ATTENTION: READ THIS MANUAL, SEPARATED COMBUSTION INDOOR DUCT FURNACE SCDFM MANUAL (EVAPORATIVE
OR COOLING COIL MANUALS IF APPLICABLE), UNIT SUBMITTAL DATA SHEETS AND ALL LABELS ATTACHED TO THE
UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATES
FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE
POINT OF INSTALLATION. RECORD THE UNIT MODEL NUMBER AND SERIAL NO.(S) IN THE SPACE PROVIDED. RETAIN
THIS DOCUMENT FOR FUTURE REFERENCE.
Model No.______________________________________________ Serial No. ________________________
MSIOM-3
J30-06624
FOR Y OUR SAFETY
The use or storage of gasoline or other
flammable vapors or liquids in open
containers in the vicinity of this appliance
is hazardous.
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open fl ames.
4. Immediately call your gas supplier.
FOR Y OUR SAFETY
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, injury or death. This appliance must be installed by a licensed
contractor or qualified service personnel. Read these installation, operating and
maintenance instructions thoroughly before installing or servicing this equipment.
APPROVED FOR USE IN CALIFORNIA
Install, operate and maintain unit in accordance with manufacturer’s
instructions to avoid exposure to fuel substances or substances from incomplete
combustion which can cause death or serious illness. The state of California has
determined that these substances may cause cancer , birth defects, or other reproductive
harm. Install and Service this product to avoid exposure to airborne particles of
glasswool fi bers and/or ceramic fi bers known to the State of Calif ornia to cause cancer
through inhalation.
12/12
INSTALLER’S RESPONSIBILITY
Installer Please Note: This equipment has been test fi red and inspected. It has been shipped
free from defects from our f actory. Ho w ever, during shipment and installation, problems such
as loose wires, leaks or loose fasteners may occur. It is the installer’s responsibility to
inspect and correct any problems that may be found.
RECEIVING INSTRUCTIONS
Inspect shipment immediately when
received to determine if any damage
has occurred to the unit during
shipment. After the unit has been
uncrated, check for any visible
damage to the unit. If any damage
is found, the consignee should sign
the bill of lading indicating such
damage and immediately file claim
for damage with the transportation
company.
IMPORTANT: Look in direction of unit air fl ow to determine
whether unit is right hand or left hand accessible.
V. START UP ......................................................20, 21
VI. MAINTENANCE .......................................21 thru 24
VII. TROUBLESHOO TING ............................25 thru 30
VIII. REPLACEMENT PARTS ...................................30
IX. SERVICE NOTE ...................................................30
X. W ARRANTY ..........................................................30
Canadian Installations ...............................................31
XI. DIMENSIONAL DATA ..............................32 thru 37
XII. MOTOR ELECTRICAL DATA .............................38
XIII. UNIT/SHIP WEIGHTS ........................................39
XIV. COOLING COIL DIMENSIONAL DATA ............40
XV. SUBMITTAL INDEX ............................................41
XVI. MODEL NUMBER DESCRIPTION ....................42
XVII. START UP SHEET ...........................................44
Unless otherwise specifi ed, the following conversions
may be used for calculating SI unit measurements:
1 foot = 0.305 m
1 inch = 25.4 mm
1 psig = 6.894 kPa
1 pound = 0.435 kg
1 gallon = 3.785 L
1 cubic foot = 0.028 m
1 inch water column =0.249 kPa
1000 Btu per hour = 0.293 kW
1000 Btu/Cu. Ft. = 37.5 MJ/m
3
liter/second = CFM x 0.472
meter/second = FPM ÷ 196.8
3
The following terms are used throughout this manual to bring
attention to the presence of potential hazards or to important
information concerning the product:
Indicates an imminently hazardous
situation which, if not av oided, will result in death,
serious injury or substantial property damage.
Indicates an imminently hazardous
situation which, if not avoided, could result in death,
serious injury or substantial property damage.
Indicates an imminently hazardous
situation which, if not avoided, may result in minor
injury or property damage.
NOTICE: Used to notify of special instructions on
installation, operation or maintenance which are
important to equipment but not related to personal
injury hazards.
I. RECEIVING INSTRUCTIONS
Make-up Air Units with multiple furnaces are shipped
in sections. Each section has a label with Order no.,
Model No., Unit No., and Part No. marked on it. Make
certian that the order, model, and part numbers agree
on each section to be connected together.
Inspect shipment immediately when received to
determine if any damage has occurred to the crate
during shipment.
After the unit has been uncrated, check for any visible damage
to the unit. Check motor position and turn blower wheel to
determine if damage has occurred to these critical parts.
If any damage is found, the consignee should sign the bill
of lading indicating such damage and immediately fi le
claim for damage with transportation company.
PRE-INSTALLATION INSTRUCTIONS
When the unit is received and uncrated, check the external
data plate and all labels on the unit for type of gas, electrical,
and operational specifi cations to confi rm that these agree
with those at point of installation. The unit is equipped with
an Indoor Duct Furnace; also check the data plate and
all labels located on each furnace.
Every Mak e-Up Air Unit will include an informational
packet which will include the following: This
make-up air manual, duct furnace, ev aporative cooler/
cooling coil manuals (if applicable to the unit order),
wiring diagram(s), and special controls/data sheets.
— 2 —
II. GENERAL SAFETY REQUIREMENTS
Open all disconnect switches
before installing the unit. If the po wer disconnect
is out of sight, lock it in the open position and ta g
it to prevent unexpected application of power.
Failure to do so may result in personal injury or
death from electrical shock.
Failure to comply with the general
requirements may result in extensive property
damage, severe personal injury or death.
Never service any component
without fi rst disconnecting all electrical and gas
supplies to the unit or severe personal injury or
death may occur.
1. Installation must be made in accordance with local
codes, or in absence of local codes, with the latest
edition of ANSI Standard Z223.1 (N.F.P.A. No 54)
National Fuel Gas Code. All ANSI and NFP A Standards
referred to in these installation instructions are the
ones that were applicable at the time the design of
this appliance was certifi ed. The ANSI Standards are
available from the National Standards Institute, Inc.,
11 West 42nd Street, New York, NY 10036 or www.
ansi.org. The NFPA Standards are available from the
National Fire Protection Association, Batterymarch
Park, Quincy , Massachusetts 02269. The heaters are
designed for use in airplane hangers when installed
in accordance with ANSI/NFP A No . 409 and in public
garages when installed in accordance with the NFP A
No. 88A and NFPA No. 88B.
2. If installed in Canada, the installation must conform
with local building codes, or in the absence of local
building codes, with the current CSA-B149.1 or B149.2
“Installation Codes for Gas Burning Appliances and
Equipment”. These indoor duct furnaces have been
designed for and certifi ed to comply with CSA 2.6.
5. Follow installation instructions CAREFULLY to
avoid creating unsafe conditions. All wir ing should
be done and checked by a qualifi ed electrician, using
copper wire only . All gas connections should be made
and leak-tested by a suitably qualifi ed individual, per
instructions in this manual.
6. Use only the fuel for which the heater is designed
(see nameplate). Using LP gas in a heater that
requires natural gas, or vice versa, will create the
risk of gas leaks, carbon monoxide poisoning and
explosion.
Do not attempt to convert the heater
for use with a fuel other than the one intended.
Such conversion is danger ous, as it could create
unsafe conditions that result in death, serious
injury or substantial property damage.
7. Make certain that power source conforms to
electrical requirements of heater. Disconnect
power before installing or servicing heater. If power
disconnect is out of sight, lock it in open position and
tag it to prevent unexpected application of power.
Failure to do so could result in fatal electric shock.
Do not depend upon a thermostat
or other switch as the sole means of disconnecting
power when installing or servicing heater. Always
disconnect power at main circuit breaker as
described above. Failure to do so could result in
fatal electric shock.
8. Special attention must be given to any grounding
information pertaining to this heater. To prevent
the risk of electrocution, the heater must be
securely and adequately grounded. This should be
accomplished by connecting a grounded conductor
from the service panel to the conduit box of the heater.
T o ensure proper ground, the g rounding means must
be tested by qualifi ed fi eld electrician.
3. No alterations are to be made on this equipment.
The duct furnace section (capacities 100 thru 400 MBH)
of these make-up air units are certifi ed by ETL for use
with natural and LP (propane) gases!
Do not alter the duct furnace in any
way or damage to the unit, se vere personal injury
or death will occur.
4. Make certain that the power sources conform to the
requirements of the heater.
— 3 —
9. Do not insert fingers or foreign objects into the
heater or its air moving device. Do not bloc k or tamper
with the heater in any manner while in operation or
just after it has been turned off, as some parts may
be hot enough to cause injury.
10. This heater is intended for general heating
applications ONLY. It must NOT be used in
potentially dangerous locations such as fl ammable
explosive, chemical-laden or wet atmospheres.
In cases in which property damage may result from
malfunction of the heater, a backup system or a
temperature sensitive alarm should be used.
LOCATION
Before placing the Make-Up Air unit in its permanent
location, make certain that the structure is capable of
carrying the additional load of this equipment. Check the
unit weight given at the end of this manual.
LOCA TIONS TO A V OID
Unit heaters should not be installed within corrosive or
fl ammable atmospheres. Do not locate any gas fi red
heater where air for combustion contains chlorinated
vapors or acid fumes.
Refer to unit data plate for required clear ances to combustible
material, and Figure 11 for manufacturer’ s recommendations .
Do not place unit in a location where
service personnel can not safely service this
equipment or personal injury could result.
NOTICE: When selecting a location for these MakeUp Air Units, both the size of the unit and the heating
requirements of the building must be considered.
NOTICE: The furnace section(s) of this unit is equipped
for bottom access serviceability only! Provide
adequate clearance (base rail to fl oor is 18 inches
minimum).
COMBUSTION AIR CONSIDERATIONS
The presence of chlorine vapors or other corrosive vapors in the
combustion air supply for gas-fi red heating equipment presents
a potential corrosive hazard. Chlorine will, when exposed
to fl ame, precipitate from the compound (usually freon or
degreaser vapors) and go into solution with any condensation
that is present in the heat exchanger or associated parts. The
result is hydrochloric acid which will readily attack all metals,
including 300 grade stainless steel. Care should be taken
to separate these vapors from the combustion process.
Presence of these air impurities can
cause premature failure of the heat exchanger and
void the warranty (See limited warranty on page 30).
The venting system must be installed in accordance with
heater manufacturer’ s instructions. The venting system is
an integral part of the unit and must not be altered in
the fi eld!
MOUNTING HEIGHT
1.
When a Gas Fired Make-Up Air Handler is discharging
directly into the heated space, a mounting height of
eight feet (2.4m) above the fl oor is recommended.
Less effi cient air distribution results at higher levels.
2. When Gas Fired Indoor Make-Up Air Handlers are
installed in airplane hangars, NFP A specifi es that the
units must be at least ten feet (3.0m) abov e the upper
surface of wings or engine enclosures of the highest
aircraft to be stored in the hangar. This measurement
should be made from the wing or engine enclosure
(whichever is higher from the fl oor) to the bottom of
the heater. Heaters must be installed at least eight
feet (2.4m) abov e the fl oor in shops, offi ces, and other
sections of the hangar where aircraft are not stored
or housed. Refer to NFPA 409 Aircraft Hangars.
3. In parking structures, Gas Fired Indoor Make-Up Air
Handlers must be installed so that the burner fl ames
are located 18" (457mm) above the fl oor or protected
by a partition not less than 18" (457mm) high as
specifi ed in NFPA 88A Parking Structures.
4. In public repair garages, Gas Fired Make-Up Air
Handlers must be installed in a detached building
or room separated from repair areas as specifi ed in
NFPA 88B Repair Garages.
— 4 —
SUSPENSION/RIGGING
Make certain that the structure
to which the single, dual, triple furnace and air
handler sections is to be mounted is capable of
supporting its weight. Under no circumstances
must the gas lines, the venting system or the
electrical conduit be used to support the heater;
or should any other objects (i.e. ladder, person)
lean against the heater , gas lines, venting system
or the electrical conduit for support.
The unit should never be lifted
by any unit component other than the base rail
assembly. Unit components other than base rail
assembly are not designed to support the total
weight and may break, causing personal injury
or unit damage.
Units can be set on field furnished supports/cradle
with access available to furnace bottom section, or
suspended by rod hangers from the sub-frame (and
lifting brackets).
Any unit that has a side base rail
longer than 104" (2.6m) requires additional fi eld
furnished supports by a qualifi ed installer. Refer
to all dimensional data in this manual. If further
information is required, contact the manufacturer’s
technical service department.
Rig unit using either belt or cable slings. Use spreader bars
to protect the top of the unit when it is lifted. Mak e sure all
hardware used in the lifting/mounting process is tightened
and secured.
Refer to Figures 1 and 2 for Single Furnace Make-Up
Air Unit rigging requirements. Refer to Figures 3, 4
and 5 for Dual/Tr iple Furnace Make-Up Air Unit rigging
requirements, which ships to the site in two sections
(Figure 3 is the air handler section and 4 and 5 are the
furnace sections.).
On units with a total length of less than 104" (2642mm),
excluding evaporative cooler, two holes are provided in
the base rail on each side of the unit. Slide pipes beneath
the unit through these holes and attach rigging to pipes
for lifting the unit.
On units with a total length of a 104" (2642mm) or greater,
excluding evaporative cooler, lifting lugs/brackets
attached to the base rail are provided. Once the unit
is set in place these lifting brackets may be removed if
required.
Attach rigging to lugs/brackets for lifting the unit. For
distance between lifting lugs/brackets and total unit
lengths, refer to the Dimensional Data section of this
manual.
The unit must be hung level from side to side and front
to back. It is recommended to use the (9/16" diameter)
hanging holes in the skid rail, and 1/2" threaded rod or
pipe, and/or whatever other supports may be required
to adequately support the unit. A fi eld supplied cradle
or other means of support may also be required. The
installer is responsible for determining adequate and
safe suspension methods.
— 5 —
Figure 1 -
(4) Lifting Point
Locations (2) At Each
End Of Air Handler Unit
Use Spreader Bars
To Prevent Damage
To Units
D6559
(8) Lifting Point
Locations (4) On Each
Side Of Duct Furnace Unit
Use Spreader Bars
To Prevent Damage
To Units
(6) Lifting Point
Locations (3) On Each
Side Of Duct Furnace Unit
Use Spreader Bars
To Prevent Damage
To Units
Hoisting of Make-Up Air Unit (Single Furnace)
Without Lifting Brackets
Figure 2 -
Hoisting of Make-Up Air Unit
With Lifting Brackets
Figure 4 - Hoisting Double Furnace Unit
D6558
Figure 5 - Hoisting Triple Furnace Unit
(Single Furnace)
Figure 3 - Hoisting Make-Up Air Handler Unit
D6558
Refer to Figures 3, 4 and 5 for dual/triple furnace Make Up
Air rigging requirements. Dual/triple furnace units ship to
the site in two sections (Figure 3 is the air handler section;
Figures 4 and 5 are the furnace sections).
— 6 —
III. INSTALLATION
Refer to all dimensional data within the manuals
equipped with your unit.
SINGLE FURNACE UNITS
Single furnace units (capacities 10-40) consist of a
furnace section and an air handler section mounted on
a common base rail.
MULTIPLE FURNACE UNITS
Multiple furnace units consist of two sections: a furnace
section with two duct furnaces (capacities 50-80) or three
duct furnaces (capacity 12) mounted on a common base
rail; and a separate air handler section mounted on its
own base rail. A fl exible connector kit is also equipped
with your unit. Each section has a label with Order
No., Model No., Unit No., and Part No. marked on it.
Make certain that the order, model, and part numbers
agree on each section to be connected together . The
two sections should be moved individually and mounted
in their permanent location (see “Suspension/Rigging”
sections). Ensure that both fl ange assemblies are in
alignment with a 5" (127mm) space between the fl ange
assemblies. See the f ollo wing instructions for installation
of the fl exible connector kit between the two sections.
INSTALLING FLEXIBLE CONNECTOR - Refer to Figure 6
1. Make sure that the furnace section and the air
handler section are in alignment and installed with a
5" (127mm) space between the fl ange assemblies.
2. Remove the top e xtension panel of the duct furnace
for access to the inside bottom fl ange assemblies.
4. Measure the distance from the top of the fl ange
assembly to the slot at the bottom of the fl ange
assembly. Make a second 90 degree bend at the
measured distance from the fi rst bend in the fl exible
duct connector.
5. Slide the flexible connector through the slots in
the fl ange assemblies until the vertical par t is tight
against the sides of the fl ange assemblies.
6.
Bend second vertical section up around the fl anges.
Make sure all bends are straight and ev en for proper fi t.
7. Bend down top section of fl exible connector. Cut
metal parts of fl exible connector to o verlap the 4 inch
section by at least 1-1/2 inches (38mm), but cut the
fabric portion 1-1/2 inches longer than the metal.
8. Screw metal portions of fl exible connector to the
flange assemblies using drill screws. Space the
screws approximately 4 to 6" (102 to 152mm) on
center. Fasten the bottom section in place by screwing
down from the inside. Fasten the overlapped area with
two screws in the metal on each side of the fabric.
Seal the fabric joint with RTV sealer and allow to cure .
Replace and reseal top extension panel on furnace
section.
9. Apply sealing tape to seams between fl anges and
fl exible connector and to vertical fl ange connections.
Test for air leaks during initial start-up. Reseal as
required.
Table 1 - Flexible Connector Kit
3. Measure fl exible connector in the fl at to confi rm that
it is correct for the unit being installed. Refer to Table
1. Make a 90 degree bend 4" (102mm) from one end
of the fl exible duct connector.
Unit (Approx.) Straight Length
Capacity Flexible Connector
(CA) Required
50 102 Inch (2.59m)
60 114 Inch (2.90m)
70 124 Inch (3.15m)
80/12 135 Inch (3.43m)
— 7 —
*
*
Furnace Assembly
Flange Assembly
with Flange
Mounts to
Air Handler
5"
Approx.
for Flexible
2" Slots
Connector
AIR FLOWAIR FLOW
Panel
Top Extension
STEP 1
14.500
Approx.
Approx.
5.000
Approx.
9.000
***
***
*
*
*
***
*
D6453-1
side of unit
Bend at approx.
4" on access
Assembly on both Furnace and Air Handler
to bottom of the inside of Flange
Remove Top Extension Panel of Duct
Furnace to fasten Flexible Connector
Connector into
Slide Flexible
place tightly
before fastening
sheet metal for
1-1/2" Overlap
proper installation
proper installation
1-1/2" Overlap
fabric for
Furnace
Duct
(4) Slots
STEP 2STEP 3
Bend at 90∞
STEP 4
STEP 5
D6453-2
Figure 6A
Figure 6B
— 8 —
Flexible Connector
Continue bending
tightly around Flange
Assembly making sure
bends are neat and even
Keep uniform distance
around Flange Assembly
on all sides, (approx. 2")
D6453-3
STEP 6
STEP 7
Figure 6C
Figure 6D
using Drill Screws provided
fasten Flexible Connector to
Flange Assembly securely
space Screws between 4" - 6"
keep uniform distance
around Flange Assembly
on all sides (approx. 2")
for sheet metal overlap use (2)
screws on each side of fabric
Flexible Connector
Assembly ready for
application of Sealing
Tape provided for testing
for air leaks (see sht. 5)
Use Sealant between
layers of fabric for
proper installation
(by others in field)
STEP 8
D6453-4
— 9 —
AIR FLOW
D6453-5
14.500
stips of Sealing Tape to be
continuous or overlapping
used when sealing Flexible
Connector to Flange Assembly
Approx.
5.000
Approx.
AIR FLOW
9.000
Approx.
***
*
*
***
*
*
*
*
*
*
*
use Sealing Tape on
inside of Bottom Flange
Flexible
Connector
Flange
Assembly
Sealing Tape covers
Screw heads and seams
Figure 6E
STEP 9
on Flange
connections
use Sealing Tape
2
1
3
— 10 —
Figure 7 - Arrangement B & D Capacities10/40
D6554
(8) Suspension Point
Locations (4) On Each
Side Of Unit
D6555
(4) Suspension Point
Locations (2) At Each
End Of Air Handler Unit
(6) Suspension Point
Locations (3) On Each
Side Of Duct Furnace Unit
Both Units Must Be
Suspended At Same
Height For Proper
Fit Of Flex Connector
D6556
Both Units Must Be
Suspended At Same
Height For Proper
Fit Of Flex Connector
(4) Suspension Point
Locations (2) At Each
End Of Air Handler Unit
(8) Suspension Point
Locations (4) On Each
Side Of Duct Furnace Unit
Figure 8 - Arrangement G Capacities 10/40
INSTALLATION CLEARANCES
Minimum clearances to combustible material are shown
on the unit data plate. It is important that clearances
be maintained for servicing the unit, and that minimum
clearances are provided from the unit to combustible
material. Clearances around the fi eld installed optional
outside air hood (if unit is to be connected to one) must
be unobstructed. See Figure 11.
Under no circumstance should
combustible material be located within the specifi ed
clearances. Failure to provide proper clearance
could result in personal injury or property damage
from fi re.
Every gas appliance should be located with respect
to building construction and other equipment so as to
permit access to the unit. Clearances between ver tical
walls and the vertical sides of the heater should be no
less than 18" (457mm). Minimum clearance between
the top of the heater and the ceiling is 6" (152mm). The
minimum clearance to the bottom of the furnace is 25"
(635mm). The minimum clearance from combustibles to
the fl ue collector is 6" (152mm). The minimum clearance
from combustibles to the vent pipe is 6" (152mm). See
Figure 11.
Figure 9 - Arrangement G Capacities 50/80
Figure 10 - Arrangement G Capacity 12
— 11 —
*It is recommended that adequate clearance be kept
to the bottom of the furnace(s) to make sure a service
technician can safely service the unit(s),
The unit should never be lifted by
furnace sections, blower housing/filter/sections,
motor mounts or fl ue connections. These are not
designed to support total weight of the unit, and may
break, causing personal injury or property damage!
Make certain that the lifting
methods used to lift the Make-Up Air Unit are
capable of supporting the weight of the heater
during installation. Failure to heed this warning
may result in property damage or personal injury.
Make certain that the structure to
which heater is to be mounted is capable of safely
supporting its weight. Under no circumstances
must the gas lines or the electrical conduit be
used to support the heater. Failure to heed these
warnings may result in property damage, personal
injury or death.
Open all disconnect switches before
installing the unit. Failure to do so may result in
personal injury or death from electrical shock.
Inspect the suspension and/or
support system for the make-up air unit to ensure that
all fasteners are tight and the unit is secure before
working underneath the unit. Failure to do so could
result in property damage, personal injury, or death.
Figure 11 - Manufacturer’s Recommended Service Clearances
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
D6573
Field
Ductwork
18(457mm)
Air
Inlet
18 (457mm)
AIR FLOW
17.5 (444mm)
Ductwork
18(457mm)
(635mm)
Field
AIR FLOW
25
Supply
Ductwork
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
36 (914mm)
Ductwork
Note: Recommended ceiling clearance 36"
(914mm) is to the top of the furnace venting
collar assembly.
18 (457mm)
Supply
VENTING†
All venting installations shall be in accordance with the
latest edition of Part 7, “Venting of Equipment”, of the
National Fuel Gas Code, ANSI Z223.1 or applicable
provisions of local building codes.
CARBON MONOXIDE! Your venting
system must not be blocked by any snow, snow
drifts or any foreign matter. Inspect your venting
system to ensure adequate ventilation exists at all
times! Failure to heed these warnings could result
in Carbon Monoxide Poisoning (symptoms include
grogginess, lethargy, inappropriate tiredness, or fl ulike symptoms).
The venting is an integral part of
the unit and must not be altered in the fi eld.
†Refer to the Separated Combustion Indoor Duct
Furnace Manual for more venting requirements.
Vent Systems
Termination Clearance Requirements
Minimum Clearance
Structure/Object
for Termination Locations
USACANADA
Door, window, or gravity vent
inlet; combustion air inlet for
other appliances
9 inch for 10,000 to
50,000 BTU/Hr
input; 12 inch for
input exceeding
50,000 BTU/Hr.
9 inch (230mm) for
10,000 to 50,000
BTU/Hr input;
12 inch (305mm)
for input exceeding
50,000 BTU/Hr.
Forced air inlet within 10 feet3 feet above6 feet (1.8m)
Adjoining Building or parapet6 feet6 feet (1.8m)
*If the vent terminal is to be installed near ground level, the vent
terminal must be positioned at least six inches (152mm) above the
maximum anticipated snow depth.
— 12 —
DUCT CONNECTIONS
All ductwork must be properly supported so that no strain
is put on the unit. Do not alter or bend the discharge duct
fl anges supplied on your make-up air unit.
Duct connections must have a removable access panel
in the duct which is connected to a duct furnace. The
duct openings shall be accessible when the unit is
installed in service, and shall be of such size that smoke
or refl ected light may be observed inside the casing to
indicate the presence of leaks in the heating element.
The covers for the panels shall be attached in such a
manner as to prevent leaks . Ducts (or optional outside air
hoods) exposed to the outdoors must be insulated and
sealed to prevent water from entering either the unit or
building through the duct.
To avoid equipment damage or
possible personal injury, do not connect gas
piping to this unit until a supply line pressure/
leak test has been completed. Connecting the
unit before completing the pressure/leak test may
damage the unit gas valve and result in a fi re hazard.
Do not rely on a gas shutoff valve to
isolate the unit while conducting gas pressure/leak
tests. These valves may not be completely shutoff,
exposing the unit gas valve to excessive pressure,
resulting in damage.
Do not over-tighten the inlet gas piping
at unit gas valve or stresses that could crack the valve
may result.
If a single, double or triple duct furnace only unit is
connected to a return air duct, or any other inlet air
restriction, the appliance shall be installed on the positive
pressure side of the air circulating blower.
When connecting return air duct to Standard or High
CFM cabinets, attach duct to return air opening fl ange
when no dampers are used. Otherwise, if dampers are
used, attach return air duct around collar at bottom of
damper assembly. Also refer to the Dimensional Data
section of this manual, Submittal Data Sheets and Indoor
Duct Furnace Manual specifi ed for your unit.
GAS PIPING††
All gas piping must be installed in accordance with local
codes. It is required that a ground union be installed
adjacent to the gas valve of each duct furnace, and
a ground union be installed just external of each duct
furnace for unit servicing. On vertical runs, a drip leg
should be provided upstream of any control manifold. A
gas shutoff valve should be, or may be required by local
codes, installed upstream of the external ground union
for each duct furnace. A 1/8" N.P.T. plugged tapping,
accessible for test gauge connection, must be installed
immediately upstream of the unit gas supply connection.
Never use an open fl ame to detect
gas leaks. Explosive conditions may e xist which
would result in personal injury or death.
The gas line should be supported so that no strain is
placed on the unit. Pipe compounds which are not solub le
to liquid petroleum gases must be used on threaded joints.
The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping
system by closing the individual manual shutoff valv e during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
For additional gas piping information, including pipe sizing
and drip leg installation, refer to Separated Combustion
Indoor Gas-Fired Duct Furnace Installation and Service
Manual.
For additional piping information, refer to the National
Fuel Gas Code Z233.1 (latest edition).
The open end of piping systems being
purged shall not discharge into areas where there are
sources of ignition or into confi ned spaces UNLESS
precautions are taken as follows: (1) By ventilation of
the space, (2) control of purging rate, (3) elimination
of all hazardous conditions. All precautions m ust be
taken to perform this operation in a safe manner!
†† For complete Gas Piping installation, see the
Separated Combustion Indoor Gas-Fired Duct
Furnace Installation and Service Manual.
— 13 —
NOTICE: If the gas duct furnace is to be fi red with LP gas,
consult local LP gas dealer for piping size information.
NOTICE: Unit installation for use with propane (bottled)
gas must be made by a qualifi ed LP gas dealer or
installer. He will insure proper joint compounds are
used for making pipe connections; that air is purged
from lines; that a thor ough test is made for leaks before
operating the unit; and that it is properl y connected to
propane gas supply system.
Before any connection is made to an e xisting line supplying
other gas appliances, contact the local gas company to
make certain that the existing line is of adequate size to
handle the combined load.
Check all connections for leaks with soap solution.
MODULATING GAS CONTROL (OPTIONAL)*
AIR FLOWAIR FLOW
Electrical Cabinet
Air Handler
Junction Box
Duct Furnace
Conduit
Low Voltage
Conduit
Line Voltage
D03304
*
*** *
*
*
***
***
Electronic: On units equipped with electronic modulating
control, follow control manufacturer’s installation
instructions for sensing of outlet air temperature.
*Also refer to the Separated Combustion Indoor Duct
Furnace Installation Manual supplied with your unit.
ELECTRICAL CONNECTIONS
Do not use any tools (i.e. screwdriver,
pliers, etc.) across terminals to check for po wer. Use
of a voltmeter is recommended.
Locate the thermostat in accordance with the instructions
supplied with the thermostat. All fi eld wiring must have
a minimum temperature rating of 185°F (85°C). Control
wiring shall be a minimum of 18 gauge wire size. Control
wiring must be sized for length of run.
HAZARDOUS VOL TAGE!
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE
DISCONNECTS BEFORE
SERVICING. Failure to
disconnect power before
servicing can cause severe
personal injury or death.
All electrical connections must conform to: the latest
edition of ANSI/NFPA No. 70, National Electrical Code,
and applicable local codes. In Canada, to the Canadian
Electrical Code, Part I CSA Standard C22.1.
Single furnace make-up air packaged units are wired
at the factory and are ready to be connected. Multiple
furnace make-up air units are shipped in two parts, the air
handler section and the furnace section. After mounting
the two sections and installing the fl exible duct connector,
connect the free end of the fl exible conduits from the air
handler section to the junction box on the duct furnace.
Each wire has a distinctive marking. Connect each wire
to its respectively marked terminal in the duct furnace
junction box. See Figure 13A. Actual unit wiring will differ
according to the options chosen. Each unit is shipped
with its own wiring diagram; refer to this wiring diagram
for all electrical connections to the unit.
Locate line voltage disconnect box per local codes. If
mounting the disconnect box to the unit, never mount
it to a unit access panel. Possible locations include
the front of the blower or fi lter section (See Figure 15).
Electrical conduit must be routed so as not to interfere
with removal of any access panel.
NOTICE: Should any original wire supplied with the unit
have to be replaced, it must be replaced with wiring
having a temperature rating of at least 221°F (105°C).
Figure 13A
All line voltage and thermostat connections are made
in the Electrical Cabinet (See Figure 13B). Line voltage
connections are made at the High Voltage Terminal
Block. Thermostat connections are made at the Main
Connection Board (See Figure 14).
— 14 —
Figure 13B - Make-Up Air Unit-Standard Blower Cabinet, Single Duct Furnace with Various Options Shown
D4108
Disconnect Box
Disconnect Box Located On Outside Air Application
D4109
Disconnect Box
Disconnect Box Located On Outside Air Application
Field Ductwork
For Outside
Air Inlet
RETURN AIR
AIR FLOW
OUTSIDE AIR
20
25
24
22
23
21
18
19
17
16
15
12345 6 7
Dampers/Filters/
Blower Cabinet
8910
12
13
FurnaceCabinet
ElectricalDuct
14
26
27
D6572
1. Mixed Air Controller
2. Return Firestat
3. Economizer
4. Filters
5. Blower Motor
6. Reverse Air Flow Switch
7. Clogged Filter Switch
8. High Voltage Barrier, Lamp
and Circuit Breaker Mount
9. Main Connection Board
with Fan Time Delay
and Function Relays
10. Power Venter Motor Assembly
(includes Relay and
Air Pressure Switch)
11. Ignition Module (not shownlocated in burner compartment)
12. Time Delay Freezestat
13. Supply Firestat
14. Duct Thermostat
15. Safety Limit Switch
16. Gas Valve
17. Primary High Limit Switch
18. Transformer
19. Electrical Wiring Inlet
20. High Voltage Terminal Block
21. Door Safety Switch
22. Contactor
23. Centrifugal Blower
24. Damper Motor
25. Outside and Return Dampers
26. Ambient Lockout
27. CO2 Monitor
Figure 14 - Electrical Cabinet
Figure 15 - Disconnect Box Locations
Return Air Inlet
Outside Air Inlet
— 15 —
DX COIL EQUIPPED UNITS (OPTIONAL)
Drain Pan Connection
H
Total
Height
of Trap
X = 1/2 “H”
H = At Least 1 Inch Plus
Casing Static Pressure
D3887
Total Height Of Trap = X+ H + (1-1/2 X Pipe Diameter)
(without Insulation)
Unit
Housekeeping
Pad
X
See Coil Installation/Maintenance Manual for Refrigerant
Piping, Liquid and Suction Line Components, Refrigerant
Charging and Thermal Expansion Valve Adjustment.
Remove coil cabinet access door located next to blower
section. Cut holes in fi xed door to allow suction and liquid
line passage. Provide weatherproof seal around suction
and liquid lines at piping plate when installed.
The DX Coil has a 300 ft/min. (1.524 m/s) minimum and
a 600 ft/min. (3.048 m/s) maximum velocity through the
coil requirement. This is due to prevention of coil icing or
condensate blow-off. To calculate the velocity through the
coil, apply the following formula:
Figure 16 - Drain Pan Connection
Velocity =
through the coil
Condensate Drain piping must have a P-trap in line
immediately downstream of drain pan connection,
external to the unit, to prevent possible outside air
leakage into unit. The P-trap shall be of sufficient
differential to overcome negative pressure of the indoor
air blower. A minimum height difference of 2" (51mm) is
required (See Figure 16). Before unit operation begins,
the P-trap must be primed with either water (summer) or
glycol (winter).
CHILLED WATER COIL
EQUIPPED UNITS (OPTIONAL)
See Coil Installation/Maintenance Manual for General
Coil Piping Recommendations. Remove coil cabinet
access door, cut holes in door to allow chilled w ater piping
passage. Provide weatherproof seal around chilled water
pipes at piping plate when installed.
The Chilled Water Coil has a 600 ft/min (3.048 m/s)
maximum velocity through the coil requirement. This is
due to prevention of condensate blow-off. To calculate
the velocity through the coil apply the following formula:
Velocity =
through the coil
Condensate Drain piping must have a P-trap in line
immediately downstream of drain pan connection,
external to the unit, to prevent possib le outside air leakage
into unit. The P-trap shall be of suffi cient differential to
overcome negative pressure of the indoor air blower. A
minimum height difference of 2" is required (See Figure
16). Bef ore unit operation begins, prime P-trap with either
water (summer) or glycol (winter).
EVAPORATIVE COOLER
EQUIPPED UNITS (OPTIONAL)
Refer to Evaporative Cooler Installation and Service
Manual for water and electrical connections.
Cooling Air Flow in CFM (m3/s)
Coil Surface Area in ft2 (m2)
Cooling Air Flow in CFM (m3/s)
Coil Surface Area in ft2 (m2)
IV. OPERATION
GENERAL INFORMATION
Refer to Separated Combusion Indoor Gas-Fired Duct
Furnace Installation and Service Manual for specifi c
information regarding the heating operation of this unit.
All units are equipped with an intermittent ignition pilot
system. The pilot is lit and e xtinguished each cycle of unit
heating operation.
On natural gas units, the ignitor will continue to spark and
pilot gas will continue to fl ow until the pilot fl ame is proven.
LP (propane) units are equipped with 100% lockout. The
lockout function shuts off the main and pilot gas valves if
the pilot gas fails to ignite within 90 seconds of the onset
of trial for ignition.
The gas control system operates at 24 VAC and is
supplied by a stepdown transf ormer found in the electrical
cabinet that will match the unit line voltage specifi ed. See
Figures 13 through 15 for unit controls location.
Do not use a thermostatic fan control switch when either
two-stage fi ring or modulated gas controls are used.
GAS CONTROL SYSTEM
The standard unit comes equipped for single stage
operation. Unit heating operation is accomplished at
full input.
Each duct furnace is equipped with an individual ignition
control system which consists of the following components:
ignition control module, gas valve and pilot burner.
The ignition control module is the heart of the ignition
control system. This control initiates all gas fl ow , provides
means to light the pilot burner, proves and monitors the
pilot burner operation.
— 16 —
The gas valve consists of two operators which provide
gas to the pilot and main burners. Both operators are
energized and de-energized by the ignition control
module each heating cycle.
The pilot burner includes an ignitor and fl ame sense
probe. The ignitor provides the spark, originating at the
ignition control module, to light the pilot. The ignition
control module proves and monitors the pilot fl ame
through the fl ame sensing probe.
SEQUENCE OF OPERATION
All units follow the same basic sequence of operation
and is as follows:
1. Thermostat calls for heat. Draftor relay energizes
draftor with call for heat.
2. Pressure switch closes circuit to ignition control
module.
3. Ignition control module energizes pilot operator of gas
valve and initiates spark at ignitor of the pilot burner.
4. Pilot burner ignition is proven to the ignition control
by the fl ame sense probe and sparking of the ignitor
is discontinued.
5. Once pilot burner operation is proven, the ignition
control module energizes the main burner operator of
the gas valve, allo wing gas fl ow to the main burners.
6. Approximately 60 seconds after the main burners
light, the fan time delay initiates fan operation.
7. Thermostat is satisfied and call for heat is
removed. Draftor relay de-energizes draftor with
removal of call f or heat.
8. Ignition control module de-energizes pilot and main
burner operators of the gas valve , ceasing all gas fl ow.
Three Stage Units:Dual duct furnace models: First
furnace is equipped with two stage heating; second
furnace is equipped with single stage heating but fi red
independently, giving three stages of heating.
Triple duct furnace models: Each duct furnace is
equipped with single stage heating but fired
independently, giving three stages. Each stage is 33%
of the unit’s full input rate. Duct furnace one will always
light fi rst and disengage last.
Four Stage Units: Dual duct furnace models only. Each
duct furnace is equipped with two stage heating but fi red
independently, giving four stages. Each stage is 25% of
the units full input rate. Duct furnace one will always light
fi rst and disengage last.
Six Stage Units: Triple duct fur nace models only. Each
duct furnace is equipped with two stage heating but fi red
independently giving six stages. Each stage is 16.5% of
the units full input rate. Duct furnace one will always light
fi rst and disengage last.
Electronic Modulation Units: These units are equipped
with an electronic modulating control which provides unit
fi ring capabilities of 50 to 100% of the units full input
rate. This control is found in the gas train downstream
of the gas valve and allows main bur ner ignition only at
the maximum rate. A thermostat with remote setpoint
adjustment modulates the gas input.
Multi-Stage w/Electronic Modulation Units:These
dual and triple duct furnace models are equipped with
an electronic modulating control on duct furnace one
and single or two stage heating on each successive
duct furnace. Furnace one (modulated) will fi re fi rst and
disengage last. Additional stages of heat will engage
after furnace one has fi red at maximum modulation
capability for the duration of the delay setting. The
amount of modulation and each stage size depends
upon
unit size and the number of stages. See following chart.
9. Approximately two minutes after satisfying the
thermostat, fan operation ceases.
OPTIONAL GAS CONTROLS
These units are available with optional gas controls
which will give either multi-stage or modulating operation.
The sequence of operation of those units equipped with
these optional gas controls differs only at what rate each
duct furnace’s main burners ignite and operate at, or the
order of duct furnace fi ring for those units equipped with
two or three duct furnaces.
Two Stage Units: Two stages of heating; fi rst stage is
50% of full rate, second stage is 100% of full rate. Main
burner ignition is at fi rst stage only.
— 17 —
Modulation Stage
Number Capabilities Size
of Stages (% of full input) (% of full input)
Remove wooden shipping support
from beneath blower housing of Blower Section
(if applicable) to prevent possible unit damage or
improper unit operation.
Static Pressure through the unit should never exceed
2.0" W.C. (0.50 kPa). Units operate at a temperature rise
range of 20 to 90°F (11 to 50°C).
It is important that the blower motor and the blower
wheel pulleys be in good alignment, with the motor and
blower shafts parallel.
Belt tension must be adjusted to give approximately
3
/4" defl ection of the belt when fi nger pressure is applied
to the middle of the belt (See Figure 17). Small changes
in this tension may be necessary for optimum operation.
Belts will stretch over a period of time, requiring an
adjustment to this tension. See MAINTENANCE section
for belt and pulley adjustments.
NOTICE: It is impor tant that the fi nal temperature
leaving the unit does not exceed 160° F (71°C). When
fi nal air throughput adjustments are being made, a
check of the discharge air temperature should be
made after unit has operated for 15 to 20 minutes.
A unit should never be allowed to
cycle on the primary limit for a prolonged period of
time. It is a safety control to prevent a fi re. If cycling
on the primary limit is noted, corrective measures
should be taken immediately. Failure to do so could
result in unit damage or a fi re.
NOTICE: At initial unit installation, unit should be
started momentarily to confi rm proper blower wheel
rotation as the unit will deliver some air with the
blower wheel running backwards.
Two basic air control systems can be used to deliver
conditioned air to the occupied space: intermittent or
constant fan operation.
Intermittent Fan Operation: The unit employs an air
control system which utilizes a fan time delay relay to
operate the fan while in the heating mode. If equipped
with cooling, the thermostat controls the fan through
a relay when in the cooling mode. Refer to unit wiring
diagram.
These units are set at the factory for the RPM required to
meet the air volume (CFM) and external static pressure
ordered. If the estimated exter nal static is incorrect, or
changes were made to the duct system, the blower RPM
may need to be changed.
Both the Standard and High CFM Blowers use motors
which are equipped with adjustable pitch pulleys. After
removing belt(s), loosen the pulley set screw and remo ve
the key, turn adjustable half of a pulley clockwise to
increase RPM, or counter-clockwise to decrease RPM.
Insert key, tighten set screw and replace belt(s). Adjust
belt tension to give 1/2" to 3/4" belt play when depressed.
Blower motor full load amps should
never be exceeded. Improper unit operation or motor
failure could result.
After changing blower RPM, confi rm blower motor full
load amps have not been exceeded. See motor data
plate for maximum full load amps.
Figure 17
Constant Fan Operation: The unit can be wired to give
an air control system which constantly circulates air
through the unit and occupied space with constant fan
operation. Refer to unit wiring diagram.
NOTICE: Check blower belt tension. Proper belt
tension is important to the long life of the belt and
motor. Proper belt tension will allow the belt to be
depressed 1/2" to 3/4".
— 18 —
LIGHTING
Refer to Separated Combustion Indoor Duct Furnace
Manual for all heating functions - general comments
are as follows.
Meter Method of Checking Input Rate
1. Obtain the heating value of the gas from the local
utility or gas dealer. This should be in units of Btu/ft3
(MJ/m3).
Purge the gas line to the unit of air before attempting to
light the pilot. Check for gas leaks.
Never use an open fl ame to detect
gas leaks. Explosive conditions may exist which
could result in personal injury or death.
This unit is equipped with an intermittent ignition system.
A lighting instruction label is attached to the unit. To set
the intermittent ignition system into operation, proceed
as follows:
1. Turn on the gas valve(s) main manual valve.
2. Turn on electrical power. The unit is now under
thermostat control.
3. Set thermostat to highest level. This will initiate the
sequence of operation detailed in the Gas Control
System section. Check main burners for operation.
4. Set thermostat to lowest level. This will interrupt power
to the ignition control and shut off gas. Confi rm pilot
and main burners have been extinguished.
5. Set the thermostat to the desired setting.
For complete unit shutdown, proceed as follows:
2. Determine the gas fl ow rate as shown in the following
example. EXAMPLE: Assume this unit has a input rate
of 250,000 Btu/hr (73.2 kW) and the heating value of
the gas is 1000 Btu/ft3 (37.3 MJ/m3).
Gas
Flow =
Rate
= 4.17 ft3/min
3. Before determining the gas fl ow rate to the unit, all
other gas appliances connected to the same meter
must be turned off.
4. Fire unit according to instructions.
5. After approximately 15 minutes of unit operation,
determine volume of gas used in fi ve minutes of unit
operation. For the Example above the unit should
use 4.17 ft3/min x 5 min or 20.8 ft3 (1.97 L/s x 5 min x
60 s/min = 591L) of gas. Minor input adjustments
can be made by removing pressure regulator cap
and turning regulator clockwise to increase input or
counter clockwise to decrease input. Any appreciable
adjustment in input rate should be made by reorifi cing.
Method to Check Manifold Pressure
1. Close the manual valve of unit gas valve.
250,000 Btu/hr
1000 Btu/ft3 x 60 min/hr
1. Turn off the gas valve(s) main manual valve.
2. Set thermostat to lowest setting.
3. Shut off all electric power.
GAS INPUT ADJUSTMENT
When shipped from the factory, all units are equipped for
the average heat content of the gas which is stamped on
the unit rating plate.
Since the heat content of gas varies by
locality, the input must be checked after installation
of the unit. If the unit is overfi red it will shorten the
life of the heat exchanger. Never exceed the input on
the rating plate.
For an accurate input rate measurement, the following
meter method should be used to determine unit input rate.
If the meter method is not possible, a manifold pressure
check should be made.
2. Install a 1/8" pipe connection in the tapped hole
provided in the gas valve body near outlet of the valve.
3. Attach manometer to 1/8" pipe connection by means
of a rubber hose.
4. Fire unit according to instructions and obser ve the
pressure and confi rm it matches the unit manifold
pressure from the unit rating plate.
5. Small variations in the manifold pressure can be
made by means of the gas valve pressure regulator.
Remove pressure regulator cap and turn regulator
clockwise to increase pressure or counter-clockwise
to decrease pressure.
— 19 —
PILOT ADJUSTMENT
1.
Disconnect wire from terminal marked MV at gas valve.
2. Provide call for heat.
3. Pilot adjustment is found on the gas valve. Remove
pilot adjustment cap.
4. Adjust the pilot screw to provide properly sized fl ame.
5. A proper pilot burner fl ame is a soft steady fl ame that
envelopes 3/8 to 1/2" (9.5 to 12.7mm) of the fl ame
sense probe tip.
6. Replace the pilot adjustment cap.
Freezestat: (Optional) Located in either the return
airstream, the supply airstream, or both, this control
monitors temperatures with setpoints which are fi eld
adjustable. If the temperature does not exceed the
setpoint, the control will cease unit operation.
V. START UP
Before starting the unit, use the “Installation Check
Sheet” (located at the end of this manual) and read the
Separated Combustion Indoor Duct Furnace Manual
entirely in conjunction with the procedures outlined
below to ensure that the unit is completely and properly
installed and ready for start up.
7. Reconnect wire to terminal MV.
PRIMARY AIR SHUTTER ADJUSTMENT
After the unit has been in operation for at least 15
minutes, adjust the primary air fl ow to the burners. Turn
the friction-locked manually rotated air shutters clockwise
to close, counter clockwise to open. For correct air
adjustment, close the air shutter until yellow tips in the
fl ame appear. Then open the air shutter to the point just
beyond the position where yellow tipping disappears.
CONTROLS
(also see the Indoor Duct Furnace Manual):
Primary Limit Control: The primary limit control is a
factory installed component surface mounted in the inlet
airstream at the end of the heat exchanger. When the
temperature reaches the limit setpoint, normally caused
by insuffi cient air throughput, all gas is shutoff. The limit
control has an automatic reset and once the unit has
cooled, it will reset itself. This is a safety control and if
cycling on the primary limit is noted, corrective action must
be taken. See unit wir ing diagram for electrical location.
This control must never be bypassed. Upon completion
of unit installation, the primary limit must be checked for
proper operation. This can be accomplished by removing
power to the indoor air blower and a call for heat.
Clogged Filter Switch: (Optional) The clogged filter
switch monitors the pressure differential across the air
fi lters. If this pressure differential becomes too great, the
switch will alert of this condition. At this point the air fi lters
must either be cleaned or replaced. The switch will reset
itself.
Firestat: (Optional) Located in either the return
airstream, the supply airstream, or both, this control
monitors temperatures with setpoints which are fi eld
adjustable. If the temperature exceeds the setpoint,
the control will cease unit operation. To resume unit
operation, a manual reset of this control is required.
It is the installer’s responsibility
to check all safety controls! Check and test
the operational functions of all safety devices
supplied with this unit. Failure to do so could
result in unsafe conditions and may result in
death, serious injury or property damage.
1. Inspect all wiring connections; connections should
be clean and tight. Trace circuits to insure that
actual wiring agrees with the “as wired” diagrams
provided with the unit. Information in the wiring
diagram title block should match the data appearing
on the unit nameplate.
2. Lubricate all electrical motors according to the
manufacturer’s recommendations.
3. Verify that the system switch is in the OFF position.
4. Check unit supply voltage to ensure that it is within
the utilization range.
5. Inspect the interior of the unit; remove any debris or
tools which may be present.
Starting Unit in Heating Mode
1. Close the unit disconnect switch which provides
power to the unit.
High voltage is present in some
areas of the unit (primarily the main electrical
cabinet) with the unit disconnect switch closed.
Failure to exercise caution when working in the
presence of energized electrical components
may result in injury or death from electrical
shock.
2. Set the thermostat/switching subbase as indicated
below: a. position the heating system switch at either
HEAT or AUTO; b. set the fan switch to AUTO.
3. Place the system switch in the ON position. With the
thermostat calling for heat, unit operation is automatic.
— 20 —
Starting Unit in Cooling Mode
1. Close the unit disconnect switch which provides
power to the unit.
High voltage is present in some
areas of the unit (primarily the main electrical
cabinet) with the unit disconnect switch closed.
Failure to exercise caution when working in the
presence of energized electrical components
may result in injury or death from electrical
shock.
Inspect the suspension and/or
support system for the make-up air unit to ensure
that all fasteners are tight and the unit is secure
before working underneath the unit. Failuree to
do so could result in property damage, personal
injury, or death.
Gas tightness of the safety shutoff valves must be checked on at least an annual
basis.
2. Set the thermostat/switching subbase as indicated
below: a. position the cooling system switch at either
COOL or AUTO; b. set the fan switch to AUTO.
3. Place the system switch in the ON position.
With the thermostat calling for cooling, unit operation is
automatic.
Final Checkout
Run the unit sequentially through its stages of heating
and cooling. Once proper unit operation is verified,
perform these fi nal steps:
1. Inspect unit for debris and/or misplaced tools and
hardware.
2. Be sure all gas valves and controls are in the operating
position if the unit will be operating immediately.
3. Cycle unit on all safety controls to verify proper unit
operation.
4. Confirm proper operating control (thermostat or
ductstat) operation by cycling unit.
5. Secure all exterior panels in place.
T o check gas tightness of the saf ety shut-off valves , turn off
the manual valve upstream of the appliance combination
control. Remo v e the 1/8" pipe plug on the inlet side of the
combination control and connect a manometer to that
tapping. Turn the manual valve on to apply pressure to
the combination control. Note the pressure reading on
the manometer, then turn the valv e off . A loss of pressure
indicates a leak. If a leak is detected, use a soap solution
to check all threaded connections. If no leak is found,
combination control is faulty and must be replaced bef ore
putting appliance back in service.
These units have been developed for indoor installation.
Maintenance is required and it is suggested that the
following unit servicing and inspections be performed
routinely. Also read in entirety and refer to the Separated
Combustion Indoor Duct Furnace Manual for maintenance
requirements.
Inspect area near unit to be sure that there is no
combustible material located within the minimum
clearance requirements (See Figure 11). Service panels
provide easy access to the blower compartment and the
electrical cabinet. To remove the service door from any
of these compartments, refer to access panel removal
section in beginning of this manual.
VI. MAINTENANCE
HAZARDOUS VOL TAGE!
DISCONNECT ALL ELECTRIC
POWER INCLUDING REMOTE
DISCONNECTS BEFORE
SERVICING. Failure to
disconnect power before
servicing can cause severe
personal injury or death.
It is the service technician’s
responsibility to check all safety controls! Check
and test the operational functions of all safety
devices supplied with this unit. Failure to do so
could result in unsafe conditions and may result
in death, serious injury or property damage.
— 21 —
Under no circumstance should
combustible material be located within the
specifi ed clearances. Failure to provide proper
clearance could result in personal injury or
property damage from fi re.
1. Follow the instructions in the maintenance section of
the of the Separated Combustion Indoor Duct Furnace
manual for servicing the furnace section of the makeup air unit.
2. Inspect and service the b lo w er section of the system.
3. Inspect and check the operational functions of all
safety devices equipped with y our unit to ensure that
all devices are performing adequately.
HIGH LIMIT AND/OR SAFETY LIMIT MAINTENANCE
Single furnace units are equipped with a primar y high
limit on the upstream side of the heat exchanger and
a secondary high limit on the downstream side of the
heat exchanger. Multiple furnace units are equipped
with a primary high limit on each fur nace section and a
secondary high limit on the downstream unit. The primary
high limit is a disk type switch while the secondary high
limit is a capillary switch. To service or replace high limit
or safety limit:
1. Turn off the manual gas v alve and electrical power to
the MS unit.
SEASONAL MAINTENANCE
The unit should be thoroughly checked before the start and
at the end of each heating and cooling season.
A. Motors and belts should be inspected.
B. Tighten belts if loose.
C. Check and clean DX or Chilled Water coil twice y early ,
if unit is so equipped per manufacturer’s service
manual. Chilled Water coil must be winterized at
beginning of heating season (i.e. drain water from coil
per manufacturer’s instructions).
2. T o access the high limits, remove the f our screws from
the top of the raceway on each furnace section and
swing the raceway down. The primary limit can be
removed by remo ving the two screws holding the high
limit bracket to the heat e xchanger and removing the
bracket and limit assemb ly from the heat e xchanger.
Note location of and remove wires from limit switch,
then remove push nuts and springs holding limit
switch to bracket. Re-assemble in reverse order
making sure that parts are assembled so that spring
pressure holds limit switch securely against bottom
header plate of heat exchanger.
3. T o remov e the secondary high limit, remove the wires
from the limit switch, remov e the screws and stand-off
sleeves holding the limit s witch body to the mounting
plate. Do not remove the screws holding the mounting plate to the heat exchanger . Slowly pulll
the switch and capillary assembly out of the retaining
tube, taking care to prev ent kinking the capillary tube.
Re-assemble in rev erse order, careefully pushing the
capillary tube into the retaining tube to prevent kinking
the capillary tube.
4. Complete appropriate start-up procedure as given in
the “Start-Up” section of this manual.
5. Check Burner Adjustment.
6.
Check gas control valv es and pipe connection for leaks.
7. Check operation of auto gas valve.
D . Check air throughput at beginning of heating season
to confirm unit operation is within the specified
temperature rise range.
E. At beginning of heating season clear Condensate
Drain Pan and P-trap of w ater if unit is equipped with
DX or Chilled water coil. Clean out drain pan and fi ll
P-trap with a non-toxic glycol solution.
F. Evaporative cooler must be cleaned and maintained
per manufacturer’s instr uction frequently during the
operating season.
G. Inspect Control Dampers during periodic maintenance.
Damper pivot points should be cleaned to ensure free
damper operation.
H. Blower wheels should be checked periodically for dirt
build-up on blades. Clean as required.
FILTERS
The fi lter section has been designed to incorporate (as
standard) one-inch washable fi lters. Other optional fi lter
types are also available: two-inch washable throwaw a ys;
or one or two inch hi-effi ciency 30% pleated fi lters.
It is recommended that air fi lters be changed or cleaned
at least four times a year . More frequent attention to fi lters
is required if the air being handled by the unit is unusually
dirty. Air fl ow reduction, caused by the dirty air fi lters, will
increase the discharge air temperature and may cause
unit cycling on the primary limit.
8. Check operation of safety devices.
9. Inspect and service blower section of system.
Filters (by others) should be serviced regularly and
changed or washed when necessary to maintain the
required air throughput. In a dusty environment, fi lters
may clog up in less than one month.
— 22 —
A
A
A
B
Standard CFM Blower Air Filter Size Requirements
Number of Filters Required
Unit Input 16 x 20 (in) 20 x 20 (in)
Belt Tension Adjustment Standard CFM Blower belt
tension can be adjusted by loosening motor mounting
bolts marked A (See Figure 18). To tighten belt, slide
motor down motor mounting bracket and re-fasten motor
to mounting bracket.
High CFM Blower belt(s) tension can be adjusted by
fi rst loosening motor mounting plate bolts marked A
(See Figure 18). To tighten belt tension, turn belt tension
adjustment screws marked B (See Figure 18) counterclockwise. To loosen belt tension, turn clockwise. Once
belt tension has been adjusted, re-fasten motor mounting
plate bolts.
— 23 —
A
A
B
B
A
A
KEY B PROJECTS TO PROVIDE A GRIP FOR REMOVING.
DO NOT OPERATE SHEAVE WITH FLANGE PROJECTING
BEYOND THE HUB END.
D3881
Blower RPM Adjustment
To adjust blower RPM:
1. Loosen and remove belt(s).
2. Match driver pulley to one found
in Figure 19.
3. Loosen set screw(s) marked A.
4. If driver pulley is equipped with
external key, marked B, remove.
5. Adjust driver pulley pitch
diameter for desired speed by
opening (slower) or closing
(faster) moving parts by half or
full turns. Do not open sheave
past point where fl ange projects
past the hub end.
6. If driver pulley is equipped with
external key, marked B, replace.
7. Tighten set screw(s) marked A.
Figure 19
8. Replace and retension belt(s).
9. Realign drive if necessary.
— 24 —
VII. TR OUBLESHOOTING
For troubleshooting of the duct furnace, refer to the Separated Combustion Indoor Gas-Fired Duct Furnace Installation
and Service Manual. F or Evaporative Cooler/Cooling Coil equipped units , refer to these specifi c manuals for additional
troubleshooting guides.
For additional troubleshooting, see following Troubleshooting Guide.
TROUBLESHOOTING GUIDE
AIR BLOWER
PROBLEM PROBABLE CAUSE SOLUTION
1. Noise Blower Wheel Hitting Scroll Side a. Blower Wheel not centered in blower housing.
b. Damaged blower housing.
c. Damaged blower wheel.
d. Shaft loose in blower bearing.
e. Blower Wheel loose on shaft.
f. Blower bearing loose in bearing support.
Blower Wheel Hitting Cutoff a. Cutoff not secure in blower housing.
b. Cutoff damaged.
c. Cutoff improperly positioned.
Drive a. Pulley not tight on shaft (motor and/or blower
wheel).
b. Belts too loose. Adjust for belt stretching after 48
hours of operation.
c. Belts too tight.
d. Belts wrong cross section.
e. Belts not matched in length on multi-belt drive.
f. Variable pitch pulleys not adjusted so each pulley
has same pitch diameter (multi-belt drives).
g. Misaligned pulleys.
h. Belts worn.
i. Motor or motor base loose.
j. Belts oily or dirty.
k. Improper drive selection.
Bearing a. Defective bearing.
b. Needs lubrication.
c. Loose on bearing support.
d. Loose on shaft.
e. Seals misaligned.
f. Foreign material in bearing.
g. Worn bearing.
h. Fretting corrosion between inner race and shaft.
Shaft Seal Squeal a. Needs lubrication.
b. Misaligned.
— 25 —
PROBLEM PROBABLE CAUSE SOLUTION
1. Noise Blower Wheel a. Loose on shaft.
b. Defective blower wheel.
Do not run blower.
Contact manufacturer.
c. Unbalanced.
d. Worn as a result of contact with
abrasive or corrosive material.
Housing a. Foreign material in housing.
b. Cutoff or other part loose (rattling
during operation).
Electrical a. Lead-in cable not secure.
b. AC hum in motor or relay.
c. Starting relay chatter.
d. Noisy motor bearings.
e. Single phasing a 3 phase motor.
Shaft a. Bent.
b. Undersized. May cause noise at
blower wheel, bearings or pulley.
c. If more than two bearings are on a shaft, they must be properly aligned.
High Air Velocity a. Duct work too small for application.
b. Blower selection too small for application.
c. Registers or grilles too small for application.
d. Cooling coil with insuffi cient face area for application.
Obstruction in High Velocity Air Stream a. Dampers.
c. Grilles.
d. Sharp elbows.
e. Sudden expansion in duct work.
f. Sudden contraction in duct work.
g. Turning vanes.
Pulsation or Surge a. Blower too large for application.
b. Ducts vibrate at same frequency as blower pulsations.
Rattles and/or Rumbles a. Vibrating duct work.
b. Vibrating cabinet parts.
c. Vibrating parts not isolated from building.
c. Cutoff missing or improperly installed.
d. Blower wheel RPM too low.
Duct System a. Actual system is more restrictive than expected.
b. Dampers closed.
c. Registers closed.
d. Leaks in supply duct.
may cause Rattle or Pure Tone Whistle
b. Blower operating backwards.
b. Registers.
— 26 —
PROBLEM PROBABLE CAUSE SOLUTION
2. CFM Low Filters Dirty or clogged.
Insuffi cient Air Flow
Obstructions in High Velocity Air Stream a. Obstruction near unit outlet.
b. Sharp elbows near unit outlet.
c. Improperly designed turning vanes.
d. Projections, dampers or other obstructions in part
of duct system where air velocity is high.
3. CFM High - System a. Oversized duct work.
Too Much Air Flow
c. Registers or grilles not installed.
d. Filters not in place.
e. System resistance lower than anticipated.
Blower Blower RPM is too great.
4. Blower Does Not Operate Installation a. Incorrect electrical connection.
b. Wrong voltage.
c. Blown fuse.
Unit a. Broken belt(s).
b. Loose pulleys.
c. Power to unit is disconnected.
d. Motor overload protector has broken circuit.
e. Optional thermostats, fi restats, freezestats may lockout blower operation if set incorrect.
Coil - DX or Chilled Water Dirty or clogged.
b. Access door open.
TROUBLESHOOTING GUIDE
ELECTRIC MOTORS
PROBLEM PROBABLE CAUSE SOLUTION
1. Motor Blown fuse or open circuit breaker. Replace fuse or reset circuit breaker.
Overload trip. Check and reset, if manual.
Improper line connections. Check connections to unit wiring diagram.
Improper current supply. Check to determine that power supply agrees with
Mechanical failure. Determine that motor and drive turn freely.
Motor overloaded. Reduce load or replace motor .
With a 3 phase power source, one Check line for open phase.
Defective capacitor. Replace capacitor.
2. Motor Stalls Wrong application. Consult manufacturer.
Overloaded motor. Reduce load or replace motor.
Low line voltage. Check across AC line and correct
phase may be open.
motor nameplate specifi cations.
Check bearings.
if possible.
— 27 —
PROBLEM PROBABLE CAUSE SOLUTION
3. Motor runs and then Partial loss of line voltage. Check for loose connections.
dies down.
4. Motor does not Motor undersized for application. Replace with larger motor.
come up to speed.
Line wiring to motor is too small. Install larger line wiring.
5. Motor takes too long Excessive load. Replace with larger motor.
to accelerate.
6. Wrong Rotation (3 Phase) Improperly wired to AC line (wrong Check unit wiring diagram. Reverse any two line
7. Motor Overheats Motor overloaded. Replace with larger motor.
Motor ventilation clogged. Clean motor.
Motor (3 phase) may have open phase. Check to insure that all connections are tight.
Line voltage too high or too low. Check across AC line and correct if possible.
Worn blower bearings. Replace blower bearings.
8. Motor Vibrates Motor mounting bolts loose. Tighten mounting bolts.
Driven equipment unbalanced. Balance driven equipment.
Worn motor bearings. Replace motor.
3 phase Motor running on single phase. Check for open circuit and correct.
Bent motor shaft. Replace motor.
9. Rapid Motor Bearing Excessive overhung load due to over Reduce belt tension.
Wear
Voltage too low at motor terminals. Check across AC line and correct if possible.
Loose connection. Check connections and tighten where necessary.
sequence of phases).
tensioned belt.
Determine adequacy of main power supply.
voltage connections.
TROUBLESHOOTING GUIDE
FAN ASSEMBLY
PROBLEM PROBABLE CAUSE SOLUTION
1. Short Belt Life Spin burns from belt slippage. Tension belt.
High ambient temperature. Use Gripnotch belts.
Grease or oil on belts. Clean belts and pulleys.
Worn pulleys. Replace pulleys.
Belt Misalignment. Realign drive.
2. Belts turn over in grooves Damaged belt. Replace belt.
3. Belt Squeal Excessive load. High starting load.Retension drive.
4. Belt Breakage Foreign material in drive. Provide drive guard.
Belts damaged during installation. Replace belts.
Extreme Overload. Eliminate overload.
5. Excessive Vibration Damaged belt cord section. Replace belts.
Loose belts. Tension drive.
Belts improperly tensioned. Tension drive with slack of each belt on the
same side of drive.
— 28 —
PROBLEM PROBABLE CAUSE SOLUTION
6. Belts mismatched Belts improperly tensioned, causing Replace belts and tension drive with slack of each
after service
Old belts and new belts used Replace with new belts.
Different brand name belts used Replace with a set of Machine Matched Belts.
Driver and driven shafts shifted Realign drive.
Belt cord section damaged during Replace belts and install properly.
7. Drive fails to adjust Fretting corrosion (drive allowed to Driver pulley must be disassembled,
more stretch of some belts than others. belt on the same side of the drive.
on same drive.
on same drive.
from parallel.
installation.
operate at one speed over a period cleaned and lubricated, then
of time). reassembled.
TROUBLESHOOTING GUIDE
DX COOLING COIL
PROBLEM PROBABLE CAUSE SOLUTION
1. No or Insuffi cient Coil icing. a. Low liquid line pressure.*
Cooling
c. Low air fl ow across coil.
Air binding. Purge and charge system.
Thermal expansion valve.** a. Bulb mounted at incorrect location.
b. Bulb not secured properly.
Insuffi cient air fl ow. a. See air blower troubleshooting.
b. Clogged coil.
Air bypassing coil. Caulk safe off.
Undersized system, demand Replace system.*
Too much outside air. Check outside air dampers.
Refrigerant leak. Determine leak location and correct.
Low liquid pressure. Determine cause and correct.*
2. Water in Conditioned Air Exceeding coil face velocity - 600 fpm. Reduce unit air fl ow.
Drain pan p-trap clogged. Clean pan and p-trap.
* Refer to condensing unit installation and service manual.
**Refer to thermal expansion valve installation instruction.
b. Thermal expansion valve.**
exceeding cooling system capacity.
— 29 —
TROUBLESHOOTING GUIDE
CHILLED WATER COOLING COIL
PROBLEM PROBABLE CAUSE SOLUTION
1. No or Insuffi cient Cooling Circulating pump failure. Repair or replace pump.*
Chilled water temperature Check chiller.*
Air binding (air in coil). Bleed coil.
Insuffi cient chilled water fl ow. a. Circulating pump capacity is inadequate.*
b. System piping losses too great.
Insuffi cient air fl ow. a. See air blower troubleshooting.
b. Clogged coil.
Air bypassing coil. Caulk safe off.
Undersized system, demand Replace system.*
Too much outside air. Check outside air dampers.
2. Water in Conditioned Air Exceeding coil face velocity - 600 fpm. Reduce unit air fl ow.
Drain pan P-trap clogged. Clean pan and p-trap.
*Refer to Manufacturer’s Installation and Service Manual.
not cool enough.
exceeding cooling system capacity.
VIII. REPLACEMENT PARTS
To order Replacement Parts, please provide the
following information to your local representative:
• Model Number
• Serial Number
• Part description and Number as shown in
Replacement Parts Literature
Due to the many confi gurations, options and voltage
characteristics available on Make-Up Air Packaged
Units, the information provided in this manual is
somewhat general in context. Should user or service
organization incur a problem, the nature of which is
not herein, we urge you to contact the manufacturer.
IX. SERVICE NOTE
It would be of great assistance to us if you can provide
If further assistance is required, please contact the
manufacturer’s customer service department
the model and serial numbers and the wiring diagram
number, as well as the access type.
X. LIMITED WARRANTY
All components are warranted by the manufacturer to be free from defects in material and workmanship for period of
one (1) year from the date of shipment from the manufacturing plant.
The manufacturer will repair or replace, at its option, any component which, upon inspection, it fi nds to be defective,
provided that the Make-Up Air Packaged Unit has been operated within its listed capacity, has been installed in
accordance with all furnished instruction, has not been misused or subjected to neglect and has received reasonable
and necessary maintenance. This warranty does not cover labor costs or other costs incurred in repairing, removing,
installing, servicing or handling of parts or completed products.
This Warranty does not cover loss due to corrosion by chemicals precipitated in the air such as halogenated hydrocarbons.
The manufacturer will in no event be liable for incidental or consequential damages of any kind whatsoever.
Written permission is required prior to the return of defective components. All returns must be sent with all transportation
charges prepaid to the plant designated in the written permission. This warranty is extended only to the original owner
of the Make-Up Air Package Unit.
— 30 —
“FOR CANADIAN INSTALLATIONS ONLY”
The following instructions apply to Canadian installations in addition to installation and operating instruction:
1. Installation must conform with local building codes, or in absense of local codes, with current CSA B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CSA B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.
2. Any reference to U.S. standards or codes in these instructions are to be ignored and the applicable
Canadian standards or codes applied.
3. Any references to deration at altitudes in excess of 2000 feet are to be ignored. When installed in
Canada at altitudes of 2000 to 4500 feet, the duct furnaces must be orifi ced to 90% of the normal
altitude rating, and be so marked in accordance with the ETL certifi cation.
4. Duct furnaces are designed certifi ed to comply with CSA 2.6.
5. In Canada, installation is suitable in airplane hangars when acceptable to the enforcing authorities,
and in public garages when installed in accordance with current CSA B149 Installation Codes for Gas Burning Appliances and Equipment.
6. All electrical connections must be in accordance with Canadian Electrical Code, P art 1, CSA Standard
C22.1.
7. In Canada, the vent system must be adequately supported to prevent sagging; but in no case shall
the supports be less than every 3 feet.
8. If using a metal vent system under positiv e gauge pressure in Canada, a slip fi t vent connection must
be secured b y a least two corrosiv e resistant scre ws , or other mechanical loc king means .
9. Canadian units require the following vent equivalent lengths; 5 feet minimum; 50 feet maximum.
10. The vent shall not terminate —
a. Less than 6 f eet from a combustion air inlet of another appliance.
b. Less than 3 feet from any other building opening or any gas service regulator.
c. Directly above a gas utility meter or service regulator .
11. V ent terminal shall be located not less than one foot abo ve grade.
12. It is recommended that the heater and vent system be checked once a year by a qualifi ed serviceman.
— 31 —
XI. DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “A”
Capacities [CA] 50 - 80
Indoor Arrangement [IA] “A”
Capacities [CA] 12
Refer to page 33 for tabulated dimensions.
— 32 —
DIMENSIONAL DATA — ARRANGEMENTS
This tabulated dimensional data applies to all dimensional drawings.
***Capacity Gas Inlet
(CA) A B C D G H J▲ L U V Dia.** NAT LP
NOTES: Unless otherwise noted the end views and dimensional data shown in the drawings and table are applicable to Indoor Arrangement [IA]-B, D, G, K.
Dimensions are in inches. Dimensions in parenthesis are in millimeters.
J▲ Dimension is an outside dimension for the return air damper.*This is an outside damper dimension.
**V = Flue Opening; the 4" to 5" reducer adaptor is to be fi eld installed for unit capacities 10 & 15.
The 5" to 6" increaser adaptor is supplied by the manufacturer for unit capacities 30, 35, 40, 60, 70, 80 & 12 (required for each furnace's fl ue).
***Capacities 10 through 40 are ETL certfi ed.
Typical
Intake Air End View
(Not applicable to [IA]-A or D
See Evaporative Cooling Specifi cations)
Typical
Discharge End View
— 33 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “B”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “B”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 34 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “D”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “D”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 35 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “G”
Capacities [CA] 20/40
(ships in one section)
Indoor Arrangement [IA] “G”
Capacities [CA] 50/12
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 36 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “K”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “K”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 37 —
XII. MOTOR ELECTRICAL DATA
Full Load Current In Amperes
1 - (115/1/60)2 - (208/1/60)3 - (230/1/60)
1
2
3
1
2
3
1
2
3
ODP
1/2 HP 7.28.64.64.63.72.83.84.32.32.3
3/4 HP 11.611.06.56.35.25.43.45.05.53.33.2
1 HP 13.013.48.68.56.66.86.56.74.34.3
1-1/2 HP 18.218.012.512.69.18.49.18.06.36.3
2 HP 21.023.017.617.611.311.510.58.18.88.8
3 HP 33.528.017.414.616.814.011.8
5 HP 23.521.023.019.1
7-1/2 HP 33.031.031.029.0
10 HP 38.0
15 HP
1
ODP
1/2 HP 2.32.01.81.72.22.51.82.01.11.00.91.0
3/4 HP 3.03.22.53.43.02.42.81.71.51.21.4
1 HP 3.43.73.13.13.43.43.03.11.71.71.51.5
1-1/2 HP 5.15.04.54.55.24.64.44.42.62.32.22.2
2 HP 6.25.86.06.05.85.83.02.92.9
3 HP 9.28.59.08.68.48.44.34.24.2
5 HP 12.811.812.011.86.05.9
7-1/2 HP 20.421.019.418.89.79.4
10 HP 26.027.025.025.012.512.5
15 HP 37.438.935.437.017.718.5
1
ODP
1/2 HP 0.80.8
3/4 HP 1.11.1
1 HP 1.31.71.21.2
1-1/2 HP 1.71.81.8
2 HP 2.32.4
3 HP 3.43.2
5 HP 5.35.3
7-1/2 HP 7.87.6
10 HP 10.09.6
15 HP 14.115.1
TE
TE
TE
PEODP4PETE
4 - (208/3/60)5 - (230/3/60)6 - (460/3/60)
2
7 - (575/3/60)
2
3
PEODP4PETE
3
PEODP4PETE
ODP
1
ODP
TE
TE
2
PEODP4PETE
3
PEODP4PETE
Motor Type (MT) Legend:
ODP - Open Drip Proof
ODP
1
ODP
TE
2
TE
TE - Totally Enclosed
PEODP - Premium Effi ciency Open Drip Proof
PETE - Premium Effi ciency Totally Enclosed
Note: The approximate shipping weights are for a basic unit (these
weights do not include the motor, cooling coil, optional outside air
hood, fl ex connector kit, or any options).
For units with double wall construction add an additional 10% of
the base unit weight.
— 39 —
XIV. COIL CABINET DIMENSIONAL DATA
INSIDE UNIT WALL
“ L” MAX.
31-3/4"
(806)
26" (660)
OUTSIDE BOTTOM PANEL
1"
(25)
1"
(25)
24"
(700)
33"
(838)
39"
(991)
3"
(76)
3"
(76)
13"(330)
MAX.
COIL
DEPTH
7/8"
(22)
TOP
53-1/4" (1353)
“ L” INSIDE MAX.
CABINET OPENING
42-1/4" (1073)
58-3/4" (1492)
31-1/4" (794)
30/35/60/70
UNIT SIZE
20/25/50
40/80
10/15
*
*
Maximum Coil Dimensions
Side Opening
of Coil Module
— 40 —
SEPARATED COMBUSTION
INDOOR MAKE-UP AIR PRODUCTS
MODEL “MS” SUBMITTAL INDEX
IA “B”
CA (10/40)
IA “D”
CA (10/40)
IA “G”
CA (10/40)
IA “K”
CA (10/40)
Single Furnace Units
(ETL Certifi ed)
Unit Type (UT): MS
Submittal
Number
MS-40-B
MS-40-D
MS-40-G
MS-40-K
IA “A”
CA (50/80)
IA “B”
CA (50/80)
IA “D”
CA (50/80)
IA “G”
CA (50/80)
IA “K”
CA (50/80)
Dual Furnace Units*
Unit Type (UT): MS
Submittal
Number
MS-80-A
MS-80-B
MS-80-D
MS-80-G
MS-80-K
IA = Indoor Arrangement (Digit #7)
CA= Capacity (Digits #3 and 4)
Refer to Complete Model Number Designation
in Catalog.
Legend:
B/F/D = Standard Blower/Filter/Damper Module
B = Hi CFM Blower Module
F/D = Hi CFM Filter/Damper Module
CC = Cooling Coil Module
EV = Evap. Cooler Module
*Flex connector kits not shown.
IA “A”
CA (12)
IA “G”
CA (12)
Triple Furnace Units*
Unit Type (UT): MS
Submittal
Number
MS-12-A
MS-12-G
— 41 —
XVI. UNIT NUMBER DESCRIPTION
SEP ARA TED COMB USTION INDOOR MAKE-UP AIR UNITS
Digit M X X — 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 +
Item Prefi x UT CA FT FM IA CO GT GC SV MT MS AI AC AS
*Single furnace capacities 10 through 40 are ETL certifi ed.
5 - Furnace Type [FT]
A - Standard Temperature Rise (20-60°F), Right Side Access
B - Standard Temperature Rise (20-60°F), Left Side Access
C - High Temperature Rise (60-90°F), Right Side Access
D - High Temperature Rise (60-90°F), Left Side Access
0 - None
Z - Other
1 - Open Drip Proof (Standard)
2 - T otally Enclosed
3 - Premium Effi ciency, Open Drip Proof
4 - Premium Effi ciency, Totally Enclosed
0 - None
Z - Other
E - Chilled Water Coil, 4 Row
-
Other
13 - Motor Sizes [MS]
A - 1/2 HP. w/Contactor M - 1-1/2 HP. w/Mag. Starter 1 - 1 HP. VFD
B - 3/4 HP. w/Contactor N - 2 HP. w/Mag. Starter 2 - 1-1/2 HP. VFD
C - 1 HP. w/Contactor P - 3 HP. w/Mag. Starter 3 - 2 HP. VFD
D - 1-1/2 HP. w/Contactor R - 5 HP. w/Mag. Starter 4 - 3 HP. VFD
E - 2 HP. w/Contactor S - 7-1/2 HP. w/Mag. Starter 5 - 5 HP. VFD
G - 3 HP. w/Contactor T - 10 HP. w/Mag. Starter 6 - 7-1/2 HP. VFD
H - 5 HP. w/Contactor U - 15 HP. w/Mag. Starter 7 - 10 HP. VFD
J - 1/2 HP. w/Mag. Starter 0 - None 8 - 15 HP. VFD
K - 3/4 HP. w/Mag. Starter Z - Other
L - 1 HP. w/Mag. Starter
14 - Air Inlet Confi guration [AI]
1 - Outside Air (OA) 4 - Outside Air and Return Air (OA/RA)
2 - Outside Air w/Air Hood* 5 - Outside and Return Air w/Air Hood*
3 - Return Air (RA) 0 - None Z - Other
15 - Air Control & Damper Arrangement [AC]
A - Outside Air 2 Pos. Motor / Spring Return
B
- Return Air 2 Pos. Motor / Spring Return
C - OA/RA 2 Pos. / Spring Return
D
- OA/RA Mod. Mtr. w/Mixed Air Control / Min. Pot.
- OA/RA Mod. Mtr. w/Mixed Air Control / Min. Pot. / SR
E
G - OA/RA Mod. Mtr. w/Mixed Air Control
H
- OA/RA Mod. Mtr. w/Mixed Air Control / SR
-
OA/RA Mod. Mtr. w/Min. Pot.
J
K - OA/RA Mod. Mtr. w/Min. Pot. / SR
- OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air Control / Min. Pot.
L
M
- OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air Control / Min. Pot. / SR
N - OA/RA Mod. Mtr. w/Enthalpy Controlled Economizer / SR
- OA/RA Mod. Mtr. w/Pressure Control (Space Pressure)
- OA/RA Mod. Mtr. w/S-350-P Proportional Mixed Air Control / SR
R
- OA/RA Mod. Mtr. w/0-10 VDC & 4-20 mA Analog Input (External Input)
S
- OA/RA Mod. Mtr. w/0-10 VDC & 4-20 mA Analog Input / SR (External Input)
T
U - ASHRAE Cycle I (OA/RA 2 Pos. Mtr. w/Warm-up Stat / SR)
W
- ASHRAE Cycle II (OA/RA Mod. Mtr. w/Warm-up Stat / Mixed Air / Min. Pot. / SR)
X - ASHRAE Cycle III (OA/RA Mod. Mtr. w/Warm-up Stat / Mixed Air / SR)
Y - Manual Dampers
0 - None MOD = Modulating Damper Motor
Z - Other OA = Outside Air RA = Return Air SR = Spring Return
16 - Accessories [AS]
A1 - Moisture Eliminators H1 - Return Firestat
A2 - Horizontal Return H2 A3 - Low Leak Damper H3 A6 - High Altitude Unit H4 A7 - High Pressure Regulator
A8 - Unit Derate J1 J2 B1 - Filters - 1" WA (Standard) J3
B2 - Filters - 2" W
B3 - Filters - 2" TA
B4 - Filters - 1" 30% K1 - Manual Reset High Limit Switch†
B5 - Filters - 2" 30% K2 - High / Low Gas Pressure Limit Switches
K3 - Status Lamp (Elec. Cabinet)
C1 - Evap. Cooler - Fill & Drain Kit K4 - Fan Time Delay (Arrangement “A” Only)
C2 - Evap. Cooler - 12" CELdek
C3 - Evap. Cooler - Freezestat
w/o Time Delay L1 C4 - Evap. Cooler - 8" GLASdek
C5 - Evap. Cooler - 12" GLASdek
L4 D1 - Time Clock - 7 Day†
D2 - Time Clock - 24 Hour†M2 M3 E1 - Clogged Filter Switch M4 E2 - G.F.I. Convenience Outlet 115VAC†M5 E3 - Remote Control Panel†
E4 - Manual Blower Switch†
F1 - Ductstat - One Stage†
Ductstat - Two Stage†R1 - Field Installed VFD
F2 R2 -
Thermostat - T87K w/Subbase† R3 - VFD Remote Keypad for use w/R1†
N5 - Service Convenience Package
N6 - Double Wall Construction
Factory Installed VFD
† R4 - CO2 Sensor - 100% OA†
† R5 - CO2 Sensor - Mixed Air†
† R6 - Pressure Sensor†
-
None
her (Specify)
*Single furnace capacities 10 through 40 are ETL certifi ed.
— 42 —
NOTES:
— 43 —
XVII. GAS EQUIPMENT START-UP
Customer ____________________________________ Job Name & Number _________________________
PRE-INSPECTION INFORMATION
With power and gas off.
Type of Equip:
Serial Number_________________________ Model Number __________________________
Name Plate Voltage:_____________ Name Plate Amperage: _____________
Type of Gas:Natural LP Tank Capacity ______ lbs. Rating: ______ BTU @ ____ °F
______ kg ______ kw @ ____ °C
Unit Heater Duct Furnace Indoor
❐ Are all panels, doors, vent caps in place?
❐ Has the unit suffered any external damage? Damage ______________________________
❐ Does the gas piping and electric wiring appear to be installed in a professional manner?
❐ Has the gas and electric been inspected by the local authority having jurisdiction?
❐ Is the gas supply properly sized for the equipment?
❐ Were the installation instructions followed when the equipment was installed?
❐ Have all fi eld installed controls been installed?
❐ Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.
(DO NOT START this equipment unless you fully understand the controls.)
GENERAL
With power and gas off.
❐ Make certain all packing has been removed.
❐ Tighten all electrical terminals and connections.
❐ Check damper linkages for tightness.
❐ Check all fans & blowers for free movement.
❐ Check all controls for proper settings.
❐ Check all set screws on blowers and bearings.
❐ Check belt tightness.
BLOWER
With power on and gas off.
❐ Check voltage L1 _____ L2 _____ L3 _____
❐ Check rotation of main blower.
❐ Check motor amps L1 _____ L2 _____ L3 _____
❐ Blower RPM _____________
❐ Check air fi lters. (Record quantity & size.)
GAS HEATING
With power and gas on.
❐ Inlet gas pressure. ____ in. W.C. or ____ kPa
❐ Pilot & main burner ignition.
❐ Manifold gas pressure. ____ in. W.C. or ____ kPa
❐ Cycle on HIGH LIMIT.
❐ Cycle fi restat and/or freezestat.
❐ Check electronic modulation. Set at: __________
❐ Cycle and check all other controls not listed.
❐ Check operation of remote panel.
❐ Entering air temp. _____ °F or ____ °C
❐ Discharge air temp. (high fi re) ____ °F. or ____ °C
❐ External static pressure ____ in. W.C. or ____ kPa
❐ Cycle by thermostat or operating control.
❐ Combustion reading:Carbon monoxide: _____ PPM
Carbon dioxide: _____ %
— 44 —
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.