10
Filling of the system
6. Now you have to drain the following quantity of liquid:
Quantity A: 0,17 l for each liter of liquid content in the
DrainMaster (for 10 l liquid content in the DrainMaster
= 1,7 l)
Quantity B: 0,04 times installation content (for 30 l
installtion content = 1,2 l)
Total draining quantity = quantity A + quantity B (example 1,7 l + 1,2 l = 2,9 l)
7. Close the shut-off valve at the pressure-side of
the pump again and ll in quantity A. By doing so
the necessary prepressure of the installation can be
reached.
8. Now the report of the controller should disappear
or the collector temperature should appear. If an error
report or the report „lling level reached“ is shown,
the installation is overlled and has to be drained until
the report diappears.
9. Open the shut-off valve, close the lling and draining valve and switch on the pump. Check the functionality of the installation and switch over to an automatic operation.
Installation without level indicator
1. Close the shut-off valve in the collector back ow
(pressure-side of the pump).
2. Loosen the upper connection at the DrainMaster.
3. Open the lling and draining valve, connect the
lling pump and slowly ll the installation until the
DrainMaster is completely lled with liquid.
4. Close lling and draining valve and open the shut-
off valve (pressure-side of the pump).
5. Slowly rell the liquid until the DrainMaster is completely completely lled.
6. Now you have to drain the following quantity of liquid:
Quantity A: 0,17 l for each liter of liquid content in the
DrainMaster (for 10 l liquid content in the DrainMaster
= 1,7 l)
Quantity B: 0,04 times installation content (for 30 l
installtion content = 1,2 l)
Total draining quantity = quantity A + quantity B (example 1,7 l + 1,2 l = 2,9 l)
Attention!
When lling the installation, the solar uid must not
be warmer than 25 °C!
The circulating pump must not be working while lling.
Filling under cloudy skies
The prepressure of the installation is calculated as
follows:
Prepressure in bar = static height in meter / 10 + 0,2
Filling in sunshine
The prepressure of the installation depends on the
temperature of the collector during the lling.
Rule of thumb for the prepressure:
Prepressure in bar = static height in meter / 10 + 0,2
+ gure stated below:
For collector temperature of approx. 50 °C + 0,1 bar
For collector temperature of approx. 100 °C + 0,2 bar
For collector temperature of approx. 150 °C + 0,3 bar
For collector temperature of approx. 200 °C + 0,4 bar
Installation with level indicator
1. Close the shut-off valve in the collector back ow
(pressure-side of the pump).
2. Open the lling and draining valve of the safety
device.
3. Connect the lling pump at the lling and
draining valve at the suction side of the pump. Fill
the installation slowly until the probe presents the
maximum lling level (when using special controllers,
the report „maximum lling level reached“ is going
to be shown).
4. Close lling and draining valve and open the
shut-off valve (pressure-side of the pump).
5. Slowly ll in the liquid until the probe presents
the maximum lling level once again (when using
special controllers, the report „maximum lling level
reached“ is going to be shown).