STI CMCP423VTA User Manual

Page 1
CMCP423VTA USER GUIDE
1
Rev. 1.0
A
CMCP423VTA
Compact Vibration Switch Manual
Page 2
CMCP423VTA USER GUIDE
2
Rev. 1.0
A
Contents
SAFEY INSTRUCTIONS................................................................................................................ 3
FUNCTIONS AND FEATURES ..................................................................................................... 3
INSTALLATION ............................................................................................................................. 3
ELECTRICAL CONNECTION ..................................................................................................... 4
SETTINGS ........................................................................................................................................ 4
MEASUREMENT RANGE ............................................................................................................. 4
SWITCHING OUTPUT BEHAVIOUR ......................................................................................... 5
OPERATING AND DISPLAY ELEMENTS ................................................................................. 6
MAINTENANCE, REPAIR AND DISPOSAL .............................................................................. 7
TECHNICAL PERFORMANCE ................................................................................................... 7
ELECTRICAL ................................................................................................................................. 7
MECHANICAL................................................................................................................................ 7
ENVIRONMENTAL ....................................................................................................................... 7
Page 3
CMCP423VTA USER GUIDE
3
Rev. 1.0
A
An instruction is indicated by "►": Example: ► Check whether the unit operates correctly.
Important note Non-compliance can result in malfunctions or interference
Information Supplementary note
SAFEY INSTRUCTIONS
Please read the product description prior to set-up of the unit Ensure that the product is suitable for your application without any restrictions
The unit conforms to the relevant regulations and EC directives.
Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application
That is why installation, electrical connection, set-up, operation and maintenance of the unit must only be carried out by qualified personnel authorized by the machine operator
FUNCTIONS AND FEATURES
The vibration sensor detects the vibration in the system (measured / evaluated physical unit = vibration velocity) this is converted into an analogue signal at the current output The switching output behavior is determined using the two setting rings
INSTALLATION
► Mount only in a thick housing wall (e.g. transport thread).
► Ensure that the signal direction is correct ► Ensure a safe vibration transmission and allow no elastic intermediate layers ► Tighten the sensor with a tightening torque of 15 Nm
Page 4
CMCP423VTA USER GUIDE
4
Rev. 1.0
A
Velocity Range
0-25 mm/sec or 0-50mm/sec 0-1 IPS or 0-2 IPS
Iout
4-20mA
Response delay
1- 60 sec
ELECTRICAL CONNECTION
The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to.
SETTINGS
RMS Set Effective value of the switching threshold, defining the limit value of the vibration velocity
Delay Set Time in seconds during which the limit value must be effectively above the switching
threshold (RMS Set) to activate the switching output (normally closed pin 4)
MEASUREMENT RANGE
Page 5
CMCP423VTA USER GUIDE
5
Rev. 1.0
A
SWITCHING OUTPUT BEHAVIOUR
1: Time delay after the switching threshold has been exceeded 2: Time delay after the switching threshold has been exceeded 3: Switch-off 4: Switching threshold 5: Delay V
= vibration
ss
velocity t = time
Implementation of the time delays
The time delay starts when the defined switching threshold is exceeded (1) / (2)
U
The time delay is cancelled when the value falls below the switching threshold (without switch-off) the switch-off is triggered when the switching threshold is exceeded during a full time delay (3)
Page 6
CMCP423VTA USER GUIDE
6
Rev. 1.0
A
OPERATING AND DISPLAY ELEMENTS
1) locking ring
2) setting rings (manually adjustable after unlocking)
3) LED green: voltage supply
4) M8 process connection
5) LED yellow: lights when switching threshold and time delay areexceeded
6) setting marks
To achieve the setting accuracy: first position the rings to the lower end stop value, then set the requested value
Page 7
CMCP423VTA USER GUIDE
7
Rev. 1.0
A
MAINTENANCE, REPAIR AND DISPOSAL
The operation of the unit is maintenance-free. It is not possible to repair the unit. After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.
TECHNICAL PERFORMANCE
Velocity Ranges: to be specified with order, ±10% Nominal 80Hz at 22°C Frequency response: 10Hz (600cpm) to 1kHz (60kcpm) ± 5% - ISO10816 False Trigger Delay: Adjustable up to 60 seconds Trip Setting: Fully adjustable
ELECTRICAL
Current Output: 4-20mA DC proportional to Velocity Range Supply Voltage: 18-32 Volts DC Switching Output: NC, PNP up to 500mA Display OK LED: Green Trip LED: Yellow Current Consumption: 18-30volts DC at 50mA
MECHANICAL
Case Material: Stainless Steel 316L/Plastic Mounting Torque: 15Nm Weight: 116gms (nominal) Screened Cable Assembly: CMCP604M-01 (straight),
CMCP604M-02 (right angle)
Mounting Threads: M8 x 1.25mm male
ENVIRONMENTAL
Operating Temperature Range: -25 to 80ºC Sealing: IP67 Maximum Shock: 100g EMC: Reverse Polarity: Protected MTBF: 510 years
EN61326-1:2013
Page 8
Connection Oetais of
Cable
Assembly
Outs:ide
1/1,ew
ot
4 PinM12 Conneictor
Brown core
Vo!hlte
()()(0
Saeen
Blue
Core
BIJ
ckCore
Freeend
F"RMtCW:.d
QO!IHSIII.-IS
'MIiie
6-
t,"\11
oore,,\llilln ro,
HS,100, HS,102, HSl20,HS-4l0
iNl'IU-
81W-n,wtr1,&lllw:kU$c,,:Ul')r
HS,100T,H!l-411 & H!l-i2S
WI\Q-i,
...
Con
necter
sealed t
o I
P66
only
when
connected to theacœlerometer.
Materials of Cable
8
10r,t1, •
t1n..a11• &1:1111et0011t11foolld
to,-
H$-i20l f;
H$.cttl' &IHl!!'il,
Conductor,bare soft oopper wire
co
to
frea of
seawa
Rèsistance
<57
2
KV