STEINEL US Oneway COM2-24, US Quattro COM2-24, US Oneway DIM-24, DT Quattro COM2-24, DT Quattro COM1-24 User Manual

...
US Quattro COM1-24 US Quattro COM2-24
US Quattro DIM-24
DT Quattro COM1-24 DT Quattro COM2-24
DT Quattro DIM-24
US Quattro US Oneway
DT Quattro
US Hallway
US Oneway DIM-24
US Hallway COM1-24 US Hallway COM2-24
US Hallway DIM-24
Information
FR EN
- 2 -
Assembly / Installation / Dimensional Drawings
l
b
a
Load module
Sensor module
Mounts to a 4" Square box, 4" Octagon box or Round 3.0 Mud-Ring
120
US Quattro / DT Quattro
US Oneway / US Hallway
120
a
Mounts directly to ceiling with quick mount spring tabs
120
120
120
41
36
61
120
61
6
120
Ø min. 68 mm (2 11/16 in)
max. 76 mm (3 in)
120
26
- 3 -
US Quattro COM2-24 / DT Quattro COM2-24 / US Oneway COM2-24 / US Hallway COM2-24
Light level setting See page 18
Occupancy time delay setting See page 18
HVAC stay-'ON' time See page 19
HVAC switch-'ON' delay See page 19
e f g
d
d
c
h
k
k
Reach setting See page 19, 20
i
- 4 -
US Quattro DIM-24 / DT Quattro DIM-24 / US Oneway DIM-24 / US Hallway DIM-24
e f m
d
d
k
k
c
Light level setting See page 18
Occupancy time delay setting See page 18
Stay 'ON' time DIM before 'OFF' See page 19
Reach setting See page 19, 20
i
EN
- 5 -
US Quattro COM1-24 / DT Quattro COM1-24 / US Oneway COM1-24 / US Hallway COM1-24
Light level setting See page 18
Occupancy time delay setting See page 18
Reach setting See page 19, 20
e f i
d
d
c
k
k
EN
- 6 -
L
Disconnect the power supply
before attempting any work on the sensor!
L
Before installation, make sure
that power has been switched off at the breaker and check that the circuit is dead with a voltage tester.
L
Installing the sensor involves
work on the line voltage power supply. This work must there
­fore be carried out profession­ally in accordance with the applicable Nation Electrical Codes and electrical operating conditions.
L
Control output DIM-24
(1-10 V) must only be used for connecting electronic ballasts with an electrically isolated 10V dimming control input.
System Components
a
Load module
b
Sensor module
c
Sensor control plate
d
Sensor DIP switch settings
(1) Normal / Test mode
(2) Manual 'ON' / Automatic
'ON' mode
(3) Momentary / Maintained
switch option
(4) 'ON' only / 'ON'&'OFF'
manual switching
(5) Constant light level DIM
control option (6)(7)(8) Trigger mode
(DT Quattro only)
e
Light level setting
f
Occupancy time delay setting
Switching output 1
g
HVAC stay-'ON' time Switching output 2
h
HVAC switch-'ON' delay Switching output 2
i
Reach setting
10.1
COM1-24 Wiring
10.2
COM2-24 Wiring
10.3
COM2-24 Multiple Sensor Wiring
10.4
DIM-24 Wiring
10.5
DIM-24 Multiple Sensor Wiring
k
Locking mechanism
l
Assembly / Installation /
Dimensional Drawings
m
Stay 'ON' time DIM before
'OFF' option
n
Trigger mode options
Assembly/Installation (see chart on page 2)
For indoor use only.
Sensor and load modules come preassembled and must be sepa­rated for access to the commis­sioning settings on the backside of sensor module by opening the locking tabs k on the sides.
Reconnect and seat the sensor to the load module and secure the locking tabs
k
for normal
operation.
Accessories:
- WGC Wire Guard Cage
- RC 3 Service Remote
- RC 4 User Remote
Operating Instructions
Installer:
This product has been manu­factured and 100% quality tested.
Please read all of the instructions before installation. This will help you to be familiarized with all the features and options available to you with these devices.
This will also assist you to mini
­mize installation time and provide maximum energy savings and trouble-free operation.
Safety Warnings
l
- 7 -
How it Works / Basic Function
The Control Pro DT Quattro and Ultrasonic presence detector product familiy is intended to control lighting and HVAC in commercial buildings, schools, public building, etc.
Lighting is controlled in relation to both the presence of motion and ambient light levels. The HVAC output on the (COM2-24) is signaled in relation to only the presence of motion.
Commissioning adjustments are made by potentiometer or dip switch settings on the sensor or by the optional (RC3 service remote) commissioning tool.
US Quattro COM1-24 DT Quattro COM1-24
US Oneway COM1-24 US Hallway COM1-24
1 switching output (COM1-24 Low Voltage) operating in relation to the detection of motion and ambient light level.
Settings:
- Light level setting
- Occupancy time delay, Pulse mode, IQ mode
US Quattro COM2-24 DT Quattro COM2-24
US Oneway COM2-24 US Hallway COM2-24
1 low voltage switching output operating in relation to the detection of motion and ambient light level. An additional isolated normally open and normally closed set of dry contact closures for signaling HVAC (heating/venti
­lation/airconditioning) in relation only to the presence of persons.
Settings:
- Light level setting
- Occupancy time delay,
Pulse mode, IQ mode
- HVAC stay-'ON' time
- HVAC switch-'ON' delay,
Auto-HVAC mode
US Quattro DIM-24 DT Quattro DIM-24
US Oneway DIM-24 US Hallway DIM-24
1 low voltage switching output operating in relation to the detection of motion and ambient light level. An additional isolated 1-10 volt dimming output operat
­ing in relation to the amount of daylight present.
Settings:
- Light level setting
- Occupancy time delay, IQ mode
- Stay 'ON' time DIM before 'OFF'
- Constant light level DIM
control option
EN
- 8 -
Note:
1.) Tangential
- motion perpendicular to the sensor
2.) Radial
- motion either directly toward or away from the sensor
3.) Presence
- minor motion as described by NEMA WD7 with the additional requirement of both radial and tangential detection
Ultrasonic signal can be increased by hard surfaces and decreased by soft surfaces.
US Oneway / US Hallway Ultrasonic Detection
m
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
ft
45.5
42.5 39 36
32.5
29.5 26 23
19.5
16.5 13 10
6.5
3.3 0
3.3
6.5 10 13
16.5
19.5 23 26
29.5
32.5 36 39
42.5
45.5
Coverage diagram at 9 ft mounting height.
One grid line = 1 m / 3.3 ft
US ONEWAY US HALLWAY
Detection Zone
m 6 5 4 3 2 1 0 1 2 3 4 5 6
ft
19.7 16 13
9.5
6.5
3.3 0
3.3
6.5
9.5 13 16
19.7
6 5 4 3 2 1 0 1 2 3 4 5 6
US Quattro / DT Quattro Ultrasonic Detection / DT Quattro Infrared Detection
Coverage diagram at 9 ft mounting height.
One grid line = 1 m / 3.3 ft
PIR RADIAL & PRESENCE DETECTION
PIR TANGENTIAL DETECTION
US TANGENTIAL & PRESENCE DETECTION
US RADIAL MAJOR MOTION DETECTION
- 9 -
COM1-24 Wiring
10.
1
Note: Power Pack must be in Auto mode.
US Quattro COM1-24 DT Quattro COM1-24 US Oneway COM1-24 US Hallway COM1-24
18 AWG wire is recommended for low voltage sensor & power pack connection.
The leads consist of five wires:
1. 24V Input (RED)
2. Control Return (BLUE)
3. Communication (BROWN)
4. Switch Input (GREEN)
5. 24V Common (BLACK)
Load
Load
Control Pro
COM1-24
Presence Detector
Control Pro
COM1-24
(Master)
Presence Detector
Control Pro
COM1-24
(Slave)
Presence Detector
Power Pack
Power Pack
Neutral
Hot
Neutral
Hot
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
(Optional Line Voltage
Maintained Contact Switch)
(Optional Line Voltage
Maintained Contact Switch)
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
EN
- 10 -
COM2-24 Wiring
10.
2
Note: Power Pack must be in Auto mode.
US Quattro COM2-24 DT Quattro COM2-24 US Oneway COM2-24 US Hallway COM2-24
18 AWG wire is recommended for low voltage sensor & power pack connection.
The leads consist of eight wires:
1. 24V Input (RED)
2. Control Return (BLUE)
3. Communication (BROWN)
4. Switch Input (GREEN)
5. 24V Common (BLACK)
6. HVAC Relay Normally Open (YELLOW WITH RED STRIPES)
7. HVAC Relay Normally Common (YELLOW)
8. HVAC Relay Normally Closed (YELLOW WITH BLACK STRIPES)
Neutral
Hot
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Load
(Optional Line Voltage
Maintained Contact Switch)
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
Power Pack
Control Pro
COM2-24
Presence Detector
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
HVAC Yellow/Red (Normally Open)
HVAC Yellow (Relay Common)
HVAC Yellow/Black (Normally Closed)
Isolated HVAC
Relay Contacts
max. 1 A Resistive load
- 11 -
COM2-24 Multiple Sensor Wiring
10.
3
Note: Power Pack must be in Auto mode.
US Quattro COM2-24 DT Quattro COM2-24 US Oneway COM2-24 US Hallway COM2-24
18 AWG wire is recommended for low voltage sensor & power pack connection.
The leads consist of five wires:
1. 24V Input (RED)
2. Control Return (BLUE)
3. Communication (BROWN)
4. Switch Input (GREEN)
5. 24V Common (BLACK)
6. HVAC Relay Normally Open (YELLOW WITH RED STRIPES)
7. HVAC Relay Normally Common (YELLOW)
8. HVAC Relay Normally Closed (YELLOW WITH BLACK STRIPES)
(Optional Line Voltage
Maintained Contact Switch)
Neutral
Hot
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
Power Pack
Control Pro
COM2-24
(Master)
Presence Detector
Control Pro
COM2-24
(Slave)
Presence Detector
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
HVAC Yellow/Red (Normally Open)
HVAC Yellow (Relay Common)
HVAC Yellow/Black (Normally Closed)
HVAC Yellow/Red (Normally Open)
HVAC Yellow (Relay Common)
HVAC Yellow/Black (Normally Closed)
Load
Isolated HVAC
Relay Contacts
max. 1 A Resistive load
EN
- 12 -
DIM-24 Wiring
10.
4
US Quattro DIM-24 DT Quattro DIM-24 US Oneway DIM-24 US Hallway DIM-24
18 AWG wire is recommended for low voltage sensor & power pack connection.
The leads consist of seven wires:
1. 24V Input (RED)
2. Control Return (BLUE)
3. Communication (BROWN)
4. Switch Input (GREEN)
5. 24V Common (BLACK)
6. +10V dimming ballast input (VIOLET)
7. -10V dimming ballast input (GRAY)
Note: Power Pack must be in Auto mode.
Neutral
Hot
0-10 V Dimming
Ballast
Power Pack
(Optional Line Voltage
Maintained Contact Switch)
Control Pro
DIM-24
Presence Detector
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
-10 V Dimming Ballast (Gray)
+10 V Dimming Ballast (Violet)
+10 V Dimming Ballast (Violet)
-10 V Dimming Ballast (Gray)
- 13 -
DIM-24 Multiple Sensor Wiring
10.
5
US Quattro DIM-24 DT Quattro DIM-24 US Oneway DIM-24 US Hallway DIM-24
18 AWG wire is recommended for low voltage sensor & power pack connection.
The leads consist of seven wires:
1. 24V Input (RED)
2. Control Return (BLUE)
3. Communication (BROWN)
4. Switch Input (GREEN)
5. 24V Common (BLACK)
6. +10V dimming ballast input (VIOLET)
7. -10V dimming ballast input (GRAY)
Note: Power Pack must be in Auto mode.
Neutral
Hot
Load
Power Pack
(Optional Line Voltage
Maintained Contact Switch)
Control Pro
DIM-24
(Master)
Presence Detector
Control Pro
DIM-24
(Slave)
Presence Detector
Blue (Control) Black (-24 VDC) Red (+24 VDC) Gray (Momentary Switch)
White (Neutral)
Black (Hot)
Red (Relay)
Red (Load)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
Blue (Control)
Black (-24 VDC)
Red (+24 VDC)
Green (Switch Input)
Brown (Communication)
+10 V Dimming Ballast (Violet)
-10 V Dimming Ballast (Gray)
-10 V Dimming Ballast (Gray)
+10 V Dimming Ballast (Violet)
+10 V Dimming Ballast (Violet)
-10 V Dimming Ballast (Gray)
EN
- 14 -
Technical Specifications
Dimensions (L x W x D) US Quattro / DT Quattro COM1-24 / COM2-24 / DIM-24 120 x 120 x 68 mm / 4.72 x 4.72 x 2.68 inches
US Oneway / US Hallway COM1-24 / COM2-24 / DIM-24 120 x 120 x 73 mm / 4.72 x 4.72 x 2.87 inches
Power supply: US / DT Quattro COM1-24 18 - 24 VDC/VAC (30 mA) 50/60 Hz US / DT Quattro COM2-24 18 - 24 VDC/VAC (34 mA) 50/60 Hz US / DT Quattro DIM-24 18 - 24 VDC/VAC (46 mA) 50/60 Hz US Oneway / US Hallway COM1-24 18 - 24 VDC/VAC (30 mA) 50/60 Hz US Oneway / US Hallway COM2-24 18 - 24 VDC/VAC (34 mA) 50/60 Hz US Oneway / US Hallway DIM-24 18 - 24 VDC/VAC (46 mA) 50/60 Hz Maximum load: US Oneway / US Hallway COM1-24 / COM2-24 / DIM-24
Control output (Blue) 1 A @ 30 VAC/VDC 50/60 Hz US Quattro / DT Quattro COM2-24 / US Oneway /
US Hallway COM2-24
Control output (Blue) 1 A @ 30 VAC/VDC 50/60 Hz HVAC dry contacts: Common (Yellow)
- Normally open (Yellow/Red)
- Normally closed (Yellow/Black) 1 A @ 30 VAC/VDC 50/60 Hz US Quattro/ DT Quattro DIM-24 / US Oneway /
US Hallway DIM-24 Control output (Blue) 1 A @ 30 VAC/VDC 50/60 Hz
1 - 10 volt dimming output (Purple & Gray) 100 mA, max. 50 (1 - 10 V electronic dimming ballasts)z
Ultrasonic detection zones: US Quattro / DT Quattro
(Coverage at 2.5 m / Presence (m): max. of 6 x 6 m (36 sq.m.) 9 ft installation height) min. of 2 x 2 m (4 sq.m.)
Presence (ft): max. of 20 x 20 ft (400 sq.ft.) min. of 6.5 x 6.5 ft (42.25 sq.ft.) Radial / Tangential (m): max. of up to 10x10 m (100 sq.m.)
(ft): max. of up to 32 x 32 ft (1000 sq.ft.) US Oneway
max. of 2 x 10 m (20 sq.m.) min. of 2 x 2.5 m (5 sq.m.) max. of 6.5 x 33 ft (214.5 sq.ft.) min. of 6.5 x 10 ft (65 sq.ft.)
US Hallway max. of 2 x 20 m (40 sq.m.) min. of 2 x 5 m (10 sq.m.) max. of 6.5 x 65 ft (422.5 sq.ft.) min. of 6.5 x 20 ft (130 sq.ft.)
PIR detection zones: DT Quattro COM1-24 / COM2-24 / DIM-24 Presence (m) max. of 3x3 m (9 sqm) Presence (ft) max. of 10x10 ft (100 sqft) Radially (m) max. of 4 x 4 m Radially (ft) max. of 13 x 13 ft Tangentially (m): max. of 8 x 8 m Tangentially (ft): max. of 26 x 26 ft
- 15 -
Technical Specifications
Time setting: Control output 30 sec. - 30 min.
Pulse mode (approx. 2 sec. 'ON' 8 sec. 'OFF') - for time delay relay IQ mode (automatic adjustment to the usage profile) HVAC dry contacts (only in COM2-24) 0 sec. - 10 min. switch 'ON' delay 1 min. - 2 hrs. stay 'ON' time Auto-HVAC mode Installation height: US Quattro / DT Quattro COM1-24 / COM2-24 / DIM-24
2.5 - 3,5 m / 8 - 12 ft US Oneway / US Hallway COM1-24 / COM2-24 / DIM-24
2.5 - 3,5 m / 8 - 12 ft
Environment: IP 20 - For indoor use only Sensor technology: DT Quattro COM1-24 / COM2-24 / DIM-24
PIR (Passive Infrared), Single pyro, 11 detection levels, 520 switching zones Ultrasonic 40 kHz
US Quattro / US Oneway / US Hallway COM1-24 / COM2-24 / DIM-24 Ultrasonic 40 kHz
Protection class: Class 2 Temperature range: 0° F to +40° C / 32° F to 104° F Certifications: UL & CUL Listed,
RoHS & California Compliant, UL 2043 plenum rated
EN
- 16 -
DIP 4
In the 'ON'-'OFF' setting, the light can be switched 'ON' and 'OFF' manually at any time (except in
pulse mode: no manual 'OFF'). In the 'ON' setting, light can not be switched 'OFF' manually.
The stay-'ON' time starts from the beginning again each time the button is pressed.
'ON' only / 'ON'&'OFF' manual switching
DIP 1
Sensor DIP Switch Settings
Test mode has priority over all other settings on the presence detector and serves the purpose of checking for proper working order as well for testing the detection zone. Irrespective
of ambient light level, the pres­ence detector activates the light to stay 'ON' for approx. 8 sec. in response to movement in the room (blue LED flashes when movement is detected). All user-
selected potentiometer settings apply in normal mode. The pres
­ence detector can also be set by means of the blue LED without any load connected.
Normal mode / Test mode (NORM / TEST)
DIP 2
The light automatically switches 'ON' and 'OFF' in relation to occupancy and daylight contribu­tion. Light can be switched 'ON' and 'OFF' manually at any time.
When switched 'OFF' manually this temporarily interrupts the automatic 'ON' function as long as the room is occupied. Once the room is no longer occupied
and the time delay of the sensor has elapsed the sensor will return to the automatic 'ON' function.
Manual ON mode (MAN) / Automatic mode (AUTO)
Automatic mode: (AUTO)
Manual ON mode: (MAN)
The load will only switch 'OFF' au­tomatically. Light is switched 'ON'
manually by the occupant and stays 'ON' for the time
setting of the sensor.
DIP 3
Tells the sensor how to interpret the incoming maintained or momentary switching signal. Assigning external (momentary) buttons / (maintained) switches allows you to operate the detector
as a manual on unit or override it manually at any time. When using the DIM-24 power module and a momentary switch, light can be dimmed manually by pressing and holding the momentary switch
until the desired light level is achieved. Maximum wire lenght between sensor and switch <50 m / 164 ft.
Momentary / Maintained switch option
COM1-24 / COM2-24 / DIM-24
DIP 5
Provides constant light level. Detector measures the level of daylight and activates sufficient artificial light to achieve the
required level of light intensity. As daylight changes, the electric light is adjusted accordingly. In addition to the daylight
component, electric light is also switched 'ON' and 'OFF' in relation to whether or not persons are present.
Constant light level DIM control option
DIM-24
d
- 17 -
DIP 6 / 7 / 8 Trigger mode
The trigger mode enables the user to choose which sensing technologies should be used to initially turn the load on and which technologies are required to keep it on. The following settings are possible:
DT Quattro COM1-24 / COM2-24 / DIM-24
Both: Requires movement recognition by PIR and US Either: Requires movement recognition by PIR or US PIR: Requires movement recognition by PIR US: Requires movement recognition by US
Inital occupancy:
Sensor technology used to turn the load on (PIR, US, Both, Either)
Maintain Occupancy:
Sensor technology used to keep the load on after initial occupancy (PIR, US, Both, Either)
The trigger mode is selected by DIP switches 6, 7 & 8.
on
1 2 3 4 5 6 7 8
TEST
MODE
MANUAL
ON / OFF
CONST. OFF
NORMAL
MODE
AUTO
ON
CONST.ONTRIGGER MODE
Trigger mode options n Initial Occupancy Maintain Occupancy
DIP
6
DIP
7
DIP
8
Option 1 Both Either OFF OFF OFF Option 2 Both Both OFF OFF ON Option 3 PIR Either OFF ON OFF Option 4 US Either OFF ON ON Option 5 (factory setting) Either Either ON OFF OFF Option 6 US US ON OFF ON Option 7 PIR PIR ON ON OFF Option 8 Either Both ON ON ON
EN
- 18 -
Functions – Settings by Potentiometer
Application Examples Light level settings
Night-time mode, minimum setting approx. 10 lux / 1 fc min Corridors, foyers 1 Stairs, escalators, moving walkways 2 Restrooms, dining areas 3 Classrooms, sales oors, gymnasiums 4 Individual oces, conference and meeting rooms 5 Laboratories, precision work areas >=6 Daylight mode max
The occupancy time delay setting for switching output 1 is adjustable from a minimum
of 30 seconds to a maximum of 30 minutes.
Occupancy time delay setting
If the dial is set to (fully coun­terclockwise), the unit is in pulse mode, i.e. the output is switched 'ON' for approx. 2 sec. Afterwards,
the sensor does not respond to movement for approx. 8 sec. For use with a time delay relay.
Turned fully clockwise: The stay­'ON' time is self-learning and adjusts dynamically to user
behaviour. The optimum time cycle is determined by means of a learning algorithm.
The shortest time is 5 min., the longest 20 min.
Pulse mode (except DIM)
IQ mode
The chosen response threshold can be adjusted from approx. 10 – 1000 lux / 1 – 100 fc.
Control dial turned fully clockwise: MAX daylight mode
Control dial turned fully counterclockwise: MIN night-time operation
Light level setting
Potentiometer e
Potentiometer f
DT Quattro COM1-24 / COM2-24 / DIM-24
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
Brightness is measured directly at the sensor.
- 19 -
Setting 1 sec. – 2 hr • Turned fully clockwise: max • Turned fully counterclockwise: min
• Setting 0 sec. – 10 min.
• Turned fully clockwise: Auto-HVAC mode
• Turned fully counterclockwise: 0 sec. (OFF)
Turning the potentiometer to the "Auto-HVAC mode" setting reduces the sensitivity of the "Presence" switching output. The contact only closes after surveying the activity of the space and then, signaling
with a high degree of certainty that multiple persons are present. The stay-'ON'- time remains active. The switch-'ON' delay is inactivated.
Switch-'ON' delay for switching output 2 HVAC
Reach Adjustment
Adjusts ultrasonic reach to specific requirements. Reach can be adjusted by using the RC3 remote control commissioning tool.
COM2-24
Potentiometer g
Potentiometer h
Potentiometer i
Provides basic illumination for the selected stay-'ON' time when am
­bient light falls below the selected brightness threshold that is set. This can be dimmed to 10% of maximum light intensity. As soon as a person is detected, the sensor switches either to 100% light intensity (constant-lighting
controller 'OFF') or adjusts to the preselected brightness level (constant-lighting controller 'ON'). When no movement is detected and the occupancy time setting
f
has elapsed , the sensor dims
light levels back to basic bright
­ness after the stay 'ON' time (1 min. - 30 min.) has expired or
the daylight level exceeds the selected level of brightness. If the occupancy time delay setting
f
is greater than the stay on time
DIM before 'OFF' setting
m
the light will not dim before turning 'OFF'.
Stay 'ON' time DIM before 'OFF' option
Potentiometer m
Stay-'ON' time for switching output 2 HVAC
DIM-24
i
EN
- 20 -
Using the remote control, functions can be conveniently activated from the floor.
Note: The pulse mode cannot be overridden by the remote control. Switch pulse mode 'OFF' manually.
Presence Control remote control unit:
- RC 3 Service Remote
- RC 4 User Remote
RC 3 Service Remote
12
5
6
7
10
11
Description
The RC 3 service remote (commissioning tool) gives the installer the ability to set basic functions of the entire line of Control Pro sensors via remote control. Each valid press of a button is indicated by a blue LED flash on the sensor.
Functions Reach setting (Control Pro Ultrasonic and DT Quattro sensors only)
Ultrasonic coverage can be selected from mini
­mum, 1/3, 2/3, or maximum by pressing these buttons. Use this setting to increase or decrease the coverage (detection range) of the sensor.
Time setting CH 1
­Stay 'ON' time for switching contact 1 The period of time you want the light to stay 'ON'
for after last detecting movement can be set from between 30 sec., 2 min., 5 min., 15 min. and 30 min. by pressing these buttons.
Setting the light to stay 'ON' for a time of your
own choice. Each press of the button increments the chosen time setting by 1 minute.
IQ mode. Stay 'ON' time is self-learning and
adjusts dynamically to user behaviour. The optimum time is determined by means of a learning algorithm. The shortest time is 2 min., the longest time 20 min.
Test mode. The test mode has the purpose of
checking for proper working order as well as testing the detection zone. The presence detec
­tor switches 'ON' for approx. 8 sec. regardless of brightness and movement. The test mode has priority over all other settings. All user-selected potentiometer settings apply in normal mode. The test mode ends automatically after 10 min.
Time setting CH 2 ­Stay 'ON' time for switching contact 2 (HVAC) The period of time you want the HVAC contacts
to signal the HVAC controller (stay 'ON') after last detecting movement can be set from 1 min., 5 min., 30 min., or 2 hours by pressing these buttons.
Light level setting
The chosen response threshold can be varied
from approx. 10 – 1000 lux / 1 - 100 fc.
Night-time mode (minimum setting
approx. 10 lux. , 1 fc.)
Daylight mode (maximum - light level function
overridden)
Teach-IN. Twilight setting at the memory but
­ton/Teach mode. This button must be pressed at the level of light at which you want the sensor to respond to movement. The current light level is saved.
No function
Reset Resets all settings to the values selected on the
detector manually or to the factory settings.
4
1
3
2
6
5
7
8
9
10
11
12
1
2
8
9
3
4
Remote Control
- 21 -
RC 4 - User Remote
Functions Dimming function
The RC 4 remote enables the user to dim up or down to desired levels when used with the Control Pro DIM-24 sensors and 0-10 volt dimming ballasts. The last light level adjustment setting is saved and will return after being switched 'OFF' and then back 'ON' again by the RC 4, switch or presence detection.
Light 'ON'/ 'OFF'
The ON/OFF remote feature allows the occupant to conveniently turn lighting OFF and ON again such as needed dur
­ing video or presentation viewing. Controls only lighting and does not effect HVAC outputs of the COM2-24. The ON/OFF function works with all of the Control Pro sensors.
Reset
Returns settings to those selected manually on the detector or to the factory setting (only applies to settings that can be changed by remote control)
1
2
3
1
3
2
Description
The RC 4 user remote control gives the occupant the ability to turn lighting 'ON' or 'OFF' with the entire line of Control Pro sensors via remote control. The dimming functions are only available with the DIM-24 sensors. Each valid press of a button is indicated by a blue LED flash on the sensor.
EN
- 22 -
Troubleshooting
Light does not switch 'ON'
Light does not switch 'OFF'
Sensor switches 'OFF' when occupied
Sensor does not switch 'OFF' quickly enough
Sensor detects initial occupancy but turns off in 2 seconds
L
No supply voltage
L
Light level setting too low
L
No motion detection
L
Light level setting too high
L
Stay-'ON' time running out
L
Interference from unintended
sources of motion, e.g.: ceiling fan, heater, HVAC, open doors and windows
L
Stay-'ON' time too short
L
Light-level threshold too low
L
Stay-'ON' time too long
L
Sensor is in pulse mode but
is not connected to a time delay relay
L
Check supply voltage
L
Slowly increase light level set-
ting until light switches 'ON'
L
Ensure unobstructed view of
detection area
L
Adjust detection zone
L
Reduce light level setting
L
Wait until stay-'ON' time
elapses; reduce stay-'ON' time if necessary
L
Readjust coverage zone or
apply masking material
L
Increase stay-'ON' time
L
Change light threshold
L
Reduce stay-'ON' time
L
Adjust sensor’s time delay or
use with a time delay relay
Malfunction Cause Remedy
Warranty
STEINEL America warrants its products against defects in material or workmanship for a period of five years.
STEINEL will replace or repair the item provided that it has not been altered or subjected to abuse, accident, improper installation or improper use. There are no obligations or liabili
­ties on the part of STEINEL for consequential damages arising out of or in connection with the use or performance of this product
or other indirect damages with respect to loss of property, reve­nue, or profit, or cost of removal, installation or reinstallation.
DAN
PLK
DEU
ENG
G
ARANTIE
FUNKTIONS
5 Jahre
GWARANCJI
5 Letnia
GARANTI
FUNKTIONS
5 Års
GARANTI
FUNKTIONS
5 Års
WARRANTY
FUNCTIONAL
5 Year
SVE
ГAPAHTИИ
110031888 09/2014 Technical changes subject to no prior notification.
STEINEL America, Inc.
9051 Lyndale Avenue South
USA - Bloomington, MN 55420
Tel: +1-800-852-4343
Fax: +1-952-888-5132
www.steinel.net
M-11127-3