STORK TRONIC ST501-KU3KA.12P User Manual

ST501-KU3KA.12P
Controller for cooling applications Order number 900220.02 0
As of: 23.03.2015, software V2.24
Product description
The microprocessor-controlled controller ST501-KU3KA.12P consists of a service and a separate power pack plate and is used for thermostatic temperature regulation in simple refrigerating plants. It is supplied with 230V AC and has four relay outputs as well as an exit for a DC voltage fan. The relays can be used for different functions, e.g. for a compressor, a defroster, an alarm relay, etc.. (see parameters U1-U4). The two resistance sensors seize the refrigerating chamber temperature and the evaporator temperature.
Sensor: PTC Range: -55...99 Front size: 106mm x 68mm Panel cut-out: 87.5mm x 56.5mm Tightness: front IP65 Connector: cage clamp
Customised Characteristics:
S1=2; P5=0; r1=2; r2=10; c3=2; d0=3; d1=1; d2=5; d3=20; d7=0; A1=-5; A3=240; A6=0; F5=0; F7=1; F8=71; F9=71; F10=5; b1=4; U3=6;
_C
Order No.: 900220.020 V2.24 1/11
Order No.: 900220.020 V2.24 2/11
SOFTWARE .12
Para­meter
Function
Adjustment range
Standard setting
Customer setting
S1
Setpoint
r1...r2
0.0°C
2.0°C
1
2
3
4
5
6
Adjustment options
Key 1: UP
Defrosting can be started any time by pressing the UP-key for 3 seconds. During the process of defrosting the respective LED is illuminated. The LED flashes if defrosting is requested, but may not be started yet due to interlock conditions.
Key 2: DOWN The DOWN key, among other functions, can acknowledge an alarm. The internal buzzer is then switched off.
Key 3: (if available) Different functions are assigned to this key by help of parameters, see parameter b1. (direct switching of a contact, standby function…). The key must be pressed for at least half a second.
Key 5: SET While SET key is pressed, the setpoint is indicated. In addition, the SET key is used for setting parameters .
Key 6: Standby With this key the controller is switched to standby mode. Pressing the key a second time, restarts the unit. The key can be deactivated by setting the respective parameter, see parameter b3.
First control level: Parameter setting for the main setpoint.
If none of the keys is pressed, the display indicates the actual value of the temperature. Pressing the SET key, the setpoint shows on the display. If the setpoint is to be changed, the SET key is to be kept pressed while adjusting the setpoint with the keys UP and DOWN. Please note that the setpoint can only be changed within the set setpoint limits.
General reference
Note that the value is transferred to the captive memory and is safe also after power failure.
Order No.: 900220.020 V2.24 3/11
Para­meter
Function
Adjustment range
Standard setting
Customer setting
r0
Hysteresis for the compressor contact
1...15 K
2 K
P2
Indication actual value of sensor F2
-
PA
Access to parameter list of the third Password:: -19
-99...+99
0
Para­meter
Function
Adjustment range
Standard setting
Customer setting
P0
Indication of actual value of sensor F1
P1
Calibration sensor F1, actual value correction
-9.9 ... +9.9 K
0.0 K
P2
Indication of actual value of sensor F2 (only available if P40)
P3
Calibration sensor F2, (only available if P40)
-9.9 ... +9.9 K
0.0 K
P4
Evaluation of sensor F2
0: not evaluated 1: evaluated as evaporator sensor
1
P5
Indication mode
0: integrals 2: accuracy 0,1 °C
1 0
P6
Display unit, indication in standby
0: Fahrenheit (“AUS”)
3: Celsius (“OFF”)
1
Second control level: Setting of control parameters
The parameters can also be set in standby mode. Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list containing frequently used parameters (the complete list of all parameters is to be found on the third control level). With the UP and DOWN keys the list can be scrolled in both directions. Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or DOWN key at the same time the value can be adjusted. Return to the initial position takes place automatically, if no key is pressed for 45 seconds, or by simultaneously pressing the UP and DOWN key for approx. 4 seconds.
control level
Parameter P2 is only indicated if P4 0.
Third control level (all parameters): Setting of control parameters
Access to the third control level is granted when selecting parameter PA on the second control level. Parameter PA is to be set at '-19'. Then the key UP and DOWN have to be simultaneously pressed for approx.. 4 seconds which will give access to the third control level, beginning with parameter P0. With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will give you the value of the respective parameter. By pressing the UP or DOWN key at the same time the value can be adjusted. Return to the initial position takes place automatically, if no key is pressed for 45 seconds, or by simultaneously pressing the UP and DOWN key for approx. 4 seconds.
actual value correction
mode
Order No.: 900220.020 V2.24 4/11
1: accuracy 0,5 °C
1: Celsius (“AUS”) 2: Fahrenheit (“OFF”)
Para­meter
Function
Adjustment range
Standard setting
Customer setting
P7
Sensor type
11: Pt100 2-wire
22: NTC 2-wire
P8
1: not active measuring values
r0
Hysteresis for the compressor contact
1...15 K
2 K
r1
Setpoint limitation (minimum)
-50 °C...r2
-50 °C
2.0°C
r2
Setpoint limitation (maximum)
r1...+150 °C
50 °C
10.0°C
r3
Switching sense of compressor
0: cooling 1: heating
0
c0
Start protection of the compressor after "cooling on"
0...240 min.
0 min.
c1
Start protection after com pr. start
0...240 min.
5 min.
c2
Start protection after compr. stop
0...240 min.
3 min.
c3
Function in the case of error of
0: relay off 2: emergency operation
0 2
d0
Defrosting interval
0 = inactive, no defrosting
1...99 h
8 h 3 h
d1
Defrosting mode
0: electrical 1: with hot gas
0 1
d2
Defrosting temperature
-50...+150 °C
10 °C
5.0°C
d3
Defrosting time limit
1...99 min.
30 min.
20 min.
d6
Indication of the refrigerating defrosting
0: actual temperature before the start of defrosting
1
d7
Drainage time
0...15 min.
2 min.
0 min.
A0
Hysteresis for alarm
1...15 K
2 K
-5 K
A1
Minimum limit value
-99.0 ... -0.1 K; 0 = inactive
-10 K
A2
Maximum limit value
+0.1...+99.0 K ; 0 = inactive
10 K
A3
Alarm suppr. time after “cooling on”
0...240 min.
120 min.
240 min.
A6
Alarm suppression time after temperature alarm
0...240 min.
2 min.
0 min.
A7
Alarm suppression time after defrosting
0...240 min
15 min.
A9
Switching sense alarm contact
0: relay on 1: relay off
1
F4
Defrosting behaviour
0: ventilator off during defrosting 1: ventilator on during defrosting
1
F5
Ventilator deceleration time after defrosting
0...240 min.
2 min.
0 min.
F7
Ventilator function at cooling
1: always on
on and sensor F2 < sensor F1
2 1
F8
Ventilator revolution number at normal cooling operation
0..100%
100
71
F9
Ventilator revolution number at defrosting
0..100%
100
71
F10
Kick-start
0..60s
0
5
(applies to both sensors)
Software filter (applies to both sensors)
sensor F1
21: PTC 2-wire 22: PT1000 2-wire
2...64: average value with 2 ... 64
1: relay on
21
8
chamber temperature during
operation
1: temperature determined just
2: on or off together with the compressor 3: on whenever the compressor is
Order No.: 900220.020 V2.24 5/11
Para­meter
Function
Adjustment range
Standard setting
Customer setting
b1
Function key A
0: no function
5: actual value sensor F2 (toggle)
0
b2
Function key B (if available)
see b1
0
b3
Function standby key
0: no function 1: controller on/off (standby)
1
b11
Function switching input E1
0: no function
standby mode
0
b12
Function switching input E2
see b11
0
b13
Function switching input E3 (if available)
see b11
0
b14
Function switching input E4 (if available)
see b11
0
U1
Exit connection K1
0: no connection
9: on, if controller on
1
U2
Exit connection K2
see U1
2
U3
Exit connection K3 (if available)
see U1
3
6
U4
Exit connection K4 (if available)
see U1
4
L0
Own ST-Bus address
0: inactive 1 ... 250
0
L40
Mask for Low-Byte of Status 0 (ST-Bus)
0 ... 255 (binary coded)
Pro
Program version
(if available)
1: controller on/off (standby) 2: Setpoint thermostat 2 (Y1) 3: relay directly, switched off in standby mode 4: relay directly, regardless of standby mode
1: controller on/off (standby) 2: starting defrost 3: relay directly, switched off in standby mode 4: relay directly, regardless of
1: connection to compressor 2: connection to defrost 3: connection to ventilator 4: connection to alarm 5: connection to thermostat 2 6: connection to key A, E1 or E3 7: connection to key B, E2 or E4 8: connection to buzzer
4
Order No.: 900220.020 V2.24 6/11
Parameter description:
The following values can change the equipment characteristics
and are therefore to be set with utmost care.
P0: Indication actual value of sensor F1
The here indicated temperature presents the sum of actual measured value of feeler F1 and the actual value correction according to parameter P1.
P1: Calibration sensor F1, actual value correction
This parameter allows the correction of actual value deviations caused for example by sensor tolerances or extremely long sensor lines. The regulation measure value is increased or decreased by the here adjusted value.
P2: Indication actual value of sensor F2
The here indicated temperature presents the sum of actual measured value of sensor F2 and the actual value correction according parameter P3.
P3: Calibration sensor F2, actual value correction
This parameter allows the correction of actual value deviations caused for example by sensor tolerances or extremely long sensor lines. The regulation measure value is increased or decreased by the here adjusted value.
P4: Evaluation of sensor F2
Sensor F2 can be used for the determination of the evaporator temperature (P4=1) or for the second thermostat (P4=2). If, in simpler refrigerant plants only the refrigerating chamber sensor is used, the feeler entrance for sensor F2 as well as its data recording (P4=0) can be deactivated here. Among other, parameter d2 has no meaning in the deactivated condition.
P5: Indication mode
The actual value can be indicated with diff er ent accuracy. Actual values and parameter values are always set for highest accuracy.
P6: Display unit, indication in standby mode
This parameter allows display settings (°F or °C) and ("AUS" or "OFF") in standby mode.
P7: Sensor type
This parameter makes it is possible to adjust the feeler type of both sensors. Depending on the hardware not all sensor settings are possible.
P8: Filter
This parameter can determine by how many measured values an average value is to be formed.
r0: Hysteresis for the compressor contact
Parameter r0 sets the temperature margin between switching off and switching on of the compressor. A small hysteresis permits a more exact regulation, however also leads to more frequent switching of the compressor. The hysteresis is set one-sided above the setpoint.
r1: Setpoint limitation (minimum) r2: Setpoint limitation (maximum)
These parameters limit the adjustment range of the setpoint S1, in order to avoid that the end user sets inadmissible values for the plant. The entire adjustment range is equivalent to the maximum operating range of a PTC sensor.
r3: Switching sense of the compressor c0: Start protection of the compressor after
"cooling on"
After cooling is switched on (e.g. by switching on the mains voltage) the start of the compressor is retarded until the protection running time is over. This secures e.g. that several cooling units do not start at the same time and load the electricity supply net.
c1: Start protection of the compressor after compressor start
This time protection starts when the compressor is switched on. After switching the compressor off, a renewed switching on is impossible until this protection time runs out. This prevents from too frequent switching-on of the compressor and thus increases its life span.
c2: Start protection of the compressor after compressor stop
This time protection starts when the compressor is switched off. After switching the compressor off, a renewed switching on is impossible until this protection time runs out.
c3: Function in the case of error of refrig erating chamber sensor F1
Here is determined whether the compressor keeps running or not in the case of an error of the refrigerating chamber feeler F1. When deep­freezing, the compressor should normally continue running, in order to prevent de-frosting of the goods. At the normal cooling range above 0 °C, a continuation, however, could lead to frost damages. In the operation mode "emergency operation" the compressor is switched on and off in 5 minute intervals. This results in a clock operation with 50 %
Order No.: 900220.020 V2.24 7/11
cooling performance.
d0: Defrosting interval
The defrosting interval defines the time, after which a defrosting process is started. With the beginning of the defrosting process, the defrosting interval starts anew, which results in periodic defrosting in firm intervals. Defrosting can also be started by pressing the key "manual defrosting" for at least 3 seconds. This automatically restarts the defrosting interval. After switching-on cooling, the controller immediately initiates cooling and starts the first defrosting process after this interval.
d1: Defrosting mode
This parameter determines whether defrosting is effected by an electrical heating coil (d1=0) or by means of hot gas (d1=1).
d2: Defrosting temperature
The defrosting process is terminated when the evaporator has reached the adjusted temperature. (Always provide good thermal contact between evaporator sensors and lamellas). In case that defrosting takes too long, the time limit set in "d3" will come into effect.
d3: Defrosting time limit
Here the maximal defrosting time can be adjusted. According to this time frame, defrosting is terminated even if the evaporator is not warm enough to be ice­free.
d6: Indication of the refrigerati n g chamber temperature during defrosting
It is to be assumed that the refrigerating chamber temperature slightly rises during the defr os ting process. d6=0 indicates the actual refrigerating chamber temperature during the defrosting process. d6=1 indicates the temperature determined just before the start of defrosting until the setpoint of the refrigerating chamber is reached again after the defrosting process is completed. Thus, an irritation of the operator during defrosting can be avoided. In the case of emergency, the display flashes and the actual temperature of the refrigerating chamber is indicated.
d7: Drainage time
Completed defrosting is immediately followed by a drainage period, in order to let the evaporator drip off. During drainage time, the exits compressor and ventilator are switched off .
A0: Switching hysteresis for alarm
The hysteresis of the alarm contact is asymmetrically, set downward at the maximum alarm value upward at the minimum alarm value.
A1/A2: Minimum/maximum limit values
The limit values serve for monitoring of the refrigerating chamber temperature. They are relative, i.e. going along with the setpoint S1 of the refrigerating chamber. Alarm is released when exceeding maximum limit value or when falling below the minimum limit value: The actual value display flashes, the buzzer (if available) goes off intermittently and the actual temperature of sensor F1 is indicated (if there is no sensor error). At A1=0 or A2=0 the respective limit value alarm is inactive. The buzzer can be turned off with the DOWN key, the display continues flashing until the alarm is turned off.
A3: Alarm suppression time after “cooling on”
After switching cooling on, an alarm is suppressed for the adjusted time, i.e. the refrigerant plant can get to work temperature without releasing alarm.
A6: Alarm suppression time after temperatu re alarm
If the refrigerating chamber temperature exceeds the limit values adjusted at A1, A2, normall y a temperature alarm should be released. With the suppression time set at A6 the alarm release can be delayed.
A7: Alarm suppression time after defrosting
Temperature alarm is avoided for the adjusted time after defrosting, in order to enable the plant t o get back to the normal operating conditions (see A1, A2).
A9: Switching sense alarm exit
Depending on application, the alarm exit requires a normally-closed or a normally-open contact. At setting A9=1 the relay tightens in normal operation and opens in the case of emergency. That way also a voltage failure of the controller can be detected (relay dead = alarm) for an external alarm chain.
F4: Defrosting behaviour
At F4=0 the ventilator is switched off during defrosting. At F4=1 the ventilator continues to run also during defrosting (normal cooling range above 0°C).
F5: Ventilator deceleration time afte r defrosting
Following drainage time d7, start of the ventilator can be delayed until the evaporator has sufficiently cold air again. If the ventilator started immediately, the warm air resulting from the defrosting process would probably be blown into the refrigerating chamber.
Order No.: 900220.020 V2.24 8/11
F7: Ventilator function at cooling operation
At F7=1 the ventilator is always on (except possibly for a defrosting process, see parameter F4). At F7=2 the ventilator is always on or off together with the compressor. At F7=3 the ventilator is switched on whenever the compressor is on and the evaporator temperature (sensor F2) is below the refrigerating chamber temperature (sensor F1). The ventilator is switched off whenever the evaporator is switched off, whereas parameter F5 is not active. In the case of sensor error the ventilator reacts as in the setting F7=2.
F8: Ventilator revolution number at normal cooling operation
This parameter determines the ventilator revolution number at normal cooling operation.
F9: Ventilator revolution number at de frosting
This parameter determines the ventilator revolution number at defrosting.
F10: Kick-start (in seconds)
If necessary, this is an option to set a time during which the ventilator starts with the maximum number of revolutions for stable operation. This parameter is only efficient, if the ventilator is newly started.
b1: Function key A b2: Function key B (if available)
At setting = 0 the respective key has no function. At setting = 1 the controller is switched to standby mode At setting = 2 the key is linked with the function “setpoint Y1 for the thermostat 2 indicate/adjust” At setting = 3 a relay (indicated with parameter Ux) can be switched on or off directly with the key. In standby mode the key is locked and the corresponding relay switched off. After restarting the corresponding relay remains switched off. At setting = 4 a relay (indicated with parameter Ux) is switched despite of the standby mode. The condition of the exit is maintained until the key is pressed again or until it is changed by an external switching entrance. After net interruption, the condition before power failure is re-installed. At setting = 5 the actual value of sensor 2 can be indicated. At setting P4=0 the key has no function.
b3: Function key 3 (standby)
At setting b3=0 the function of the key can be deactivated.
b11: Function external entrance E1 b12: Function external entrance E2 b13: Function external entrance E3 b14: Function external entrance E4
Depending on existing hardware there are no or not all external entrances. At setting = 1 the controller is switched to the standby mode. At setting = 2 defrosting of both controllers is started. At setting = 3 a relay (indicated with parameter Ux) is switched on or off directly. In standby mode it is locked and the relay is switched off. At setting = 4 a relay is switched directly (indicated with parameter Ux) regardless of the standby mode. After net interruption the condition before power failure is re-installed.
U1: Exit connection K1 U2: Exit connection K2 U3: Exit connection K3 U4: Exit connection K4
Depending on existing hardware there may not be all output relays. This parameter assigns the respective relay to the internal controller exits, to function key 1 or 2, to one external entrance or the buzzer. At setting =6 or =7 the relay is switched manually. It changes its condition with each pressure of the key and adopts the condition of the respective switching entrance whenever the latter changes. If the corresponding key or switching entrance has not been released for this function (see parameters b1, b2 and b11 to b14), the relay remains switched off. The buzzer connection in its function is comparable to the alarm connection. The buzzer, however, can be switched off with the DOWN key.
L0: Own ST-Bus address
Reserved for ST-Bus
L40 :Mask for Low-Byte of Status 0 (ST-Bus)
Reserved for ST-Bus
Pro: Program version
This parameter shows the program version.
Order No.: 900220.020 V2.24 9/11
Status messages
Message
Cause
Error elimination ON/OFF
Standby modus, no regulation
Switch on by key or switching input
Temperature
Refrigerating chamber temperature (parameter A1, A2)
E0
Refrigerating chamber sensor F1 error,
Control sensor. parameter c3.
E1
Sensor F2 error,
Control sensor.
At setting [c3=2] see parameter Y6.
EP
Data loss at parameter memory (basic contact 1 and 2 are dead)
If error cannot be eliminated by switching on/off, the controller must be repaired.
indication flashes
flashes
flashes
beyond alarm limits
break or short-circuit
break or short-circuit
Controller operates according to with
At setting [c3=1] the controller operates in timed defrosting modus (defrosting time as set in d3).
Error message E0, E1 and EP changes in the display with the actual value of sensor F1, unless the latter is defective. This happens independently from the selected indication mode. After the error is eliminated and confirmed with the DOWN key, the previously set indication mode becomes active again.
If there is a connection to the buzzer with parameters U1... U4, the buzzer can be switched off with the DOWN key.
Order No.: 900220.020 V2.24 10/11
Technical data of ST501-KU3KA.12P
Measuring input F1: Temperature sensor, refrigerating chamber F2: Temperature sensor, evaporator
Measuring range: PTC (KTY81-121) -50°C...+130°C PT1000 -99°C...+300°C NTC -40°C...+105°C Pt100 -80°C...+400°C (resistance < 1 Ohm) Accuracy: ±0.5K ± 0.5 % at 25°C, without sensor ±1K ± 0.5 % of scale range (0 – +55°C), without sensor
Outputs K1: Relay, 30(6)A 250V~, normally-open contact, function see U1,
permanent current max. 16(6)A, limited by connectors and/or conductive strips
K2: Relay, 16(2.2)A 250V~, normally-open contact, function see U2 K3: Relay, 16(2.2)A 250V~, normally-open contact, function see U3 K4: Relay, 16(2.2)A 250V~, normally-open contact, fan
voltage output for DC-fan: 0..24V, max. 800mA (corresponds 20W)
Display
One 3-digit LED-Display, height 13 mm, for temperature indication Three LEDs, diameter 3mm, for status display of the outputs
Power supply
230V 50/60Hz, power consumption max. 40 VA
Connectors
Cage clamp 5 x 3-pole, for cable up to 2.5mm² Cage clamp 1 x 6-pole, for cable up to 1.5mm²
Ambient conditions:
Storage temperature: -20...+70°C Operating temperature: 0...+55°C Relative humidity: max. 75% without dew
Weight
ca. 500g, without sensor
Enclosure
Front IP65, IP00 from back
Installation data
The unit is to be installed in an instrument panel. Front size: 106 x 68 mm Installation depth: ca. 60 mm with connector Power plate: 100 x 160mm
Order No.: 900220.020 V2.24 11/11
Loading...