STI-1229-HAZEnclosure only
STI-1229HTR-HAZEnclosure with 110 VAC Heater Option
STI-1229HTR240-HAZ Enclosure with 240 VAC Heater Option
Features:
• Hazardous Classification Class II Groups F&G Div. 2 and Class III locations.
• Maintains operating strobe appliance temperature with external
temperatures to -70°F (-57°C).
• Enclosure tested to NEMA 4X Standards. Equivalent to an IP 66 rating.
• UL/cUL Listed.
• CSFM requires local approval only.
• Protects ADA compliant strobes to UL 1971 Standards.
Operation:
For use in areas where temperature or environmental conditions exceed the
operating range of fire strobe signaling devices. Unit requires 24 VDC
continuous for fan operation and 110 VAC or 240 VAC for heater, as well as
power for strobe operation and supervision for temperature indicator. Fan
runs continuously to maintain uniform temperature. Heater cycles as
required to maintain operating temperature range for listed strobes.
We protect the things that protect you.
Page 2
Warnings
!
The enclosure is used to protect UL/cUL listed 1638 and 1971 visual
notification appliances at temperatures down to -70˚F (-57˚C). It is the
installer’s responsibility to comply with NEC 70 Articles 502 and 503, NFPA72,
and other applicable fire and electrical codes. Conduit or raceway paths need
to be sealed as near to the enclosure as possible. Installer should have
maintained supervision over the low temperature thermostat. The low
temperature monitoring thermostat makes the circuit at +32°F (0°C) and
clears the circuit at +50°F (+10°C). This listing requires that the fire alarm
supervisory control module be only of the latching type. On the appliance
mounting plate is a label where you should record the installation date. Also
include below the serial number and installation date on the instruction sheet
for quick reference.
Serial Number ____________________________________
Installation Date __________________________________
Installation Notes
1. The enclosure is rated to protect signaling appliances indoors and
outdoors and in areas of direct weather exposure.
2. When covering fire-signaling appliances with the enclosure, some light
loss occurs. Please follow the guidelines listed during installation.
3. Strobe light loss values for respective manufacturers are shown on page
3. To determine the new composite candela value of the use with the
guard refer to the sample calculation shown on page 3 for a
manufacturer’s strobe.
4. Record the manufacturer’s candela value as “A” and the light loss value
as “B” and the assembly value as “C”. Example: A 60 candela strobe with
a 30% light loss transmission value. Value “A” is now 60. Value “B” is
(60 times 30% or 0.30) in this case 18.
5. Now value “C” is value “A” minus value “B” or 60-18 = 42 candela light
source. Now refer to NFPA tables for proper room size that newly
established value “C” will work in. Then submittal installation drawings
must show the composite candela value in this example 42.
6. On a multiple candela value strobe such as 15/30/75 a calculation must
be done for each value and the drawing notation composite value for
each number on the strobe.
7. All field wiring within this enclosure must be rated for a minimum
operating range of 0ºC - 110ºC.
2
Page 3
Performance Review
ManufacturerCategory/ModelLight Loss
American Security Equip. Co. Select-a-strobe SL24W-15307536% Light Loss
Faraday270033% Light Loss
GentexSee note below*36% Light Loss
System SensorSS24110ADA35% Light Loss
*NOTE FOR GENTEX: GES24 may be followed by W, R or P.
Polycarbonate Cleaning Instructions
Rinse with water to remove abrasive dust and dirt. Wash with soap or mild
detergent, using a soft cloth. Rinse once more, then dry with a soft cloth or
chamois. Exercise caution when using water inside enclosure. Make sure unit
is completely dry inside before reassembling. (Do not use razor blades).
Specifications
Polycarbonate Enclosure:
Flammability:UL94 V-2
Wall Thickness:0.2 in (5.1mm)
NEMA Rating:4X, indoor and outdoor use
Hazardous Rating:Class II Groups F&G Div. 2
polycarbonate in normal use (one year on electro
mechanical and electronic components).
Fan:
24 VDC, 90 mAUL Recognized Component
Life:5 Years Continuous Duty
WARNING: The polarity of the circulating fan is important as it only
!
rotates in one direction with red lead being positive.
Gasket:
Material:Neoprene
Life:5 Years
3
Page 4
Installation Instructions
3/
4 in
.
(
25m
m
)
N
P
T
N
IP
P
L
E
(
N
O
T
P
R
O
V
ID
E
D
)
E
N
CL
O
S
E
D
B
A
CK
B
O
X
H
E
AT
E
R
A
S
S
E
MBL
Y
H
IGH
V
O
L
T
A
GE
T
E
R
MIN
AL
BL
O
CK
S
CR
E
W
#8
-
32 x
3/
8 in
.
(
4)
P
R
O
V
ID
E
D
S
T
R
O
BE
AP
P
L
IAN
CE
GA
S
K
E
T
(
1)
P
R
O
V
ID
E
D
S
O
L
ID
CL
E
AR
C
O
V
E
R
W
A
S
H
E
R
(
6)
P
R
O
V
ID
E
D
#8
-
32 x
3/
4 in
.
S
O
CK
E
T
CAP
S
CR
E
W
(
6)
P
R
O
V
ID
E
D
L
O
W
V
O
L
T
AGE
E
L
E
CT
R
ICAL
E
N
T
R
Y
1/
4 in
.
(
6.
3m
m
)
D
IA
.
H
O
L
E
A
N
CH
O
R
(
4)
P
R
O
V
ID
E
D
S
CR
E
W
#10 x
1 1/
2 in
.
(
4)
P
R
O
V
ID
E
D
L
O
W
V
O
L
T
A
GE
T
E
R
MIN
AL
BL
O
CK
3/
4 in
.
N
P
T
.
N
IP
P
L
E
(
N
O
T
P
R
O
V
ID
E
D
)
H
IG
H
V
O
L
T
A
G
E
E
L
E
CT
R
ICA
L
E
N
T
R
Y
AP
P
L
I
ANC
E
W
I
RE
3/
4 in
.
N
PT
H
U
B (
2)
P
R
OV
ID
E
D
(
W
IT
H
O
U
T
H
E
AT
E
R
(
1)
P
R
OV
ID
E
D
)
1
HEATER ASSEMBLY
HEATER
OVERTEMP SAFETY
THERMOSTAT
HIGH VOLTAGE
TERMINAL BLOCK
PIN 6
PIN 5
PIN 4
2 A FUSE
CONTROL THERMOSTAT
1
2
3
4
5
6
1
2
MOUNT BACKBOX TO WALL (Refer to Fig. 1)
1. Remove appliance heater assembly from back box and set aside.
2.Mount back box in desired location (wall mount only) using the four #10
x 1-1/2” screws and anchors (provided). Drill a 1/4” diameter pilot hole
for plastic anchors at spacing in Fig. 1.
3. Attach conduit hub to a 3/4” NPT nipple and conduit seal fitting to the back
box, top and bottom.
FIGURE 1
Note: A conduit seal fitting must be used on both top and bottom
conduit entries as close to the unit as possible. Use conduit seal CrouseHinds 3/4” EYSX 21 or equivalent. Conduit should be installed according
to applicable NEC and local codes.
4. Pull wiring into back box.
Note: High Voltage (110 or 240 VAC) wiring must enter thru bottom
conduit and low voltage and signaling wires must enter thru top conduit
and remain separated per NFPA
70, NEC, and local codes.
HIGH VOLTAGE WIRING (Refer to Fig. 2)
5. Connect high voltage:
Pin 6AC HOTL-1
Pin 5NeutralL-2
Pin 4Ground Ground
110 or 240 VAC power is “OFF”.
Refer to high voltage schematic
diagram on page 6.
110 VAC240 VAC
Make sure
FIGURE 2
4
Page 5
LOW VOLTAGE WIRING (Refer to Fig. 3 & Schematic drawings on Page 6)
HEATER ASSEMBLY
FAN
LOW VOLTAGE
TERMINAL BLOCK
LOW TEMP
WARNIN G
FAN POWER
STROBE
POWER
LOW TEMP WARNING
THERMOSTAT
STROBE
(NOT PROVIDED)
S
TROBE HOOK-UP
WIRE
HEATER ASSEMBLY
MOUNTING SCREW
STROBE MOUNTING BOSS
1
2
3
4
5
6
-
+
+
-
1
2
WARNING LABEL
6.Connect Supervisory Module Connect EOL device (not included) between
pins 1 and 2 of low voltage terminal block. Pins 1 and 2 should then be
connected to the fire alarm supervisory control module.
Note: Fire alarm supervisory control module must be of the latching type only.
Pin 1Alarm Supervisory
Pin 2Control Module
EOL
DEVICE
7.Connect Fan Power
Note: Fan will not operate if polarity is reversed. Refer to low voltage
schematic on page 6.
Pin 3-24 VDC
Pin 4+24 VDC
8.Connect strobe appliance power
Pin 5- 16-33 VDC
Pin 6+16-33 VDC
9.Attach heater assembly to back box using (4) #8-32 x 3/8” flat head
screws into heater assembly mounting bosses on back box (see Fig. 1).
Make sure all service wiring is gathered away from the heater and be
careful not to pinch wire under heater assembly. Fan must be mounted
toward top of
enclosure.
10. Wire strobe using
Teflon coated wire
provided. (WhiteP os i t i ve /B l a ck Negative)and
attach to the strobe
mounting bosses on
heater assembly.
11. Record installation
date on label and in
manual (page 2).
12. Install cover and
gasket with (6) #832 x 3/4” socket cap screws and (6) flat washers as shown in Fig. 4.
13. Turn all power to “ON” position.
Note: Fan runs continuously. This system requires three sources of power:
1. 110 or 240 VAC heater on the load side of the fuse holder.
2. 24 VDC power source for the circulating fan. Check fan to see if
operating; if not check polarity and reverse then try again
3. 16-33 VDC fire alarm notification circuit for strobes and temperature
warning monitor.
FIGURE 3
5
Page 6
Schematic Diagrams
2
AMP FUSE
OVERTEMP SAFETY
1
2
4
3
5
6
CONTROL
110 OR 240 VAC
SINGLE PHASE
4
5
3
6
1
2
STROBE
PWR
FAN
PWR
TEMP
WARNING
SUPERVISOR
_
+
+
_
FAN
LOW TEMP WARNING
STROBE (16-33VDC 600mA)
S
LOW VOLTAGE CIRCUIT
HIGH VOLTAGE CIRCUIT
TERMINAL
BLOCK
TERMINAL
BLOCK
CHASSIS
HEATER
EOL DEVICE
SUPPLIED BY
CUSTOMER
OPEN @ 70˚F
CLOSE @ 50˚F
OPEN @ 120˚F
CLOSE @ 80˚F
OPEN @ 50
˚
F
CLOSE @ 32˚F
(24VDC 90mA)
110 OR 240 VAC 50/60 Hz
100 WATTS
6
Page 7
9.37 in.(238mm)
PRODUCT DIMENSIONS
2.87 in.(73mm)
APPLIANCE MOUNTING
BACKPLATE
5.5 in.
(140mm)
7.25 in.(184mm)
SE
ALING HUB
(NO
T PROVIDED
)
3
/4 in
.
(2
5
mm)
N
P
T
NIPPLE
(NOT PR
O
VID
ED)
ENC
L
OSED B
A
C
K
B
O
X
HE
AT
ER
A
S
S
EM
BL
Y
F
AN
H
I
GH VOLT
A
GE
T
ERM
I
NAL BL
O
C
K
FUS
E
C
O
NT
R
OL T
HER
M
O
S
T
A
T
S
C
R
EW #8-32
x
3/
8 i
n.
(
4) PR
OVI
DED
S
T
R
OBE A
PPLI
AN
C
E
GA
S
KE
T
(1) P
R
O
VI
DE
D
S
O
LI
D
C
LE
A
R
C
O
V
ER
W
A
S
HE
R (
6)
PR
O
VI
D
ED
#
8-
3
2 x
3/
4 i
n. S
O
C
K
E
T
C
AP
S
C
R
EW
(
6
)
PR
O
VI
D
ED
LOW VOLTAGE
ELE
CTRICAL ENTR
Y
IN AR
E
A
S WHER
E FRE
Q
UENT
WA
SH
DO
WNS O
C
CUR
W
A
SH
ER
S MA
Y
BE USED
T
O
S
T
AND
OFF ENCL
O
SED
SP
A
CER
(NOT
PR
OVIDED
)
1
/
4 in. (6.3mm)
D
I
A
. HOLE
AN
C
H
O
R
(
4
)
PR
O
VIDED
S
C
R
EW
#1
0
x
1
1
/
2
i
n.
(
4)
P
R
O
V
I
D
ED
L
O
W
V
O
L
T
A
G
E
T
ERM
I
N
A
L
BL
O
C
K
3/
4
i
n
.
N
P
T
.
N
I
P
P
LE
(
N
O
T
P
R
O
V
I
D
ED
)
H
I
G
H
V
O
L
T
A
G
E
ELE
C
T
RI
C
A
L
EN
T
R
Y
W
A
RN
I
N
G
LA
BEL
S
E
A
LI
N
G
H
UB
(
N
O
T
P
R
O
V
I
D
ED
)
A
PPL
IA
NCE
W
IR
E
3
/4
in
. NP
T HUB (2) PROVIDED (WITHOUT HEATER (1) PROVIDED)
LOW TE
M
P
W
A
R
N
IN
G
THE
R
M
OS
T
A
T
FIGURE 4
Product Assembly
7
Page 8
Warranty
Three year guarantee against breakage of polycarbonate in normal use
(one year on electro mechanical and electronic components).