Mechanical
Hygrostat
KFR 012
Fixed relative humidity setpoint
High switching capacity
DIN rail mountable
The KFR 012 is designed to control the relative air humidity
inside of enclosures. When connected to an enclosure heater,
(de-humidifier), it will turn the heater on at the preset humidity
E
Z
IS
L
A
setpoint in order to raise the dew point. This helps prevent
damage and malfunction of electronic components caused by
condensation and corrosion. The KFR 012 can also be used to
control cooling fans, warning lights or other devices.
Technical Data MFR 012
Part No.: 01240.0-00 - 65% RH setpoint
01241.0-00 - 50% RH setpoint
Switching tolerance:
Switching difference (hysteresis):
Permissible air velocity:
Contact type:
Contact resistance:
Service life:
Minimum switching capacity:
Maximum switching capacity:
EMI/EMC compliance:
Connection:
Mounting:
Dimensions (H x W x D):
Housing:
Weight:
Operating temperature:
Storage temperature:
Protection type:
Agency approvals:
Application examples:
+/- 5% RH
4% RH (+/- 3% tolerance)
50 ft/sec (15 m/s)
Contact maker (normally open)
<10mW
100,000 cycles
100mA @ AC/DC 20 V
5A @ AC 250 V (resistive load)
1.0A @ AC 250 V (inductive load
at cos j = 0.8)
DC 20 W
EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
2-pole terminal, AWG 14 max. (2.5 mm²)
Clip for 35 mm DIN rail (EN 50022)
2.4 x 1.3 x 1.7” (60 x 33 x 43 mm)
Plastic, UL94V-O
1.4 oz. (40 g)
32 to 140°F (0 to 60°C)
-4 to 176°F (-20 to 80°C)
IP 20
UL submitted for approval
Electrical & Electronic enclosures
Telecommunication systems
Display panels
Ticket dispensers
Automatic teller machines (ATM’s)
Access & Parking control systems