Stego FZK 011 Data Sheet

Technical Data
Regulating and Monitoring
||
FZK011/06-08/US
Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.
STEGO, Inc. · 1395 South Marietta Parkway · Building 800 · Marietta, GA 30067 · Tel: (770) 984-0858 · Fax: (770) 984-0615
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
Wide adjustment range
SPDT (Change-over) contact
DIN rail mountable
The FZK 011 mechanical thermostat is used for controlling heating and cooling equipment, fil­ter fans or signal devices where a higher degree of sensing accuracy is required. An integrated resistor (RF) can be connected to improve the switch temperature difference.
1)
The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact.
Switching difference approx. 7°F (4K), ± 2.7°F (1.5K) tolerance
1)
Sensor element thermostatic bimetal
Contact type SPDT / change-over contact
Contact resistance < 10m
˜
Service life > 100,000 cycles
Max. switching capacity, NC 10A resistive / 4A inductive @ 120VAC
10A resistive / 4A inductive @ 250VAC
DC 30W
Max. switching capacity, NO 5A resistive / 2A inductive @ 120VAC
5A resistive / 2A inductive @ 250VAC
DC 30W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 4-pole terminal, clamping torque 0.5Nm max.:
solid wire - AWG 14 max. (2.5mm²)
stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm²)
Housing plastic, UL 94V-0, light grey
Mounting clip for 35mm DIN rail, EN 60 715
Mounting position vertical
Operating temperature -4 to +176°F (-20 to +80°C)
Storage temperature -49 to +176°F (-45 to +80°C)
Dimensions 2.64 x 1.97 x 1.5” (67 x 50 x 38mm)
Weight approx. 3.5 oz. (100g)
Protection type IP20
1)
Connecting terminal "N" (RF heating resistor) causes the thermal feedback to work, reducing the switch
temperature difference to approx. 1°F (0.5K).
Part No. Operating voltage
2)
Setting range Approvals
01170.0-00 230VAC 5 to 60°C UL File No. E164102
01170.0-01 230VAC 40 to 140°F UL File No. E164102
01170.9-00 120VAC 40 to 140°F UL File No. E164102
01170.9-01 120VAC 5 to 60°C UL File No. E164102
1.5” (38 mm)
1.97” (50 mm)
2.64” (67 mm)
FZK 011 Mechanical Thermostat
2) Voltage only needs to be specified if the optional use of the RF resistor is desired.
Enclosure heater
Filter fan, cooling equipment, signal device
Wiring examples
FZK 011 Thermostat Heater
FZK 011 Thermostat
e.g. Filter Fan
FZK 011 Thermostat e.g. Signal Device