Storage Battery Systems SBS SBS-H2 Manual

SBS-H2
Hydrogen Gas Detector Kit
For battery charging rooms and other areas where hydrogen gas may be present
INSTALLATION, OPERATION & MAINTENANCE
INSTRUCTIONS
Protects Life, Property and Profits
Electrical Safety – UL 61010-1
Compliant with NFPA 70E® and IEEE Recommendations
Pollution Degree 2
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
Warnings
This detector is added protection, not a substitute for prudent safety measures, for
where hydrogen gas may be present.
For large or highly-sensitive areas, SBS recommends installing additional sensors for
increased coverage area.
The hydrogen sensor does not provide protection from fires or hydrogen explosions.
The relay contacts are intended to be connected to a safety system that would enable audible alarms, system shutdown and ventilation.
Ensure that installation complies completely with all relevant Local, State, Federal and
OSHA safety and health regulations.
If a sensor enters warning or alarm mode there is a risk of combustion or explosion. To
avoid injury, leave the area immediately.
The sensor is calibrated for operation in air. Tampering with the sensor or operation in
environments that are exposed to other types of gases can lead to inaccurate readings, false alarms or permanent damage.
Please see troubleshooting guide for list of gases and compounds that may damage or
alter a sensor’s performance.
Uncured silicone compounds or extended exposure to silicone off gassing can give
inaccurate readings or false alarms on a sensor.
SBS-H2 Users Manual, Rev. 07-17-TNEMH2 Page 2 July 2017
Table of Contents
Description
Page
Section
Overview 5 1.0
Benefits 5 2.0
How It Works 5 3.0
Specifications
6
4.0
Sensor 7 5.0
Main Control 7 6.0
Installation
8 - 11
7.0
Operation
12
8.0
Electrical Testing
13
9.0
Testing the Sensor
13
10.0
Troubleshooting/Maintenance
14 - 15
11.0
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
SBS-H2 Users Manual, Rev. 07-17-TNEMH2 Page 3 July 2017
TestEquipmentDepot.com
Main Unit and Accessories
Part No.
Description
SBS-H2
Hydrogen Gas Detector Includes: one (1) main control, one (1) H2-SENSOR and one (1) 25 ft. cable
H2-JB
Junction Box with Knockouts, 4 11/16" X 4 11/16", Metal
H2-SENSOR
Hydrogen Gas Sensor Only (No Cable)
H2-SENSOR-25FT
Additional/Replacement Hydrogen Gas Sensor with 25 ft. Cable
H2-SENSOR-50FT
Additional/Replacement Hydrogen Gas Sensor with 50 ft. Cable
H2-SENSOR-100FT
Additional/Replacement Hydrogen Gas Sensor with 100 ft. Cable
H2-TESTKIT
Field Test Kit for SBS-H2 Includes: case, regulator, tubing and two (2) cylinders of H2 gas (1% and 2%)
H2-TESTKIT-INTL
Field Test Kit for SBS-H2 Includes: case, regulator and tubing – does not include H2 gas cylinders
E190399
110Vac 3 Prong AC Cord, 10 Ft., 18-3 AWG
SBS-H2 Users Manual, Rev. 07-17-TNEMH2 Page 4 July 2017
1.0 Overview
Batteries on charge emit hydrogen gas as part of the chemical reaction of recharge. Concentrations of 4.1% to 75% H2 mixed with air can be explosive. Sparks or hot surfaces can ignite hydrogen gas.
The SBS-H2 hydrogen detector acts as a monitor and provides a visual and audible alarm when hydrogen is detected. The unit also has a 1% concentration relay that can trigger exhaust fan operation and a 2% concentration relay that can trigger a building management/alarm system (via SCADA/Modbus) before the gas reaches the lower explosive limit (LEL) of 4.1%.
2.0 Benefits
In addition to protecting employees and property, the detector may also reduce the following costs:
Energy Efficiencies
Instead of continuously running an exhaust fan to prevent hydrogen gas accumulation, use the detector to activate a fan only if the gas concentration reaches 1%.
Insurance Savings
Installation of a detector in areas where batteries are charged may result in a premium reduction.
3.0 How it Works
Should the concentration of hydrogen gas in the air surrounding the sensor reach 1% by volume, the “1% Warning” yellow LED will light up on the main control of the unit. In addition, the 1% internal relay will energize and can be used to activate a remote exhaust fan.
Should the hydrogen gas concentration reach 2% by volume, the “2% Alarm” red LED will light up, the strobe will flash and an audible alarm will sound. In addition, the 2% internal relay will energize and can be used to activate a building management/alarm system (via SCADA/Modbus).
The SBS-H2 provides automatic operation, continuous detection, high sensitivity, stability and solid­state reliability. The unit uses 120/240 Vac 50/60 Hz and/or 12 - 48 Vdc operating voltages.
SBS-H2 Users Manual, Rev. 07-17-TNEMH2 Page 5 July 2017