Strand ProPack (2008) ProPack Users Manual

ProPack
User’s Manual
Issued August 1 2008
Strand Lighting is a Philips group brand
Strand Lighting Asia,
20/F Delta House, 3 On Yiu Street, Shatin, N.T. Hong Kong Tel: + 852 2757 3033 Fax: + 852 2757 1767 Strand Lighting Europe Limited,
Unit 2 Royce Road, Fleming Way, Crawley, West Sussex. United Kingdom. RH10 9JY
Tel: + 44 1293 554 010 Fax: + 44 1293 554 019 Strand Lighting Inc,
6603 Darin Way, Cypress, CA 90630, USA Tel: +1 714 230 8200 Fax: +1 714 230 8173 The material in this manual is for information purposes only and is subject to change
without notice. Strand Lighting assumes no responsibility for any errors or omissions, which may appear in this manu al. For comments and suggestions regarding corrections and/or updates to this manual, please contact the nearest Strand Lighting office.
El contenido de este manual es solamen te para in for m ac ió n y está suje to a cam bi os sin previo aviso. Strand Lighting no asum e res pons ab i lidad po r errore s o omision e s que puedan aparecer. Cualquier comentario, sugerencia o corrección con respecto a este manual, favor de dirigirlo a la oficina de Strand Lighting más cercana.
Der Inhalt dieses Handbu ches ist nur für Informationszwecke gedacht, Aend erungen sind vorbehalten. Stra nd Light ing u eb ern im m t kein e Verantw o rtung für Fehler oder Irrtuemer, die in diesem Handbuch auftreten. Für Bemerkungen und Verbesserungsvorschlaege oder Vorschlaege in Bezug auf Korrekturen und/oder Aktualisierungen in diesem Han db u ch, moech t en wi r Sie bit te n, Ko nt a kt mit der naechsten Strand Lighting-Niederlassung aufzunehmen.
Le matériel décrit dans ce manuel est pour information seulement et est sujet à changements sans préavis. La compagnie Strand Lighting n’assume aucune responsabilité sur toute erreur ou omission inscrite dans ce manuel. Pour tous commentaires ou suggestions concernant des corrections et/ou les mises à jour de ce manuel, veuillez si vous plait contacter le bureau de Strand Lighting le plus proche.
© 2008 Philips Group. All Rights Reserved. Information contained in this document may not be duplicated, in full or in part, by
any person without prior written approval of Strand Lighting. Its sole purpose is to provide the user with detailed installation informa tion for the equipment suppl ied. The use of this document for all other purposes is specifically prohibited.
2
Table of contents
Introduction ..................................................................................................................................................... 5
120v Specifications ......................................................................................... ................................................ 6
Power Requirements .................................................................... .............................................................. 6
Dimming Capacity ...................................................................................................................................... 6
Dimmer Output Connections ...................................................................................................................... 6
Control Inputs ........................ .................................................. ................................................................... 6
Physical Dimensions (unpacked) ............................................................................................................... 6
Environment (Operating) ......................................................... ................................................................... 6
Protection ................................................................................................................................................... 6
Installation .................................................................................................................................................. 6
120v Installation Notes ....................................................... ............................................................................ 7
Mains Power Input Connections ....................................................................................... .......................... 7
Mains Cable Entry ............. ......................................................................................................................... 8
Rear Cable Entry ............................................................ .... ..... ......... ..... .... ......... ..... .... .......................... 8
Mains Cable Termination .................................................... ..... ......... ..... .... ......... ..... .... ......... ................. 8
Protection ............................................................................................................................................... 9
Power Distribution ...................................................................................................................................... 9
Rack Mounting ........................................................................................................................................... 9
230v Specifications ......................................................................................... .............................................. 10
Power Requirements .................................................................... ............................................................ 10
Dimming Capacity .................................................................................................................................... 10
Dimmer Output Connections .................................................................................................................... 10
Control Inputs ........................ .................................................. ................................................................. 10
Physical Dimensions (unpacked) ............................................................................................................. 10
Environment (Operating) ......................................................... ................................................................. 10
Protection ................................................................................................................................................. 10
Installation ................................................................................................................................................ 10
230v Installation Notes ....................................................... .......................................................................... 11
Mains Power Input Connections ....................................................................................... ........................ 11
Mains Cable Entry ............. ....................................................................................................................... 11
Rear Cable Entry ............................................................ .... ..... ......... ..... .... ......... ..... .... ........................ 12
Rear Cable Entry ............................................................ .... ..... ......... ..... .... ......... ..... .... ........................ 12
Mains Cable Termination .................................................... ..... ......... ..... .... ......... ..... .... ......... ............... 12
Protection ............................................................................................................................................. 13
Power Distribution .................................................................................................................................... 13
Rack Mounting ......................................................................................................................................... 13
Control Input ................................................................... .............................................................................. 14
DMX512 ................................................................................................................................................... 14
Dimmer Outputs ........................................................................................................... ............................ 14
Service and Maintenance ........................................................ ......... .... ..... ..... ......... .... ..... ............................ 15
Safety Tests ..................................................... .... ..... ......... ..... .... ......... ..... ..... ......... .... ................................. 15
Set up ...................... .... ......... ..... ..... ......... .... ..... ......... ..... .... ......... ..... .... .......... .... ..... ..................................... 16
Set Level ... ..... ......... .... ..... ......... ..... .... ......... ..... ......... .... ..... ......... ..... .... ......... ..... ..... ..................................... 17
Set all Dimmer Levels ......................................................... ..................................................................... 17
Set single Dimmer Level .......................................................................................................................... 17
Address ........................................................................................................................................................ 18
Start Address ........................................................................................................................................... 18
Patch ........................................................................................................................................................ 18
Curves .......................................................................................................................................................... 19
Set Curve for all Dimmers ............................................... ..................................................................... 19
Set Curve for Single Channel ................................................... ............................................................ 19
Preset ........................................................................................................................................................... 20
Set Level ....................... ....................................................................................................................... 20
Snap Shot ............................................................................................................................................ 20
Preset Call .................................................................................................................................................... 21
Local .................................................................................................................................................... 21
Minimum Output .......................................... ..... .... .......... .... ..... ......... .... ..... ......... ..... .... ..... ............................ 22
Set Minimum Output for All, Odd or Even Dimmers ............................................................................. 22
3
Set Minimum Output Level for Single Dimmer ...................................................................... ............... 22
Maximum Output ................................ .......................................................................................................... 23
Set Maximum Output Level for All, Odd or Even Dimmers ................................................................... 23
Set Maximum Output Level for a Single Dimmer.......................................................... ........................ 23
Setup ............................................................................................................................................................ 24
DMX Fail .............................................................................................................................................. 24
Setting the Delay when DMX512 fails ................................................... ............................................... 24
Set Preset when DMX512 fails........................................................................ .... ..... ......... ..... .............. 24
Ventilation ............................................................................................................................................ 25
Information ................................................................................................................................................... 26
4
Introduction
p
Strand Lighting ProPack dimmer packs are compact, portable dimmin g units, designed for use in conjunction with a lighting control console.
The ProPack accepts standard DMX512 multiplexed digital control input The physical dimensions of a ProPack dimmer pack are shown in Figure 1.
75321 Terminal Strip 230v 75331 Terminal Strip 120v
Note: Load terminals are not enclosed within the dimmer pack. Terminal strip packs must be mounted in an enclosure
75332 Stage Pin 120v
75322 Socapex Connector 230v 75333 Soca
ex Connector 120v
Figure 1
5
120v Specifications
Power Requirements
Voltage: 100 - 120 Volts AC. Frequency: 60 Hz. Three phase + Neutral + Ground
All ProPack dimmer packs must be Grounded.
Dimming Capacity
Each pack contains twel ve dimmers each with a Maximum load of 2.0kW (20A Magnetic Breaker) per dimmer - total 24kW per dimmer pack.
Dimmer Output Connections
ProPack is available with a variety of output options to suit different operating conditions and national standards.
Connector Options Part Number 75331 Terminal Strips
Part Number 75332 Stage Pin Part Number 75333 2 x Socapex Connector
Control Inputs
USITT DMX512(1990) multiplexed dig ita l con trol , via 5 pin XLR conne ct o r.
Physical Dimensions (unpacked)
Height: 3.75” Width: 19” Depth: 18”
Weight: 34 lbs (approximately)
Environment (Operating)
Temperature: 0°C - 37°C. Relative humidity: 60% - 90%. Condensation level: Zero.
ProPack are suitable only for use in an area of office level cleanliness. The space should have sufficient volume to allow exhaust air to circulate and cool.
Protection
Classification IP30. Equipment Class Class 1.
Installation
WARNING
Hazardous voltages are present in Propack. Ensure that the mains supp ly is isolated before opening the equipment for
installation or servicing. Dimmer packs should be installed and serviced only by suitably qualified personnel. ProPack may be installed mounted together in a rack (for hire or touring purposes).
6
120v Installation Notes
In order to enhance the reliability of the dimmers, it is recommended that they are operated within the following environmental limits:
Temperature: 18°C - 25° C Relative Humidity: 60% - 80% Condensation level: Zero
The dimmers may emit a slight buzzing noise when in operation. They should be installed away from areas where such noise would be undesirable.
Figure 2
Mains Power Input Connections
ProPack dimmer packs require a nominal mains input at 120V 60Hz AC. This supply must be three phase. Separate Neutral and Ground conductors are required.
WARNING
ProPack dimmer packs must be Grounded.
The Neutral conductor must have the same (or greater) cross-sectional area, as the Phase conductor(s).
(SCR dimmers operate using ‘phase control’. This renders the ‘balancing’ of loads across phases - and thus a reduction in Neutral currents impossible)
ProPack dimmer packs should be connected to their mains supplies via adequately rated cable, together with any associated plug and socket connectors. For full power operation the supply must be rated at 80A for three phase operation. These ratings may be reduced if the supply protective devices are selected to limit the current drawn to appropriate limits. Should supply diversity be applied care is required in the sizing of supply neutral conductors. If in doubt please seek advice from Strand Lighting.
For safety in operation each ProPack must be fed from an appropriately fused supply.
It is strongly recommended that the mains supply to the ProPack is taken via a local circuit breaker, so that the supply may be easily discon nected for plugging and unplugging of load connectors and for service or maintenance.
All cables, switchgear and prote ct io n equ ipmen t must be selec te d and in st all e d in accordance with locally electrical regulations.
7
Mains Cable Entry
The mains input cable wil l enter the pack via the Rear Connection Panel.
Rear Cable Entry
Remove the Rear Connection Panel. It is secured to the base by four screws, as shown in Figure 3. The panel should be punched with a single hole to accept the appropriate cables and strain relief for your installation.
Figure 3
Mains Cable Termination
The mains input is connected at a set of screw terminal blocks, situated inside the pack, at the right hand side (looking from the front of the pack). The terminals will accept cables of up to #6 AWG in size. Always connect ground and neutral first.
1. Loosen all three phase terminals Neutral and Ground.
2. Place incoming cable inside terminals and tighten s ecurely.
3 Phase Operation at 80A per phase
8
Protection
The mains supply to each ProPack must be protected against external overload. Appropriate circuit breaker ratings should not exceed 80 Amps for a three phase supply. If the available mains supply is not capable of providing the full rated currents, the protection device rating must be reduced accordingly; it will not be possible to use the dimmers with their maximum rated loads.
Protection systems on the supply to each dimm e r pa ck should limit th e po te nti al fau lt current level to 10,000AIC or less.
Power Distribution
To achieve correct Grounding and mains power distribution, it is recommended that all dimmers and lighting control equipment within the installation should draw mains power from one central distribution point. This should be as close as possible to the mains power intake for the site or building. The wiring from the distribution point to the lighting equipment should ideally be used for supplying power to the lighting equipment alone, and not to other appliances or equipment.
ProPack must be properly Grounded, both for safety and to ensure correct operation. It is essential that all Ground connection s w ith in the o vera ll ins tal lat ion ar e at
comparable potentials. If this is not the case, circulating currents may be generated in signal earth connection s, possibly leading to fluctuating light levels and (in some extreme cases) damage to wiring or equipment.
If in doubt, as to the nature of your local electrical supply arrangements please seek advice from an authorative person at your site or an electrical contractor.
Rack Mounting
The ProPack dimmer pack is designed for rack mounting. Care should be taken to mount the unit securely in an equipment rack des igned to hold equipment of this type.
To prevent overheating of rack-mounted dimmers when in use, a fan, or set of fans, should be fitted to the top of the equipment rack, such that air is extracted upwards. To ensure adequate cooling, the fan(s) should provide an airflow of about 16 litres per second across the top of each dimmer pack.
A gap of 1 U (1.5 inches) is requ ired between adjacent pairs of dimmer racks. Leave a rear ventilation clearance of 4 inches. Due to the weight of the unit, rack side supports are recommended, but care must be taken to ensure that these do not obstruct ventilation.
WARNING
Additional Forced ventilation may be advised if racks are mounted within a flight
case or similar closely constraining enclosure.
9
230v Specifications
Power Requirements
Voltage: 200 - 260 Volts AC. Frequency: 50 - 60 Hz. Three phase + Neutral + Earth
All ProPack dimmer packs must be Earthed for safety in use.
Dimming Capacity
Each pack contains twelve dimmers each with a Maximum load of 15A (3kW) per dimmer - total 36kW per dimmer pack.
Dimmer Output Connections
ProPack is available with a variety of output options to suit different operating conditions and national standards.
Socket Options Part Number 75321 Terminal Strips
Part Number 75322 2 x Socapex Connector
Control Inputs
USITT DMX512(1990) multiplexed dig ita l con trol , via 5 pin XLR conne ct o r.
Physical Dimensions (unpacked)
Height: 90 mm. Width: 483 mm Depth: 460 mm
Weight: 15.3Kg (approximately)
Environment (Operating)
Temperature: 0°C - 37°C. Relative humidity: 60% - 90%. Condensation level: Zero.
ProPack are suitable only for use in a dry, internal en vi ronme nt.
Protection
Classification IP30. Equipment Class Class 1.
Installation
WARNING
Hazardous voltages are present in Propack.
Ensure that the mains supp ly is isolated before opening the equipment for
installation or servicing. Dimmer packs should be installed and serviced only by suitably qualified personnel. ProPack may be installed mounted together in a rack (for hire or touring purposes).
10
230v Installation Notes
In order to enhance the reliability of the dimmers, it is recommended that they are operated within the following environmental limits:
Temperature: 18°C - 25° Relative Humidity: 60% - 80% Condensation level: Zero
ProPack dimmers are designed such that Earth leakage current s are minimised, allowing their use on mains power supplies protected by 30mA Residual Current Devices. However, utilising RCD protection in dimming installations may pre sent problems. For specific advice please contact Strand Lighting
The dimmers may emit a slight buzzing noise when in operation. They should be installed away from areas where such noise would be undesirable.
Figure 5
Mains Power Input Connections
ProPack dimmer packs require a nominal mains input at 230V 50Hz AC. This supply may be either single or three phase (star only), depending on the method of connection. In either case separate Neutral and Earth conductors are required.
WARNING
ProPack dimmer packs must be Earthed for safety in operation.
The Neutral conductor must have the same (or greater) cross-sectional area, as the Phase conductor(s).
(Triac and thyristor dimmers operate using ‘phase control’. This rende rs the ‘balancing’ of loads across phases - and thus a reduction in Neutral currents impossible)
ProPack dimmer packs should be connected to their mains supplies via adequately rated cable, together with any associated plug and socket connectors. For full power operation the supply must be rated at 125A for single phase operation, 63A for three phase operation. The se ratings may be reduced if the supply protective devices are selected to limit the curren t drawn to appropriate lim its. Should supply diversity be applied care is required in the sizing of supply neutral condu ctors. If in doubt please seek advice from Strand Lighting.
For safety in operation each rack must be fed from an appropriately fused supply. It is strongly recommended that the mains supply to the dimmers is taken via a local
isolating switch, so that the supply may be easily di sconnected for plugging and unplugging of load connectors and for service or maintenance.
All cables, switchgear and protection equipment must be selected and installed in accordance with locally prevailing electrical regulations.
Mains Cable Entry
The mains input cable wil l enter the pack via the Rear Connection Panel.
11
Rear Cable Entry
Remove the Rear Connection Panel. It is secured to the base by four screws, as shown in Figure 2.
Rear Cable Entry
Remove the Rear Connection Panel. It is secured to the base by four screws, as shown in Figure 6.
Figure 6
Mains Cable Termination
The mains input is connected at a set of screw terminal blocks, situated inside the pack, at the right hand side (looking from the front of the pack). The terminals will accept cables of up to 16 mm2 in size. If it is required to connect a ProPack to a single phase supply, the link bar supplied with the pack should be used to join the three phase terminals together, as follows (refer to right-hand diagram in Figure 73):
1. Loosen all three phase terminals.
2. Place incoming cable inside terminals and tighten securely.
3 Phase Operation at 80A per phase
Single Phase Operation 230v
Figure 7 Mains Jumper Settings
WARNING
Do NOT fit the link bar when the pack is connected to a three phas e supply
12
Protection
The mains supply to each dimmer pack must be protected against external overload. Appropriate fuse or circuit breaker ratings are 63A for a three phase supply. If the available mains supply is not capable of providing the full rated currents, the protection device rating must be reduced accordingly; it will not be possible to use the dimmers with their maximum rated loads.
Protection systems on the supply to each dimm e r pa ck should limit th e po te nti al fau lt current level to 1500A or less.
Power Distribution
To achieve correct Earthing and mains power distribution, it is recommended that all dimmers and lighting control equipment within the installation should draw mains power from one central distribution point. This should be as close as possible to the mains power intake for the site or building. The wiring from the distribution point to the lighting equipment should ideally be used for supplying power to the lighting equipment alone, and not to other appliances or equipment.
ProPack must be properly Earthed, both for safety and to ensure correct operation. It is essential that all Earth connections within the overall installation are at
comparable potentials. If this is not the case, circulating currents may be generated in signal earth connection s, possibly leading to fluctuating light levels and (in some extreme cases) damage to wiring or equipment.
Care should be taken when differing electrical supplies (for example local generation for dimmers, public mains for control console) are in use or internal mains power distribution is TN-C (combined neutral & earth conductors)
If in doubt, as to the nature of your local electrical supply arr ang e men ts ple ase seek advice from an authorative person at your site.
Rack Mounting
The ProPack dimmer pack is designed for rack mounting. Care should be taken to mount the unit securely in an equipment rack des igned to hold equipment of this type.
To prevent overheating of rack-mounted dimmers when in us e, a fan, or set of fans, should be fitted to the top of the equipment rack, such that air is extracted upwards. To ensure adequate cooling, the fan(s) should pr ovide an airflow of about 16 litres per second across the top of each dimmer pack.
A gap of 1 U (44.5mm) is required between adjacent pairs of dim mer racks. Leave a rear ventilation clearance of 100mm. Due to the weight of the unit, rack side supports are recommended, but ca re must be taken to ensure that these do not obstruct ventilation.
WARNING
Additional Forced ventilation may be advised if racks are mounted within a flight
case or similar closely constraining enclosure.
13
Control Input
The ProPack accepts DMX512 cont rol inputs:
DMX512
The DMX512 input will accept a multiplexed digit al control signal which conforms to USITT specification DMX5 12 (1990). Details of this specification are available from USITT on request.
The DMX512 control input is via a five-pin male XLR type connector. Pin connections are shown in Figure 8. A five-pin female XL R conn ec tor is also fitted to allow a series of ProPack dimmer packs (or other DMX512 equipment) to be daisy chained together.
Figure 8 DMX512 Pin Outs
Dimmer Outputs
Dimmer output connections are by means of either receptacle/socket outlets on all styles of the ProPack dimmer packs, except the terminal strip version. Terminals on all terminal strip packs are exposed and these packs m ust be mounted in an enclosure.
When operating from a three phase supply, dimme rs 1, 2, 3 & 4 are connecte d to phase 1, dimmers 5, 6, 7 & 8 to phase 2, and dimmers 9, 10, 11 & 12 to phase 3.
Plugs and Connectors used for dimmer output connections must be of the correct type to match the socket outlets.
It is important that plugs are w ired correctly. Figure 9 shows the various types of socket outlets fitted to ProPack dimmer packs.
Terminal Strip
Socapex
Stage Pin (120v Only) Figure 9
14
Service and Maintenance
ProPack dimmer packs do not require routine maintenance other than external cleaning. However, in common with all electrical eq uipment, they should be periodically checked to ensure that they remain in good condition. Any repairs or maintenance to the internal electronics, or other circuitry, should be carried out only by authorised Strand Lighting Service personnel or approved Service Providers.
Safety Tests
ProPack dimmer packs are subjected to safety inspections and tests prior to shipment from the Strand Lighting factory.
If, as part of routine maintenance, the packs are to be subjected to electrical safety tests applied using a ‘standard’ Po rta bl e Appl i an ce Te st e r, the fo ll ow ing poi nt s should be observed:
The nature of the electronic dimmer circuits means that an ‘insulation test’ using a voltage in the order of 500V will give a result of approximately 1.7MO. Although this may appear as a test fai lure, the apparently low resistance is normal for these dimmer packs and is not du e to failing insulation. Use r safety is not at risk.
Caution
A high voltage ‘Flash’ test must not be applied to a ProPack dimmer pack.
Note
A high current Earth/Ground continuity test must not be applied to the signal
ground pins of the control input connector(s).
15
Set up
Figure 10 Set up keys and displays
The ProPack dimmer pack offers a selection of set up and configuration features that are accessed from the front panel using the four set up keys and LCD Display.
Menu and setting selections are made with the Up and - keys. To exit any menu press the ESC escape key and OK is the confirmation key.
At the top level of the menu with the display of ProPack, press +/- to navigat e through the menus.
16
Set Level
Set all Dimmer Levels
Set single Dimmer Level
When a control console is not available, the dimmer levels on Pro Pack dimmer systems can be individually set to a desired level using the front panel keys. After the selection of +/- key to the Set Level display, press OK to enter into the Set Level Menu
Press “-“ to change the display to ALL, OK to confirm setting of all dimmer level s.
Press +/- to select the required dimmer (1-12), OK to confirm setting of that particular channel.
The Default is Input, press +/- to select the required level of that dimmer follow by OK.
17
Address
This menu is to set either the DMX512 start address if the dimmer channels are used sequentially, or each DMX512 address can be patched individually to each dimmer channel.
Start Address
Patch
18
Curves
This menu is used to select a dimmer curve for any or a ll the dimmers in a system. There are five dimmer curves available to choose from S-Curve, Square, Non –Dim, Low Cut and Linear Power laws.
When the Curve menu is shown after p ressing the OK key, use the + and - keys to select either the “Curve All” menu for all dimmers or for the “Curve Independent” menu for a single dimmer.
Set Curve for all Dimmers
When in the “Curve All” menu, pr ess the OK key once, then use the + and - keys to select one of the five curves.
Set Curve for Single Channel
When in the “Curve Independent” menu, press the OK key once, the dimme r Channel # will be displayed, use the + and - keys to select the dimmer channel (1 –
12) to be set. Press the OK key again followed by the + and - keys to select the preferred curve. Repeat the above process until all channels are set.
19
Preset
The Preset Menu allows the editing and recordin g of the in t erna l ly stored presets. Presets can be stored in any one of the 40 internal prese t s.
Set Level
The Set Level menu allows you to edit the saved levels stored for each dimmer in each preset.
Snap Shot
Snapshot is to take a snap shot from the DMX512input, when the sn aps disp lay on the LCD window, press OK to take the DMX512level from the DMX512input.
20
Preset Call
Local
The preset call menu allows you to replay one of the previously stored presets. These can either be triggered locally from the cont rol panel or remotely.
Choose the Local Option wit h OK and then select the required scene to playback using the + / - keys and sele ct using the OK button.
21
Minimum Output
This menu is to set the minimum output level of all or selected dimmers. Press the OK key once to confirm and press the + and - keys to select either the “Min Output DIM All”, “Min Output DIM Odd” “Min Output DIM Even” or individual dimmers
Set Minimum Output for All, Odd or Even Dimmers
When in the “Min Ouput Dim All” “Min Output DIM Odd” or “Min Output DIM Even ” menu, press the OK key once and the minimum level will be displayed as a percentage.
Use the + and - keys to select the minimum level (0 to 30%) for all dimmers.
Set Minimum Output Level for Single Dimmer
When in the “Min Output DIM #” menu, press the “+ / -“ key once, to select the desired dimmer (1 – 12) to be set and t hen press the OK key
Now the percentage min level will be displayed, Use the + and - keys to select the desired Min Level (0 – 30% ). Repeat the above process until all dimmers are set.
22
Maximum Output
This menu is to set the Maximum output level of all or selected dimmers. Press the OK key once to confirm and press the + and - keys to select either the “Max Output DIM All”, “Max Output DIM Odd” “Max Output DIM Even” or individual dimmers
Set Maximum Output Level for All, Odd or Even Dimmers
When in the “Max Output Dim All” “Max Output DIM Odd” or “Max Output DIM Even” menu, press the OK key once, the Maximum level will be displayed as a percentage.
Use the + and - keys to select the Maximum level (70 to 100%) for all dimmers.
Set Maximum Output Level for a Single Dimmer
When in the “Max Output DIM #” menu, press the “+ / -“ key once, to select the desired dimmer (1 – 12) to be set and then press the OK key.
Now the percentage min level will be displayed, Use the + and - keys to select the desired Maximum Level (70 – 100%). Repeat the above process until all channels are set.
23
Setup
DMX Fail
This menu is to select what action the dimmer pack should follow on loss of DMX512 or DMX512 absence. The dimmer pack can be set as Off, Switch Off after a time interval, Select a Preset or Hold the last state when the DMX512 fails.
Press the OK key once to confirm and press the + and - keys to sele ct either “Off” to hold the last lighting level.
“Off after” to hold the lighting level for a ce rtain period of delay time “Preset” to hold the lighting level to a lighting preset. Or “Last Hold” to keep the last good received DMX512 state
Setting the Delay when DMX512 fails
When in the “Off after” menu, press the OK key once, then use the + and - keys to select the delay before before th e system black outs. Press OK key once to confirm the delay time.
Set Preset when DMX512 fails
When in the “Preset” menu, press the OK key once, then use the + and - keys to select the Preset # of lighting level while DMX512 fail. Press OK key once to confirm the Preset number.
24
Ventilation
The ventilation control menu allows you to control how the internal cooling fans operate. The menu gives you a choice of Normal (Fans on with Temperature), On with DMX512 Signal, Silent (no Fans) or Fans On.
25
Information
To view the software version select the Software Vision and Press OK
To view the internal dimmer rack temperature, select the Temperature and press OK. Two temperatures are displayed, one for the left heat sink (dimmers 1 – 6) and the other for the right heat sink (dimmers 7 – 12).
26
27
Strand Lighting is a Philips group brand Strand Lighting Europe Limited,
Unit 2 Royce Road, Fleming Way, Crawley, West Sussex. United Kingdom. RH10 9JY Tel: + 44 1293 554 010 Fax: + 44 1293 554 019
Strand Lighting Asia, 20/F Delta House, 3 On Yiu Street, Shatin, N.T. Hong Kong Tel: + 852 2757 3033 Fax: + 852 2757 1767
Strand Lighting Inc, 6603 Darin Way, Cypress, CA 90630, USA Tel: +1 714 230 8200 Fax: +1 714 230 8173
© 2008 Philips Group. All Rights Reserved.
Loading...