valves in the heating flow and return are open.
3. The heating system has been fully vented.
4. The burner door is closed securely.
5. The burner plug is wired in correctly.
6. The fresh air supply to the boiler room is open.
7. Oil or gas supply is sound and purged.
8. All fuses are intact.
9. The mains switch is turned on.
Fault finding
Heating is cold
• Is boiler up to temperature? Check correct heat settings of
heating circuit controls.
• If automatic control does not operate ie is faulty, switch off
“control” switch off “control” switch and regulate via “manual”
control. Consult specialist.
• If boiler temperature has dropped and burner indicates
malfunction, refer to the burner suppliers’ instructions (press
malfunction button).
General check on whether:
• Fuse is intact.
• Mains switch is turned on and other controls are calling for
heat.
• Burner plug is correctly plugged in.
• Heating pump and filling pump are operating.
• Burner indicates malfunction.
• Control is switched on and displays the correct time.
• All valves are open.
• Fuel is available.
• All switches and knobs are set as per instructions.
• Boiler has switched off due to excess temperature.
Maintenance
• Clean the boiler regularly, proceed as follows:
− Turn off mains switch and control.
− Open burner door.
− Clean heating gas flue-ways and combustion chamber.
− Close burner door and tighten nuts firmly.
• Never tap water from the boiler for domestic use.
• If the system is to be out of operation for an extended period
of time, clean the boiler thoroughly , spray it out with a
mixture of oil and graphite and close the door firmly.
• If there is a frost hazard when the system is out of operation,
drain the boiler. Leave the stop-cock open (unless it contains
anti-freeze).
• Perform maintenance of heating controls and burner
according to the manufacturers’ instructions.
Hazards:
• Operate the boiler at a maximum temperature of 95ºC. If the
boiler overheats as a result of incorrect operation, switch the
burner off immediately. Do not refill with water until the boiler
has cooled off.
• Never fill the hot boiler with cold water.
• Flue gas temperature of less than 160ºC can cause sooting in
masonary chimneys.
• Consult the heating installers’ service department if heating
gas flue-ways become severely fouled or condensation
occurs.
• Only refill the oil tank when the system is switched off. Start up
no earlier than the next day, so the dirt which has been
disturbed in the tank can settle again.
• Inspect the door seal gasket between the front section and the
door. If the gasket is damaged, a specialist should fit a
replacement. Close the cleaning door ensuring it is firmly
sealed. Check all the door bolts are firmly tightened.