Sterling EV User Manual

Page 1
IIEVC-6
J30-05401
INSTALLATION SERVICE MANUAL
OUTDOOR ROOFTOP EVAPORATIVE COOLING UNITS
*Unit Type (EV) - Capacity (CA) - (10-40)
Evaporative Cooling systems meet a wide range of heating and ventilating requirements. The Evaporative Cooler may be purchased as an individual unit in four sizes from 800 CFM to 8500 CFM (0.4 to 4.0 m3/s) or, it can be combined with Rooftop Packaged Units (Natural or Power Vented), Air Handlers, or Make-up Air Handlers. In any combination, the Evaporative Cooler will replace the need for 100% Outside Air Inlet Hood.
Evaporative Cooling is the simplest and most-cost effective cooling method without the use of mechanical refrigeration.
FPO
ATTENTION: Read This manual IIEVC, manuals RISM* and RBM*, submittal/data sheets, and all labels attached to the unit carefully before attempting to install, operate, or ser­vice the Evaporative Cooling Unit! Retain this manual for future reference.
Maintain water in sumps by proper microbicidal water treatment to mini­mize the risks of illness caused by Legionella Pneumophila (the bacteria that causes Legionnaire's Disease) and other bacteria. Refer to local codes regar ding any additional treatment or restrictions regarding water supplies and usage.
INSTALLER'S RESPONSIBILITY
Installer Please Note: This equipment has been tested and inspected. It has been shipped
free from defects from our f actory . Ho wever , during shipment and installation, problems such as loose wires, leaks or loose fasteners ma y occur . It is the installer's responsibility to inspect
and correct any problems that may be found.
The model and serial numbers are located on the data plate attached to the side of the cooler. Record this information in the spaces provided below.
Model No. Serial No.
*This manual may also be used for the following: Unit Types (UT) - (RT or PV) Rooftop Arrangements (RA) - (D or E) and Unit Type (UT) - (AH) Rooftop Arrangements (RA) - (P or R) Capacity (CA) - (20 or 40)
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 568-9571 FAX: (413) 562-8437
www.mestek.com
Page 2
RECEIVING INSTRUCTIONS
Inspect shipment immediately after receiving to determine if any damage has occurred during shipment If any damage is found, the consignee should sign the bill of lading, indicating such damage, and immediately fi le claim for damage with the transportation company.
TABLE OF CONTENTS
Description Page
General Information ...........................................Cover, 2
PERFORMANCE & SPECIFICATION DATA Evaporative Cooler - Dimensional
& Performance Data .............................................. 3
CELdek® Media Data and Effi ciency Chart .............3
Gas-Fired Rooftop Packaged Units
with Evaporative Cooler .................................... 4, 5
Air Handler with Evaporative Cooler ......................... 6
PARTS IDENTIFICATION ............................................ 7
INSTALLATION
Mounting to Roof ...................................................... 8
Connecting Water Supply ......................................... 8
Faucet Use ............................................................... 8
Adjusting Water Level and Float Valve ..................... 9
Adjusting Water Flow ................................................ 9
Bleed-Off .................................................................. 9
Electrical Connections ...................................... 10, 11
MAINTENANCE
Maintenance Schedule ........................................... 12
Changing Media ................................................12, 13
Cleaning Water Pump .............................................13
Washing Media ........................................................13
Washing Inlet Filter ..................................................13
Cabinet Cleaning and Touch-up ..............................13
Winter Shut-Down ...................................................13
Evaporative Cooler Curb Assembly Diagram ..........14
Model Number Description ......................................15
Replacement Parts ..................................................15
The following terms are used throughout this manual, in addition to the other requirements, to bring attention to the presence of potential hazards or to important information concerning the product:
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not av oided, ma y result in minor injury or property damage.
NOTICE: Used to notify of special instructions on installation, operation, or maintenance which are important to equipment but not related to personal injury.
Failure to comply with the General Safety Information may result in extensive property damage, severe personal injury, or death.
GENERAL SAFETY INFORMATION
Unless otherwise specifi ed, the following conv ersions may be used for calculating SI/metric unit measurements: 1 lb. = 0.453 kg 1 cubic foot = 0.028m
3
1000 Btu per hour = 0.293 kW 1 foot = 0.305 m 1 inch water column = 0.249 kPa 1 inch = 25.4 mm 1 gallon = 3.785 L 1 psig = 6.894 kPa 1000 BTU/cu. ft. = 37.5 MJ/m
3
1liter/second = CFM x 0.472 meter/second = FPM ÷ 196.8
2
Disconnect all power before installing or servicing the unit. If power disconnect is out of sight, lock it in the open position and ta g it to prevent unexpected application of power. Failure to do so could result in fatal electrical shock or severe personal injury.
Do not alter the unit in any way, or damage to the unit and/or severe personal injury or death may occur.
Do not depend on a thermostat or other switch as a sole means of disconnecting power when installing or servicing unit. Always disconnect power at the main circuit breaker as described above. Failure to do so could result in fatal electrical shock.
Page 3
4"
(102)
8" CELdek® (Optional 12")
2" CELdek®
Overflow
Pump
Ball Valve
1/4" Water Inlet
Float Valve
Bleed-off
Water Distribution Assembly
“A”
Intake Filter
S
S
SECTION S-S
3/4" NPT
Drain
(Capped)
Junction Box
Liquid Tight Electrical Tubing
43"
(1092)
36"
(914)
Figure 1
200
0.5
100%
90%
80%
70%
60%
0.4
0.3
0.2
0.1
Air Velocity - FPM
Evaporative Cooling Efficiency
Air Pressure Drop Inches - WG
300 400 500 600 700 800
12"
8"
8"
12"
Evaporative Cooling Efficiency
Air Pressure Drop
PERFORMANCE AND SPECIFICATION DATA
Evaporative Cooling Units
Capacity
10/15
20/25/50
30/35 60/70
40/80
A
32-7/8"
(835)
43-7/8"
(1114)
54-7/8"
(1394)
60-3/8"
(1534)
Table 1 (Refer to individual unit submittals for more specifi cations.)
Performance and Dimensional Data
8" Saturation 12" Saturation 8" or 12" Media Pressure Drop “A” Unit Shipping Operating CFM Effi ciency Effi ciency Face Area Size in W.C. Width Wt. Wt. (cu. m/s) (cu. m/s) Range Range Ft. *Capacity MIN. MAX. MIN. MAX. MIN. MAX. (m
10,15 800 4,500 78 88 89 92 7.01 31 x 32-9/16 0.03 0.23 32-3/4 137 301 (0.378) (2.124) (0.65) (787 x 827) (0.01) (0.06) (832) (62) (136) 20, 25, 50 1,600 5,500 77 88 88 92 9.38 31 x 43-9/16 0.03 0.20 43-3/4 166 386 (0.755) (2.596) (0.87) (787 x 1106) (0.01) (0.05) (1111) (75) (175) 30, 35, 60, 70 2,400 8,500 77 86 88 92 11.75 31 x 54-9/16 0.05 0.30 54-3/4 192 468 (1.133) (4.012) (1.09) (787 x 1386) (0.01) (0.07) (1391) (87) (212)) 40, 80 3,200 8,500 77 86 87 92 12.92 31 x 60 0.07 0.28 60-1/4 206 509 (1.510) (4.012) (1.20) (787 x 1524) (0.02) (0.07) (1530) (93) (231) *Capacities - (50, 60, 70 and 80) are for Dual Furnace Unit Types only.
2
in. (kPa) (kPa) in. lb. lb.
2
) (mm) MIN. MAX. (mm) (kg) (kg)
CELdek® EVAPORATIVE MEDIA
The Evaporative Cooler utilizes high effi ciency CELdek® media. CELdek® is made from a special cellulose paper, impregnated with insoluble anti­rot salts and rigidifying saturants. The cross fl uted design of the pads induces highly-turbulent mixing of air and water for optimum heat and moisture transfer. The evaporative coolers are available with standard 8 or optional 12 inch media which produce high effi ciency and high face velocities, along with a 2" distribution pad to disperse the water evenly over the pads.
Figure 2
3
Page 4
Rooftop Packaged Unit
D4163 T4160BD
B
Discharge
Opening
1-5/16" (33) Typ. Anchor Hole Location
5"
(127)
A
C (Typ. Sq.)
*
F
D
39"
(991)
G
Outside
1" (25)
Curb Cap
5/8" (16) Typ. Anchor Hole Location
6-1/16"
(154)
8-3/4 (222)
26"
(660)
Electrical Connections
Vent Caps Are Shipped In Separate Cartons
Gas Connection
§
L
Evaporative Cooler
18-7/8" (479)
x J Typ.
O.S. Damper
Opening
6-1/2"
(165)
36"
(914)
C
L
1-1/8" (29)
Typ. Duct
Flange
1" (25)
Typ.
19"
(483)
Discharge
Opening
10-1/8"
(257)
§
U (Capacities 10/40)
§
U (Capacities 50/80)
36"
(914)
with Evaporative Cooling
Figure 3 - Natural Vent Rooftop Unit with Evaporative Cooler (without Supply Plenum)
Table 2A
A.G.A. C.G.A. GAS INLET CAPACITY A B C D D *F G ▲J L §U NAT LP
10 32-7/8 15-9/16 12 11 20-11/16 19-3/8 31-1/16 24 77-3/8 72-1/4 1/2 1/2 (835) (395) (305) (279) (525) (492) (789) (610) (1965) (1835) 15 32-7/8 18-5/16 21-1/2 16 25-3/16 23-1/2 31-1/16 24 77-3/8 72-1/4 1/2 1/2 (835) (465) (546) (406) (640) (597) (789) (610) (1965) (1835) 20 43-7/8 23-13/16 23-1/2 16 25-3/16 26-1/4 42-1/16 35 77-3/8 72-1/4 1/2 1/2 (1114) (605) (597) (406) (640) (667) (1068) (889) (1965) (1835) 25 43-7/8 29-5/16 23-1/2 16 25-3/16 34-1/2 42-1/16 35 77-3/8 72-1/4 3/4 1/2 OR 3/4 (1114) (745) (597) (406) (640) (876) (1068) (889) (1965) (1835) 30 54-7/8 34-13/16 26 17-1/2 26-11/16 37-1/4 53-1/16 46 77-3/8 72-1/4 3/4 1/2 OR 3/4 (1394) (884) (660) (445) (678) (946) (1348) (1168) (1965) (1835) 35 54-7/8 40-5/16 26 17-1/2 26-11/16 45-1/2 53-1/16 46 77-3/8 72-1/4 3/4 1/2 OR 3/4 (1394) (1024) (660) (445) (678) (1156) (1348) (1168) (1965) (1835) 40 60-3/8 45-13/16 26 17-1/2 26-11/16 51 58-9/16 51-1/2 77-3/8 72-1/4 3/4 1/2 OR 3/4 (1534) (1164) (660) (445) (678) (1295) (1487) (1308)
50 43-7/8 29-5/16 23-1/2 16 25-3/16 34-1/2 42-1/16 35 103-3/8 98-1/4 3/4 1/2 OR 3/4
(1114) (745) (597) (406) (640) (876) (1068) (889) (2626) ( 60 54-7/8 34-13/16 26 17-1/2 26-11/16 37-1/4 53-1/16 46 103-3/8 98-1/4 3/4 1/2 OR 3/4 (1394) (884) (660) (445) (678) (946) (1348) (1168) (2626) ( 70 54-7/8 40-5/16 26 17-1/2 26-11/16 45-1/2 53-1/16 46 103-3/8 98-1/4 3/4 1/2 OR 3/4 (1394) (1024) (660) (445) (678) (1156) (1348) (1168) (2626) ( 80 60-3/8 45-13/16 26 17-1/2 26-11/16 51 58-9/16 51-1/2 103-3/8 98-1/4 3/4 1/2 OR 3/4 (1534) (1164) (660) (445) (678) (1295) (1487) (1308) (2626) (2496)
NOTE: REFER TO UNIT SUBMITTALS FOR MORE SPECIFICATIONS/UNIT ARRANGEMENTS. DIMENSIONS ARE IN INCHES, DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS. * “F” DIMENSION IS THE RECOMMENDED CLEARANCE TO SERVICE THE BURNER DRAWER(S). ▲“J” DIMENSION IS AN OUTSIDE DIMENSION FOR RETURN AIR DAMPERS.
§ “U” ALL DIMENSIONS ARE TABULATED FOR ROOFTOP ARRANGEMENTS B & D PER CAPACITIES 10 THROUGH 80 ACCORDINGLY (CAPACITIES 50/80 ARE SHOWN PICTORIALLY). NATURAL VENT UNIT DIMENSIONS SHOWN ABOVE; FOR POWER VENT DIMENSIONS, CONTACT CUSTOMER SERVICE FOR POWER VENT UNIT SUBMITTAL SHEETS.
4
(1965) (1835)
2496)
2496)
2496)
Page 5
Rooftop Packaged Unit
J Inside
Supply Opening
1-5/16" (33) Typ. Anchor Hole Location
5"
(127)
A
C (Typ.) Sq.
*
F
C
L
D
39"
(991)
G
1" (25)
Curb Cap
D4165 T4160CE
5/8" (16) Typ. Anchor Hole Location
6-1/16"
(154)
Vent Caps Are Shipped In Separate Cartons
Gas Connection
6-1/16"
(154)
Evaporative Cooler
18-7/8" (479)
x J Typ.
Inside
Opening
34-3/4"
(883)
26"
(660)
18-7/8" (479)
x J Typ.
O.S. Damper
Opening
6-1/2"
(165)
3-9/16"
(90)
Lifting Brackets
Electrical Connections
Outside
§
R
§
Q
§
L
§
U
26"
(660)
26"
(660)
36"
(914)
with Evaporative Cooling
Figure 4 - Natural Vent Rooftop Unit with Evaporative Cooler (with Supply Plenum)
Table 2B
A.G.A. C.G.A. GAS INLET CAPACITY A C D D *F G ▲J L Q R §U NAT LP
10 32-7/8 12 11 20-11/16 19-3/8 31-1/16 24 103-3/8 NA NA 98-1/4 1/2 1/2 (835) (305) (279) (525) (492) (789) (610) (2626) (2496) 15 32-7/8 21-1/2 16 25-3/16 23-1/2 31-1/16 24 103-3/8 NA NA 98-1/4 1/2 1/2 (835) (546) (406) (640) (597) (789) (610) (2626) (2496) 20 43-7/8 23-1/2 16 25-3/16 26-1/4 42-1/16 35 103-3/8 NA NA 98-1/4 1/2 1/2 (1114) (597) (406) (640) (667) (1068) (889) (2626) (2496) 25 43-7/8 23-1/2 16 25-3/16 34-1/2 42-1/16 35 103-3/8 NA NA 98-1/4 3/4 1/2 OR 3/4 (1114) (597) (406) (640) (876) (1068) (889) (2626) (2496) 30 54-7/8 26 17-1/2 26-11/16 37-1/4 53-1/16 46 103-3/8 NA NA 98-1/4 3/4 1/2 OR 3/4 (1394) (660) (445) (678) (946) (1348) (1168) (2626) (2496) 35 54-7/8 26 17-1/2 26-11/16 45-1/2 53-1/16 46 103-3/8 NA NA 98-1/4 3/4 1/2 OR 3/4 (1394) (660) (445) (678) (1156) (1348) (1168) (2626) (2496) 40 60-3/8 26 17-1/2 26-11/16 51 58-9/16 51-1/2 103-3/8 NA NA 98-1/4 3/4 1/2 OR 3/4 (1534) (660) (445) (678) (1295) (1487) (1308) (2626) (2496) 50 43-7/8 23-1/2 16 25-3/16 34-1/2 42-1/16 35 129-5/16 58-3/4 38-5/8 124-1/4 3/4 1/2 OR 3/4 (1114) (597) (406) (640) (876) (1068) (889) (3285) (1492) (981) (3156) 60 54-7/8 26 17-1/2 26-11/16 37-1/4 53-1/16 46 129-5/16 58-3/4 38-5/8 124-1/4 3/4 1/2 OR 3/4 (1394) (660) (445) (678) (946) (1348) (1168) (3285) (1492) (981) (3156) 70 54-7/8 26 17-1/2 26-11/16 45-1/2 53-1/16 46 129-5/16 58-3/4 38-5/8 124-1/4 3/4 1/2 OR 3/4 (1394) (660) (445) (678) (1156) (1348) (1168) (3285) (1492) (981) (3156) 80 60-3/8 26 17-1/2 26-11/16 51 58-9/16 51-1/2 129-5/16 58-3/4 38-5/8 124-1/4 3/4 1/2 OR 3/4 (1534) (660) (445) (678) (1295) (1487) (1308) (3285) (1492) (981) (3156)
NOTE: REFER TO UNIT SUBMITTALS FOR MORE SPECIFICATIONS/UNIT ARRANGEMENTS. DIMENSIONS ARE IN INCHES, DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS. * “F” DIMENSION IS THE RECOMMENDED CLEARANCE TO SERVICE THE BURNER DRAWER(S).
“J” DIMENSION IS AN OUTSIDE DIMENSION FOR RETURN AIR DAMPERS. “J” DIMENSION IS ALSO AN INSIDE DIMENSION FOR SUPPLY AIR (WITHOUT DAMPER).
§ “U” ALL DIMENSIONS ARE TABULATED FOR ROOFTOP ARRANGEMENTS C & E PER CAPACITIES 10 THROUGH 80 ACCORDINGLY (CAPACITIES 50/80 ARE SHOWN PICTORIALLY).
NATURAL VENT UNIT DIMENSIONS SHOWN ABOVE; FOR POWER VENT DIMENSIONS, CONTACT CUSTOMER SERVICE FOR POWER VENT UNIT SUBMITTAL SHEETS.
5
Page 6
Air Handler Packaged Unit
18-7/8" (479)
x J Typ.
Damper
Opening
39"
(991)
5"
(154)
1" (25) Curb Cap
5/8" (16) Typ. Anchor Hole Location
6-1/16"
(154)
72"
(1829)
51-1/2"
(1306)
6-1/2"
(165)
36"
(883)
Electrical Connections
Evap. Cooler
19" (483)
x B
Discharge
Opening
10-1/8"
(257)
A
Water Inlet 1/4"
Overflow
3/4" Npt Drain (Capped)
Intake Filter
D3666B T3672FR
1" (25) Typ. Duct Flange
18-7/8" (479)
x J Typ.
Damper Opening
39"
(991)
5"
(127)
1" (25) Curb Cap
6-1/16"
(154)
5/8" (16) Typ. Anchor Hole Location
72"
(1829)
77-3/8"
(1964)
6-1/2"
(165)
36"
(883)
Electrical Connections
Evap. Cooler
19" (483)
x J
Discharge
Opening
6-1/16"
(154)
A
Water Inlet 1/4"
Overflow
3/4" NPT Drain (Capped)
Intake Filter
D3667B T3672FR
with Evaporative Cooling
Figure 5 - Standard Air Handler with Evaporative Cooler (without Supply Plenum)
Table 3
CAPACITY A B C G J
20 43-7/8" 23-13/16" 21-15/16 42-1/16" 35" (1114) (605) (557) (1068) (889) 40 60-3/8" 45-13/16" 30-3/16" 58-9/16" 51-1/2" (1534) (1164) (767) (1487) (1308)
NOTE: REFER TO UNIT SUBMITTALS FOR MORE SPECIFICATIONS/UNIT ARRANGEMENTS. DIMENSIONS ARE IN INCHES, DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS.
“J” DIMENSION IS AN OUTSIDE DIMENSION FOR RETURN AIR DAMPERS. “J” DIMENSION IS ALSO AN INSIDE OPENING FOR SUPPLY AIR (WITHOUT DAMPERS)
Figure 6 - Standard Air Handler with Evaporative Cooler (with Supply Plenum)
6
Page 7
16
15
EVAPORATIVE COOLER PARTS IDENTIFICATION
32
4
5
14
13
6
7
8
9
10
11
112
1. Bulk Head Fitting (Drain Overfl ow)
2. Water Distribution Assembly
3. Clip Assembly (Water Distribution
Assembly)
4. Ball Valve
5. Line Filter
6. Brass Needle Cock Valve
7. Worm Clamp
8. PVC Flexible Hose
9. Pump Support Bracket
10. Pump
11. Poly Tubing - 1/4" O.D.
12. Pump Basket Screen
13. Float Valve
14. Media Pad ( 8" or Opt. 12" W)
15. Media Distribution Pad (2" x 8" x L or 2" x 12" x L)
16. Hood Water Distribution
7
Page 8
INSTALLATION
3-1/4"
FLOAT VALVE
ROD LEVEL ADJUSTMENT SCREW
1/4" TUBING FROM COOLER
FAUCET WITH HOSE BIBB
BRASS NEEDLE COCK
BRASS STOP COCK WITH DRAIN
WATER SUPPLY
ROOF LINE
NUT AND FERRULE
D3870
This manual is for Evaporative Cooler Module Installations only.
Refer to the Installation and Service Manuals for Rooftop Packaged Units
and Outdoor Furnaces for these unit installations.
Mounting to Roof
1. Before positioning the unit in its permanent location, make certain that the roof is capable of carrying the load of this equipment. Note that when the cooler is fi lled with water, the unit will be much heavier than when dry . See “Performance and Dimension Data” table for appropriate operating weight.
2. If unit is to be mounted on a curb, refer to the curb specifi cations for installation requirements.
3. Make cer tain that the mounting surface is level in all directions.
4. Make certain that you have suffi cient means for lifting the unit into place.
5. Installation must conform to local and national building and safety codes.
6. The units are mounted on skid rails and are suitab le for use on combustible fl ooring. It is recommended that the skids be mounted either on solid planking or on steel channels, but nev er on a soft tar roof where the skids could sink and reduce the 4" clearance between the bottom pan and the roof.
7. Inspect all internal parts of the cooler section to determine if any damage has occurred during shipment. See roof curb specifi cations at the end of the manual.
Connecting the Water Supply
NOTICE: Soft water equipment should not be attached to water lines going to the cooler. “Soft Water” will cause corrosion and decrease the effective life of the cooler.
Figure 7 - Float Valve Assembly
NOTICE: There will be a slight odor during the initial start-up of the unit. The odor will disappear within the fi rst few days of operation if the bleed-off is adjusted correctly.
Faucet Use
1. To connect the water line to the water supply, install a sillcock and water valve on the faucet.
2. Place tubing nut and ferrule on tube end, and insert valve.
3. Tighten the nuts on the valve and the tube.
NOTICE: If a faucet is not to be used for the water supply, install the valve on the water line to be used. Follow the procedure above for securing the tubing to the valve.
Figure 8 - Evaporative Cooler Water Connections
1. A water valve should be installed at a convenient
2. Place tube nut and ferrule over the end of the
3. Insert tubing into factory-installed fl oat valve and
location to allow water to be turned on and off. Use 1/4" tubing to supply water to Evaporative Cooler. A water connector kit is available at your local wholesaler.
tubing. tighten securely.
8
Page 9
Adjusting the Water Level and Float Valve
Fill the tank as follows:
1. Turn the water supply on. Fill the tank to a depth of approximately 3.25" (82.6mm). While fi lling the tank, check for good pressure and fl ow from the fl oat valve.
2. The fl oat valve should shut down the water supply at the 3.25" (82.6mm) level. It may be necessary to adjust the fl oat valve by bending the rod. The rod level adjustment screw should be set in lower notch on lever.
3. Check the tank and all connections for leaks.
NOTE: The overfl ow fi tting is set so that the water will begin to fl ow at the 3.25" (82.6mm) depth. It is important that the water level not be above the pump basket screen!
Adjusting the Water Flow
Proper water flow over the media is important. Insufficient water flow will result in increased accumulation of minerals on the media. Excessive water fl ow will result in deterioration of the media and moisture carryover.
1. Using the ball valve handle, adjust the water fl ow so that the media is damp from the top to the bottom. If you can see water fl owing on the entering side, your water level is too high. Adjust the valve so that the media is just damp on the entering side. Repeated drying of the media will cause rapid buildup of mineral deposits in the media. Drying is due to improper adjustment of the water fl ow valv e, frequent shut-down of the pump to control the evaporative cooling/humidifi cation, or localized air velocities across the surface of the media. The area where dry spots occur will exhibit high mineral deposits. The valve must be adjusted so that no dry spots appear on entering or leaving side, and when adjusted correctly, enough water will fl ow through the media to wash out most of the airborne dirt and other debris.
2. Prior to start-up, it is recommended that the tank be fi lled, and the pump turned on, allowing the unit to run for approximately 10 minutes. Repeat this procedure two times to help fl ush any dirt that may have accumulated during shipping.
Bleed-Off
Bleed-Off is required to maintain the water quality of the system. When water evaporates, minerals and other impurities are left behind, impurities are scrubbed from the air fl owing through the system, and make-up water (even good quality make-up water) adds more minerals and impurities. These form deposits on the media during the evaporative process.Therefore, it is important to bleed-off a small quantity of recirculating water to keep the concentration of impurities under control. The bleed-off rate required is dependent upon the quality of the water used and the rate of evaporation. As climate conditions change, the rate of evaporation may increase, requiring an increase in the bleed-off rate. It is recommended that the bleed-off rate be adjusted for the maximum water evaporation. An indication of insuffi cient bleed-off is a uniform build-up of minerals on the entering air face of the media. If this condition is observed, increase the rate of bleed-off until the mineral deposits dissipate.
Adjusting the Bleed-Off
1. The bleed-off is attached to the PVC tee. This bleed-off system will eliminate a small quantity of water from recirculation, which will reduce scale build-up. This water will drain through the attached tube, and out through the overfl ow. Disposal of this water should comply with local codes.
2. Adjust the bleed-off rate according to Table 4.
Table 4
Unit Size Seconds to Fill Capacity 12 oz. Can
10/15 69 46 20/25/50 52 34 30/35/60/70 41 27 40/80 38 25
9
Page 10
ELECTRICAL CONNECTIONS
HAZARDOUS VOL TAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
Refer to the unit data plate to determine the supply voltage.
Do not service before disconnecting power or there could be a potential for an electrical shock hazard.
The motor name-plate and electrical rating on the transformer should be checked before energizing the unit electrical system. All external wir ing must conform to ANSI/NFPA No. 70-1996, National Electrical Code (or the latest edition of) and applicable local codes; in Canada, to the Canadian Electrical Code, Part 1 CSA Standard C22.1
“Dashed” lines represent either fi eld wiring (by others) or optional equipment. Ref er to optional items (shown on wir­ing diagram included with unit) - these will be hard wired.
Do not jumper factory wiring. Mis-wiring of safety circuits may result in fi r e or death.
Do not use any tools (i.e. screwdriver, pliers, etc.) acr oss the terminals to chec k f or po wer. Use a voltmeter.
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. Failure to do so may cause damage to the equipment.
It is recommended that the electrical power to each unit be provided by a separate, fused, and permanently live electrical circuit. A disconnect switch of suitable electrical rating for each unit should be placed as close to the controls as possible. Each unit must be electrically grounded in accordance with the latest edition of the National Electrical Code, ANSI/NFPA No. 70-1996, or CSA Standard C22.1. Sample wiring connections are depicted in Figures 9 & 10.
NOTICE: Consult the factory before making any changes to factory wiring.
OPTIONAL FILL AND DRAIN KIT: Optional Evaporative
Cooler Fill and Drain Kit consists of two motorized valv es, installed in the building, and piped and wired to the roof. The kit eliminates the need to go to the roof to fi ll or drain the cooler for seasonal changeover, and automatically maintains the water level. See sample Figure 10. Refer to the kit's instruction.
GROUNDING: Install a ground wire to suitable ground according to local codes.
NOTICE: For all wiring connections, refer to the wiring diagram shipped with the unit (either affi xed to the side jacket or enclosed in the unit’ s installation instruction envelope). Should any original wire supplied with the unit have to be replaced, it m ust be replaced with wiring material having a temperature rating of at least 105°C.
10
Page 11
ELECTRICAL CONNECTIONS (continued)
Figure 9
Figure 10
11
Page 12
MAINTENANCE
Open all disconnect switches and secure in that position before servicing unit. Failure to do so may result in personal injury or death from electrical shock.
Because of the nature of the evaporative process, algae buildup, biological f ouling, scale build-up, and corrosion are distinct possibilities. Proper water treatment and regularly scheduled maintenance will minimize or eliminate most problems. a.) Cooling Pad Check List: √ Reduce the number of on/off cycles. √ Shade the pads and pump. √ Dry pads out completely once every 24 hours. √ Maintain a suitable water bleed-off rate. √ Drain and disinfect the entire water system quarterly. √ Avoid harmful contaminants, including dust, fumes, harsh cleaners, and water treatment chemicals. √ Circulate the recommended quantity of water over the pads. √ Avoid dry areas on the pads. √ Clean the fi lters regularly. b.) Controlling Algae: Scale and mineral deposits can form on the cooling pad because the mineral content of the water is too high.
Increase the water fl ow over the face of the pads. Make certain that the fl ow of water is even from
one end of the distribution pipe to the other end. Clean and fl ush the distributor pipe regularly;
especially if dry areas appear on the pads. Maintain the pH of the recirculating water
between 6 and 8. Maintain suffi cient bleed-off rate. For more details, check MUNTERS
®
Engineering
Bulletin EB-WTM-502 (included with this manual).
c.) Preventing Algae in the Evaporative Pads: Algae needs light, moisture, and nutrients
to survive. Eliminating, or reducing, these elements will help to control algae. For specifi c details, see MUNTERS® Engineering Bulletin EB-WTM-502 (included with this manual).
d.) Biological Fouling Control: Uncontrolled growth of organic matter can lead to
plugged media, metal deterioration, and biologi­cal contamination of the airstream. Whenever the possibility of biological contamination of water in an airstream exists, transmittal of Legionnaire’s Disease should be addressed. While there are no reported cases of Legionnaire’s Disease as­sociated with rigid media type evaporativ e cooling systems, the Legionella Pneumophila bacteria is present in almost all water supplies. Howe v er , the mere presence of the bacteria does not create a hazard: the bacteria must be transmitted as an aerosol in suffi cient densities to be infectious.
NOTICE: It is highly recommended that the services of a water treatment company be retained to advise on the proper treatment of the sump water for biological, scale, and corrosion control. For more information, see MUNTERS
®
Engineering Bulletin
EB-WTM-502 (included with this manual).
Maintenance Schedule
Regular maintenance is the key to successful service from your Evaporativ e Cooler. Use the f ollowing schedule as a guide to maintain you unit:
Maintenance Annual Annual
Requirements Start-Up Shut-Down Changing Media At Beginning of 6th Year or if Passages are blocked Cleaning Water Pump Cleaning & Touch-Up Adjusting Bleed-Off Periodic Inspection During Cooling During Cooling Season Season Washing Down As Required During Media with Hose Season Washing Inlet Filter with Hose Drain Unit
Following are e xplanations of the procedures outlined in the above schedule.
Changing the Media
This should be done every 5 years or if passages become blocked.
1. Remove fi lter/frame assemblies.
2. Disconnect the water hood panel from the top panel by removing screws.
3. Snap out water distribution system.
4. Remove top media distribution pad.
5. Lift out media sections (Note the position of media with respect to airfl ow. See Figure 11)
12
Page 13
®
45° TYP.
15° TYP.
AIR FLOW
D3883
6. Replace with new CELdek
media sections. (See replacement part section). Aspen and other evaporative media will not work.
7. When re-installing media, be sure all media
sections are installed in the proper direction. See Figure 11.
8. Replace top media distribution pad, water dis-
tribution system, water hood panel, and fi lter/frame assemblies.
Figure 11 - Evaporative Cooling Media Pad Section
Cleaning the Water Pump
Do not allow the pump to topple over or become submerged. Water will damage the pump motor. This is not a submersible pump.
Washing the Media
Avoid splashing water on the blower motor at all times (this could cause electrical problems)!
1. Scale and dust should be washed off the intake side of
the media annually , using a garden hose and nozzle; this will help to unclog passages.
2. Using a stiff brush, lightly br ush the intake edges of
the media. This will not harm the openings, but will remove any hardened scale.
3. Occasionally, there will be a b uild-up of algae or odors.
The best solution for both of these problems is to allow the pads to dry thoroughly on a regular basis. If cooling is not needed at night during the cooling season, allow the blower to run for a few hours after the pump has been shut-down to dry pads daily.
4. During the cooling season, we recommend that
the pads be shut down nightly if possible with the blower running to dry the pads out for a few hours before the unit is shut down.
Washing the Inlet Filter
The pre-fi lter should be cleaned periodically as follows:
1. Turn the four latches and remove filter frame
assemblies.
2. Carefully remove the aluminum fi lters. Wash the fi lters
with warm water and a mild soap, rinse thoroughly.
3. Re-install in unit.
4. If the aluminum mesh fi lters are damaged or cannot
be cleaned, replace the mesh fi lter (See replacement parts section).
Disassemble and clean water pump as follows:
1. Disconnect power.
2. Disconnect the liquid tight connector from the junction box to remove cord and connector.
3. Disconnect the pump mounting bracket and hose.
4. Remove the pump and basket screen.
5. To clean pump, snap out base of the pump; notice the impeller.
6. Using a mild detergent solution, wash all deposits from the impeller and the impeller base plate.
7. Spin the impeller to dislodge any foreign material. Make sure that the impeller spins freely.
8. Carefully snap the impeller and impeller base plate back onto the pump.
9. Wash the pump basket screen using the same detergent solution, and rinsing thoroughly to remove any debris. If unable to clean, replace with a new screen (See replacement part section).
NOTICE: The pump motor does not require any lubrication.
Cabinet Cleaning and Touch-Up
The cabinet and all internal parts of the Evaporative Cooler should be cleaned annually using a soft cloth, warm water, and a mild cleanser.
NOTE: Avoid using steel wool or sandpaper in normal cleaning of the unit.
Winter Shut Down
1. Clean and fl ush out Evaporative Cooler media and sump.
2. Clean water distributor holes.
3. Drain fi ll pipe and leave open. DO NOT LEAVE ANY WATER IN THE SYSTEM. FREEZING CAN CA USE MAJOR DAMAGE TO THE UNIT.
4. Remove and clean pump if necessary.
5. Check sump tank for leaks and repair if necessary. Sump tank is fabricated from stainless steel.
13
Page 14
Roof Curb Kit - RC015* (-1, -2, -3, -4)
For use with:
Unit type (UT) - EV
Capacities (CA) - 10/40
*Evaporative Cooler Platform Only
(Included with Roof Curb Kit No's RC002, RC004, RC008, RC012)
Roof Curb Kit RC015 Contents:
1 Evaporative Cooler Assembly (sold separately) 2 Curb (2 platforms per kit) 3 1/4-20 “KEPS” Nut (8) required 4 1/4-20 x 5/8 LG. Hex HD. Bolt (8) required
Club Platform to Unit Assembly
Approximate Curb Kit
Shipping Weight
Curb Kit No. Capacity (CA) Weight (lbs.)
RC015-1 10/15 RC015-2 20/25/50 RC015-3 30/35/60/70 RC015-4 40/80 1 lb. = 0.453 kg
30
*One Platform Kit fi ts All Evaporative Cooler Modules/Capacities (CA) - 10/80
Capacities 50, 60, 70 and 80 are for (RT/PV) unit types only.
14
Page 15
How to order Replacement Parts
Please provide the following information to your local representative:
Model Number
• Serial Number (if any)
• Part Description and Number as shown in Replacement Parts Literature If further assistance is needed, please contact the manufacturer's customer service department.
Evaporative Cooler Model Number Description
Digit E X X — E V 3* 4* 0 0 0 0 0 0 11* 0 0 0 0 16* 17* + Item Prefi x UT CA FT FM RA CO GT GC SV MT MS AI AC AS
(Internal use Only)
*See Model No. Description below.
1, 2 - Unit Type [UT]
EV - Evaporative Cooler Only
3, 4 - Capacity [CA]
10 - 100,000 BTU/HR 15 - 150,000 BTU/HR 20 - 200,000 BTU/HR 25 - 250,000 BTU/HR 30 - 300,000 BTU/HR 35 - 350,000 BTU/HR
40 - 400,000 BTU/HR
5 - Furnace Type [FT]
0 - None
6 - Furnace Construction Material [FM]
0 - None
7 - Rooftop Arrangement [RA]
0 - None
8 - Coil Options [CO]
0 - None
9 - Gas Type [GT]
0 - None
10 - Gas Control [GC]
0 - None
11 - Supply Voltage [SV]
1 - 115/1/60 2 - 208/1/60
3 - 230/1/60
12 - Motor Type [MT]
0 - None
13 - Motor Sizes [MS]
0 - None
14 - Air Inlet Confi guration [AI]
0 - None
15 - Air Control & Damper Arrangement [AC]
0 - None
16 - Accessories [AS]
C1 - Evap. Cooler - Fill & Drain Kit C2 - Evap. Cooler - 12" Celdek C3 - Evap. Cooler - Freezestat
D1 - Time Clock - 7 Day D2 - Time Clock - 24 Hour
E2 - G.F .I. Conv enience Outlet 115V AC E3 - Remote Control Panel
F1 - Ductstat - One Stage F2 - Ductstat - T wo Stage
G1 - Thermostat - T87F w/Subbase G2 - Thermostat - T87F w/Subbase & Guard G3 - Thermostat - T834H w/Subbase (Sterling Stat) G4 - Thermostat - T7300 - 7 Day Programmable G5 - Thermostat - T874 (T wo Stage)
H1 - Return Firestat H2 - Supply Firestat H3 - Freezestat
L1 - 30 Amp, Fused Disconnect Switch L2 - 30 Amp, Non Fused Disconnect Switch L3 - 60 Amp, Fused Disconnect Switch L4 - 60 Amp, Non Fused Disconnect Switch
0 - Other (Specify)
®
Media
LIMITED W ARRANTY
The complete unit is warranted by the manufacturer to be free from defects in material and workmanship for a period of one (1) year from the date of manufacture.
The manufacturer will repair or replace, at its option, any component which, upon inspection, it fi nds to be defective, provided that the unit has been operated within its listed capacity, has been installed in accordance with the furnished instructions, has not been misused or subjected to negligence and has received reasonable and necessary maintenance. The warranty does not cover labor costs or other costs incurred in repairing, removing, installing, servicing or handling of parts or completed products.
The warranty does not cover loss due to corrosion by chemicals precipitated in the air such as halogenated hydrocarbons. The manufacture will in no event be liable for incidental or consequential damages of any kind whatsoever.
Written permission is required prior to the return of defective components. All returns must be sent with all transportation charges prepaid to the plant designated in the written permission.
This warranty is extended only to the original owner of the unit.
15
Page 16
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 568-9571 FAX: (413) 562-8437
www.mestek.com
Loading...