Biotec
Typographical and printing errors, changes
in construction and dimensions expected.
21
Boiler controller
6.7 Setting parameters
Changes of particular parameters can be done by pressing
the buttons
and at the same time. Below, a list of the
parameters with the factory settings in brackets (value Biotec 25/
value Biotec 40).
The parameters can be altered by pressing
or . The setting
is confi rmed with the enter button and the menu directs the user
back to the basic display.
S1: Duration of start-up fan (30 s/30s)
S2: Fan-power (100 %/100 %)
S3: Duration of screw start-up dose (30 s/30 s)
S4: Fan-power during start-up (30 %/30 %)
S5: Delayed start of ignition (60 s/60 s)
S6: Duration of start-up ignition (60 s/60 s)
S7: Fan-power during ignition (80 %/80 %)
S8: Duration of second ignition (600 s/600 s)
S9: Duration of stabilisation (200 s/200 s)
S10: Operating duration of screw during stabilisation (1,5 s/1,5 s)
S11: Pausing duration of screw during stabilisation (10,0 s/10,0 s)
S12: Fan-power during stabilisation (90 %/90 %)
S13: Stabilisation delay (300 s/300 s)
S14: Operating duration of screw P1 (2,5 s/4,0 s)
S15: Pausing duration of screw P1 (10,0 s/10,0 s)
S16: Fan-power during heating operation P1 (40 %/55 %)
S17: Operating duration of screw P2 (3,0 s/4,5 s)
S18: Pausing duration of screw P2 (10,0 s/10,0 s)
S19: Fan-power during heating operation P2 (45 %/60 %)
S20: Operating duration of screw P3 (3,0 s/5,0 s)
S21: Pausing duration of screw P3 (10,0 s/10,0 s)
S22: Fan-power during heating operation P3 (46 %/62 %)
S23: Duration of cool-down phase (240 s/240 s)
S24: Power of fan during cool-down phase (50 %/50 %)
S25: Boiler delay with room thermostat OFF (0 s/0 s)
S26: Max. fl ue gas temp. for ignition (100 °C/100 °C)
S27: Min. fl ue gas temp. (7,0 °C/7,0 °C)
S28: Min. Abgastemperatur (50 °C/50 °C)
S29: Max. decrease of fl ue gas temp. (20 °C/min / 20 °C/min)
S30: Duration of disregarded fl ue gas temp. in partial load opera tion (30 min./30 min)
S31: Minimum operation (5 °C/5 °C)
S32: Factor of boiler rated value for modulation (10 x/10 x)
S33: Fan-power reduction permitted (5 %/5 %)
S34: Hysteresis (5,0 °C/5,0 °C)
S35: Turn-on temp. for return increase pump (55 °C/55 °C)
S36: Diff. between turn-on and -off temp. (10 °C/10 °C)
S37: Pump overrun with RT OFF (0 s/0 s)
S38: Difference boiler to tank (5,0 °C/5,0 °C)
S39: Boiler probe adjustment (0,0 °C/0,0 °C)
S40: Flue gas probe adjustment (0,0 °C/0,0 °C)
S41: Compensator tank probe adjustment (0,0 °C/0,0 °C)
S42: Domestic water probe adjustment (0,0 °C/0,0 °C)