Strebel Turbotec 20-30, 40S-70, 40, 50L – 100L Installation Manual

Installation manual
for the authorised specialist
Turbotec lambda control 20-100 kW
20-30, 40S-70 40, 50L – 100L
12/2014
READ THE INSTRUCTION BOOKLET AND THESE SUPPLEMENTARY
INSTRUCTIONS CAREFULLY BEFORE INSTALLATION
These supplementary instructions together with those further in the instruction booklet cover the basic principles to ensure the satisfactory installation of the boiler, although detail may need slight modification to suit particular local site conditions. In all cases the installation must comply with current Building Regulations, Local Authority
Byelaws and other specifications or regulations as they affect the installation of the boiler. It should be noted that the Building Regulations requirements may be met by adopting the
relevant recommendations given in British Standards BS 8303, BS EN 15287-1:2007 as an alternative means to achieve an equivalent level of performance to that obtained following the guidance given in Approved Document J.
British Standards BS 6700, BS EN 14336:2004: Heating Systems in Buildings. Installation and commissioning of water based heating systems. BS EN 12828: 2003; Heating Systems in Buildings. Design of water based heating systems. BS EN 12831: 2003; Heating Systems in Buildings. Method for calculation of the design heat load. All as applicable to the appliance.
Please note that it is a legal requirement under England and Wales Building Regulations that the installation of the boiler is either carried out under Local Authority Building Control approval or is installed by a Competent Person registered with a Government approved Competent Persons Scheme. HETAS Ltd operate such a Scheme and a listing of their Registered Competent Persons can be found on their website at www.hetas.co.uk.
CO Alarms:-
Building regulations require that when ever a new or replacement fixed solid fuel or wood/biomass appliance is installed in a dwelling a carbon monoxide alarm must be fitted in the same room as the appliance. Further guidance on the installation of the carbon
monoxide alarm is available in BS EN 50292:2002 and from the alarm manufacturer’s
instructions. Provision of an alarm must not be considered a substitute for either installing the appliance
correctly or ensuring regular servicing and maintenance of the appliance and chimney system.
HEALTH AND SAFETY PRECAUTIONS
Special care must be taken when installing the boiler such that the requirements of the Health and Safety at Work Act are met.
Handling
Adequate facilities must be available for loading, unloading and site handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of contact wash immediately with plenty of water.
Asbestos
This boiler contains no asbestos. If there is a possibility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment.
Metal Parts
When installing or servicing this boiler care should be taken to avoid the possibility of personal injury.
BOILER PERFORMANCE
Refer to the main instruction further in this manual for details of the boiler’s performance.
PREPARATORY WORK AND SAFETY CHECKS
IMPORTANT WARNING
This boiler must not be installed into a chimney that serves any other heating appliance.
There must not be an extractor fan fitted in the same room as the boiler as this can cause the boiler to emit fumes into the room.
Chimney
In order for the boiler to perform satisfactorily the chimney height must be sufficient to ensure an adequate draught of approximately 10 - 15 Pa so as to clear the products of combustion and prevent smoke problems into the room.
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet of the boiler to the top of the chimney should be satisfactory. Alternatively the calculation procedure given in EN 13384­1 may be used as the basis for deciding whether a particular chimney design will provide sufficient draught. Ensuring the minimum chimney draught is responsibility of the Chimney specialist appointed.
The outlet from the chimney should be above the roof of the building in accordance with the
provisions of Building Regulations Approved Document J.
Because the boiler runs at high efficiencies, the temperature of the flue gases is at times lower than conventional solid fuel appliances. Although it is not classed as a condensing appliance, the low flue gas temperature results in condensation occurring within the flue. Any chimney flue system must therefore be able to withstand the effects of condensate and operate under wet conditions (designation letter W). In addition it should be soot fire resistant and able to withstand the corrosive effects of flue products generated by solid fuels (designation G and 3 respectively). If installation is into an existing masonry chimney then it will require re-lining with a liner meeting the specification described above. Existing concrete or clay lined chimneys are not suitable for this boiler and must be lined as described above. All installations must be in accordance with Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immediately before installation of the lining system. Where the chimney is believed to have previously served an open fire installation it is possible that the higher flue gas temperature from a closed appliance may loosen deposits that were previously firmly adhered, with the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a second time within a month of regular use after installation.
If there is no existing chimney then any new system must be to the designation described above
and in accordance with Building Regulations Approved Document J.
A single wall metal fluepipe is suitable for connecting the boiler to the chimney but is not
suitable for use as the complete chimney. The chimney and connecting fluepipe must have a
minimum diameter of 150 mm and its dimension should be not less than the size of the outlet
socket of the boiler.
Any bend in the chimney or connecting fluepipe should not exceed 45. 90 bends should not be used.
Combustible material should not be located where the heat dissipating through the walls of fireplaces or flues could ignite it. Therefore when installing the boiler in the presence of combustible materials due account must be taken of the guidance on the separation of combustible material given in Building Regulations Approved Document J and also in these boiler instructions.
2
Dear Installer,
The Turbotec central heating boiler has been subjected to type and performance testing by the officially authorised testing bodies Wieselburg, TGM Vienna and TÜV Bavaria. All boilers below 45kW are MCS Approved.
According to the test report, the Turbotec complies with the applicable requirements of EN303-5 for wood fuel.
The Turbotec lambda control is a highly developed product, which is not to be judged by conventional standards and for
the installation of which certain special features need to be taken into account. Therefore, we request that you follow the instructions below precisely. Compliance with the installation instructions is a prerequisite for trouble-free operation and guarantee. Please consider that errors during the installation sooner or later can lead to difficulties with approval authorities, to malfunctions or even to damage; i.e. in all cases
to customer’s complaints.
Moreover, subsequent rectification is always more
expensive than a proper, careful implementation right from the start. A commissioning protocol is included with the delivery.
It must be our common goal to hand over to the customer a correctly operating, highly efficient system, every unit and part of which functions as expected.
In order to attain this goal, you have to make a very significant contribution – we wish you every success in doing so.
Best regards
Strebel Ltd
Unit 1F Albany Park Industrial Estate, Frimley, Camberley Tel: 01276 685422 Fax: 01276 685405 Email: info@strebel.co.uk
Thermostrom
Energietechnik Gesellschaft mbH A-4407 Steyr-Dietachdorf, Ennser Strasse 91
Tel. 0043-7252 / 382 71 Fax 0043-7252 / 382 73 25 Email: thermostrom@strebel.at
3
Overview General instructions
Area of use/scope of delivery
Overview General instructions................................................. 3
Illustration of boiler types 20-70............................... 4
Illustration of boiler type 60 L................................... 5
Boiler technical data................................................ 6
Boiler dimensions.................................................... 7
Control technical data.............................................. 8
Boiler room/air supply/installation site …..……….... 9
Checks following transport....................................... 9
Assembly Assembly of the cladding with insulation………….. 10
Flue......................................................................... 11
Mounting the air regulation units............................. 11
Mounting the induced draft fan….............................11
Filling and draining.................................................. 11
Heating connections.................................................11
Raising the return temperature............................... 12
Thermal discharge safety device..............................12
Mounting the O2 probe and exhaust fume
sensor.......................................................................12
Mounting the storage tank sensor .......................... 13
Mounting the hydraulic unit .................................... 13
Mounting the control …........................................... 13
Hydraulic diagrams - overview ............................... 14
Hydraulic diagram – system 3 ................................ 15
Electrical connection diagram ................................ 15
System 3................................................................. 16
Functional description ............................................ 16
Important instruction .............................................. 16
Hydraulic diagram – system 3.1 ............................. 17
Electrical connection diagram ................................ 17
System 3.1.............................................................. 18
Function description …........................................... 18
Important instruction .............................................. 18
Settings for system 3 ..............................................19
Table for noting system settings ............................ 20
Aggregate test ...................................................... ..20
Commissioning Instruction/commissioning/handover ...................... 21
Commissioning the control ..................................... 21
Setting the boiler water temperature ...................... 21
Commissioning the boiler........................................ 22
Heating up/adding fuel ........................................... 22
Circuit diagram ....................................................... 23
Short operating instructions: lambda control OFF .. 24
Short operating instructions: lambda control ON..... 25
Maintenance Boiler maintenance ................................................ 26
Malfunctions Troubleshooting ..................................................... 26
General instructions
Installation, assembly, electrical connections and first commissioning are tasks for a qualified expert. He is responsible for ensuring proper implementation.
Explanation of our warranty conditions.
We have to exclude our warranty for damages occurring due to the following reasons:
- inappropriate or improper use
- incorrect assembly resp. commissioning by the purchaser or a third party, including the fitting of third party parts
- operation of the system with excessive pressure.
The prerequisites for the provision of a warranty are:
- correct operation of the boiler
- operation of the system within the performance limits specified by the manufacturer
- use of suitable fuels.
- the return of the completed commissioning protocol to thermostrom Energietechnik Gesellschaft mbH.
Instruction for the user
The system will retain its safety and functions if it is serviced regularly every year.
Fields of use
Boilers from the Turbotec series are suitable and approved for use as heat generators in hot water heating systems with a permissible flow temperature of up to 100 °C. They can be installed in open and closed systems according to DIN 4751, sheets 1 and 2, or ÖNORM B 8130 and B 8131.
Scope and method of delivery
Boiler body loose. Cladding with insulation in a carton. Lambda control, storage tank sensor, exhaust fume sensor, O2 probe, induced draft fan, air regulator units, ash tray, commissioning protocol, installation and operating manual stored inside the filling chamber.
4
Overview Boiler illustration
20 - 30, 40S, 50 - 70
1 Computer-controlled lambda
control 2 Cladding, front lid 4 Filling door (type 40S-70has two
filling doors) 5 Inner door 6 Filling chamber (fuel storage
chamber) 7 Burner grating 8 Burner brick 9 Primary air regulator unit with seal 10 Secondary air regulator unit with
seal 11 Cladding, actuator cover 12 Flame duct 13 Ashes door with sight glass
14 Ashes chamber 15 Cleaning lid 16 2 sleeves 1/2” 17 Heat exchanger connection R1/2”
for thermal discharge safety device 18 Heating feed connection 19 Opening rod for the gas vent flap 20 Heating return connection 21 Sleeve for O2 probe 22 Exhaust fume nozzle 23 Induced draft fan 24 Filling and emptying sleeve 1/2" 25 Gas vent flap 26 Opening handle for the gas vent
flap 27 Cladding, rear lid
28 Cladding, left side, with plug-in
wiring 29 Transport eye bolt 30 Cladding, right side 31 Insulating panel, top 32 Immersion sleeve for STL and
boiler temperature sensor 33 Exhaust fume baffle plate 34 Cladding, rear side
35 Thread for exhaust fume sensor
36 Ancillary heating surface 37 Cladding, base 38 Secondary air apertures 39 Primary air apertures 40 Drip tray
5
Overview Boiler illustration
50L - 100L (Top loading door optional)
1 Computer-controlled lambda
control 2 Cladding, front lid 3 Filling lid 4 Filling door 5 Inner door 6 Filling chamber (fuel storage
chamber) 7 Burner grating 8 Burner brick 9 Primary air regulator unit with
seal 10 Secondary air regulator unit with
seal 11 Cladding, actuator cover 12 Flame duct 13 Ashes door with sight glass
14 Ashes chamber 15 Cleaning lid 16 2 sleeves 1/2” 17 Heat exchanger connection R1/2”
for thermal discharge safety
device 18 Heating feed connection 19 Opening rod for the gas vent flap 20 Heating return connection 21 Sleeve for O2 probe 22 Exhaust fume nozzle 23 Induced draft fan 24 Filling and emptying sleeve 1/2" 25 Gas vent flap 26 Opening handle for the gas vent
flap 27 Cladding, rear lid
28 Cladding, left side, with plug-in
wiring 29 Transport eye bolt 30 Cladding, right side 31 Insulating panel, top 32 Immersion sleeve for STL and
boiler temperature sensor 33 Exhaust fume baffle plate 34 Cladding, rear side 35 Thread for exhaust fume sensor 36 Ancillary heating surface 37 Cladding, base 38 Secondary air apertures 39 Primary air apertures 40 Drip tray 41 Optional Top loading door for 50L, 60L & 75L
6
Overview Boiler technical data
Boiler
20
25
30
40
40S
50
60
70
50L
60L
75L
100L
Filling doors H/W (2x for 40S-70)
cm
60/34
60/34
60/34
36/54
36/54
36/54
36/54
36/54
36/54
36/54
36/54
36/54 Flow /return
F/R
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1¼’’
1½‘’
1½’’
Drain D 1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4
3/4
Safety heat exchanger
HE
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
Opt. Filling lid height/width
cm – –
– – – – – – 36/54
36/54
36/54
Weight
kg
515
515
515
710
925
925
925
925
940
940
1080
1200
Transport width
cm
50
50
50
69
69
69
69
69
69
69
69
89
General operatin g data
Rated heating power
kW
20
25
30
40
40
50
60
70
50
60
75
93
Max. operating overpressure
bar 3 3 3 3 3 3 3 3 3 3 3 3
Permissible feed temperature
°C
100
100
100
100
100
100
100
100
100
100
100
100
Min. return temperature
°C
55
55
55
55
55
55
55
55
55
55
55
55
Qmin. (SWT)
ltr/h
600
600
600
1000 1200
1200
1200
1200
1200
1200
1200
1400
Δp (20K)
mbar
0.57
0.89
1.3
2.3
2.3
3.6
5.2
7.1
3.6
5.2
5.2
6.6
Power and emission data at tested rated power
Exhaust fume temperature
°C
158
160
163
169
169
173
178
182
173
172
171
169
CO2 content
%
15
15
15
15
15
15
15
16
16
16
15
15
CO (at 13% O2)
mg/Nm3
80
91
102
123
123
144
166
187
126
135
149
172
Solids emission (dust)
mg/Nm3
15
15
14
14
14
14
15
15
14
14
14
14
Boiler efficiency
%
91
90.8
90.6
90.1
90.1
90.3
90.4
90.6
90
90.4
91
91.9
Contents
Boiler water capacity
litres
115
115
115
210
255
255
255
255
370
370
410
470
Filling chamber volume
litres
150
150
150
190
290
290
290
290
340
340
400
460
Filling chamber depth
cm
60
60
60
60
60
60
60
60
110
110
130
110
Combustion duration
approx.
hrs.
7 6 5 5 8 7 6 5 8 6 6
6
Storage tank volume
Minimum Volume Recommended by Strebel
litres
1200
1500
1800
2400
2400
3000
3600
4200
3000
3600
5000
8000
Flue
Required outlet pressure
mbar
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
0,10
Exhaust fume mass flow rate
g/s
15
19
23
30
30
39
46
54
39
45
45
80
Diameter of exhaust nozzle
cm
15
15
15
18
18
18
18
18
18
18
20
20
The manufacturer’s tables are authoritative for the dimensioning of the flue etc. Austria/Germany: in the case of existing systems, the flue must be inspected by a master chimney sweep! UK & Eire: the chimney must be swept as per local regulations. Strebelwerk GMBH reserve the right to change any data without prior notice.
7
Overview Boiler dimensions
Turbotec 40 lambda control
Turbotec 20 – 30 lambda control
Turbotec 40S – 70 lambda control
Turbotec 50L – 100L lambda control (Showing optional filling lid centre line)
8
Overview Control technical data
Mains power supply
230V +10/-15% / 50Hz
Power consumption, electronics
max. 30VA at 230V
Maximum current consumption, entire system
Imax = 6.3 A
Fuse use
5 x 20 mm / 6.3 A quick-blow
Switch-off temperature of the safety temperature limiter
T = 100 C +0 / -5%
Heating circuit pump
Switching output: 230 V / max. 1.5 A
Charge pump for tap water storage tank
Switching output: 230 V / max. 1.5 A
Actuator drive for charge valve
Switching output: 230 V / max. 0.1 A
Induced draft fan
Switching output: 230 V / max. 1.5 A
Primary pump
Switching output: 230 V / max. 1.5 A
Actuator drive for return valve
Switching output: 230 V / max. 0.1 A
Floating switchover contact
Contact load: 230 V / max. 5 A
Control outputs for air regulator units
0 to 10 V / max. 3 mA
Power supply output for air regulator units
AC voltage output: 24 V / 6 VA
Electromagnetic door opener
AC voltage output: 12 V / 16 VA
Power supply output for O2 probe
AC voltage output: 12 V / 16 VA
Measurement input for Pt100 (R=108/20C)
- Storage tank sensor
- boiler sensor
- exhaust fume sensor
Maximum sensor temperature: Tmax = 150C Tmax = 150C Tmax = 600C
Immersion sleeve for boiler sensor and safety temperature limiter
2x LW7 with cable ties Ms63, PN16, immersion depth 100
Protection class
IP 40 (appliance detached: IP 00)
Ambient operating temperature
0 C to +50 C
Ambient storage temperature
–20 C to +70 C
There are several controllers available in the Strebel Turbotec boiler range, each with their own special features. These controllers DO NOT alter the performance of the appliance, only supplementing system/control outputs. Covered in this manual is LC1.
Loading...
+ 26 hidden pages