Sterling MS User Manual

INSTALLATION AND SERVICE MANUAL
SEPARATED COMBUSTION
INDOOR MAKE-UP AIR UNIT ARRANGEMENTS
FOR HEATING, COOLING AND VENTILATING SYSTEMS
ATTENTION: READ THIS MANUAL, SEPARATED COMBUSTION INDOOR DUCT FURNACE SCDFM MANUAL (EVAPORATIVE OR COOLING COIL MANUALS IF APPLICABLE), UNIT SUBMITTAL DATA SHEETS AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATES FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF INSTALLATION. RECORD THE UNIT MODEL NUMBER AND SERIAL NO.(S) IN THE SPACE PROVIDED. RETAIN THIS DOCUMENT FOR FUTURE REFERENCE.
Model No.______________________________________________ Serial No. ________________________
MSIOM-3
J30-06624
FOR Y OUR SAFETY
The use or storage of gasoline or other flammable vapors or liquids in open containers in the vicinity of this appliance is hazardous.
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open fl ames.
4. Immediately call your gas supplier.
FOR Y OUR SAFETY
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. This appliance must be installed by a licensed contractor or qualified service personnel. Read these installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
APPROVED FOR USE IN CALIFORNIA
Install, operate and maintain unit in accordance with manufacturer’s instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness. The state of California has determined that these substances may cause cancer , birth defects, or other reproductive harm. Install and Service this product to avoid exposure to airborne particles of glasswool fi bers and/or ceramic fi bers known to the State of Calif ornia to cause cancer through inhalation.
12/12
INSTALLER’S RESPONSIBILITY
Installer Please Note: This equipment has been test fi red and inspected. It has been shipped
free from defects from our f actory. Ho w ever, during shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer’s responsibility to
inspect and correct any problems that may be found.
RECEIVING INSTRUCTIONS
Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment. After the unit has been uncrated, check for any visible damage to the unit. If any damage is found, the consignee should sign the bill of lading indicating such damage and immediately file claim for damage with the transportation company.
IMPORTANT: Look in direction of unit air fl ow to determine whether unit is right hand or left hand accessible.
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 568-9571 FAX: (413) 562-8437
www.mestek.com
TABLE OF CONTENTS
I. RECEIVING & PRE-INSTALLATION
INSTRUCTIONS ......................................................... 2
II. GENERAL INSTALLATION SAFETY
REQUIREMENTS ..............................................3, 4
Location ........................................................................4
Combustion Air Considerations ....................................4
Suspension/Rigging ..................................................5
III. INSTALLATION
Installation Clearances ...............................................11
Venting ........................................................................12
Duct Connections .......................................................13
Gas Piping ..................................................................13
Modulating Gas Control ..............................................14
Electrical Connections ..........................................14, 15
DX Coil Equipped Units ..............................................16
Chilled Water Coil Equipped Units ..............................16
Evaporative Cooling Equipped Units ..........................16
IV. OPERATION
General Information ....................................................16
Gas Control System ...................................................16
Sequence of Operation ..............................................17
Optional Gas Controls ................................................17
Air Handling Requirements and Adjustments ............18
Lighting .......................................................................19
Gas Input Adjustment ................................................. 19
Pilot Adjustment .......................................................... 20
Primary Air Shutter Adjustment .................................. 20
Controls ......................................................................20
V. START UP ......................................................20, 21
VI. MAINTENANCE .......................................21 thru 24
VII. TROUBLESHOO TING ............................25 thru 30
VIII. REPLACEMENT PARTS ...................................30
IX. SERVICE NOTE ...................................................30
X. W ARRANTY ..........................................................30
Canadian Installations ...............................................31
XI. DIMENSIONAL DATA ..............................32 thru 37
XII. MOTOR ELECTRICAL DATA .............................38
XIII. UNIT/SHIP WEIGHTS ........................................39
XIV. COOLING COIL DIMENSIONAL DATA ............40
XV. SUBMITTAL INDEX ............................................41
XVI. MODEL NUMBER DESCRIPTION ....................42
XVII. START UP SHEET ...........................................44
Unless otherwise specifi ed, the following conversions may be used for calculating SI unit measurements: 1 foot = 0.305 m 1 inch = 25.4 mm 1 psig = 6.894 kPa 1 pound = 0.435 kg 1 gallon = 3.785 L 1 cubic foot = 0.028 m
1 inch water column =0.249 kPa 1000 Btu per hour = 0.293 kW 1000 Btu/Cu. Ft. = 37.5 MJ/m
3
liter/second = CFM x 0.472 meter/second = FPM ÷ 196.8
3
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product:
Indicates an imminently hazardous situation which, if not av oided, will result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or property damage.
NOTICE: Used to notify of special instructions on installation, operation or maintenance which are important to equipment but not related to personal injury hazards.
I. RECEIVING INSTRUCTIONS
Make-up Air Units with multiple furnaces are shipped in sections. Each section has a label with Order no.,
Model No., Unit No., and Part No. marked on it. Make certian that the order, model, and part numbers agree on each section to be connected together.
Inspect shipment immediately when received to determine if any damage has occurred to the crate during shipment.
After the unit has been uncrated, check for any visible damage to the unit. Check motor position and turn blower wheel to determine if damage has occurred to these critical parts.
If any damage is found, the consignee should sign the bill of lading indicating such damage and immediately fi le claim for damage with transportation company.
PRE-INSTALLATION INSTRUCTIONS
When the unit is received and uncrated, check the external data plate and all labels on the unit for type of gas, electrical, and operational specifi cations to confi rm that these agree with those at point of installation. The unit is equipped with an Indoor Duct Furnace; also check the data plate and all labels located on each furnace.
Every Mak e-Up Air Unit will include an informational packet which will include the following: This make-up air manual, duct furnace, ev aporative cooler/ cooling coil manuals (if applicable to the unit order), wiring diagram(s), and special controls/data sheets.
— 2 —
II. GENERAL SAFETY REQUIREMENTS
Open all disconnect switches before installing the unit. If the po wer disconnect is out of sight, lock it in the open position and ta g it to prevent unexpected application of power. Failure to do so may result in personal injury or death from electrical shock.
Failure to comply with the general requirements may result in extensive property damage, severe personal injury or death.
Never service any component without fi rst disconnecting all electrical and gas supplies to the unit or severe personal injury or death may occur.
1. Installation must be made in accordance with local codes, or in absence of local codes, with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No 54) National Fuel Gas Code. All ANSI and NFP A Standards referred to in these installation instructions are the ones that were applicable at the time the design of this appliance was certifi ed. The ANSI Standards are available from the National Standards Institute, Inc., 11 West 42nd Street, New York, NY 10036 or www. ansi.org. The NFPA Standards are available from the National Fire Protection Association, Batterymarch Park, Quincy , Massachusetts 02269. The heaters are designed for use in airplane hangers when installed in accordance with ANSI/NFP A No . 409 and in public garages when installed in accordance with the NFP A No. 88A and NFPA No. 88B.
2. If installed in Canada, the installation must conform with local building codes, or in the absence of local building codes, with the current CSA-B149.1 or B149.2 “Installation Codes for Gas Burning Appliances and Equipment”. These indoor duct furnaces have been designed for and certifi ed to comply with CSA 2.6.
5. Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wir ing should be done and checked by a qualifi ed electrician, using copper wire only . All gas connections should be made and leak-tested by a suitably qualifi ed individual, per instructions in this manual.
6. Use only the fuel for which the heater is designed (see nameplate). Using LP gas in a heater that requires natural gas, or vice versa, will create the risk of gas leaks, carbon monoxide poisoning and explosion.
Do not attempt to convert the heater for use with a fuel other than the one intended. Such conversion is danger ous, as it could create unsafe conditions that result in death, serious injury or substantial property damage.
7. Make certain that power source conforms to electrical requirements of heater. Disconnect power before installing or servicing heater. If power disconnect is out of sight, lock it in open position and tag it to prevent unexpected application of power. Failure to do so could result in fatal electric shock.
Do not depend upon a thermostat or other switch as the sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric shock.
8. Special attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a grounded conductor from the service panel to the conduit box of the heater. T o ensure proper ground, the g rounding means must be tested by qualifi ed fi eld electrician.
3. No alterations are to be made on this equipment. The duct furnace section (capacities 100 thru 400 MBH)
of these make-up air units are certifi ed by ETL for use with natural and LP (propane) gases!
Do not alter the duct furnace in any way or damage to the unit, se vere personal injury or death will occur.
4. Make certain that the power sources conform to the requirements of the heater.
— 3 —
9. Do not insert fingers or foreign objects into the heater or its air moving device. Do not bloc k or tamper with the heater in any manner while in operation or just after it has been turned off, as some parts may be hot enough to cause injury.
10. This heater is intended for general heating applications ONLY. It must NOT be used in potentially dangerous locations such as fl ammable explosive, chemical-laden or wet atmospheres.
In cases in which property damage may result from malfunction of the heater, a backup system or a temperature sensitive alarm should be used.
LOCATION
Before placing the Make-Up Air unit in its permanent location, make certain that the structure is capable of carrying the additional load of this equipment. Check the unit weight given at the end of this manual.
LOCA TIONS TO A V OID
Unit heaters should not be installed within corrosive or fl ammable atmospheres. Do not locate any gas fi red heater where air for combustion contains chlorinated vapors or acid fumes.
Refer to unit data plate for required clear ances to combustible material, and Figure 11 for manufacturer’ s recommendations .
Do not place unit in a location where service personnel can not safely service this equipment or personal injury could result.
NOTICE: When selecting a location for these Make­Up Air Units, both the size of the unit and the heating requirements of the building must be considered.
NOTICE: The furnace section(s) of this unit is equipped for bottom access serviceability only! Provide adequate clearance (base rail to fl oor is 18 inches minimum).
COMBUSTION AIR CONSIDERATIONS
The presence of chlorine vapors or other corrosive vapors in the combustion air supply for gas-fi red heating equipment presents a potential corrosive hazard. Chlorine will, when exposed to fl ame, precipitate from the compound (usually freon or degreaser vapors) and go into solution with any condensation that is present in the heat exchanger or associated parts. The result is hydrochloric acid which will readily attack all metals, including 300 grade stainless steel. Care should be taken to separate these vapors from the combustion process.
Presence of these air impurities can cause premature failure of the heat exchanger and void the warranty (See limited warranty on page 30).
The venting system must be installed in accordance with heater manufacturer’ s instructions. The venting system is an integral part of the unit and must not be altered in
the fi eld!
MOUNTING HEIGHT
1.
When a Gas Fired Make-Up Air Handler is discharging directly into the heated space, a mounting height of eight feet (2.4m) above the fl oor is recommended. Less effi cient air distribution results at higher levels.
2. When Gas Fired Indoor Make-Up Air Handlers are
installed in airplane hangars, NFP A specifi es that the units must be at least ten feet (3.0m) abov e the upper surface of wings or engine enclosures of the highest aircraft to be stored in the hangar. This measurement should be made from the wing or engine enclosure (whichever is higher from the fl oor) to the bottom of the heater. Heaters must be installed at least eight feet (2.4m) abov e the fl oor in shops, offi ces, and other sections of the hangar where aircraft are not stored or housed. Refer to NFPA 409 Aircraft Hangars.
3. In parking structures, Gas Fired Indoor Make-Up Air
Handlers must be installed so that the burner fl ames are located 18" (457mm) above the fl oor or protected by a partition not less than 18" (457mm) high as specifi ed in NFPA 88A Parking Structures.
4. In public repair garages, Gas Fired Make-Up Air
Handlers must be installed in a detached building or room separated from repair areas as specifi ed in NFPA 88B Repair Garages.
— 4 —
SUSPENSION/RIGGING
Make certain that the structure to which the single, dual, triple furnace and air handler sections is to be mounted is capable of supporting its weight. Under no circumstances must the gas lines, the venting system or the electrical conduit be used to support the heater; or should any other objects (i.e. ladder, person) lean against the heater , gas lines, venting system or the electrical conduit for support.
The unit should never be lifted by any unit component other than the base rail assembly. Unit components other than base rail assembly are not designed to support the total weight and may break, causing personal injury or unit damage.
Units can be set on field furnished supports/cradle with access available to furnace bottom section, or suspended by rod hangers from the sub-frame (and lifting brackets).
Any unit that has a side base rail longer than 104" (2.6m) requires additional fi eld furnished supports by a qualifi ed installer. Refer to all dimensional data in this manual. If further information is required, contact the manufacturer’s technical service department.
Rig unit using either belt or cable slings. Use spreader bars to protect the top of the unit when it is lifted. Mak e sure all hardware used in the lifting/mounting process is tightened and secured.
Refer to Figures 1 and 2 for Single Furnace Make-Up Air Unit rigging requirements. Refer to Figures 3, 4 and 5 for Dual/Tr iple Furnace Make-Up Air Unit rigging requirements, which ships to the site in two sections (Figure 3 is the air handler section and 4 and 5 are the furnace sections.).
On units with a total length of less than 104" (2642mm), excluding evaporative cooler, two holes are provided in the base rail on each side of the unit. Slide pipes beneath the unit through these holes and attach rigging to pipes for lifting the unit.
On units with a total length of a 104" (2642mm) or greater, excluding evaporative cooler, lifting lugs/brackets attached to the base rail are provided. Once the unit is set in place these lifting brackets may be removed if required.
Attach rigging to lugs/brackets for lifting the unit. For distance between lifting lugs/brackets and total unit lengths, refer to the Dimensional Data section of this manual.
The unit must be hung level from side to side and front to back. It is recommended to use the (9/16" diameter) hanging holes in the skid rail, and 1/2" threaded rod or pipe, and/or whatever other supports may be required to adequately support the unit. A fi eld supplied cradle or other means of support may also be required. The installer is responsible for determining adequate and safe suspension methods.
— 5 —
Figure 1 -
(4) Lifting Point Locations (2) At Each End Of Air Handler Unit
Use Spreader Bars To Prevent Damage To Units
D6559
(8) Lifting Point Locations (4) On Each Side Of Duct Furnace Unit
Use Spreader Bars To Prevent Damage To Units
(6) Lifting Point Locations (3) On Each Side Of Duct Furnace Unit
Use Spreader Bars To Prevent Damage To Units
Hoisting of Make-Up Air Unit (Single Furnace)
Without Lifting Brackets
Figure 2 -
Hoisting of Make-Up Air Unit
With Lifting Brackets
Figure 4 - Hoisting Double Furnace Unit
D6558
Figure 5 - Hoisting Triple Furnace Unit
(Single Furnace)
Figure 3 - Hoisting Make-Up Air Handler Unit
D6558
Refer to Figures 3, 4 and 5 for dual/triple furnace Make Up Air rigging requirements. Dual/triple furnace units ship to the site in two sections (Figure 3 is the air handler section; Figures 4 and 5 are the furnace sections).
— 6 —
III. INSTALLATION
Refer to all dimensional data within the manuals equipped with your unit.
SINGLE FURNACE UNITS
Single furnace units (capacities 10-40) consist of a furnace section and an air handler section mounted on a common base rail.
MULTIPLE FURNACE UNITS
Multiple furnace units consist of two sections: a furnace section with two duct furnaces (capacities 50-80) or three duct furnaces (capacity 12) mounted on a common base rail; and a separate air handler section mounted on its own base rail. A fl exible connector kit is also equipped with your unit. Each section has a label with Order
No., Model No., Unit No., and Part No. marked on it. Make certain that the order, model, and part numbers agree on each section to be connected together . The
two sections should be moved individually and mounted in their permanent location (see “Suspension/Rigging” sections). Ensure that both fl ange assemblies are in alignment with a 5" (127mm) space between the fl ange assemblies. See the f ollo wing instructions for installation of the fl exible connector kit between the two sections.
INSTALLING FLEXIBLE CONNECTOR - Refer to Figure 6
1. Make sure that the furnace section and the air
handler section are in alignment and installed with a 5" (127mm) space between the fl ange assemblies.
2. Remove the top e xtension panel of the duct furnace
for access to the inside bottom fl ange assemblies.
4. Measure the distance from the top of the fl ange assembly to the slot at the bottom of the fl ange assembly. Make a second 90 degree bend at the measured distance from the fi rst bend in the fl exible duct connector.
5. Slide the flexible connector through the slots in the fl ange assemblies until the vertical par t is tight against the sides of the fl ange assemblies.
6.
Bend second vertical section up around the fl anges. Make sure all bends are straight and ev en for proper fi t.
7. Bend down top section of fl exible connector. Cut metal parts of fl exible connector to o verlap the 4 inch section by at least 1-1/2 inches (38mm), but cut the fabric portion 1-1/2 inches longer than the metal.
8. Screw metal portions of fl exible connector to the flange assemblies using drill screws. Space the screws approximately 4 to 6" (102 to 152mm) on center. Fasten the bottom section in place by screwing down from the inside. Fasten the overlapped area with two screws in the metal on each side of the fabric. Seal the fabric joint with RTV sealer and allow to cure . Replace and reseal top extension panel on furnace section.
9. Apply sealing tape to seams between fl anges and fl exible connector and to vertical fl ange connections. Test for air leaks during initial start-up. Reseal as required.
Table 1 - Flexible Connector Kit
3. Measure fl exible connector in the fl at to confi rm that it is correct for the unit being installed. Refer to Table
1. Make a 90 degree bend 4" (102mm) from one end of the fl exible duct connector.
Unit (Approx.) Straight Length Capacity Flexible Connector (CA) Required
50 102 Inch (2.59m) 60 114 Inch (2.90m) 70 124 Inch (3.15m) 80/12 135 Inch (3.43m)
— 7 —
*
*
Furnace Assembly
Flange Assembly
with Flange
Mounts to
Air Handler
5"
Approx.
for Flexible
2" Slots
Connector
AIR FLOWAIR FLOW
Panel
Top Extension
STEP 1
14.500
Approx.
Approx.
5.000
Approx.
9.000
***
***
* * *
***
*
D6453-1
side of unit
Bend at approx.
4" on access
Assembly on both Furnace and Air Handler
to bottom of the inside of Flange
Remove Top Extension Panel of Duct Furnace to fasten Flexible Connector
Connector into
Slide Flexible
place tightly
before fastening
sheet metal for
1-1/2" Overlap
proper installation
proper installation
1-1/2" Overlap
fabric for
Furnace
Duct
(4) Slots
STEP 2 STEP 3
Bend at 90
STEP 4
STEP 5
D6453-2
Figure 6A
Figure 6B
— 8 —
Flexible Connector
Continue bending
tightly around Flange
Assembly making sure
bends are neat and even
Keep uniform distance
around Flange Assembly
on all sides, (approx. 2")
D6453-3
STEP 6
STEP 7
Figure 6C
Figure 6D
using Drill Screws provided
fasten Flexible Connector to
Flange Assembly securely
space Screws between 4" - 6"
keep uniform distance
around Flange Assembly
on all sides (approx. 2")
for sheet metal overlap use (2)
screws on each side of fabric
Flexible Connector Assembly ready for
application of Sealing
Tape provided for testing
for air leaks (see sht. 5)
Use Sealant between
layers of fabric for
proper installation (by others in field)
STEP 8
D6453-4
— 9 —
AIR FLOW
D6453-5
14.500
stips of Sealing Tape to be
continuous or overlapping
used when sealing Flexible
Connector to Flange Assembly
Approx.
5.000
Approx.
AIR FLOW
9.000
Approx.
***
* *
***
*
*
*
*
*
*
*
use Sealing Tape on
inside of Bottom Flange
Flexible
Connector
Flange
Assembly
Sealing Tape covers
Screw heads and seams
Figure 6E
STEP 9
on Flange
connections
use Sealing Tape
2
1
3
— 10 —
Figure 7 - Arrangement B & D Capacities10/40
D6554
(8) Suspension Point Locations (4) On Each Side Of Unit
D6555
(4) Suspension Point Locations (2) At Each End Of Air Handler Unit
(6) Suspension Point Locations (3) On Each Side Of Duct Furnace Unit
Both Units Must Be Suspended At Same Height For Proper Fit Of Flex Connector
D6556
Both Units Must Be Suspended At Same Height For Proper Fit Of Flex Connector
(4) Suspension Point Locations (2) At Each End Of Air Handler Unit
(8) Suspension Point Locations (4) On Each Side Of Duct Furnace Unit
Figure 8 - Arrangement G Capacities 10/40
INSTALLATION CLEARANCES
Minimum clearances to combustible material are shown on the unit data plate. It is important that clearances be maintained for servicing the unit, and that minimum clearances are provided from the unit to combustible material. Clearances around the fi eld installed optional outside air hood (if unit is to be connected to one) must be unobstructed. See Figure 11.
Under no circumstance should combustible material be located within the specifi ed clearances. Failure to provide proper clearance could result in personal injury or property damage from fi re.
Every gas appliance should be located with respect to building construction and other equipment so as to permit access to the unit. Clearances between ver tical walls and the vertical sides of the heater should be no less than 18" (457mm). Minimum clearance between the top of the heater and the ceiling is 6" (152mm). The minimum clearance to the bottom of the furnace is 25" (635mm). The minimum clearance from combustibles to the fl ue collector is 6" (152mm). The minimum clearance from combustibles to the vent pipe is 6" (152mm). See Figure 11.
Figure 9 - Arrangement G Capacities 50/80
Figure 10 - Arrangement G Capacity 12
— 11 —
*It is recommended that adequate clearance be kept to the bottom of the furnace(s) to make sure a service technician can safely service the unit(s),
The unit should never be lifted by furnace sections, blower housing/filter/sections, motor mounts or fl ue connections. These are not designed to support total weight of the unit, and may break, causing personal injury or property damage!
Make certain that the lifting methods used to lift the Make-Up Air Unit are capable of supporting the weight of the heater during installation. Failure to heed this warning may result in property damage or personal injury.
Make certain that the structure to which heater is to be mounted is capable of safely supporting its weight. Under no circumstances must the gas lines or the electrical conduit be used to support the heater. Failure to heed these warnings may result in property damage, personal injury or death.
Open all disconnect switches before installing the unit. Failure to do so may result in personal injury or death from electrical shock.
Inspect the suspension and/or support system for the make-up air unit to ensure that all fasteners are tight and the unit is secure before working underneath the unit. Failure to do so could result in property damage, personal injury, or death.
Figure 11 - Manufacturer’s Recommended Service Clearances
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
D6573
Field
Ductwork
18(457mm)
Air
Inlet
18 (457mm)
AIR FLOW
17.5 (444mm)
Ductwork
18(457mm)
(635mm)
Field
AIR FLOW
25
Supply
Ductwork
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
5/16
(8mm)
36 (914mm)
Ductwork
Note: Recommended ceiling clearance 36" (914mm) is to the top of the furnace venting collar assembly.
18 (457mm)
Supply
VENTING†
All venting installations shall be in accordance with the latest edition of Part 7, “Venting of Equipment”, of the National Fuel Gas Code, ANSI Z223.1 or applicable provisions of local building codes.
CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts or any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, inappropriate tiredness, or fl u­like symptoms).
The venting is an integral part of
the unit and must not be altered in the fi eld.
†Refer to the Separated Combustion Indoor Duct Furnace Manual for more venting requirements.
Vent Systems
Termination Clearance Requirements
Minimum Clearance
Structure/Object
for Termination Locations
USA CANADA
Door, window, or gravity vent inlet; combustion air inlet for other appliances
9 inch for 10,000 to 50,000 BTU/Hr input; 12 inch for input exceeding 50,000 BTU/Hr.
9 inch (230mm) for 10,000 to 50,000 BTU/Hr input; 12 inch (305mm) for input exceeding
50,000 BTU/Hr. Forced air inlet within 10 feet 3 feet above 6 feet (1.8m) Adjoining Building or parapet 6 feet 6 feet (1.8m)
Adjacent public walkways
7 feet above grade
7 feet (2.1m) above
grade
3 feet (0.9m)
horizontally from
meter/regulator Electric, gas meters & regulators
4 feet horizontal
asembly. 6 feet
(1.8m), any
direction, from
a gas service
regulator vent outlet Above grade level* 1 foot* 1 foot (0.3m)*
*If the vent terminal is to be installed near ground level, the vent terminal must be positioned at least six inches (152mm) above the maximum anticipated snow depth.
— 12 —
DUCT CONNECTIONS
All ductwork must be properly supported so that no strain is put on the unit. Do not alter or bend the discharge duct fl anges supplied on your make-up air unit.
Duct connections must have a removable access panel in the duct which is connected to a duct furnace. The duct openings shall be accessible when the unit is installed in service, and shall be of such size that smoke or refl ected light may be observed inside the casing to indicate the presence of leaks in the heating element. The covers for the panels shall be attached in such a manner as to prevent leaks . Ducts (or optional outside air hoods) exposed to the outdoors must be insulated and sealed to prevent water from entering either the unit or building through the duct.
To avoid equipment damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/ leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fi re hazard.
Do not rely on a gas shutoff valve to isolate the unit while conducting gas pressure/leak tests. These valves may not be completely shutoff, exposing the unit gas valve to excessive pressure, resulting in damage.
Do not over-tighten the inlet gas piping at unit gas valve or stresses that could crack the valve may result.
If a single, double or triple duct furnace only unit is connected to a return air duct, or any other inlet air restriction, the appliance shall be installed on the positive pressure side of the air circulating blower.
When connecting return air duct to Standard or High CFM cabinets, attach duct to return air opening fl ange when no dampers are used. Otherwise, if dampers are used, attach return air duct around collar at bottom of damper assembly. Also refer to the Dimensional Data section of this manual, Submittal Data Sheets and Indoor Duct Furnace Manual specifi ed for your unit.
GAS PIPING††
All gas piping must be installed in accordance with local codes. It is required that a ground union be installed adjacent to the gas valve of each duct furnace, and a ground union be installed just external of each duct furnace for unit servicing. On vertical runs, a drip leg should be provided upstream of any control manifold. A gas shutoff valve should be, or may be required by local codes, installed upstream of the external ground union for each duct furnace. A 1/8" N.P.T. plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the unit gas supply connection.
Never use an open fl ame to detect gas leaks. Explosive conditions may e xist which would result in personal injury or death.
The gas line should be supported so that no strain is placed on the unit. Pipe compounds which are not solub le to liquid petroleum gases must be used on threaded joints.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing the individual manual shutoff valv e during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
For additional gas piping information, including pipe sizing and drip leg installation, refer to Separated Combustion Indoor Gas-Fired Duct Furnace Installation and Service Manual.
For additional piping information, refer to the National Fuel Gas Code Z233.1 (latest edition).
The open end of piping systems being purged shall not discharge into areas where there are sources of ignition or into confi ned spaces UNLESS precautions are taken as follows: (1) By ventilation of the space, (2) control of purging rate, (3) elimination of all hazardous conditions. All precautions m ust be taken to perform this operation in a safe manner!
†† For complete Gas Piping installation, see the Separated Combustion Indoor Gas-Fired Duct Furnace Installation and Service Manual.
— 13 —
NOTICE: If the gas duct furnace is to be fi red with LP gas, consult local LP gas dealer for piping size information.
NOTICE: Unit installation for use with propane (bottled) gas must be made by a qualifi ed LP gas dealer or installer. He will insure proper joint compounds are used for making pipe connections; that air is purged from lines; that a thor ough test is made for leaks before operating the unit; and that it is properl y connected to propane gas supply system.
Before any connection is made to an e xisting line supplying other gas appliances, contact the local gas company to make certain that the existing line is of adequate size to handle the combined load.
Check all connections for leaks with soap solution.
MODULATING GAS CONTROL (OPTIONAL)*
AIR FLOW AIR FLOW
Electrical Cabinet
Air Handler
Junction Box
Duct Furnace
Conduit
Low Voltage
Conduit
Line Voltage
D03304
*
*** *
*
*
***
***
Electronic: On units equipped with electronic modulating control, follow control manufacturer’s installation instructions for sensing of outlet air temperature.
*Also refer to the Separated Combustion Indoor Duct Furnace Installation Manual supplied with your unit.
ELECTRICAL CONNECTIONS
Do not use any tools (i.e. screwdriver, pliers, etc.) across terminals to check for po wer. Use of a voltmeter is recommended.
Locate the thermostat in accordance with the instructions supplied with the thermostat. All fi eld wiring must have a minimum temperature rating of 185°F (85°C). Control wiring shall be a minimum of 18 gauge wire size. Control wiring must be sized for length of run.
HAZARDOUS VOL TAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
All electrical connections must conform to: the latest edition of ANSI/NFPA No. 70, National Electrical Code, and applicable local codes. In Canada, to the Canadian Electrical Code, Part I CSA Standard C22.1.
Single furnace make-up air packaged units are wired at the factory and are ready to be connected. Multiple furnace make-up air units are shipped in two parts, the air handler section and the furnace section. After mounting the two sections and installing the fl exible duct connector, connect the free end of the fl exible conduits from the air handler section to the junction box on the duct furnace. Each wire has a distinctive marking. Connect each wire to its respectively marked terminal in the duct furnace junction box. See Figure 13A. Actual unit wiring will differ according to the options chosen. Each unit is shipped with its own wiring diagram; refer to this wiring diagram for all electrical connections to the unit.
Locate line voltage disconnect box per local codes. If mounting the disconnect box to the unit, never mount it to a unit access panel. Possible locations include the front of the blower or fi lter section (See Figure 15). Electrical conduit must be routed so as not to interfere with removal of any access panel.
NOTICE: Should any original wire supplied with the unit have to be replaced, it must be replaced with wiring having a temperature rating of at least 221°F (105°C).
Figure 13A
All line voltage and thermostat connections are made in the Electrical Cabinet (See Figure 13B). Line voltage connections are made at the High Voltage Terminal Block. Thermostat connections are made at the Main Connection Board (See Figure 14).
— 14 —
Figure 13B - Make-Up Air Unit-Standard Blower Cabinet, Single Duct Furnace with Various Options Shown
D4108
Disconnect Box
Disconnect Box Located On Outside Air Application
D4109
Disconnect Box
Disconnect Box Located On Outside Air Application
Field Ductwork For Outside Air Inlet
RETURN AIR
AIR FLOW
OUTSIDE AIR
20
25
24
22
23
21
18
19
17
16
15
12345 6 7
Dampers/Filters/ Blower Cabinet
8 910
12
13
FurnaceCabinet
Electrical Duct
14
26
27
D6572
1. Mixed Air Controller
2. Return Firestat
3. Economizer
4. Filters
5. Blower Motor
6. Reverse Air Flow Switch
7. Clogged Filter Switch
8. High Voltage Barrier, Lamp and Circuit Breaker Mount
9. Main Connection Board with Fan Time Delay and Function Relays
10. Power Venter Motor Assembly (includes Relay and Air Pressure Switch)
11. Ignition Module (not shown­located in burner compartment)
12. Time Delay Freezestat
13. Supply Firestat
14. Duct Thermostat
15. Safety Limit Switch
16. Gas Valve
17. Primary High Limit Switch
18. Transformer
19. Electrical Wiring Inlet
20. High Voltage Terminal Block
21. Door Safety Switch
22. Contactor
23. Centrifugal Blower
24. Damper Motor
25. Outside and Return Dampers
26. Ambient Lockout
27. CO2 Monitor
Figure 14 - Electrical Cabinet
Figure 15 - Disconnect Box Locations
Return Air Inlet
Outside Air Inlet
— 15 —
DX COIL EQUIPPED UNITS (OPTIONAL)
Drain Pan Connection
H
Total
Height
of Trap
X = 1/2 “H” H = At Least 1 Inch Plus Casing Static Pressure
D3887
Total Height Of Trap = X+ H + (1-1/2 X Pipe Diameter) (without Insulation)
Unit
Housekeeping
Pad
X
See Coil Installation/Maintenance Manual for Refrigerant Piping, Liquid and Suction Line Components, Refrigerant Charging and Thermal Expansion Valve Adjustment. Remove coil cabinet access door located next to blower section. Cut holes in fi xed door to allow suction and liquid line passage. Provide weatherproof seal around suction and liquid lines at piping plate when installed.
The DX Coil has a 300 ft/min. (1.524 m/s) minimum and a 600 ft/min. (3.048 m/s) maximum velocity through the coil requirement. This is due to prevention of coil icing or condensate blow-off. To calculate the velocity through the coil, apply the following formula:
Figure 16 - Drain Pan Connection
Velocity = through the coil
Condensate Drain piping must have a P-trap in line immediately downstream of drain pan connection, external to the unit, to prevent possible outside air leakage into unit. The P-trap shall be of sufficient differential to overcome negative pressure of the indoor air blower. A minimum height difference of 2" (51mm) is required (See Figure 16). Before unit operation begins, the P-trap must be primed with either water (summer) or glycol (winter).
CHILLED WATER COIL EQUIPPED UNITS (OPTIONAL)
See Coil Installation/Maintenance Manual for General Coil Piping Recommendations. Remove coil cabinet access door, cut holes in door to allow chilled w ater piping passage. Provide weatherproof seal around chilled water pipes at piping plate when installed.
The Chilled Water Coil has a 600 ft/min (3.048 m/s) maximum velocity through the coil requirement. This is due to prevention of condensate blow-off. To calculate the velocity through the coil apply the following formula:
Velocity = through the coil
Condensate Drain piping must have a P-trap in line immediately downstream of drain pan connection, external to the unit, to prevent possib le outside air leakage into unit. The P-trap shall be of suffi cient differential to overcome negative pressure of the indoor air blower. A minimum height difference of 2" is required (See Figure
16). Bef ore unit operation begins, prime P-trap with either water (summer) or glycol (winter).
EVAPORATIVE COOLER EQUIPPED UNITS (OPTIONAL)
Refer to Evaporative Cooler Installation and Service Manual for water and electrical connections.
Cooling Air Flow in CFM (m3/s)
Coil Surface Area in ft2 (m2)
Cooling Air Flow in CFM (m3/s)
Coil Surface Area in ft2 (m2)
IV. OPERATION
GENERAL INFORMATION
Refer to Separated Combusion Indoor Gas-Fired Duct Furnace Installation and Service Manual for specifi c information regarding the heating operation of this unit.
All units are equipped with an intermittent ignition pilot system. The pilot is lit and e xtinguished each cycle of unit heating operation.
On natural gas units, the ignitor will continue to spark and pilot gas will continue to fl ow until the pilot fl ame is proven.
LP (propane) units are equipped with 100% lockout. The lockout function shuts off the main and pilot gas valves if the pilot gas fails to ignite within 90 seconds of the onset of trial for ignition.
The gas control system operates at 24 VAC and is supplied by a stepdown transf ormer found in the electrical cabinet that will match the unit line voltage specifi ed. See Figures 13 through 15 for unit controls location.
Do not use a thermostatic fan control switch when either two-stage fi ring or modulated gas controls are used.
GAS CONTROL SYSTEM
The standard unit comes equipped for single stage operation. Unit heating operation is accomplished at full input.
Each duct furnace is equipped with an individual ignition control system which consists of the following components: ignition control module, gas valve and pilot burner.
The ignition control module is the heart of the ignition control system. This control initiates all gas fl ow , provides means to light the pilot burner, proves and monitors the pilot burner operation.
— 16 —
The gas valve consists of two operators which provide gas to the pilot and main burners. Both operators are energized and de-energized by the ignition control module each heating cycle.
The pilot burner includes an ignitor and fl ame sense probe. The ignitor provides the spark, originating at the ignition control module, to light the pilot. The ignition control module proves and monitors the pilot fl ame through the fl ame sensing probe.
SEQUENCE OF OPERATION
All units follow the same basic sequence of operation and is as follows:
1. Thermostat calls for heat. Draftor relay energizes draftor with call for heat.
2. Pressure switch closes circuit to ignition control module.
3. Ignition control module energizes pilot operator of gas valve and initiates spark at ignitor of the pilot burner.
4. Pilot burner ignition is proven to the ignition control by the fl ame sense probe and sparking of the ignitor is discontinued.
5. Once pilot burner operation is proven, the ignition control module energizes the main burner operator of the gas valve, allo wing gas fl ow to the main burners.
6. Approximately 60 seconds after the main burners light, the fan time delay initiates fan operation.
7. Thermostat is satisfied and call for heat is removed. Draftor relay de-energizes draftor with removal of call f or heat.
8. Ignition control module de-energizes pilot and main burner operators of the gas valve , ceasing all gas fl ow.
Three Stage Units: Dual duct furnace models: First furnace is equipped with two stage heating; second furnace is equipped with single stage heating but fi red independently, giving three stages of heating. Triple duct furnace models: Each duct furnace is equipped with single stage heating but fired independently, giving three stages. Each stage is 33% of the unit’s full input rate. Duct furnace one will always light fi rst and disengage last.
Four Stage Units: Dual duct furnace models only. Each duct furnace is equipped with two stage heating but fi red independently, giving four stages. Each stage is 25% of the units full input rate. Duct furnace one will always light fi rst and disengage last.
Six Stage Units: Triple duct fur nace models only. Each duct furnace is equipped with two stage heating but fi red independently giving six stages. Each stage is 16.5% of the units full input rate. Duct furnace one will always light fi rst and disengage last.
Electronic Modulation Units: These units are equipped with an electronic modulating control which provides unit fi ring capabilities of 50 to 100% of the units full input rate. This control is found in the gas train downstream of the gas valve and allows main bur ner ignition only at the maximum rate. A thermostat with remote setpoint adjustment modulates the gas input.
Multi-Stage w/Electronic Modulation Units:These dual and triple duct furnace models are equipped with an electronic modulating control on duct furnace one and single or two stage heating on each successive duct furnace. Furnace one (modulated) will fi re fi rst and disengage last. Additional stages of heat will engage after furnace one has fi red at maximum modulation capability for the duration of the delay setting. The amount of modulation and each stage size depends
upon
unit size and the number of stages. See following chart.
9. Approximately two minutes after satisfying the thermostat, fan operation ceases.
OPTIONAL GAS CONTROLS
These units are available with optional gas controls which will give either multi-stage or modulating operation. The sequence of operation of those units equipped with these optional gas controls differs only at what rate each duct furnace’s main burners ignite and operate at, or the order of duct furnace fi ring for those units equipped with two or three duct furnaces.
Two Stage Units: Two stages of heating; fi rst stage is 50% of full rate, second stage is 100% of full rate. Main burner ignition is at fi rst stage only.
— 17 —
Modulation Stage
Number Capabilities Size of Stages (% of full input) (% of full input)
2 25 - 50 50 3 16.5 - 33 33 4 25 -50 25 6 16.5 - 33 16.5
AIR HANDLING REQUIREMENTS
1/2" TO 3/4"
AND ADJUSTMENTS
Remove wooden shipping support from beneath blower housing of Blower Section (if applicable) to prevent possible unit damage or improper unit operation.
Static Pressure through the unit should never exceed
2.0" W.C. (0.50 kPa). Units operate at a temperature rise range of 20 to 90°F (11 to 50°C).
It is important that the blower motor and the blower wheel pulleys be in good alignment, with the motor and blower shafts parallel.
Belt tension must be adjusted to give approximately
3
/4" defl ection of the belt when fi nger pressure is applied to the middle of the belt (See Figure 17). Small changes in this tension may be necessary for optimum operation. Belts will stretch over a period of time, requiring an adjustment to this tension. See MAINTENANCE section for belt and pulley adjustments.
NOTICE: It is impor tant that the fi nal temperature leaving the unit does not exceed 160° F (71°C). When fi nal air throughput adjustments are being made, a check of the discharge air temperature should be made after unit has operated for 15 to 20 minutes.
A unit should never be allowed to cycle on the primary limit for a prolonged period of time. It is a safety control to prevent a fi re. If cycling on the primary limit is noted, corrective measures should be taken immediately. Failure to do so could result in unit damage or a fi re.
NOTICE: At initial unit installation, unit should be started momentarily to confi rm proper blower wheel rotation as the unit will deliver some air with the blower wheel running backwards.
Two basic air control systems can be used to deliver conditioned air to the occupied space: intermittent or constant fan operation.
Intermittent Fan Operation: The unit employs an air control system which utilizes a fan time delay relay to operate the fan while in the heating mode. If equipped with cooling, the thermostat controls the fan through a relay when in the cooling mode. Refer to unit wiring diagram.
These units are set at the factory for the RPM required to meet the air volume (CFM) and external static pressure ordered. If the estimated exter nal static is incorrect, or changes were made to the duct system, the blower RPM may need to be changed.
Both the Standard and High CFM Blowers use motors which are equipped with adjustable pitch pulleys. After removing belt(s), loosen the pulley set screw and remo ve the key, turn adjustable half of a pulley clockwise to increase RPM, or counter-clockwise to decrease RPM. Insert key, tighten set screw and replace belt(s). Adjust belt tension to give 1/2" to 3/4" belt play when depressed.
Blower motor full load amps should never be exceeded. Improper unit operation or motor failure could result.
After changing blower RPM, confi rm blower motor full load amps have not been exceeded. See motor data plate for maximum full load amps.
Figure 17
Constant Fan Operation: The unit can be wired to give
an air control system which constantly circulates air through the unit and occupied space with constant fan operation. Refer to unit wiring diagram.
NOTICE: Check blower belt tension. Proper belt tension is important to the long life of the belt and motor. Proper belt tension will allow the belt to be depressed 1/2" to 3/4".
— 18 —
LIGHTING Refer to Separated Combustion Indoor Duct Furnace Manual for all heating functions - general comments are as follows.
Meter Method of Checking Input Rate
1. Obtain the heating value of the gas from the local
utility or gas dealer. This should be in units of Btu/ft3 (MJ/m3).
Purge the gas line to the unit of air before attempting to light the pilot. Check for gas leaks.
Never use an open fl ame to detect gas leaks. Explosive conditions may exist which could result in personal injury or death.
This unit is equipped with an intermittent ignition system. A lighting instruction label is attached to the unit. To set the intermittent ignition system into operation, proceed as follows:
1. Turn on the gas valve(s) main manual valve.
2. Turn on electrical power. The unit is now under thermostat control.
3. Set thermostat to highest level. This will initiate the sequence of operation detailed in the Gas Control System section. Check main burners for operation.
4. Set thermostat to lowest level. This will interrupt power to the ignition control and shut off gas. Confi rm pilot and main burners have been extinguished.
5. Set the thermostat to the desired setting.
For complete unit shutdown, proceed as follows:
2. Determine the gas fl ow rate as shown in the following example. EXAMPLE: Assume this unit has a input rate of 250,000 Btu/hr (73.2 kW) and the heating value of the gas is 1000 Btu/ft3 (37.3 MJ/m3).
Gas Flow = Rate = 4.17 ft3/min
3. Before determining the gas fl ow rate to the unit, all other gas appliances connected to the same meter must be turned off.
4. Fire unit according to instructions.
5. After approximately 15 minutes of unit operation, determine volume of gas used in fi ve minutes of unit operation. For the Example above the unit should use 4.17 ft3/min x 5 min or 20.8 ft3 (1.97 L/s x 5 min x 60 s/min = 591L) of gas. Minor input adjustments can be made by removing pressure regulator cap and turning regulator clockwise to increase input or counter clockwise to decrease input. Any appreciable adjustment in input rate should be made by reorifi cing.
Method to Check Manifold Pressure
1. Close the manual valve of unit gas valve.
250,000 Btu/hr
1000 Btu/ft3 x 60 min/hr
1. Turn off the gas valve(s) main manual valve.
2. Set thermostat to lowest setting.
3. Shut off all electric power.
GAS INPUT ADJUSTMENT
When shipped from the factory, all units are equipped for the average heat content of the gas which is stamped on the unit rating plate.
Since the heat content of gas varies by locality, the input must be checked after installation of the unit. If the unit is overfi red it will shorten the life of the heat exchanger. Never exceed the input on the rating plate.
For an accurate input rate measurement, the following meter method should be used to determine unit input rate. If the meter method is not possible, a manifold pressure check should be made.
2. Install a 1/8" pipe connection in the tapped hole provided in the gas valve body near outlet of the valve.
3. Attach manometer to 1/8" pipe connection by means of a rubber hose.
4. Fire unit according to instructions and obser ve the pressure and confi rm it matches the unit manifold pressure from the unit rating plate.
5. Small variations in the manifold pressure can be made by means of the gas valve pressure regulator. Remove pressure regulator cap and turn regulator clockwise to increase pressure or counter-clockwise to decrease pressure.
— 19 —
PILOT ADJUSTMENT
1.
Disconnect wire from terminal marked MV at gas valve.
2. Provide call for heat.
3. Pilot adjustment is found on the gas valve. Remove pilot adjustment cap.
4. Adjust the pilot screw to provide properly sized fl ame.
5. A proper pilot burner fl ame is a soft steady fl ame that envelopes 3/8 to 1/2" (9.5 to 12.7mm) of the fl ame sense probe tip.
6. Replace the pilot adjustment cap.
Freezestat: (Optional) Located in either the return airstream, the supply airstream, or both, this control monitors temperatures with setpoints which are fi eld adjustable. If the temperature does not exceed the setpoint, the control will cease unit operation.
V. START UP
Before starting the unit, use the “Installation Check Sheet” (located at the end of this manual) and read the Separated Combustion Indoor Duct Furnace Manual entirely in conjunction with the procedures outlined below to ensure that the unit is completely and properly installed and ready for start up.
7. Reconnect wire to terminal MV.
PRIMARY AIR SHUTTER ADJUSTMENT
After the unit has been in operation for at least 15 minutes, adjust the primary air fl ow to the burners. Turn the friction-locked manually rotated air shutters clockwise to close, counter clockwise to open. For correct air adjustment, close the air shutter until yellow tips in the fl ame appear. Then open the air shutter to the point just beyond the position where yellow tipping disappears.
CONTROLS (also see the Indoor Duct Furnace Manual): Primary Limit Control: The primary limit control is a
factory installed component surface mounted in the inlet airstream at the end of the heat exchanger. When the temperature reaches the limit setpoint, normally caused by insuffi cient air throughput, all gas is shutoff. The limit control has an automatic reset and once the unit has cooled, it will reset itself. This is a safety control and if cycling on the primary limit is noted, corrective action must be taken. See unit wir ing diagram for electrical location. This control must never be bypassed. Upon completion of unit installation, the primary limit must be checked for proper operation. This can be accomplished by removing power to the indoor air blower and a call for heat.
Clogged Filter Switch: (Optional) The clogged filter switch monitors the pressure differential across the air fi lters. If this pressure differential becomes too great, the switch will alert of this condition. At this point the air fi lters must either be cleaned or replaced. The switch will reset itself.
Firestat: (Optional) Located in either the return airstream, the supply airstream, or both, this control monitors temperatures with setpoints which are fi eld adjustable. If the temperature exceeds the setpoint, the control will cease unit operation. To resume unit operation, a manual reset of this control is required.
It is the installer’s responsibility to check all safety controls! Check and test the operational functions of all safety devices supplied with this unit. Failure to do so could result in unsafe conditions and may result in death, serious injury or property damage.
1. Inspect all wiring connections; connections should be clean and tight. Trace circuits to insure that
actual wiring agrees with the “as wired” diagrams provided with the unit. Information in the wiring
diagram title block should match the data appearing on the unit nameplate.
2. Lubricate all electrical motors according to the manufacturer’s recommendations.
3. Verify that the system switch is in the OFF position.
4. Check unit supply voltage to ensure that it is within the utilization range.
5. Inspect the interior of the unit; remove any debris or tools which may be present.
Starting Unit in Heating Mode
1. Close the unit disconnect switch which provides power to the unit.
High voltage is present in some areas of the unit (primarily the main electrical cabinet) with the unit disconnect switch closed. Failure to exercise caution when working in the presence of energized electrical components may result in injury or death from electrical shock.
2. Set the thermostat/switching subbase as indicated below: a. position the heating system switch at either HEAT or AUTO; b. set the fan switch to AUTO.
3. Place the system switch in the ON position. With the thermostat calling for heat, unit operation is automatic.
— 20 —
Starting Unit in Cooling Mode
1. Close the unit disconnect switch which provides power to the unit.
High voltage is present in some areas of the unit (primarily the main electrical cabinet) with the unit disconnect switch closed. Failure to exercise caution when working in the presence of energized electrical components may result in injury or death from electrical shock.
Inspect the suspension and/or support system for the make-up air unit to ensure that all fasteners are tight and the unit is secure before working underneath the unit. Failuree to do so could result in property damage, personal injury, or death.
Gas tightness of the safety shut­off valves must be checked on at least an annual basis.
2. Set the thermostat/switching subbase as indicated below: a. position the cooling system switch at either COOL or AUTO; b. set the fan switch to AUTO.
3. Place the system switch in the ON position.
With the thermostat calling for cooling, unit operation is automatic.
Final Checkout
Run the unit sequentially through its stages of heating and cooling. Once proper unit operation is verified, perform these fi nal steps:
1. Inspect unit for debris and/or misplaced tools and hardware.
2. Be sure all gas valves and controls are in the operating position if the unit will be operating immediately.
3. Cycle unit on all safety controls to verify proper unit operation.
4. Confirm proper operating control (thermostat or ductstat) operation by cycling unit.
5. Secure all exterior panels in place.
T o check gas tightness of the saf ety shut-off valves , turn off the manual valve upstream of the appliance combination control. Remo v e the 1/8" pipe plug on the inlet side of the combination control and connect a manometer to that tapping. Turn the manual valve on to apply pressure to the combination control. Note the pressure reading on the manometer, then turn the valv e off . A loss of pressure indicates a leak. If a leak is detected, use a soap solution to check all threaded connections. If no leak is found, combination control is faulty and must be replaced bef ore
putting appliance back in service. These units have been developed for indoor installation.
Maintenance is required and it is suggested that the following unit servicing and inspections be performed routinely. Also read in entirety and refer to the Separated Combustion Indoor Duct Furnace Manual for maintenance requirements.
Inspect area near unit to be sure that there is no combustible material located within the minimum clearance requirements (See Figure 11). Service panels provide easy access to the blower compartment and the electrical cabinet. To remove the service door from any of these compartments, refer to access panel removal section in beginning of this manual.
VI. MAINTENANCE
HAZARDOUS VOL TAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
It is the service technician’s responsibility to check all safety controls! Check and test the operational functions of all safety devices supplied with this unit. Failure to do so could result in unsafe conditions and may result in death, serious injury or property damage.
— 21 —
Under no circumstance should combustible material be located within the specifi ed clearances. Failure to provide proper clearance could result in personal injury or property damage from fi re.
1. Follow the instructions in the maintenance section of the of the Separated Combustion Indoor Duct Furnace manual for servicing the furnace section of the make­up air unit.
2. Inspect and service the b lo w er section of the system.
3. Inspect and check the operational functions of all safety devices equipped with y our unit to ensure that all devices are performing adequately.
HIGH LIMIT AND/OR SAFETY LIMIT MAINTENANCE
Single furnace units are equipped with a primar y high limit on the upstream side of the heat exchanger and a secondary high limit on the downstream side of the heat exchanger. Multiple furnace units are equipped with a primary high limit on each fur nace section and a secondary high limit on the downstream unit. The primary high limit is a disk type switch while the secondary high limit is a capillary switch. To service or replace high limit or safety limit:
1. Turn off the manual gas v alve and electrical power to the MS unit.
SEASONAL MAINTENANCE
The unit should be thoroughly checked before the start and at the end of each heating and cooling season.
A. Motors and belts should be inspected. B. Tighten belts if loose. C. Check and clean DX or Chilled Water coil twice y early ,
if unit is so equipped per manufacturer’s service manual. Chilled Water coil must be winterized at beginning of heating season (i.e. drain water from coil per manufacturer’s instructions).
2. T o access the high limits, remove the f our screws from the top of the raceway on each furnace section and swing the raceway down. The primary limit can be removed by remo ving the two screws holding the high limit bracket to the heat e xchanger and removing the bracket and limit assemb ly from the heat e xchanger. Note location of and remove wires from limit switch, then remove push nuts and springs holding limit switch to bracket. Re-assemble in reverse order making sure that parts are assembled so that spring pressure holds limit switch securely against bottom header plate of heat exchanger.
3. T o remov e the secondary high limit, remove the wires from the limit switch, remov e the screws and stand-off sleeves holding the limit s witch body to the mounting plate. Do not remove the screws holding the mounting plate to the heat exchanger . Slowly pulll the switch and capillary assembly out of the retaining tube, taking care to prev ent kinking the capillary tube. Re-assemble in rev erse order, careefully pushing the capillary tube into the retaining tube to prevent kinking the capillary tube.
4. Complete appropriate start-up procedure as given in the “Start-Up” section of this manual.
5. Check Burner Adjustment.
6.
Check gas control valv es and pipe connection for leaks.
7. Check operation of auto gas valve.
D . Check air throughput at beginning of heating season
to confirm unit operation is within the specified temperature rise range.
E. At beginning of heating season clear Condensate
Drain Pan and P-trap of w ater if unit is equipped with DX or Chilled water coil. Clean out drain pan and fi ll P-trap with a non-toxic glycol solution.
F. Evaporative cooler must be cleaned and maintained
per manufacturer’s instr uction frequently during the operating season.
G. Inspect Control Dampers during periodic maintenance.
Damper pivot points should be cleaned to ensure free damper operation.
H. Blower wheels should be checked periodically for dirt
build-up on blades. Clean as required.
FILTERS
The fi lter section has been designed to incorporate (as standard) one-inch washable fi lters. Other optional fi lter types are also available: two-inch washable throwaw a ys; or one or two inch hi-effi ciency 30% pleated fi lters.
It is recommended that air fi lters be changed or cleaned at least four times a year . More frequent attention to fi lters is required if the air being handled by the unit is unusually dirty. Air fl ow reduction, caused by the dirty air fi lters, will increase the discharge air temperature and may cause unit cycling on the primary limit.
8. Check operation of safety devices.
9. Inspect and service blower section of system.
Filters (by others) should be serviced regularly and changed or washed when necessary to maintain the required air throughput. In a dusty environment, fi lters may clog up in less than one month.
— 22 —
A
A
A
B
Standard CFM Blower Air Filter Size Requirements
Number of Filters Required Unit Input 16 x 20 (in) 20 x 20 (in)
100 MBH (29.3 kW) 4 150 MBH (44.0 kW) 4 200 MBH (58.6 kW) 4 250 MBH (73.2 kW) 4 300 MBH (87.9 kW) 4 2 350 MBH (102.6 kW) 4 2 400 MBH (117.2 kW) 6 500 MBH (146.5 kW) 4 600 MBM (175.8 kW) 4 2 700 MBM (205.1 kW) 4 2 800 MBH (234.4 kW) 6
High CFM Blower Air Filter Size Requirements
Number of Filters Required
Figure 18
STANDARD CFM BLOWER
HIGH CFM BLOWER
Unit Input 16 x 20 (in) 20 x 20 (in)
100 MBH (29.9 kW) 8 150 MBH (44.0 kW) 8 200 MBH (58.6 kW) 8 250 MBH (73.2 kW) 8 300 MBH (87.9 kW) 8 4 350 MBH (102.6 kW) 8 4 400 MBH (117.2 kW) 12 500 MBH (146.5 kW) 8 600 MBH (175.8 kW) 8 4 700 MBH (205.1 kW) 8 4 800 MBH (234.4 kW) 12 1,200 MBH (351.6kW) 12
AIR BLOWER
Belt Tension Adjustment Standard CFM Blower belt tension can be adjusted by loosening motor mounting bolts marked A (See Figure 18). To tighten belt, slide motor down motor mounting bracket and re-fasten motor to mounting bracket.
High CFM Blower belt(s) tension can be adjusted by fi rst loosening motor mounting plate bolts marked A (See Figure 18). To tighten belt tension, turn belt tension adjustment screws marked B (See Figure 18) counter­clockwise. To loosen belt tension, turn clockwise. Once belt tension has been adjusted, re-fasten motor mounting plate bolts.
— 23 —
A
A
B
B
A
A
KEY B PROJECTS TO PROVIDE A GRIP FOR REMOVING. DO NOT OPERATE SHEAVE WITH FLANGE PROJECTING
BEYOND THE HUB END.
D3881
Blower RPM Adjustment
To adjust blower RPM:
1. Loosen and remove belt(s).
2. Match driver pulley to one found in Figure 19.
3. Loosen set screw(s) marked A.
4. If driver pulley is equipped with external key, marked B, remove.
5. Adjust driver pulley pitch diameter for desired speed by opening (slower) or closing (faster) moving parts by half or full turns. Do not open sheave past point where fl ange projects past the hub end.
6. If driver pulley is equipped with external key, marked B, replace.
7. Tighten set screw(s) marked A.
Figure 19
8. Replace and retension belt(s).
9. Realign drive if necessary.
— 24 —
VII. TR OUBLESHOOTING
For troubleshooting of the duct furnace, refer to the Separated Combustion Indoor Gas-Fired Duct Furnace Installation and Service Manual. F or Evaporative Cooler/Cooling Coil equipped units , refer to these specifi c manuals for additional troubleshooting guides.
For additional troubleshooting, see following Troubleshooting Guide.
TROUBLESHOOTING GUIDE
AIR BLOWER
PROBLEM PROBABLE CAUSE SOLUTION
1. Noise Blower Wheel Hitting Scroll Side a. Blower Wheel not centered in blower housing.
b. Damaged blower housing. c. Damaged blower wheel. d. Shaft loose in blower bearing. e. Blower Wheel loose on shaft. f. Blower bearing loose in bearing support. Blower Wheel Hitting Cutoff a. Cutoff not secure in blower housing. b. Cutoff damaged. c. Cutoff improperly positioned. Drive a. Pulley not tight on shaft (motor and/or blower wheel). b. Belts too loose. Adjust for belt stretching after 48 hours of operation. c. Belts too tight. d. Belts wrong cross section. e. Belts not matched in length on multi-belt drive. f. Variable pitch pulleys not adjusted so each pulley has same pitch diameter (multi-belt drives). g. Misaligned pulleys. h. Belts worn. i. Motor or motor base loose. j. Belts oily or dirty. k. Improper drive selection. Bearing a. Defective bearing. b. Needs lubrication. c. Loose on bearing support. d. Loose on shaft. e. Seals misaligned. f. Foreign material in bearing. g. Worn bearing. h. Fretting corrosion between inner race and shaft. Shaft Seal Squeal a. Needs lubrication.
b. Misaligned.
— 25 —
PROBLEM PROBABLE CAUSE SOLUTION
1. Noise Blower Wheel a. Loose on shaft.
b. Defective blower wheel. Do not run blower. Contact manufacturer. c. Unbalanced. d. Worn as a result of contact with abrasive or corrosive material. Housing a. Foreign material in housing. b. Cutoff or other part loose (rattling during operation). Electrical a. Lead-in cable not secure. b. AC hum in motor or relay. c. Starting relay chatter. d. Noisy motor bearings. e. Single phasing a 3 phase motor. Shaft a. Bent. b. Undersized. May cause noise at blower wheel, bearings or pulley. c. If more than two bearings are on a shaft, they must be properly aligned. High Air Velocity a. Duct work too small for application. b. Blower selection too small for application. c. Registers or grilles too small for application. d. Cooling coil with insuffi cient face area for application. Obstruction in High Velocity Air Stream a. Dampers.
c. Grilles. d. Sharp elbows. e. Sudden expansion in duct work. f. Sudden contraction in duct work. g. Turning vanes. Pulsation or Surge a. Blower too large for application. b. Ducts vibrate at same frequency as blower pulsations. Rattles and/or Rumbles a. Vibrating duct work. b. Vibrating cabinet parts. c. Vibrating parts not isolated from building.
2. CFM Low - Blower a. Forward curved blower wheel installed backwards.
Insuffi cient Air Flow
c. Cutoff missing or improperly installed. d. Blower wheel RPM too low. Duct System a. Actual system is more restrictive than expected. b. Dampers closed. c. Registers closed. d. Leaks in supply duct.
may cause Rattle or Pure Tone Whistle
b. Blower operating backwards.
b. Registers.
— 26 —
PROBLEM PROBABLE CAUSE SOLUTION
2. CFM Low Filters Dirty or clogged.
Insuffi cient Air Flow
Obstructions in High Velocity Air Stream a. Obstruction near unit outlet. b. Sharp elbows near unit outlet. c. Improperly designed turning vanes. d. Projections, dampers or other obstructions in part of duct system where air velocity is high.
3. CFM High - System a. Oversized duct work.
Too Much Air Flow
c. Registers or grilles not installed. d. Filters not in place. e. System resistance lower than anticipated. Blower Blower RPM is too great.
4. Blower Does Not Operate Installation a. Incorrect electrical connection.
b. Wrong voltage. c. Blown fuse. Unit a. Broken belt(s). b. Loose pulleys. c. Power to unit is disconnected. d. Motor overload protector has broken circuit. e. Optional thermostats, fi restats, freezestats may lockout blower operation if set incorrect.
Coil - DX or Chilled Water Dirty or clogged.
b. Access door open.
TROUBLESHOOTING GUIDE
ELECTRIC MOTORS
PROBLEM PROBABLE CAUSE SOLUTION
1. Motor Blown fuse or open circuit breaker. Replace fuse or reset circuit breaker.
Overload trip. Check and reset, if manual. Improper line connections. Check connections to unit wiring diagram. Improper current supply. Check to determine that power supply agrees with
Mechanical failure. Determine that motor and drive turn freely.
Motor overloaded. Reduce load or replace motor . With a 3 phase power source, one Check line for open phase.
Defective capacitor. Replace capacitor.
2. Motor Stalls Wrong application. Consult manufacturer.
Overloaded motor. Reduce load or replace motor. Low line voltage. Check across AC line and correct
phase may be open.
motor nameplate specifi cations.
Check bearings.
if possible.
— 27 —
PROBLEM PROBABLE CAUSE SOLUTION
3. Motor runs and then Partial loss of line voltage. Check for loose connections.
dies down.
4. Motor does not Motor undersized for application. Replace with larger motor.
come up to speed.
Line wiring to motor is too small. Install larger line wiring.
5. Motor takes too long Excessive load. Replace with larger motor.
to accelerate.
6. Wrong Rotation (3 Phase) Improperly wired to AC line (wrong Check unit wiring diagram. Reverse any two line
7. Motor Overheats Motor overloaded. Replace with larger motor.
Motor ventilation clogged. Clean motor. Motor (3 phase) may have open phase. Check to insure that all connections are tight. Line voltage too high or too low. Check across AC line and correct if possible. Worn blower bearings. Replace blower bearings.
8. Motor Vibrates Motor mounting bolts loose. Tighten mounting bolts.
Driven equipment unbalanced. Balance driven equipment. Worn motor bearings. Replace motor. 3 phase Motor running on single phase. Check for open circuit and correct. Bent motor shaft. Replace motor.
9. Rapid Motor Bearing Excessive overhung load due to over Reduce belt tension.
Wear
Voltage too low at motor terminals. Check across AC line and correct if possible.
Loose connection. Check connections and tighten where necessary.
sequence of phases).
tensioned belt.
Determine adequacy of main power supply.
voltage connections.
TROUBLESHOOTING GUIDE
FAN ASSEMBLY
PROBLEM PROBABLE CAUSE SOLUTION
1. Short Belt Life Spin burns from belt slippage. Tension belt.
High ambient temperature. Use Gripnotch belts. Grease or oil on belts. Clean belts and pulleys. Worn pulleys. Replace pulleys. Belt Misalignment. Realign drive.
2. Belts turn over in grooves Damaged belt. Replace belt.
Excessive vibration. Tension belts. Replace belts if damaged. Worn pulleys. Replace pulleys. Pulley Misalignment. Realign drive.
3. Belt Squeal Excessive load. High starting load.Retension drive.
4. Belt Breakage Foreign material in drive. Provide drive guard.
Belts damaged during installation. Replace belts. Extreme Overload. Eliminate overload.
5. Excessive Vibration Damaged belt cord section. Replace belts.
Loose belts. Tension drive. Belts improperly tensioned. Tension drive with slack of each belt on the
same side of drive.
— 28 —
PROBLEM PROBABLE CAUSE SOLUTION
6. Belts mismatched Belts improperly tensioned, causing Replace belts and tension drive with slack of each
after service
Old belts and new belts used Replace with new belts.
Different brand name belts used Replace with a set of Machine Matched Belts.
Driver and driven shafts shifted Realign drive.
Belt cord section damaged during Replace belts and install properly.
7. Drive fails to adjust Fretting corrosion (drive allowed to Driver pulley must be disassembled,
more stretch of some belts than others. belt on the same side of the drive.
on same drive.
on same drive.
from parallel.
installation.
operate at one speed over a period cleaned and lubricated, then of time). reassembled.
TROUBLESHOOTING GUIDE
DX COOLING COIL
PROBLEM PROBABLE CAUSE SOLUTION
1. No or Insuffi cient Coil icing. a. Low liquid line pressure.*
Cooling
c. Low air fl ow across coil. Air binding. Purge and charge system. Thermal expansion valve.** a. Bulb mounted at incorrect location. b. Bulb not secured properly. Insuffi cient air fl ow. a. See air blower troubleshooting. b. Clogged coil. Air bypassing coil. Caulk safe off. Undersized system, demand Replace system.*
Too much outside air. Check outside air dampers. Refrigerant leak. Determine leak location and correct. Low liquid pressure. Determine cause and correct.*
2. Water in Conditioned Air Exceeding coil face velocity - 600 fpm. Reduce unit air fl ow.
Drain pan p-trap clogged. Clean pan and p-trap. * Refer to condensing unit installation and service manual.
**Refer to thermal expansion valve installation instruction.
b. Thermal expansion valve.**
exceeding cooling system capacity.
— 29 —
TROUBLESHOOTING GUIDE
CHILLED WATER COOLING COIL
PROBLEM PROBABLE CAUSE SOLUTION
1. No or Insuffi cient Cooling Circulating pump failure. Repair or replace pump.*
Chilled water temperature Check chiller.*
Air binding (air in coil). Bleed coil. Insuffi cient chilled water fl ow. a. Circulating pump capacity is inadequate.* b. System piping losses too great. Insuffi cient air fl ow. a. See air blower troubleshooting. b. Clogged coil. Air bypassing coil. Caulk safe off. Undersized system, demand Replace system.*
Too much outside air. Check outside air dampers.
2. Water in Conditioned Air Exceeding coil face velocity - 600 fpm. Reduce unit air fl ow.
Drain pan P-trap clogged. Clean pan and p-trap. *Refer to Manufacturer’s Installation and Service Manual.
not cool enough.
exceeding cooling system capacity.
VIII. REPLACEMENT PARTS
To order Replacement Parts, please provide the following information to your local representative:
• Model Number
• Serial Number
• Part description and Number as shown in
Replacement Parts Literature
Due to the many confi gurations, options and voltage characteristics available on Make-Up Air Packaged Units, the information provided in this manual is somewhat general in context. Should user or service organization incur a problem, the nature of which is not herein, we urge you to contact the manufacturer.
IX. SERVICE NOTE
It would be of great assistance to us if you can provide If further assistance is required, please contact the manufacturer’s customer service department
the model and serial numbers and the wiring diagram
number, as well as the access type.
X. LIMITED WARRANTY
All components are warranted by the manufacturer to be free from defects in material and workmanship for period of one (1) year from the date of shipment from the manufacturing plant.
The manufacturer will repair or replace, at its option, any component which, upon inspection, it fi nds to be defective, provided that the Make-Up Air Packaged Unit has been operated within its listed capacity, has been installed in accordance with all furnished instruction, has not been misused or subjected to neglect and has received reasonable and necessary maintenance. This warranty does not cover labor costs or other costs incurred in repairing, removing, installing, servicing or handling of parts or completed products.
This Warranty does not cover loss due to corrosion by chemicals precipitated in the air such as halogenated hydrocarbons. The manufacturer will in no event be liable for incidental or consequential damages of any kind whatsoever. Written permission is required prior to the return of defective components. All returns must be sent with all transportation charges prepaid to the plant designated in the written permission. This warranty is extended only to the original owner of the Make-Up Air Package Unit.
— 30 —
“FOR CANADIAN INSTALLATIONS ONLY”
The following instructions apply to Canadian installations in addition to installation and operating instruction:
1. Installation must conform with local building codes, or in absense of local codes, with current CSA B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CSA B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.
2. Any reference to U.S. standards or codes in these instructions are to be ignored and the applicable Canadian standards or codes applied.
3. Any references to deration at altitudes in excess of 2000 feet are to be ignored. When installed in Canada at altitudes of 2000 to 4500 feet, the duct furnaces must be orifi ced to 90% of the normal altitude rating, and be so marked in accordance with the ETL certifi cation.
4. Duct furnaces are designed certifi ed to comply with CSA 2.6.
5. In Canada, installation is suitable in airplane hangars when acceptable to the enforcing authorities, and in public garages when installed in accordance with current CSA B149 Installation Codes for Gas Burning Appliances and Equipment.
6. All electrical connections must be in accordance with Canadian Electrical Code, P art 1, CSA Standard C22.1.
7. In Canada, the vent system must be adequately supported to prevent sagging; but in no case shall the supports be less than every 3 feet.
8. If using a metal vent system under positiv e gauge pressure in Canada, a slip fi t vent connection must be secured b y a least two corrosiv e resistant scre ws , or other mechanical loc king means .
9. Canadian units require the following vent equivalent lengths; 5 feet minimum; 50 feet maximum.
10. The vent shall not terminate — a. Less than 6 f eet from a combustion air inlet of another appliance. b. Less than 3 feet from any other building opening or any gas service regulator. c. Directly above a gas utility meter or service regulator .
11. V ent terminal shall be located not less than one foot abo ve grade.
12. It is recommended that the heater and vent system be checked once a year by a qualifi ed serviceman.
— 31 —
XI. DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “A”
Capacities [CA] 50 - 80
Indoor Arrangement [IA] “A”
Capacities [CA] 12
Refer to page 33 for tabulated dimensions.
— 32 —
DIMENSIONAL DATA — ARRANGEMENTS
This tabulated dimensional data applies to all dimensional drawings.
***Capacity Gas Inlet (CA) A B C D G H J L U V Dia.** NAT LP
10 32- 7/8 15- 9/16 16- 7/8 19- 3/8 30- 3/16 37-1/16 24 N/A N/A 4 1/2 1/2 (835) (395) (418) (492) (767) (640) (610) (102)
15 32- 7/8 18- 5/16 16- 7/8 19- 3/8 30- 3/16 37- 1/16 24 N/A N/A 4 1/2 1/2 (835) (465) (418) (492) (767) (640) (610) (102
20 43- 7/8 23- 13/16 21- 15/16 24- 7/8 41- 3/16 37- 7/16 35 N/A N/A 5 1/2 1/2 (1114) (605) (557) (632) (1046) (678) (889) (127)
25 43- 7/8 29- 5/16 21- 15/16 24- 7/8 41- 3/16 37- 7/16 35 N/A N/A 5 3/4 1/2 OR 3/4 (114) (745) (557) (632) (1046) (678) (889) (127)
30 54- 7/8 34- 13/16 27- 7/16 30-3/8 52- 3/16 36- 11/16 46 N/A N/A 6 3/4 1/2 OR 3/4 (1394) (884) (697) (772) (1326) (640) (1168) (152)
40 60- 3/8 45- 13/16 30- 3/16 33- 3/16 57- 11/16 36- 11/16 51- 1/2 N/A N/A 6 3/4 1/2 OR 3/4 (1534) (1164) (767) (841) (1465) (640) (1308) (152)
50 43- 7/8 29- 5/16 21- 15/16 24- 7/8 42- 1/16 37- 7/16 35 N/A N/A 5 3/4 1/2 OR 3/4 (114) (745) (557) (632) (1068) (678) (889) (127)
60 54- 7/8 34- 13/16 27- 7/16 30- 3/8 53- 1/16 36- 11/16 46 N/A N/A 6 3/4 1/2 OR 3/4 (1394) (884) (697) (772) (1348) (640) (1168) (152
70 54- 7/8 40-5/16 27- 7/16 30- 3/8 53- 1/16 36- 11/16 46 N/A N/A 6 3/4 1/2 OR 3/4 (1394) (1024) (697) (772) (1348) (640) (1168) (152
80 60- 3/8 45- 13/16 30- 3/16 33- 1/8 58- 9/16 36- 11/16 51- 1/2 181-1/4 177 6 3/4 1/2 OR 3/4 (1534) (1164) (767) (841) (1487) (932) (1308) (4604) (4495) (152)
12 60- 3/8 45- 13/16 30- 3/16 33- 1/8 58- 9/16 36- 11/16 51- 1/2 218-1/4 217 6 3/4 1/2 OR 3/4 (1534) (1164) (767) (841) (1487) (932) (1308) (5544) (5512) (152)
NOTES: Unless otherwise noted the end views and dimensional data shown in the drawings and table are applicable to Indoor Arrangement [IA]-B, D, G, K. Dimensions are in inches. Dimensions in parenthesis are in millimeters. J▲ Dimension is an outside dimension for the return air damper. *This is an outside damper dimension. **V = Flue Opening; the 4" to 5" reducer adaptor is to be fi eld installed for unit capacities 10 & 15. The 5" to 6" increaser adaptor is supplied by the manufacturer for unit capacities 30, 35, 40, 60, 70, 80 & 12 (required for each furnace's fl ue). ***Capacities 10 through 40 are ETL certfi ed.
Typical
Intake Air End View
(Not applicable to [IA]-A or D
See Evaporative Cooling Specifi cations)
Typical
Discharge End View
— 33 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “B”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “B”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 34 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “D”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “D”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 35 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “G”
Capacities [CA] 20/40
(ships in one section)
Indoor Arrangement [IA] “G”
Capacities [CA] 50/12
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 36 —
DIMENSIONAL DATA — ARRANGEMENTS
Indoor Arrangement [IA] “K”
Capacities [CA] 10/40
(ships in one section)
Indoor Arrangement [IA] “K”
Capacities [CA] 50/80
(ships in two sections)
Refer to page 33 for tabulated dimensions.
— 37 —
XII. MOTOR ELECTRICAL DATA
Full Load Current In Amperes
1 - (115/1/60) 2 - (208/1/60) 3 - (230/1/60)
1
2
3
1
2
3
1
2
3
ODP
1/2 HP 7.2 8.6 4.6 4.6 3.7 2.8 3.8 4.3 2.3 2.3 3/4 HP 11.6 11.0 6.5 6.3 5.2 5.4 3.4 5.0 5.5 3.3 3.2
1 HP 13.0 13.4 8.6 8.5 6.6 6.8 6.5 6.7 4.3 4.3
1-1/2 HP 18.2 18.0 12.5 12.6 9.1 8.4 9.1 8.0 6.3 6.3
2 HP 21.0 23.0 17.6 17.6 11.3 11.5 10.5 8.1 8.8 8.8 3 HP 33.5 28.0 17.4 14.6 16.8 14.0 11.8 5 HP 23.5 21.0 23.0 19.1
7-1/2 HP 33.0 31.0 31.0 29.0
10 HP 38.0 15 HP
1
ODP
1/2 HP 2.3 2.0 1.8 1.7 2.2 2.5 1.8 2.0 1.1 1.0 0.9 1.0 3/4 HP 3.0 3.2 2.5 3.4 3.0 2.4 2.8 1.7 1.5 1.2 1.4
1 HP 3.4 3.7 3.1 3.1 3.4 3.4 3.0 3.1 1.7 1.7 1.5 1.5
1-1/2 HP 5.1 5.0 4.5 4.5 5.2 4.6 4.4 4.4 2.6 2.3 2.2 2.2
2 HP 6.2 5.8 6.0 6.0 5.8 5.8 3.0 2.9 2.9 3 HP 9.2 8.5 9.0 8.6 8.4 8.4 4.3 4.2 4.2 5 HP 12.8 11.8 12.0 11.8 6.0 5.9
7-1/2 HP 20.4 21.0 19.4 18.8 9.7 9.4
10 HP 26.0 27.0 25.0 25.0 12.5 12.5 15 HP 37.4 38.9 35.4 37.0 17.7 18.5
1
ODP
1/2 HP 0.8 0.8 3/4 HP 1.1 1.1
1 HP 1.3 1.7 1.2 1.2
1-1/2 HP 1.7 1.8 1.8
2 HP 2.3 2.4 3 HP 3.4 3.2 5 HP 5.3 5.3
7-1/2 HP 7.8 7.6
10 HP 10.0 9.6 15 HP 14.1 15.1
TE
TE
TE
PEODP4PETE
4 - (208/3/60) 5 - (230/3/60) 6 - (460/3/60) 2
7 - (575/3/60) 2
3
PEODP4PETE
3
PEODP4PETE
ODP
1
ODP
TE
TE
2
PEODP4PETE
3
PEODP4PETE
Motor Type (MT) Legend:
ODP - Open Drip Proof
ODP
1
ODP
TE
2
TE
TE - Totally Enclosed PEODP - Premium Effi ciency Open Drip Proof PETE - Premium Effi ciency Totally Enclosed
PEODP4PETE
3
PEODP4PETE
— 38 —
XIII. UNIT/SHIP WEIGHTS
Motor Shipping Weight (lbs) - Approximate
1 - (115/1/60) 2 - (208/1/60) 3 - (230/1/60)
1
2
3
1
2
3
1
2
3
ODP
1/2 HP 20 24 32 30 21 24 32 21 24 32 30 3/4 HP 23 30 30 41 23 30 30 25 30 30 41
1 HP 32 32 40 44 32 32 32 32 40 44
1-1/2 HP 40 41 47 57 40 41 40 41 47 57
2 HP 42 67 65 64 50 67 42 48 65 64 3 HP 78 86 78 86 78 86 90 5 HP 87 87 99 95
7-1/2 HP 134 138 134 138
10 HP 165 140 161 15 HP
1
ODP
1/2 HP 19 18 22 22 19 18 22 22 19 18 22 22 3/4 HP 27 26 27 27 22 27 31 27 22 27 31
1 HP 24 26 36 37 24 26 36 37 24 26 36 37
1-1/2 HP 28 34 40 42 28 34 40 42 28 34 40 42
2 HP 35 46 49 35 46 49 35 46 49 3 HP 48 69 69 48 69 69 48 69 69 5 HP 76 77 76 77 76 77
7-1/2 HP 117 136 117 136 117 136
10 HP 128 158 128 158 128 158 15 HP 217 255 217 255 217 255
1
ODP
1/2 HP 22 18 3/4 HP 20 22
1 HP 28 26 33 38
1-1/2 HP 40 42
2 HP 46 48 3 HP 66 69 5 HP 74 91
7-1/2 HP 114 143
10 HP 145 153 15 HP 234 302
TE
TE
TE
PEODP4PETE
4 - (208/3/60) 5 - (230/3/60) 6 - (460/3/60) 2
7 - (575/3/60) 2
3
PEODP4PETE
3
PEODP4PETE
ODP
1
ODP
TE
TE
2
PEODP4PETE
3
PEODP4PETE
Motor Type (MT) Legend:
ODP - Open Drip Proof
ODP
1
ODP
TE
2
TE
TE - Totally Enclosed PEODP - Premium Effi ciency Open Drip Proof PETE - Premium Effi ciency Totally Enclosed
PEODP4PETE
3
PEODP4PETE
Cooling Coil Weight Adder (Approximate)
DX COIL
(CA) Capacity 4 Row 6 Row 10, 15 97 lbs. 132 lbs. 20, 25, 50 126 lbs. 177 lbs. 30, 35, 60, 70 165 lbs. 229 lbs. 40, 80 177 lbs. 249 lbs.
CHILLED WA TER COIL
(CA) Capacity 4 Row 6 Row 10, 15 75 lbs. 102 lbs. 20, 25, 50 98 lbs. 135 lbs. 30, 35, 60, 70 125 lbs. 176 lbs. 40, 80 135 lbs. 196 lbs.
Indoor Arrangement [IA] "A, B, D, G, K"
Shipping Weights (lbs.)
Outside
Air Hood
w/Bird Screen
Weight Adder
Capacity [CA]
Arrangement [IA]
ABDGK
10 742 904 1137 43
15 739 956 1188 43
20 916 1102 1206 1394 51
25 957 1114 1249 1436 51
30 1092 1301 1452 1659 59
35 1143 1352 1495 1702 59
40 1222 1443 1583 1799 63
50 550 1423 1595 1689 1915 51
60 650 1616 1812 1951 2195 59
70 800 1707 1902 2033 2278 59
80 850 1833 1240 2166 2420 63
12 1300 2741 63
Note: The approximate shipping weights are for a basic unit (these
weights do not include the motor, cooling coil, optional outside air
hood, fl ex connector kit, or any options).
For units with double wall construction add an additional 10% of
the base unit weight.
— 39 —
XIV. COIL CABINET DIMENSIONAL DATA
INSIDE UNIT WALL
“ L” MAX.
31-3/4"
(806)
26" (660)
OUTSIDE BOTTOM PANEL
1"
(25)
1"
(25)
24"
(700)
33"
(838)
39"
(991)
3"
(76)
3"
(76)
13"(330)
MAX. COIL
DEPTH
7/8" (22)
TOP
53-1/4" (1353)
“ L” INSIDE MAX.
CABINET OPENING
42-1/4" (1073)
58-3/4" (1492)
31-1/4" (794)
30/35/60/70
UNIT SIZE
20/25/50
40/80
10/15
*
*
Maximum Coil Dimensions
Side Opening
of Coil Module
— 40 —
SEPARATED COMBUSTION
INDOOR MAKE-UP AIR PRODUCTS
MODEL “MS” SUBMITTAL INDEX
IA “B”
CA (10/40)
IA “D”
CA (10/40)
IA “G”
CA (10/40)
IA “K”
CA (10/40)
Single Furnace Units
(ETL Certifi ed)
Unit Type (UT): MS
Submittal
Number
MS-40-B
MS-40-D
MS-40-G
MS-40-K
IA “A”
CA (50/80)
IA “B”
CA (50/80)
IA “D”
CA (50/80)
IA “G”
CA (50/80)
IA “K”
CA (50/80)
Dual Furnace Units*
Unit Type (UT): MS
Submittal
Number
MS-80-A
MS-80-B
MS-80-D
MS-80-G
MS-80-K
IA = Indoor Arrangement (Digit #7) CA= Capacity (Digits #3 and 4) Refer to Complete Model Number Designation
in Catalog.
Legend:
B/F/D = Standard Blower/Filter/Damper Module B = Hi CFM Blower Module F/D = Hi CFM Filter/Damper Module CC = Cooling Coil Module EV = Evap. Cooler Module
*Flex connector kits not shown.
IA “A”
CA (12)
IA “G”
CA (12)
Triple Furnace Units*
Unit Type (UT): MS
Submittal
Number
MS-12-A
MS-12-G
— 41 —
XVI. UNIT NUMBER DESCRIPTION
SEP ARA TED COMB USTION INDOOR MAKE-UP AIR UNITS
Digit M X X — 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 + Item Prefi x UT CA FT FM IA CO GT GC SV MT MS AI AC AS
(Internal use Only)
1, 2 - Unit Type [UT]
MS - Separated Combustion Indoor Make-up Air Unit
3, 4 - Capacity [CA]
*Single Furnace Double Furnace 10 - 100,000 BTU/HR 50 - 500,000 BTU/HR. 15 - 150,000 BTU/HR 60 - 600,000 BTU/HR 20 - 200,000 BTU/HR 70 - 700,000 BTU/HR 25 - 250,000 BTU/HR 80 - 800,000 BTU/HR 30 - 300,000 BTU/HR 35 - 350,000 BTU/HR Triple Furnace 40 - 400,000 BTU/HR 12 - 1,200,000 BTU/HR
*Single furnace capacities 10 through 40 are ETL certifi ed.
5 - Furnace Type [FT]
A - Standard Temperature Rise (20-60°F), Right Side Access B - Standard Temperature Rise (20-60°F), Left Side Access C - High Temperature Rise (60-90°F), Right Side Access D - High Temperature Rise (60-90°F), Left Side Access 0 - None Z - Other
6 - Furnace Construction Material [FM]
1 - Aluminized Steel
- 409 Stainless Steel (First Furnace Only)
2
- 409 Stainless Steel (All Furnace Sections)
3
- 321 Stainless Steel (First Furnace Only)
4
- 321 Stainless Steel (All Furnace Sections)
5
- 409 Stainless Steel Package (First Furnace Only)
6
- 409 Stainless Steel Package (All Furnace Sections)
7
- 321 Stainless Steel Package (First Furnace Only)
8
- 321 Stainless Steel Package (All Furnace Sections)
9
- None
0
- Other
Z
7 - Indoor Arrangement (includes furnace section(s) [IA]
A - Duct Furnace (50-12 [CA] only) K - Blower (High CFM) / Cooling
- Blower (Standard) 0 - None
B D - Blower (Standard) / Evap. Z - Other
- Blower (High CFM)
G
8 - Coil Options [CO]
A - DX Coil, 4 Row Single Circuit
- DX Coil, 4 Row Dual Circuit G - Chilled Water Coil, 6 Row
B
- DX Coil, 6 Row Single Circuit 0 - None
C D - DX Coil, 6 Row Dual Circuit Z
9 - Gas Type [GT]
1 - Natural Gas
- LP Gas (Propane)
2
- Natural Gas w/100% Shutoff
3 0 - None
10 - Gas Control [GC]
A - Single Stage Gas (Standard) B - Two Stage Gas H - Electronic Modulation w/Room Sensing
-
Electronic Modulation w/Duct Sensing
J K - Electronic Modulation w/Duct Sensing & Ovrd. Stat
-
Electronic Modulation w/External 4-20 mA Input (Furnace One)
L M
- Electronic Modulation w/External 4-20 mA Input (All Furnaces) N - Electronic Modulation w/External 0-10 VDC Input (Furnace One) P - Electronic Modulation w/External 0-10 VDC Input (All Furnaces) R - Two Stage Remote Temperature Control w/Duct Sensor
-
Three Stage Remote Temperature Control w/Duct Sensor
S
- Four Stage Remote Temperature Control w/Duct Sensor
T U - S-350 2 Stage Modular Electronic Control System
- S-350 3 Stage Modular Electronic Control System
W X - S-350 4 Stage Modular Electronic Control System
- S-350 6 Stage Modular Electronic Control System
Y
- None
0 Z - Other
11 - Supply Voltage [SV]
1 - 115/1/60 5 - 230/3/60 2 - 208/1/60 6 - 460/3/60 3 - 230/1/60 7 - 575/3/60 4 - 208/3/60 0- None Z - Other
12 - Motor Type [MT]
1 - Open Drip Proof (Standard) 2 - T otally Enclosed 3 - Premium Effi ciency, Open Drip Proof 4 - Premium Effi ciency, Totally Enclosed 0 - None Z - Other
E - Chilled Water Coil, 4 Row
-
Other
13 - Motor Sizes [MS]
A - 1/2 HP. w/Contactor M - 1-1/2 HP. w/Mag. Starter 1 - 1 HP. VFD B - 3/4 HP. w/Contactor N - 2 HP. w/Mag. Starter 2 - 1-1/2 HP. VFD C - 1 HP. w/Contactor P - 3 HP. w/Mag. Starter 3 - 2 HP. VFD D - 1-1/2 HP. w/Contactor R - 5 HP. w/Mag. Starter 4 - 3 HP. VFD E - 2 HP. w/Contactor S - 7-1/2 HP. w/Mag. Starter 5 - 5 HP. VFD G - 3 HP. w/Contactor T - 10 HP. w/Mag. Starter 6 - 7-1/2 HP. VFD H - 5 HP. w/Contactor U - 15 HP. w/Mag. Starter 7 - 10 HP. VFD J - 1/2 HP. w/Mag. Starter 0 - None 8 - 15 HP. VFD K - 3/4 HP. w/Mag. Starter Z - Other L - 1 HP. w/Mag. Starter
14 - Air Inlet Confi guration [AI]
1 - Outside Air (OA) 4 - Outside Air and Return Air (OA/RA) 2 - Outside Air w/Air Hood* 5 - Outside and Return Air w/Air Hood* 3 - Return Air (RA) 0 - None Z - Other
15 - Air Control & Damper Arrangement [AC]
A - Outside Air 2 Pos. Motor / Spring Return B
- Return Air 2 Pos. Motor / Spring Return
C - OA/RA 2 Pos. / Spring Return D
- OA/RA Mod. Mtr. w/Mixed Air Control / Min. Pot.
- OA/RA Mod. Mtr. w/Mixed Air Control / Min. Pot. / SR
E G - OA/RA Mod. Mtr. w/Mixed Air Control H
- OA/RA Mod. Mtr. w/Mixed Air Control / SR
-
OA/RA Mod. Mtr. w/Min. Pot.
J K - OA/RA Mod. Mtr. w/Min. Pot. / SR
- OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air Control / Min. Pot.
L M
- OA/RA Mod. Mtr. w/Dry Bulb / Mixed Air Control / Min. Pot. / SR
N - OA/RA Mod. Mtr. w/Enthalpy Controlled Economizer / SR
- OA/RA Mod. Mtr. w/Pressure Control (Space Pressure)
P
- OA/RA Mod. Mtr. w/Carbon Dioxide (CO2) R/A Monitor
Q
- OA/RA Mod. Mtr. w/S-350-P Proportional Mixed Air Control / SR
R
- OA/RA Mod. Mtr. w/0-10 VDC & 4-20 mA Analog Input (External Input)
S
- OA/RA Mod. Mtr. w/0-10 VDC & 4-20 mA Analog Input / SR (External Input)
T U - ASHRAE Cycle I (OA/RA 2 Pos. Mtr. w/Warm-up Stat / SR) W
- ASHRAE Cycle II (OA/RA Mod. Mtr. w/Warm-up Stat / Mixed Air / Min. Pot. / SR) X - ASHRAE Cycle III (OA/RA Mod. Mtr. w/Warm-up Stat / Mixed Air / SR) Y - Manual Dampers 0 - None MOD = Modulating Damper Motor Z - Other OA = Outside Air RA = Return Air SR = Spring Return
16 - Accessories [AS]
A1 - Moisture Eliminators H1 - Return Firestat A2 - Horizontal Return H2 ­A3 - Low Leak Damper H3 ­A6 - High Altitude Unit H4 ­A7 - High Pressure Regulator A8 - Unit Derate J1 ­ J2 ­B1 - Filters - 1" WA (Standard) J3 B2 - Filters - 2" W B3 - Filters - 2" TA B4 - Filters - 1" 30% K1 - Manual Reset High Limit Switch B5 - Filters - 2" 30% K2 - High / Low Gas Pressure Limit Switches K3 - Status Lamp (Elec. Cabinet) C1 - Evap. Cooler - Fill & Drain Kit K4 - Fan Time Delay (Arrangement “A” Only) C2 - Evap. Cooler - 12" CELdek C3 - Evap. Cooler - Freezestat w/o Time Delay L1 ­C4 - Evap. Cooler - 8" GLASdek C5 - Evap. Cooler - 12" GLASdek L4 ­D1 - Time Clock - 7 Day D2 - Time Clock - 24 Hour M2 ­ M3 ­E1 - Clogged Filter Switch M4 ­E2 - G.F.I. Convenience Outlet 115VAC M5 ­E3 - Remote Control Panel E4 - Manual Blower Switch
F1 - Ductstat - One Stage
Ductstat - Two Stage R1 - Field Installed VFD
F2 ­ R2 -
Thermostat - T87K w/Subbase R3 - VFD Remote Keypad for use w/R1
G1 -
Thermostat - T87K w/Subbase & Guard
G2 -
Thermostat - T834N w/Subbase (Sterling Stat)
G3 -
Thermostat - TB8220U - 7 Day Programmable
G4 -
Thermostat - TH5220D (Two Stage)R7 - 2-Speed VFD Relays
G5 -
Locking Thermostat Cover R8 - 3-Speed VFD Relays
G6 -
Note: All thermostats are Mercury free 0
Z1- Ot
† = Field Installed
A
J4 - Interlock Relay - 24V Coil 4PDT 10A
®
Media K5 - Air Flow Prove Switch (Dwyer 1910-0)
®
Media L2 - 30 Amp, Non-fused Disconnect Switch
®
Media L3 - 60 Amp, Fused Disconnect Switch
Supply Firestat Freezestat w/Time Delay Ambient Lockout
Interlock Relay - 24V Coil DPDT 10A, Plug-in Interlock Relay - 24/115V Coil SPDT 10A
-
Interlock Relay - 24/115/230V Coil DPDT 10A
30 Amp, Fused Disconnect Switch
60 Amp, Non-fuse Disconnect Switch
Vent Caps Adaptor(s) (4"-5" inches) Vertical Concentric Vent Kit Horizontal Concentric Vent Kit
N5 - Service Convenience Package N6 - Double Wall Construction
Factory Installed VFD
R4 - CO2 Sensor - 100% OA†
R5 - CO2 Sensor - Mixed Air†
R6 - Pressure Sensor†
-
None
her (Specify)
*Single furnace capacities 10 through 40 are ETL certifi ed.
— 42 —
NOTES:
— 43 —
XVII. GAS EQUIPMENT START-UP
Customer ____________________________________ Job Name & Number _________________________
PRE-INSPECTION INFORMATION
With power and gas off.
Type of Equip:
Serial Number _________________________ Model Number __________________________ Name Plate Voltage: _____________ Name Plate Amperage: _____________ Type of Gas: Natural LP Tank Capacity ______ lbs. Rating: ______ BTU @ ____ °F
______ kg ______ kw @ ____ °C
Unit Heater Duct Furnace Indoor
Are all panels, doors, vent caps in place? ❐ Has the unit suffered any external damage? Damage ______________________________ ❐ Does the gas piping and electric wiring appear to be installed in a professional manner? ❐ Has the gas and electric been inspected by the local authority having jurisdiction? ❐ Is the gas supply properly sized for the equipment? ❐ Were the installation instructions followed when the equipment was installed? ❐ Have all fi eld installed controls been installed? ❐ Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.
(DO NOT START this equipment unless you fully understand the controls.)
GENERAL
With power and gas off.
Make certain all packing has been removed. Tighten all electrical terminals and connections. Check damper linkages for tightness. Check all fans & blowers for free movement. Check all controls for proper settings. Check all set screws on blowers and bearings. Check belt tightness.
BLOWER
With power on and gas off.
Check voltage L1 _____ L2 _____ L3 _____ Check rotation of main blower. Check motor amps L1 _____ L2 _____ L3 _____ Blower RPM _____________Check air fi lters. (Record quantity & size.)
GAS HEATING
With power and gas on.
Inlet gas pressure. ____ in. W.C. or ____ kPa
Pilot & main burner ignition. Manifold gas pressure. ____ in. W.C. or ____ kPa Cycle on HIGH LIMIT. Cycle fi restat and/or freezestat. Check electronic modulation. Set at: __________ Cycle and check all other controls not listed. Check operation of remote panel. Entering air temp. _____ °F or ____ °C Discharge air temp. (high fi re) ____ °F. or ____ °C External static pressure ____ in. W.C. or ____ kPa Cycle by thermostat or operating control. Combustion reading: Carbon monoxide: _____ PPM
Carbon dioxide: _____ %
— 44 —
Loading...