Sterling SDRIOM-2 User Manual

FOR YOUR SAFETY
If you smell gas:
1. Open Windows
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS UNIT! CHECK UNIT RATING PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT POINT OF INSTALLATION. RETAIN FOR FUTURE REFERENCE.
HVAC PRODUCTS
FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR
SDR MODEL DIRECT GAS-FIRED HEATERS
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
WARNING: Install, operate and maintain unit in accordance with manufacturer’s instructions to avoid exposure to fuel substances or substances for incomplete combustion which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.
lINSTALLER’S RESPONSIBILITY
Installer Please Note: This equipment has been test fired and inspected. It has been shipped free from defects from our factory. However, during shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer’s responsibility to inspect and
correct any problems that may be found.
4830 TRANSPORT DRIVE, DALLAS,TX 75247
PHONE: 214-638-6010 FAX: 214-905-0806 www.sterlinghvac.com
SDRIOM-2
PN# 94.2000.03
P
POST AND MAINTAIN THESE INSTRUCTIONS IN LEGIBLE CONDITION
c
2
SECTION II - GENERAL INFORMATION
I.As is the case with any fine piece of equipment, care must
be taken to provide the proper attention to the operation and maintenance details of this machine.
This manual of instructions has been prepared in order for you to become well-acquainted with those details, and in doing so, you will be able to give your Direct Gas-Fired System the care and attention which any piece of equipment needs and deserves.
Table Of Contents
Section I: Forward and Table of Contents........................ 2
Section II: General Information........................................... 2
Section III: Installation............................................................ 3
Section IV: Pre Start-Up........................................................ 5
Section V: Unit Start-Up........................................................ 5
Section VI: Unit Shut Down.................................................. 6
Section VII: Troubleshooting Guide..................................... 7
Section VIII: Maintenance Schedule and
Lubrication Requirements............................ 13
Section IX: Maxon NP-I Airflo® Burners........................ 16
Section X: Maxitrol Valve Adjustments and
Preliminary Circuit Analysis............................17
Section XI: Replacement Parts........................................... 19
Section XII: Recirculation.................................................... 20
SECTION I - FORWARD
A. Purpose
The purpose of this manual is to present a guide for proper installation, maintenance, and operation of the Direct Gas­Fired System, and supplement, but not to replace, the services of qualified field service personnel to supervise the initial start-up and adjustment of the unit. Persons without previous experience with commercial and industrial heating equipment should not attempt the initial adjustment and checkout procedure which is essential before such installations may be considered ready for operation. This manual should be made readily available to all operating personnel as an aid in troubleshooting and proper maintenance.
B. Shipping
Direct Gas-Fired units are shipped completely assembled where shipping limitations allow. Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling. Any optional accessories shipped separately are shipped as assembled sections.
Shipments are made F.O.B. Dallas,Texas by flatbed truck or LTL shipment. The unit is securely strapped, tied, and blocked to prevent shipping damage. All shipments are checked by an inspector before they are accepted by the carrier. Parts that are shipped unmounted are noted on the bill of lading. These parts, where feasible, are packaged and shipped with the units. Upon receipt of shipment, all units should be checked against the bill of lading to insure all items have been received. All equipment (and any optional accessories) should be checked carefully for physical damage in the presence of the carrier’s representative. If parts are missing or damage has occurred, a claim should be filed immediately with the carrier.
All Direct Gas-Fired units are given a minimum 140 point operations test and control circuit checkout before ship­ment. Copies of the wiring diagram, piping diagram and bill of material are included with each unit shipped. If correspondence with the factory is necessary, please provide the unit model and serial number.
C. Optional Factory Service
Periodic service on any piece of mechanical equipment is necessary for efficient operation. A nationwide service support network is available to provide quick and dependable servicing of make-up air, heating, ventilating, or air handling types of equipment. The factory also offers start-up service which includes the presence of a service engineer to supervise the initial start-up and adjustment of the equipment and provide instructions for the owner’s maintenance personnel on proper operations and maintenance. Consult factory for quotations on periodic or start-up service.
3
This equipment must be installed and wired in accordance with regulations of the National Board of Fire Under­writers, National Electrical Code, and local governing bodies. The following recommendations are not intended to supplant any requirements of federal, state, or local codes having jurisdiction. Authorities having jurisdiction should be consulted before installations are made. Local codes may require additional safety controls and/or interlocks.
All installations in airplane hangers must be in accordance with current ANSI/NFPA No. 409. All installations in public garages must be in accordance with the current Standard for Parking Garages, NFPA No. 88A, or the Standard for Repair Garages, NFPA No. 88B, and with CAN/CGA B149 Installation Codes.
CAUTION: Do not install heating system in corrosive or flammable atmospheres! Premature failure of, or severe damage to the unit will result!
CAUTION: Heating system must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!
A. Handling the Equipment
The Direct Gas-Fired unit has been designed for rigging and handling through the use of special lifting lugs installed on the ends of each unit. As explained previously, the basic unit is designed for shipping in one piece where shipping limitations allow. Some optional accessories may require field mounting.
When unloading and setting the unit, use the lifting lugs provided or move the equipment on rollers. Hooks, jacks or chains must not be used around the casing, main control panel or exterior mounted controls.
During transit, unloading and setting of the unit, bolts and nuts may have become loosened, particularly in the pillow block ball bearing assemblies in the fan section. It is recommended that all nuts and set screws be tightened. Turn fan shaft by hand to make certain that blower does not rub against blower housing, and that bearing set screws are tight.
Open the cover on the electrical control box located on the unit. Inspect all wire terminals and wiring terminations to ensure that all connections are tight.
If this unit is not installed immediately, cover all openings that might be exposed to the weather. Rotate fan monthly.
B. Locating the Unit
Prior to locating the unit, authorities having jurisdiction should be consulted before installations are made. Approval permits should be checked against the unit received.
Recirculation of room air is not permitted. All air must be ducted from the outdoors.
If in doubt regarding the application of this appliance, consult the factory.
Locate the unit exactly level. Special attention should be given to the duct, electrical, and fuel connection points. Install duct work with adequate flexible connections to isolate vibrations from the duct work. All duct work should have taped or caulked seams. Duct work should be properly sized so as not to inhibit airflow. This information should be cross-checked with the position of support beams and stand pipes to insure that clearance dimensions coincide with those of the unit. The minimum clearance to combustible material must be maintained as listed in Table 1.
On outdoor curb mounted installations, flash and seal roof curb to prevent leakage. The cross section of factory provided curb is formed to accept wood nailing strip and insulation provided by others.
C. Location of Accessories
Where applicable, standard or optional accessories will be placed inside the fan section of the unit for shipment, and must be removed and installed by the mechanical or electrical contractor.
Field provided discharge or inlet dampers must be equipped with an end switch and interlocked to insure maximum design opening before starting and running circuits may be energized.
Field constructed intake accessories should be properly designed to minimize the entry of rain and snow.
Adequate building relief must be provided, so as to not over-pressurize the building, when the heater is operating
at its rated capacity. This can be accomplished by taking into account, through standard engineering methods, the struc­ture’s designed infiltration rate, by providing properly sized relief openings, by interlocking a powered exhaust system, or by a combination of these methods.
SECTION III - INSTALLATION
Table 1
Minimum clearance to combustible material and access
clearance (consult local codes and regulations)
Clearances to Combustible Material
Vertical Units Horizontal Units Front* 36 inches 36 inches Rear 6 inches 6 inches Right 6 inches 6 inches Left 6 inches 6 inches Top 12 inches 12 inches Floor Zero 6 inches
* Consider control side as front of unit.
4
D. Electrical Connections
NOTE: Before installing any wiring, check the unit rating plate for supply power rating.
All electrical connections and wiring must conform to the current edition of:ANSI/NFPA No. 70 National Electrical Code and applicable state and local codes.
Entry location for all field-installed and control wiring is located beside the control panel.
If optional disconnect is not furnished with heater, the field provided disconnect must be of the proper size and voltage. Refer to unit nameplate for minimum circuit ampacity and voltage. The disconnect must be installed in accordance with Article 430 of the current edition of ANSI/NFPA No. 70 National Electrical Code.
Check the supply voltage before energizing the unit. The maximum voltage variation unbalance must not exceed 2%.
NOTE: Should any original wire supplied with the heater have to be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C.
E. Field Piping
All gas piping must be in accordance with the requirements outlined in the National Fuel Gas Code - ANSI Z223.1. It is required that a ground union be installed adjacent to the manifold for easy servicing. A drip leg and/or filter should be provided upstream of the unit’s inlet gas connection. A shut-off must be located external of the unit’s enclosure. The location of this valve must comply with all local codes. A 1/8 inch N.P.T. test gauge connection must be installed immediately upstream of the gas supply connection to the unit.
Refer to the heaters rating plate for determining the minimum gas supply pressure for obtaining the maximum gas capacity for which this heater is specified.
The gas line should be supported so that no strain is placed on the unit. Pipe compounds, which are not soluble to liquid petroleum gases, should be used on threaded joints.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSIG.
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 PSIG.
Correctly sized piping must be run to the unit. Please note that gas line pressure must be as shown on rating plate when unit is operating at full input.
F. Field Wiring and Remote Control Installation
1. Connect the power lines to the line side of the main
disconnect switch.
2. Mount and wire remote control panel, thermostats,
temperature sensors, and any other field installed controls as indicated on the unit control wiring diagram.
3. Connect the wires to the appropriate field wiring
terminals as indicated on the unit control wiring diagram.
4. If the optional low-temperature limit was not an integral
part of the heater, the factory recommends that a low­temperature limit control be installed in areas where freeze protection is needed in the event of burner shut­down.
G. Locating Temperature Controls
The room or outdoor thermostats should be mounted where they will not be subjected to direct impact of the heated air or radiant heat from the sun. It is also recommended that thermostats, especially those with mercury bulb contacts, be mounted on a vibration free surface. Interior walls or the side of building columns away from the heater are usually the location best suited for mounting thermostats.
Controls with outdoor bulbs require that the outdoor bulb be shielded from direct radiation from the sun. Unit mounted sensors are factory located and mounted.
WARNING: Controls must be protected from water. Do not allow water to drip on the ignition system.
WARNING: Open all disconnect switches and secure in that position before wiring unit. Failure to do so may result in personal injury or death from electrical shock.
WARNING: To avoid equipment damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fire hazard.
DANGER: Never use an open flame to detect gas leaks. Explosive conditions may exist which would result in personal injury or death.
5
SECTION IV - PRE START-UP
A. Pre Start-Up
All equipment has been factory tested, adjusted, metered and inspected to meet conditions set at the time the order was placed. Only minimal adjustments should be required. All information in this service manual is typical. All products are semi-custom and changes may occur.
Suggested Tools and Instruments
Volt/Ohm Meter Thermometer Tachometer Ammeter Manometer (0-10" W.C.) Microammeter Standard Hand Tools D.C Volt Meter Gas Pressure Gauge (0-35 lbs.)
NOTE: All servicing and adjustments of the Direct Gas-Fired unit should be performed by a qualified service engineer.
1. The owner’s representative or equipment operator should be present during start-up to receive instructions on care and adjustments of the equipment.
2. Remove all shipping blocks, brackets and bolts from supply fan base with optional isolation base.
3. Check all wiring for loose connections and tighten if necessary.
CAUTION: Line side of disconnect may be energized.
4. Inspect all fan and motor bearings and lubricate if necessary.Tighten setscrews on pulleys, bearings, and fans.
CAUTION: Do not rupture grease seals.
5. Inspect pulleys and belts for tightness, tension and alignment. Do not over tighten belts.
6. Check set screws on all bearings, pulleys and fans for tightness.
7. Check voltage supplied to disconnect switch. The maximum voltage variation should not exceed ±10%. Phase voltage unbalance must not exceed 2%.
8. Check thermostat(s) for normal operation.
9. Check that system duct work is installed and free from obstructions.
10. Check that fans turn free in housing.
11. Check burner for proper location and alignment.
12. Check that filters and accessories are installed correctly.
13. Check that vent lines have been run to atmosphere on indoor units. Note that some units will use vent limiters and vent lines are not required.
14. Check that all manual gas shut-off valves are closed.
15. When failure or malfunction of this heater creates a hazard to other fuel burning equipment, (e.g. when the heater provides make-up air to a boiler room), the heater is to be interlocked to open inlet air dampers or other such devices.
16. If inlet duct is attached to the heater, a purge timer must be provided and set to purge 4 times the inlet duct volume.
Purge time in seconds = 4 x L x W x H x 60
SCFM L = duct length in feet,W = duct width in feet, H = duct height in feet, SCFM = rating plate air throughput.
Refer to the electrical schematic for the proper circuit placement. Purge timer P/N 65.0711.00.
6
SECTION V - UNIT START-UP
Close or replace all doors and service panels.
Turn main disconnect switch off. Verify the incoming line voltage matches the unit nameplate rating. If the voltage is over ±10% of nameplate rating or phase voltage unbalance is over 2%, notify the contractor or power company.
Turn Heat OFF/ON switch to the OFF position. Turn main disconnect switch on. Turn Fan OFF/ON switch to the ON position. Damper opens. Blower fan turns on.
Turn Fan OFF/ON switch to OFF position and check sup­ply blower for proper rotation.
NOTE: To change rotation of the blower, simply interchange any two (2) of the line leads of the motor starter for three (3) phase motors. Refer to motor nameplate for reversing single (1) phase motors.
Turn Fan OFF/ON switch to the ON position. Check for proper blower rpm. Check that all motor amp draws do not exceed nameplate ratings, and the overload relay is set to the motor nameplate amperage.
Check dampers for proper operation. Be sure they operate freely, and the linkage does not bind.
Make sure all manual gas shut-off valves are in the closed position.
Turn Heat OFF/ON switch to the ON position. Blower fan will run.
Turn Fan and Heat OFF/ON switches to OFF position.
Setting Burner
NOTE: To adjust gas pressure on supply lines where a regulator has been installed (to reduce the inlet pressure to 1/2 PSIG or less), remove dust cap of main gas regulator and turn adjusting screw clockwise to increase pressure, or counter-clockwise to decrease pressure.
Set all thermostats to call for heat. Set inlet ductstat (if applicable) above outside air temperature.
Connect a DC microammeter between the SENSE terminal and the flame rod sensing wire.
Turn Fan and Heat OFF/ON switches to ON position.
Open inlet manual gas shut-off valve slowly. Reset high and (if applicable) low gas pressure switches. Check main gas line for leaks using soap solution.
Unit will run for 5 seconds before ignition trial.
NOTE: 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE.
United Technologies Electronic Controls Spark Ignitor
Watch microammeter carefully. The reading should be at least 5.0 microamps. If the reading is too low, slowly turn the low-fire adjustment on the modulating valve in or out until satisfactory readings are obtained. When adjusting low fire, there should be a continuous flame along the entire burner length without any blowout spots.
Refer to Maxitrol Valve Adjustment instructions in Section IX for setting high and low fire gas pressure settings.
When the flame is adjusted, shut the unit off by turning the Fan and Heat switches to OFF.
Setting Main Flame
Install manometer at test port on the last tee of the burner manifold or modulating valve.
Slowly open all manual gas shut-off valves.
Restart unit. After main gas valves open and burner lights check gas lines for leaks.
Adjust high gas pressure reading (from manometer) to match firing rate shown on unit nameplate.
Adjust the high and low fire setting according to the Maxitrol Valve Adjustment instructions in Section IX. The high fire setting must not exceed the pressure stated on the rating plate.
When adjusting low fire, there should be a continuous flame along the entire burner length without any blow out spots.
Main flame is now set. Recheck the microamp signal on the ignition control throughout the full burner input range. Re­check low fire setting. Cycle unit 2 or 3 times to insure good ignition.
Safety Controls Check
A. High Temperature Limit and Firestats – These limit
controls are not adjustable and are checked by the factory. Reset the red button(s) to be sure they are ready for operation. Contact the factory if these switch­es fail to reset.
B. Ignition Control - Operate unit in Heat mode. After
flame has been established, close last manual gas valve before main burner. The ignition control must trip out within 15 seconds. Reset the ignition control by turning the HEAT switch to the OFF position.
7
SECTION VI - UNIT SHUTDOWN
C. Gas Pressure Switches - Operate unit in Heat mode.
The low pressure switch will trip out and must be reset before resuming operation when the inlet gas valve is turned off during operation.The high pressure switch may be checked out by reducing the setting of its trip point below unit operating pressure. It should then trip out and shut off the burner. Return the adjustment to its original setting and reset to resume operation.
When checking operation of gas pressure switches on systems without pilot the heat switch will have to be turned off for approximately five seconds to reset the ignition control.
D. Air Pressure Switches - The high air pressure switch is
checked by removing the sensing tube from the enter­ing air side of the burner. Switch operation will shut off the burner. Recycle is automatic when the sensing tube is replaced.The low air pressure switch is checked by removing the sensing tube from the leaving air side of the burner. Switch operation will shut off the burner. Recycle is automatic when the sensing tube is replaced.
When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni­tion control.
E. Temperature Controls – These controls are checked by
adjusting control settings to a lower temperature setting while the unit is operating on high fire and observing cutoff. The controls should be reset to settings shown below:
Suggested Control Settings
TC-01 Room Thermostat ................... Customer Discretion
TC-03 On-Off Inlet Ductstat ............................................65°F
TC-08 Freeze Thermostat .................................. 3 min.,...45°F
PS-04 Low Gas Pressure Switch ................................1.0”w.c
PS-07 High Gas Pressure Switch............125% of firing rate
TC-09 Night Set Back Room .................Customer Discretion
TC-52 Remote Temperature Selector .... Customer Discretion
FL-02 High Temperature Limit (manual) ........ Not adjustable
RE-26 High Limit Discharge Ductstat ................................ 95°F
RE-26 Low Limit Discharge Ductstat ................................ 55°F
PS-12 Clogged Filter Switch ....... Adjust to Field Conditions
PS-13 Building Pressure Switch .. Adjust to Field Conditions
A. Extended Shutdown -
1. Set the Heat OFF/ON switch to the OFF, then turn the Fan switch to the OFF position.
2. Close all manual gas valves.
3. Open the main electrical disconnect switch.
B. Emergency Shutdown ONLY -
1. Open the main electrical disconnect switch.
2. Close all manual gas valves.
1. Low or no voltage.
2. Fuse(s) blown.
3. Customer interlock not closed or connected.
4. Fan Off-On switch in Off position.
5. Time clock, night setback thermo­stat or field installed controls open.
6. Freeze protection tripped.
7. Damper motor not operating, or its end switch not making.
8. Overload protection on motor starter tripped.
9. Belts loose or broken
10. Bearings seized.
11. Motor may be burned or incor­rectly wired.
12. Motor overheating.
1. Heat Off-On switch in Off position.
2. Burner enable relay open (if applicable).
3. Outside air temperature higher than On-Off inlet ductstat (if applicable).
4. Field purge timer open (if applicable).
1. Manual gas shut-off valve closed.
2. Inlet gas pressure lower than required gas pressure.
3. Type of gas (Natural, LP) supplied different from factory required type.
4. Auxiliary switch on starter not closed.
5. Air flow switches not closing.
6. High temperature limit switch open.
7. High or low gas pressure switches open (if applicable).
8. Main gas valve relay open.
8
SECTION VII – TROUBLESHOOTING
Symptom
Cause
Remedy
A. If blower does not operate.
B. If there is no voltage at ignition
control.
C. Burner does not light after 5 sec-
onds pre purge of flame safeguard relay and there is voltage at igni­tion control.
1. Check power source.
2. Check and replace.
3. Close or connect customer interlock.
4. Switch to On position.
5. Check time clock, night setback thermostat and field installed controls for proper settings.
6. Reset freeze stat by interrupting power. Check for proper setting and burner operation.
7. Check for power at damper motor and that end switch has been wired correctly to the N.O. (normally open) contact. Check that the linkage is clear and not binding.
8. Push reset button on starter and check amps.
9. Turn power off and check belts.
10. Check and replace.
11. Turn power off and check motor and wiring.
12. Check burner firing rate.
1. Switch to On position.
2. Check for power and replace if necessary.
3. Lower On-Off inlet ductstat setting.
4. Check for power and replace if necessary.
1. Slowly open valve.
2. Increase gas pressure.
3. Replace with factory required type of gas.
4. Check for power and replace if necessary.
5. Adjust the air flow and external static pressure to match rating plate.
6. Correct problem. Reset by pushing down the reset button.
7. Correct problem. Reset both switches.
8. Check for power and replace if necessary.
System without Pilot
Loading...
+ 16 hidden pages