STEINEL US Oneway COM2-24, US Quattro COM2-24, US Oneway DIM-24, DT Quattro COM2-24, DT Quattro COM1-24 User Manual

...
US Quattro COM1-24 US Quattro COM2-24
US Quattro DIM-24
DT Quattro COM1-24 DT Quattro COM2-24
DT Quattro DIM-24
US Quattro US Oneway
DT Quattro
US Hallway
US Oneway DIM-24
US Hallway COM1-24 US Hallway COM2-24
US Hallway DIM-24
Information
FR EN
- 2 -
Assembly / Installation / Dimensional Drawings
l
b
a
Load module
Sensor module
Mounts to a 4" Square box, 4" Octagon box or Round 3.0 Mud-Ring
120
US Quattro / DT Quattro
US Oneway / US Hallway
120
a
Mounts directly to ceiling with quick mount spring tabs
120
120
120
41
36
61
120
61
6
120
Ø min. 68 mm (2 11/16 in)
max. 76 mm (3 in)
120
26
- 3 -
US Quattro COM2-24 / DT Quattro COM2-24 / US Oneway COM2-24 / US Hallway COM2-24
Light level setting See page 18
Occupancy time delay setting See page 18
HVAC stay-'ON' time See page 19
HVAC switch-'ON' delay See page 19
e f g
d
d
c
h
k
k
Reach setting See page 19, 20
i
- 4 -
US Quattro DIM-24 / DT Quattro DIM-24 / US Oneway DIM-24 / US Hallway DIM-24
e f m
d
d
k
k
c
Light level setting See page 18
Occupancy time delay setting See page 18
Stay 'ON' time DIM before 'OFF' See page 19
Reach setting See page 19, 20
i
EN
- 5 -
US Quattro COM1-24 / DT Quattro COM1-24 / US Oneway COM1-24 / US Hallway COM1-24
Light level setting See page 18
Occupancy time delay setting See page 18
Reach setting See page 19, 20
e f i
d
d
c
k
k
EN
- 6 -
L
Disconnect the power supply
before attempting any work on the sensor!
L
Before installation, make sure
that power has been switched off at the breaker and check that the circuit is dead with a voltage tester.
L
Installing the sensor involves
work on the line voltage power supply. This work must there
­fore be carried out profession­ally in accordance with the applicable Nation Electrical Codes and electrical operating conditions.
L
Control output DIM-24
(1-10 V) must only be used for connecting electronic ballasts with an electrically isolated 10V dimming control input.
System Components
a
Load module
b
Sensor module
c
Sensor control plate
d
Sensor DIP switch settings
(1) Normal / Test mode
(2) Manual 'ON' / Automatic
'ON' mode
(3) Momentary / Maintained
switch option
(4) 'ON' only / 'ON'&'OFF'
manual switching
(5) Constant light level DIM
control option (6)(7)(8) Trigger mode
(DT Quattro only)
e
Light level setting
f
Occupancy time delay setting
Switching output 1
g
HVAC stay-'ON' time Switching output 2
h
HVAC switch-'ON' delay Switching output 2
i
Reach setting
10.1
COM1-24 Wiring
10.2
COM2-24 Wiring
10.3
COM2-24 Multiple Sensor Wiring
10.4
DIM-24 Wiring
10.5
DIM-24 Multiple Sensor Wiring
k
Locking mechanism
l
Assembly / Installation /
Dimensional Drawings
m
Stay 'ON' time DIM before
'OFF' option
n
Trigger mode options
Assembly/Installation (see chart on page 2)
For indoor use only.
Sensor and load modules come preassembled and must be sepa­rated for access to the commis­sioning settings on the backside of sensor module by opening the locking tabs k on the sides.
Reconnect and seat the sensor to the load module and secure the locking tabs
k
for normal
operation.
Accessories:
- WGC Wire Guard Cage
- RC 3 Service Remote
- RC 4 User Remote
Operating Instructions
Installer:
This product has been manu­factured and 100% quality tested.
Please read all of the instructions before installation. This will help you to be familiarized with all the features and options available to you with these devices.
This will also assist you to mini
­mize installation time and provide maximum energy savings and trouble-free operation.
Safety Warnings
l
- 7 -
How it Works / Basic Function
The Control Pro DT Quattro and Ultrasonic presence detector product familiy is intended to control lighting and HVAC in commercial buildings, schools, public building, etc.
Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output on the (COM2-24) is signaled in relation to only the presence of motion.
Commissioning adjustments are made by potentiometer or dip switch settings on the sensor or by the optional (RC3 service remote) commissioning tool.
US Quattro COM1-24 DT Quattro COM1-24
US Oneway COM1-24 US Hallway COM1-24
1 switching output (COM1-24 Low Voltage) operating in relation to the detection of motion and ambient light level.
Settings:
- Light level setting
- Occupancy time delay, Pulse mode, IQ mode
US Quattro COM2-24 DT Quattro COM2-24
US Oneway COM2-24 US Hallway COM2-24
1 low voltage switching output operating in relation to the detection of motion and ambient light level. An additional isolated normally open and normally closed set of dry contact closures for signaling HVAC (heating/venti
­lation/airconditioning) in relation only to the presence of persons.
Settings:
- Light level setting
- Occupancy time delay,
Pulse mode, IQ mode
- HVAC stay-'ON' time
- HVAC switch-'ON' delay,
Auto-HVAC mode
US Quattro DIM-24 DT Quattro DIM-24
US Oneway DIM-24 US Hallway DIM-24
1 low voltage switching output operating in relation to the detection of motion and ambient light level. An additional isolated 1-10 volt dimming output operat
­ing in relation to the amount of daylight present.
Settings:
- Light level setting
- Occupancy time delay, IQ mode
- Stay 'ON' time DIM before 'OFF'
- Constant light level DIM
control option
EN