STEINEL HF 360 COM1 AP, HF 360 DIM, HF 360 COM 2, DUAL HF COM 1 AP, DUAL HF DIM Information

...
Page 1
110028877 08/2013_E Technische Änderungen vorbehalten.
D STEINEL-Schnell-Service
Dieselstraße 80-84 · 33442 Herzebrock-Clarholz Tel: +49/5245/448-188 · Fax: +49/5245/448-197 · www.steinel.de
A Steinel Austria GmbH
Hirschstettner Strasse 19/A/2/2 · A-1220 Wien Tel.: +43/1/2023470 · Fax: +43/1/2020189 · info@steinel.at
CH PUAG AG
GB STEINEL U.K. LTD.
25, Manasty Road · Axis Park · Orton Southgate GB-Peterborough Cambs PE2 6UP Tel.: +44/1733/366-700 · Fax: +44/1733/366-701 steinel@steinel.co.uk
IRL Socket Tool Company Ltd
Unit 714 Northwest Business Park Kilshane Drive · Ballycoolin Dublin 15 Tel.: 00353 1 8809120 · Fax: 00353 1 8612061 info@sockettool.ie
F STEINEL FRANCE SAS
ACTICENTRE - CRT 2 · Rue des Famards - Bât. M - Lot 3 F-59818 Lesquin Cedex · Tél.: +33/3/20 30 34 00 Fax: +33/3/20 30 34 20 · info@steinelfrance.com
NL VAN SPIJK AGENTUREN
Postbus 2 · 5688 HP OIRSCHOT · De Scheper 260 5688 HP OIRSCHOT · Tel. +31 499 571810 Fax. +31 499 575795 · vsa@vanspijk.nl · www.vanspijk.nl
B VSA handel Bvba
Hagelberg 29 · B-2440 Geel Tel.: +32/14/256050 · Fax: +32/14/256059 info@vsahandel.be · www.vsahandel.be
L Minusines S.A.
8, rue de Hogenberg · L-1022 Luxembourg Tél. : (00 352) 49 58 58 1 · Fax : (00 352) 49 58 66/67 www.minusines.lu
E SAET-94 S.L.
C/ Trepadella, n° 10 · Pol. Ind. Castellbisbal Sud E-08755 Castellbisbal (Barcelona) Tel.: +34/93/772 28 49 · Fax: +34/93/772 01 80 saet94@saet94.com
I STEINEL Italia S.r.l.
Largo Donegani 2 · I-20121 Milano Tel.: +39/02/96457231 · Fax: +39/02/96459295 info@steinel.it · www.steinel.it
P Pronodis - Soluções Tecnológicas, Lda.
Zona Industrial Vila Verde Sul, Rua D, n.º 11 P-3770-305 Oliveira do Bairro Tel.: +351/234/484031 · Fax: +351/234/484033 pronodis@pronodis.pt · www.pronodis.pt
S KARL H STRÖM AB
Verktygsvägen 4 · S-55302 Jönköping Tel.: +46/36/31 42 40 · Fax: +46/36/31 42 49 · www.khs.se
DK Roliba A/S
Hvidkærvej 52 · DK-5250 Odense SV Tel.: +45 6593 0357 · Fax: +45 6593 2757 · www.roliba.dk
FI Oy Hedtec Ab
Lauttasaarentie 50 · FI-00200 Helsinki Tel.: +358/207 638 000 · Fax: +358/9/673 813 www.hedtec.fi/valaistus · lighting@hedtec.fi
N Vilan AS
Tvetenveien 30 B · N-0666 Oslo Tel.: +47/22725000 · Fax: +47/22725001 · post@vilan.no
GR PANOS Lingonis + Sons O. E.
Aristofanous 8 Str. · GR-10554 Athens Tel.: +30/210/3212021 · Fax: +30/210/3218630 lygonis@otenet.gr
PL "LŁ" Spółka z ograniczoną odpowiedzialnością sp.k.
Byków, ul. Wrocławska 43 · PL-55-095 Mirków Tel.: +48/71/3980861 · Fax: +48/71/3980819 firma@langelukaszuk.pl
CZ ELNAS s.r.o.
Oblekovice 394 · CZ-67181 Znojmo · Tel.: +420/515/220126 Fax: +420/515/244347 · info@elnas.cz · www.elnas.cz
TR EGE SENSORLU AYDİNLATMA İTH. İHR. TİC. VE PAZ. Ltd. STİ.
Gersan Sanayi Sitesi 2305 · Sokak No. 510 TR-06370 Bati Sitesi (Ankara) Tel.: +90/3 12/2 57 12 33 · Fax: +90/3 12/2 55 60 41 ege@egeithalat.com.tr · ww.egeithalat.com.tr
ATERSAN İTHALAT MAK. İNŞ. TEKNIK MLZ. SAN. ve TİC. A.Ş.
Tersane Cad. No: 63 · 34420 Karaköy / İstanbul Tel. +90/212/2920664 Pbx. · Fax. +90/212/2920665 info@atersan.com · www.atersan.com
H DINOCOOP Kft
Radvány u. 24 · H-1118 Budapest Tel.: +36/1/3193064 · Fax: +36/1/3193066 dinocoop@dinocoop.hu
LT KVARCAS
Neries krantine 32 · LT-48463, Kaunas Tel.: +370/37/408030 · Fax: +370/37/408031 · info@kvarcas.lt
EST FORTRONIC AS
Teguri 45c · EST 51013 Tartu Tel.: +372/7/475208 · Fax: +372/7/367229 · info@fortronic.ee
SLO Log-line d.o.o.
Suha pri predosljah 12 · SLO-4000 Kranj Tel.: +386 42 521 645 · Fax: +386 42 312 331 info@log-line.si · www.log.si
SK NECO SK, a.s.
Ružová ul. 111 · SK-01901 Ilava Tel.: +421/42/4 45 67 10 · Fax: +421/42/4 45 67 11 neco@neco.sk · www.neco.sk
RO Steinel Distribution SRL
Parc Industrial Metrom · RO - 500269 Brasov · Str. Carpatilor nr. 60 Tel.: +40(0)268 53 00 00 · Fax: +40(0)268 53 11 11 www.steinel.ro
HR Daljinsko upravljanje d.o.o.
Bedricha Smetane 10 · HR-10000 Zagreb t/ 00385 1 388 66 77 · f/ 00385 1 388 02 47 daljinsko-upravljanje@inet.hr · www.daljinsko-upravljanje.hr
LV Ambergs SIA
Brivibas gatve 195-16 · LV-1039 Riga Tel.: 00371 67550740 · Fax: 00371 67552850 · www.ambergs.lv
BG ТАШЕВ-ГАЛВИНГ ООД
Бул. Климент Охридски № 68 · 1756 София, България Тел.: +359 2 700 45 45 4 · Факс: +359 2 439 21 12 info@tashev-galving.com · www.tashev-galving.com
RUS Датчики, светильники
Представитель в России Сенсорные технологии Телефон:(499)2372868 · www.steinel-rus.ru
CN STEINEL China
Representative Office Shanghai Rm. 21 A-C, · Huadu Mansion No. 838 Zhangyang Road Shanghai 200122 Tel: +86 21 5820 4486 · Fax: +86 21 5820 4212 www.steinel.cn · info@steinel.net
DGBCZSKPLROSLOHRESTLTLVRUSBG
HF 360 COM 1
HF 360 COM1 AP
HF 360 COM 2
HF 360 DIM
DUAL HF COM 1
DUAL HF COM 1 AP
DUAL HF DIM
Information
PC PRO HF360_DualHF_Osteuropa.indd 2-3PC PRO HF360_DualHF_Osteuropa.indd 2-3 11.09.13 10:3511.09.13 10:35
Page 2
- 2 - - 3 -
60
120
12032
B1 B2
Ø 90
44,5
101 120
120
25
22
1
9
98
120
120
120
120
120
120
120
120
LUX
1
6
5
3
2
4
NORM. TEST
AUTO. MAN
ON
ON/OFF
4
NORM. TEST
AUTO. MAN
ON
ON/OFF
LUX
1
6
5
3
2
4
min.
30
sec.
30
IQ
1
min.
15
5
2
9
min.
30
sec.
30
IQ
1
min.
15
5
2
65
LUX
1
6
5
3
2
4
min.
max.
min.
max.
HF 360 COM 1/COM 1 AP / DUAL HF COM 1/ COM 1 AP
COM 1 AP
PC PRO HF360_DualHF_Osteuropa.indd 2-3PC PRO HF360_DualHF_Osteuropa.indd 2-3 11.09.13 10:3611.09.13 10:36
Page 3
- 4 - - 5 -
HF 360 DIM / DUAL HF DIMHF 360 COM 2
5 6 7 89
LUX
1
6
5
3
2
4
1
120
605
min.
t
off
10 30
0
10
7
2
30
sec.
min.
t
on
5
min.
30
sec.
30
IQ
1
min.
15
5
2
NORM. TEST
AUTO. MAN
ON
ON/OFF
4
NORM. TEST
AUTO. MAN
ON
ON/OFF
LUX
1
6
5
3
2
4
min.
1
120
605
0
10
7
2
30 sec.
min.
t
off
min.
t
on
5
10 30
30
sec.
30
IQ
1
min.
15
5
2
min. max.
min.
max.
min.
max.
9
6
5
0
sec.
30
ON
1
min.
15
5
2
15
LUX
1
6
5
3
2
4
30
sec.
30
IQ
1
min.
15
5
2
NORM. TEST
AUTO. MAN
ON
ON/OFF
LUX
1
6
5
3
2
4
min.
NORM. TEST
AUTO. MAN
ON
ON/OFF
4
CONST. ON CONST. OFF
CONST. ON CONST. OFF
30 sec.
30
IQ
1
min.
15
5
2
0
sec.30ON
1
min.
15
5
2
min.
max.
PC PRO HF360_DualHF_Osteuropa.indd 4-5PC PRO HF360_DualHF_Osteuropa.indd 4-5 11.09.13 10:3611.09.13 10:36
Page 4
- 6 - - 7 -
PSN
LL'
PSN
LL'
N
L
Master Master
LN
OUT IN
Treppen­haus­automat
PSN
LL'
PSN
LL'
N
L
Master Slave
PSN
LL'
Slave
14.1
14.1
14.2
14.3
14.4
*
*
*
*
*
*
*
*
*
cable length < 50 m
PC PRO HF360_DualHF_Osteuropa.indd 6-7PC PRO HF360_DualHF_Osteuropa.indd 6-7 11.09.13 10:3611.09.13 10:36
Page 5
- 8 - - 9 -
PSN
L
1-10V
L'
+
N
L
Master Slave
N
L
1-10V
1-10V
PSN
L
1-10V
L'
+
PSN
L
1-10V
L'
+
14.5
HF 360
*
*
cable length < 50 m
PC PRO HF360_DualHF_Osteuropa.indd 8-9PC PRO HF360_DualHF_Osteuropa.indd 8-9 11.09.13 10:3611.09.13 10:36
Page 6
- 20 - - 21 -
How it works / Basic function
The high-frequency presence detectors from the Control PRO range control lighting as well as heating, ventilation and air-con­ditioning (COM 2 only), e.g. in of­fices, WCs, public buildings or at home, in relation to ambient light level and the presence of persons. Modern, high-frequen-
cy technology guarantees that movement is detected absolute­ly anywhere irrespective of radi­ated temperature. Sensing movement in two directions, the DUAL HF sensor is ideal for corri­dors in hotels, schools and office buildings. The presence detec­tor's switching outputs and
reach are set at the potentio­meters and dip switches or by means of the optional remote control. Presence Control has a low intrinsic power consump­tion.
Presence Control PRO HF 360 COM 1 / COM 1 AP
DUAL HF COM 1 / COM 1 AP
1 switching output operating in relation to brightness setting and presence of persons.
Settings:
- Brightness setting
- Stay-'ON' time, pulse mode, IQ mode
Presence Control PRO HF 360 COM 2
1 switching output, such as COM 1. Plus a 2nd switching output for HVAC (heating / ventilation / air conditioning) governed by presence.
Settings:
- Stay-'ON' time
- Switch-'ON' delay
- Room surveillance
Presence Control PRO HF 360 DIM
DUAL HF DIM
1 switching output operating in relation to brightness setting and presence of persons.
Settings:
- Brightness setting
- Stay-'ON' time, IQ mode
- Orientation light
- Constant lighting control
Detection zone
The reach of the HF 360 is electronically adjustable. 1 or 2 detection directions can be masked out for adjustment to the room situation. An angle of cov­erage of 360° provides a max. reach of 8 m.
The DUAL HF sensor has 2 special HF sensors that detect movement from the ceiling in both direc­tions. Controlled electronically, reach is infinitely variable in both directions from 3 x 3 m – 10 x 3 m.
HF 360 mounting height 2.8 m DUAL HF mounting height 2.8 m
Disconnect the power supply
before attempting any work on the sensor!
During installation, the elec-
tric power cable to be con­nected must be dead. There­fore, switch 'OFF' the power first and use a voltage tester to make sure the wiring is off circuit.
Installing the sensor involves
work on the mains power supply. This work must there­fore be carried out profes­sionally in accordance with the applicable national wir­ing regulations and electrical operating conditions (VDE
0100).
It is only permissible to use
electronic ballasts with isolated control signal at the DIM 1-10 V control output.
System components
Load module Sensor module Sensor base Dip switches
(1) Normal/test mode (2) Semi-/fully automatic mode (3) Button/switch (4) 'ON' / 'ON'-'OFF' button (5) DIM option
Constant lighting control 'ON'/'OFF'
Twilight setting Time setting
Switching output 1
HVAC stay-'ON' time
Switching output 2
HVAC switch-'ON' delay
Switching output 2
Reach setting Clamping-type ceiling
adapter, optional
Surface-mounting adapter
IP 54, optional
Locking mechanism Assembly/Installation Parallel-connected
configurations
Stay-'ON' time
Orientation light DIM option
Film shroud for minimising
the detection zone (HF 360).
Assembly/Installation (see chart on page 2)
The sensor is only intended for concealed, indoor installation in ceilings (apart from the COM 1 AP - surface-mounted - option). A clamping-type ceiling adapter or surface-mounting adapter is not included.
Sensor and load module come ready assembled and must be plugged together after fitting the load module and setting the potentiometers/dip switches.
Accessories: Clamping-type ceiling adapter, EAN no.: 4007841 000370 Surface-mounting adapter, EAN no.: 4007841 000363 Guard cage, EAN no.: 4007841 003036 Service remote control, EAN no.: 4007841 000387 User remote control, EAN no.: 4007841 003012
Operating instructions
GB
Dear Customer,
Congratulation on purchasing your new STEINEL presence de­tector and thank you for the confidence you have shown in us. You have chosen a high-qual­ity product that has been manu­factured, tested and packed with the greatest care.
Please familiarise yourself with these instructions before at­tempting to install the presence detector because prolonged, re­liable and trouble-free operation will only be ensured if it is fitted and used properly.
We hope your new STEINEL sensor will bring you lasting pleasure.
Safety warnings
GB
PC PRO HF360_DualHF_Osteuropa.indd 20-21PC PRO HF360_DualHF_Osteuropa.indd 20-21 11.09.13 10:3611.09.13 10:36
Page 7
- 22 - - 23 -
Technical SpecificationsElectrical installation/Automatic mode
In selecting the wiring leads, it is important to meet the wiring regulations laid down in VDE 0100 (see Safety warnings on page 19). The following applies to wiring presence detectors: According to
section 6 of VDE 0100 520, a multi­ple-core lead containing both the mains voltage leads and the con­trol leads (e.g. NYM 5 x 1.52) may be used for wiring between the sensor and electronic ballast. The
mains connection lead must be no greater than 10 mm in diameter. The clamping range of the mains terminal is designed for a maxi­mum of 2 x 1.5 mm
2
or 1 x 2.5 mm2.
PSN
LL'
L
N
P
L
N
COM1
PSN
LL'
L
N
L
N
1-10V
1-10V
+
max. 100 mA
DIM
DIMCOM 1 COM 2
COM 1 AP
GB
Dimensions (w x h x d)
HF 360 120 x 120 x 56 mm
Dual HF
120 x 120 x 76 mm Supply voltage 230 – 240 V, 50 Hz / 60 Hz Capacity, switching output 1
(COM 1/COM 2)
Relay 230 V Resistive load 2000 W max. (cos ϕ = 1) 1000 VA max. (cos ϕ = 0,5)
Electronic ballast: (COM 1/COM 1 AP/ COM 2/DIM)
Max. 'ON' current 800 A/200 μs 30 x (1 x 18 W), 25 x (2 x 18 W) 25 x (1 x 36 W), 15 x (2 x 36 W) 20 x (1 x 58 W), 10 x (2 x 58 W) Pay attention to specific 'ON' currents of electronic ballasts! A relay or contactor must be provided on line side for higher switching capacities.
Capacity, switching output 2 (COM 2 only) (HF 360 only)
Presence
230 W max. / 230 V
1A max. (cos ϕ = 1) for HVAC (heating/ventilation/air-conditioning) Application indoors Mounting height
(mounted to ceiling)
2.5 m – 3.5 m ceiling height
Detection angle HF 360
360° with 140° aperture angle
also through glass, wood and
stud walls. 1 or 2 detection direc-
tions can be masked out for ad-
justment to the room situation.
Dual HF
see diagrams on p. 21 also through glass, wood and stud walls
Reach HF 360
8 m max. all round,
electronically and infinitely
variable
Dual HF
10 x 3 m max. in each direction, electronically and infinitely adjustable
Switching output 1 Time setting
30 sec. – 30 min., pulse mode (approx. 2 sec.)
IQ mode (automatic adjustment to use profile) Switching output 2
Time setting (HF 360 only)
COM2 only for HVAC
0 sec. – 10 min. switch-'ON' delay
1 min. – 2 h stay-'ON' time
Automatic room surveillance
DIM:
Time setting
30 sec. - 30 min.
IQ mode (automatic adjustment to use profile) Control output
1 – 10 V / max. of 50 electronic ballasts, max. of 100 mA Sensor system High-frequency 5.8 GHz, transmission power < 1mW Function setting by
DIP switches
DIP 1 Normal / test mode
DIP 2 Semi- / fully automatic mode
DIP 3 Button / switch mode
DIP 4 'ON' button / 'ON'-'OFF' button
DIP 5 Constant-lighting control 'ON'-'OFF' (DIM) Parallel connections Master/slave
Master/master User-friendly setting capability Teach-in (with optional remote control RC3) Light-level setting 10 – 1000 lux, ∞ / daylight
DIM 100 – 1000 lux IP rating IP 20 (IP 54 with surface-mounted box) Safety class II Temperature range 0° to +40° C Housing UV-resistant, paintable
PC PRO HF360_DualHF_Osteuropa.indd 22-23PC PRO HF360_DualHF_Osteuropa.indd 22-23 11.09.13 10:3611.09.13 10:36
Page 8
- 24 - - 25 -
Functions – Settings by potentiometer
Examples of use Brightness settings
Night-time mode min Corridors, foyers 1 Stairs, escalators, moving walkways 2 Washrooms, toilets, switchrooms, canteens 3 Sales fl oor, kindergartens, nursery school rooms,
sports halls
4
Work environments: Offi ces, conference and mee­ting rooms, precision assembly activities, kitchens
5
Working areas requiring good light: Laboratory, technical drawing, precision work
>=6
Daylight mode max
Stay-'ON' time for switching output 1 Setting 30 sec. – 30 min.
The chosen stay-'ON' time is infi­nitely variable from a minimum of approx. 30 sec. to a maximum of 30 min. Light is calibrated after
3 min. When the threshold is exceeded, the sensor switches 'OFF' after the stay-'ON' time expires.
Time setting
If the dial is set to (fully anti­clockwise), the unit is in pulse mode, i.e. the output is switched 'ON' for approx. 2 sec. (e.g. for stair-
well lighting timer). Afterwards, the sensor does not respond to movement for approx. 8 sec.
Day mode is the only mode possi­ble here because of dazzle by light from external sources.
Turned fully clockwise: The stay­'ON' time is self-learning and ad­justs dynamically to user behav-
iour. The optimum time cycle is determined by means of a learning algorithm.
The shortest time is 5 min., the longest 20 min.
Pulse mode (except DIM)
IQ mode
The chosen response threshold can be infinitely varied from approx. 10 – 1000 lux.
Control dial turned fully clockwise: MAX daylight mode Control dial turned fully anti-clock­wise: MIN night-time operation
Depending on the site of installa­tion, the setting may need to be corrected by 1-2 marks on the scale.
Twilight setting
Potentiometer
Potentiometer
COM 1 + COM 2
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
DIP 4
In the 'ON'-'OFF' setting, the light can be switched 'ON' and 'OFF' manually at any time (except in
pulse mode: no manual 'OFF'). In the 'ON' setting, light can no longer be switched 'OFF' manu-
ally. The stay-'ON' time starts from the beginning again each time the button is pressed.
'ON'/'ON'-'OFF' button
DIP 1
Functions – Settings by DIP switch
Test mode has priority over all other settings on the presence detector and serves the purpose of checking for proper working order as well for testing the de­tection zone. Irrespective of am-
bient light level, the presence detector activates the light to stay 'ON' for approx. 8 sec. in re­sponse to movement in the room (blue LED flashes when movement is detected). All user-
selected potentiometer settings apply in normal mode. The pres­ence detector can also be set by means of the blue LED without any load connected.
Normal mode / Test mode (NORM / TEST)
DIP 2
The light automatically switches 'ON' and 'OFF' in relation to brightness when someone is present. Light can be switched 'ON' and 'OFF manually at any time. This temporarily interrupts
the automatic switching func­tion. Irrespective of the settings selected, light stays 'ON' for 4 hours after manually pressing the button twice or switches 'OFF' after manually pressing the
button once. Pressing the but­ton before the 4 hours elapse returns the Presence Control IR Quattro to the normal operating mode.
Semi-automatic mode (MAN) / fully automatic mode (AUTO)
Fully automatic mode: (AUTO)
Semi-automatic mode: (MAN)
The light now only switches 'OFF' automatically. Light is switched 'ON' manually. Light must be requested using the
button and stays 'ON' for the time set at the potentiometer. (pressing twice switches 'ON' for 4 hours).
DIP 3
Tells the sensor how to interpret the incoming signal. Assigning external buttons/switches allows you to operate the detector as a semi-automatic unit and over­ride it manually at any time.
Operation either by button
or switch
Several buttons possible
on one control input
Only use illuminated push-
button with neutral conductor connected
Cable length between sensor
and switch < 50 m
Button/switch
COM 1 + COM 2
DIP 5
Provides a constant level of brightness. Detector measures the prevailing level of daylight and activates sufficient artificial light to achieve the required lev-
el of brightness. As daylight changes, the switched-in artifi­cial lighting component is ad­justed accordingly. In addition to the daylight component, artificial
light is also switched 'ON' and 'OFF' in relation to whether or not persons are present.
Constant light 'ON'/'OFF'
DIM
GB
PC PRO HF360_DualHF_Osteuropa.indd 24-25PC PRO HF360_DualHF_Osteuropa.indd 24-25 11.09.13 10:3611.09.13 10:36
Page 9
- 26 - - 27 -
The master/slave configuration permits detection of movement in large-type rooms or spaces (load connected = master, no load =
slave). The level of brightness pre­vailing in the room is only evaluat­ed at the master. The slaves report movements detected to the mas-
ter. Lighting or HVAC is switched 'ON' and 'OFF' by the master only.
Master/slave
A parallel-connected configuration also permits the use of several masters. In this case, each master operates the lighting group in accordance with the level of
brightness it measures. Delay times and brightness thresholds are selected at each master as re­quired. The switched load is spread among the individual masters.
Presence is still detected collec­tively by all detectors. The pres­ence output can be picked off from any master.
Master/master
Remote control
Using the remote control (option­al), functions can be conveniently activated from the floor.
Note: The pulse mode cannot be overridden by the remote control. Switch pulse mode 'OFF' manually.
Presence Control remote control unit: EAN no.: 4007841 000387
Parallel-connected configurations
Two detectors linked with an
external stairwell lighting timer
Old building / building moderni­sation
External light source activated by button. No twilight mode, day mode only.
Detector as stairwell lighting
timer
14.1
14.2
14.3
14.4
When using several detectors, they must be connected to the same phase!
DIM detector
14.5
• Setting 1 sec. – 2 hr.
• Turned fully clockwise: max
• Turned fully anti-clockwise: min
• Setting 0 sec. – 10 min.
• Turned fully clockwise: Room surveillance
• Turned fully anti-clockwise:
0 sec. ('OFF')
Turning the potentiometer to the "Surveillance" setting reduces the sensitivity of the "Presence" switching output. The contact only closes on detecting a pronounced movement, signalising with a high degree of certainty that persons are present.
The stay-'ON- time remains active. The switch-'ON' delay is inactivated.
Switch-'ON' delay for switching output 2 HVAC
Reach adjustment
COM 2
Potentiometer
Potentiometer
Provides basic illumination for the selected stay-'ON' time when ambi­ent light falls below the selected brightness threshold that is set. This can be dimmed to 10% of maxi­mum light intensity. As soon as a person enters the scene, the detec­tor switches either to 100% light
intensity (constant-lighting control­ler 'OFF') or adjusts to the preselect­ed brightness level (constant-light­ing controller 'ON'). When no move­ment is being detected, the detec­tor dims back to basic brightness after the stay-'ON' time expires. This is switched 'OFF' when stay-'ON'
time (1 min. – 30 min.) has expired or the daylight component is suffi­cient to exceed the selected level of brightness. In the 'ON' setting, the detector switches basic brightness 'ON' and 'OFF' as soon as the level of light falls below the brightness threshold.
Basic brightness (DIM option)
Potentiometer
Stay-'ON' time for switching output 2 HVAC
The reach required (response threshold) is infinitely variable.
HF 360 1 m min. – 8 m max.
DUAL HF min. 3 x 3 m – 10 x 3 m in
each direction
Turned fully anticlockwise (factory setting) = minimum reach
Turned fully clockwise (factory setting) = maximum reach
Potentiometer
GB
PC PRO HF360_DualHF_Osteuropa.indd 26-27PC PRO HF360_DualHF_Osteuropa.indd 26-27 11.09.13 10:3611.09.13 10:36
Page 10
- 28 - - 29 -
Functional Warranty
Declaration of Conformity
This product complies with
- Low Voltage Directive 2006/95/EC
- EMC Directive 2004/108/EC
- RoHS Directive 2011/65/EC
- WEEE Directive 2012/19/EC
This Steinel product has been manufactured with utmost care, tested for proper operation and safety and then subjected to ran­dom sample inspection. Steinel guarantees that it is in perfect condition and proper working order.
The warranty period is 36 months and starts on the date of sale to the consumer. We will remedy defects caused by material flaws or manufacturing faults. The war­ranty will be met by repair or re­placement of the defective parts at our own discretion. The war­ranty shall not cover damage to wear parts, damage or defects caused by improper treatment or maintenance. Further conse­quential damage to other ob­jects is excluded.
Claims under the warranty will only be accepted if the product is sent fully assembled and well packed complete with a brief de­scription of the fault as well as a receipt or invoice (date of pur­chase and dealer's stamp) to the appropriate Service Centre.
Repair service: Please ask your nearest service centre how to proceed for repair­ing faults not covered by the warranty or occurring after the warranty expires.
Troubleshooting
Light does not switch 'ON'
Light does not switch 'OFF'
Sensor switches 'OFF' in spite of persons being present
Sensor does not switch 'OFF' quickly enough
Sensor does not switch 'ON' quickly enough when approached from the front
Sensor does not switch 'ON' when persons are present in spite of it being dark
No supply voltage Lux setting too low
No motion detection
Lux setting too high Stay-'ON' time running out
Interference from sources of
heat, e.g.: fan heater, open doors and windows, pets, light bulb/halogen floodlight, moving objects
Stay-'ON' time too short Light-level threshold too low
Stay-'ON' time too long
Reach is reduced when
approached from the front
Lux setting too low
Check supply voltage Slowly increase lux setting
until light switches 'ON'
Ensure unobstructed sensor
vision
Check detection zone
Reduce lux setting Wait until stay-'ON' time
elapses; reduce stay-'ON' time if necessary
Use stickers to mask out
stationary sources of interference
Increase stay-'ON' time Change light threshold
Reduce stay-'ON' time
Install additional sensors
Reduce distance between
two sensors
Sensor deactivated by
switch/button?
Semi-automatic mode? Increase light-level threshold
Malfunction Cause Remedy
GB
PC PRO HF360_DualHF_Osteuropa.indd 28-29PC PRO HF360_DualHF_Osteuropa.indd 28-29 11.09.13 10:3611.09.13 10:36