MFR 012 Mechanical Hygrostat
Regulating and Monitoring
Efficient condensation control
Adjustable relative humidity range
High switching capacity
DIN rail mountable
The MFR 012 electromechanical thermostat is designed to control the relative humidity inside
enclosures. When connected to an enclosure heater (dehumidifier), it will energize the heater
at the humidity set point in order to raise the dew point. This helps prevent damage and malfunction of electronic components caused by condensation and corrosion.
1)
The MFR 012 can also be used to control cooling fans, warning lights or other devices.
Switching difference 4% RH (± 3% tolerance) - at 50% RH
Permissible air velocity 50 ft/sec (15m/s)
Contact type SPDT / change-over contact
Contact resistance < 10m
˜
Service life > 100,000 cycles
Min. Switching capacity 100mA @ AC/DC 20V
Max. Switching capacity 5A resistive / 1A inductive @ 250VAC
DC 20W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 3-pole terminal, clamping torque 0.5Nm max.:
solid wire - AWG 14 max. (2.5mm²)
stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm²)
Housing plastic, UL 94V-0, light grey
Mounting clip for 35mm DIN rail, EN 60 715
Mounting position vertical
Operating temperature +32 to +140°F (0 to +60°C)
Storage temperature -4 to +176°F (-20 to +80°C)
Dimensions 2.64 x 1.97 x 1.5” (67 x 50 x 38mm)
Weight approx. 2 oz. (60g)
Protection type IP20
Approvals UL File No. 164102
1)
The critical relative humidity level for most components is 65%. Above 65% RH, condensation can form and cause
malfunctions of electronic equipment. Long term, this can lead to corrosion and permanent damage of electronic components and systems.
Part No. Setting range
01220.0-00 35 to 95% RH