STI 1229HTR240 User Manual

Page 1
Stopper Dome
Heated Enclosure
STI-1229HTR / STI-1229HTR240
Features:
· Maintains operating strobe appliance temperature with external temperatures to ­70°F (-57°C). Independently tested to -102°F (-73°C).
· Enclosure tested to NEMA 4X Standards. Equivalent to an IP 66 rating.
· UL, cUL Listed.
· CSFM requires local approval only.
· Protects ADA compliant strobes to UL 1971 Standards.
· Can be used for UL 1638 Strobes for colored lens (see Amseco’s spec sheet).
For use in areas where temperature or environmental conditions exceed the operational range of fire strobe signaling devices. Unit requires 24 VDC continuous for fan operation and 110 or 240 VAC operation for heater, as well as power for strobe operation and supervision for temperature indicator. Fan runs continuously to maintain uniform temperature. Heater cycles as required to maintain operating temperature range for listed strobes.
We protect the things that protect you.
Page 2
Warnings
!
The enclosure is used to protect UL Listed 1638 and 1971 visual notification appliances at temperatures down to -70˚F (-57˚C). It is the installer’s responsibility to comply with NEC 70 Articles 502 and 503, NFPA 72, and other applicable fire and electrical codes. Conduit or raceway paths need to be sealed as near to the enclosure as possible. Installer should have maintained supervision over the low temperature thermostat. The low temperature monitoring thermostat makes the circuit at +32°F (0°C) and clears the circuit at +50°F (+10°C). This listing requires that the fire alarm supervisory control module be only of the latching type. On the appliance mounting plate is a label where you should record the installation date. Also include below the serial number and installation date on the instruction sheet for quick reference.
Serial Number ____________________________________
Installation Date __________________________________
Installation Notes
1. The enclosure is rated to protect signaling appliances indoors and outdoors and in areas of direct weather exposure.
2. When covering fire-signaling appliances with the enclosure, some light loss occurs. Please follow the guidelines listed during installation.
3. Strobe light loss values for respective manufacturers are shown on page
3. To determine the new composite candela value of the use with the guard refer to the sample calculation shown on page 3 for a manufacturer’s strobe.
4. Record the manufacturer’s candela value as “A” and the light loss value as “B” and the assembly value as “C”. Example: A 60 candela strobe with a 30% light loss transmission value. Value “A” is now 60. Value “B” is (60 times 30% or 0.30) in this case 18.
5. Now value “C” is value “A” minus value “B” or 60-18 = 42 candela light source. Now refer to NFPA tables for proper room size that newly established value “C” will work in. Then submittal installation drawings must show the composite candela value in this example 42.
6. On a multiple candela value strobe such as 15/30/75 a calculation must be done for each value and the drawing notation composite value for each number on the strobe.
7. All field wiring within this enclosure must be rated for a minimum operating range of 0ºC - 110ºC.
2
Page 3
Performance Review
Manufacturer
SYSTEM SENSOR (P2, PC2, P4, PC4, SX, SC) WHEELOCK (RSS 24MCW) ADT SECURITY (ADTG1-V Series), EST/EDWARDS (G1-V, G1-HV, G1-HOV, EG1-V, EG1-HV, EG1-HOV Series), HONEYWELL (XLSG1-V, XLSG1-HV Series), MIRCOM (MG1-V, MG1-HV, MG1-HOV, Series), MIRTONE (MG1-V Series), SIEMENS (G1-V Series) FARADAY LLC (2700), SIEMENS (U-MCS Series) EST/EDWARDS (2440S, 202 Series), HONEYWELL (XLS202 Series), MIRCOM(MS
Series), SIEMENS (202), ZITON PTY LTD (ZG1-V Series) SYSTEM SENSOR (SS24110ADA) AMSECO (SL24W-153075), AMSECO - COLORED LENSES (SL24W-153075 A, B, G or R,
SL24C-3075110 A B, G or R, CSL24W-A, B, G or R, CSL24C-A, B, G or R), HONEYWELL (XLSG1-HOV Series), MIRCOM (FS-240), POTTER ELECTRIC (AS-24-153075R, AS-24­153075W)
Note: Can be used for UL 1638 Strobes for colored lens (see Amseco’s spec sheet).
Light
Loss %
28% 31% 32%
33% 34%
36% 37%
Polycarbonate Cleaning Instructions
Rinse with water to remove abrasive dust and dirt. Wash with soap or mild detergent, using a soft cloth. Rinse once more, then dry with a soft cloth or chamois. Exercise caution when using water inside enclosure. Make sure unit is completely dry inside before reassembling. (Do not use razor blades).
Specifications
Polycarbonate Enclosure:
Flammability: Cover: UL94 V-2
Backbox: UL94 5VA Wall Thickness: 0.2 in (5.1mm) NEMA Rating: 4X, indoor and outdoor use Warranty: Three year guarantee against breakage of polycarbonate in
Silicone Laminate Heater:
STI-1229HTR 110 VAC 50/60 Hz UL Recognized Component STI-1229HTR240 240 VAC 50/60 Hz UL Recognized Component
100 Watts Life: @ -10˚C (14˚F) ~ 70˚C (158˚F) 5 Years Duty Cycle: -40˚F (-40˚C) 53%
normal use
(one year on electro mechanical and electronic components).
-70˚F (-57˚C) 71%
Fan:
24 VDC (±10%), 90 mA UL Recognized Component
Life: 5 Years Continuous Duty WARNING: The polarity of the circulating fan is important as it only
!
rotates in one direction with red lead being positive.
Gasket:
Material: Neoprene Life: 5 Years
3
Page 4
STI-1229HTR Installation Instructions
3
/
4
i
n.
(
2
5
m
m
)
N
P
T
N
I
P
PL
E
(
N
O
T
PR
O
VI
DED)
EN
C
LO
S
ED
B
A
C
K
B
O
X
H
EA
TER
AS
S
EMB
L
Y
H
I
G
H
V
O
L
TA
G
E
TER
MI
N
A
L
B
L
O
C
K
S
C
R
EW
#
8-
3
2
x
3
/
8
i
n.
(
4
)
PRO
VI
DED
STR
O
B
E
A
PPL
I
A
N
C
E
G
AS
KE
T
(
1
)
PRO
VI
DED
S
O
L
I
D
C
L
EA
R
C
O
VE
R
W
AS
H
ER
(
6
)
PR
O
VI
DED
#
8-
3
2
x
3
/
4
i
n.
S
O
C
KET
C
A
P
S
C
R
EW
(
6
)
PR
O
VI
DED
LO
W
V
O
L
TA
G
E
EL
E
C
TR
I
C
A
L
EN
TR
Y
1
/
4
i
n.
(
6
.3
m
m
)
DI
A
.
H
O
L
E
A
N
C
H
O
R
(
4
)
PRO
VI
DED
S
C
R
EW
#
1
0
x
1
1
/
2
i
n.
(
4
)
PRO
VI
DED
LO
W
V
O
L
TA
G
E
TER
MI
N
A
L
B
LO
C
K
3
/
4
i
n.
N
P
T
.
N
I
PPL
E
(
N
O
T
PR
O
VI
DED)
H
I
G
H
V
O
L
TA
G
E
EL
E
C
TR
I
C
A
L
EN
TRY
AP
P
LI
ANCE
W
I
R
E
3
/
4
i
n.
N
P
T
H
UB
(
2
)
P
RO
V
I
DED
HEATER ASSEMBLY
HEATER
OVERTEMP SAFETY THERMOSTAT
HIGH VOLTAGE TERMINAL BLOCK
PIN 6 PIN 5
PIN 4
2 A FUSE
CONTROL THERMOSTAT
1
2
3
4
5
6
1
2
MOUNT BACKBOX TO WALL (Refer to Fig. 1)
1. Remove appliance heater assembly from back box and set aside.
2. Mount back box in desired location (wall mount only) using the four #10
x 1-1/2” screws and anchors (provided). Drill a 1/4” diameter pilot hole for plastic anchors at spacing in Fig. 1.
3. Attach conduit hub to a 3/4” NPT nipple and conduit seal fitting to the back
box, top and bottom.
FIGURE 1
Note: A conduit seal fitting must be used on both top and bottom conduit entries as close to the unit as possible. Use conduit seal Crouse­Hinds 3/4” EYSX 21 or equivalent. Conduit should be installed according to applicable NEC and local codes.
4. Pull wiring into back box.
Note: High Voltage (110 or 240 VAC) wiring must enter thru bottom conduit and low voltage and signaling wires must enter thru top conduit and remain separated per NFPA 70, NEC, and local codes.
HIGH VOLTAGE WIRING (Refer to Fig. 2)
5. Connect high voltage:
110 or 240 VAC power is “OFF”. Refer to high voltage schematic diagram on page 6.
Pin 6 AC HOT L-1 Pin 5 Neutral L-2 Pin 4 Ground Ground
110 VAC 240 VAC
Make sure
FIGURE 2
4
Page 5
HEATER ASSEMBLY
FAN
LOW VOLTAGE
TERMINAL BLOCK
LOW TEMP
WARNIN G
FAN POWER
STROBE
POWER
LOW TEMP WARNING
THERMOSTAT
STROBE
(NOT PROVIDED)
STROBE HOOK-UP WIRE
HEATER ASSEMBLY MOUNTING SCREW
STROBE MOUNTING BOSS
1
2
3
4
5
6
-
+
+
-
1
2
WARNING LABEL
LOW VOLTAGE WIRING (Refer to Fig. 3 & Schematic drawings on Page 6)
6. Connect Supervisory Module Connect EOL device (not included) between
pins 1 and 2 of low voltage terminal block. Pins 1 and 2 should then be connected to the fire alarm supervisory control module.
Note: Fire alarm supervisory control module must be of the latching type only.
Pin 1 Alarm Supervisory Pin 2 Control Module
7. Connect Fan Power
Note: Fan will not operate if polarity is reversed. Refer to low voltage
schematic on page 6. Pin 3 -24 VDC
EOL DEVICE
Pin 4 +24 VDC
8. Connect strobe appliance power
Pin 5 - 16-33 VDC Pin 6 +16-33 VDC
9. Attach heater assembly to back box using (4) #8-32 x 3/8” flat head
screws into heater assembly mounting bosses on back box (see Fig. 1). Make sure all service wiring is gathered away from the heater and be careful not to pinch wire under heater assembly. Fan must be mounted toward top of enclosure.
10. Wire strobe using
Teflon coated wire provided. (White­P o s i t i v e / B l a c k­Negative) and attach to the strobe mounting bosses on heater assembly.
11. Record installation
date on label and in manual (page 2).
12. Install cover and
gasket with (6) #8­32 x 3/4” socket cap screws and (6) flat washers as shown in Fig. 4.
13. Turn all power to “ON” position.
FIGURE 3
Note: Fan runs continuously. This system requires three sources of power:
1. 110 or 240 VAC heater on the load side of the fuse holder.
2. 24 VDC power source for the circulating fan. Check fan to see if operating; if not check polarity and reverse then try again
3. 16-33 VDC fire alarm notification circuit for strobes and temperature warning monitor.
5
Page 6
Schematic Diagrams
2
AMP FUSE
OVERTEMP SAFETY
1
2
4
3
5
6
CONTROL
110 OR 240 VAC
SINGLE PHASE
4
5
3
6
1
2
STROBE
PWR
FAN
PWR
TEMP
WARNING
SUPERVISOR
_
+
+
_
FAN
LOW TEMP WARNING
STROBE (16-33VDC 600mA)
S
LOW VOLTAGE CIRCUIT
HIGH VOLTAGE CIRCUIT
TERMINAL
BLOCK
TERMINAL
BLOCK
CHASSIS
HEATER
EOL DEVICE
SUPPLIED BY
CUSTOMER
OPEN @ 70˚F
CLOSE @ 50˚F
OPEN @ 120˚F CLOSE @ 80˚F
OPEN @ 50
˚
F
CLOSE @ 32˚F
(24VDC 90mA)
110 OR 240 VAC 50/60 Hz 100 WATTS
6
Page 7
FIGURE 4
SEA
LING
HUB
(
NOT PR
OVI
D
ED
)
3/
4 in.
(
25mm)
NPT NIP
PLE
(
NOT PR
OVI
D
ED
)
E
NC
LOS
E
D
B
ACK
BOX
HEA
T
ER
AS
SEMBL
Y
FAN
HIGH
VOL
T
AG
E
T
ERMIN
AL
BL
OCK
FU
S
E
C
ON
T
ROL
T
HER
MOS
T
AT
S
CREW
#
8-
3
2
x
3
/8
in.
(4
)
PRO
V
IDED
S
T
R
OBE
AP
P
LIAN
CE
GAS
KE
T
(1
)
P
RO
V
IDED
S
OLID
CLEAR
C
OV
E
R
WAS
HER
(6
)
P
R
OVI
DED
#
8-
3
2
x
3
/4
in.
S
OCKE
T
CAP
SCREW
(6
)
P
R
OVI
DED
LOW
VO
L
TAG
E
ELE
CTRICAL ENTR
Y
IN A
REA
S WHERE FRE
Q
UE
NT
WAS
H DOWNS O
CC
UR
WAS
HE
RS MAY B
E
USE
D
T
O
STA
ND
O
FF E
NCLOSE
D
SP
ACE
R
(
NOT PR
OVIDED
)
1/
4
in.
(
6
.
3
mm)
DIA. HOLE
A
N
C
HO
R
(
4)
P
R
O
V
IDE
D
S
CREW
#
1
0
x
1
1
/2
in.
(4
)
P
RO
V
IDE
D
L
O
W
V
O
L
T
A
G
E
T
E
R
M
IN
AL
B
L
O
C
K
3
/
4
in.
N
P
T
.
N
IP
P
L
E
(N
OT
P
R
O
V
I
DE
D)
HIGH
V
O
L
T
A
G
E
E
L
E
C
T
R
IC
AL
E
N
T
R
Y
W
AR
N
IN
G
L
AB
E
L
S
EAL
IN
G
HU
B
(N
OT
P
R
O
VI
DE
D)
A
P
P
LI
A
N
C
E
W
I
RE
3/
4 in. NPT HUB (
2)
P
R
OV
IDED
LOW TE
M
P
WA
R
N
IN
G
THE
R
M
OS
T
A
T
9.37 in.(238mm)
PRODUCT DIMENSIONS
2
.8
7
in.(
7
3
mm)
APP
LI
AN
CE MOUN
T
I
N
G
BACKP
LAT
E
5
.5
i
n.
(
1
4
0
mm)
7
.2
5
i
n.(
1
8
4
mm)
Product Assembly
7
Page 8
Warranty
Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components).
Electronic warranty form at www.sti-usa.com/wc14.
2306 Airport Road
Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Toll Free: 800-888-4784 • Fax: 248-673-1246
sti-usa.com
www.
Safety Technology International (Europe) Ltd.
Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch
Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999
Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only)
E-mail: info@sti-europe.com • Web: www.sti-europe.com
Printed in USA SUBJECT TO CHANGE WITHOUT NOTICE Inst. Sht. 1229HTR IS OCTOBER2006