Stego DCT 010 Catalog Page

18.02.2020 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
REGULATING
83
83
DCT 010 |
DC 20 to DC 56 V
2.09" (53mm) 1.73" (44mm)
3.66" (93mm)
> High DC switching capacity > Adjustable temperature > Small hysteresis
> Integrated switch module > Precise measurement via an external
sensor
> Optical operating display (LED)
The electronic thermostat with integrated switch module is used to control DC powered devices with high capa­cities in control and switch cabinets. Heaters, coolers, filter fans or signal devices can directly be controlled via an internal electronic circuit. The external sensor can be positioned freely anywhere in the control cabinet for precise temperature measurements. Additionally, this thermostat is available in versions that not only measure temperature via the external sensor, but also the relative humidity.
TECHNICAL DATA
Switching difference (temperature) 3 K (±1 K tolerance) at +77 °F (+25 °C), 50 % RH
Reaction time approx. 5 sec.
External sensor cable 2 m with snap in connector (included in the delivery)
Contact type contact maker NO (MOSFET) or contact breaker NC (MOSFET)
Service life > 100,000 cycles
Operating voltage DC 20 to 56 V
Optical indicator LED
1
Connection 6-pole terminal: stranded wire
Mounting clip for 35 mm DIN rail, EN 60715
Housing plastic, UL 94V-0, grey (bicolor)
Dimensions 3.7 x 2.1 x 1.7" (93 x 53 x 44 mm)
Weight approx. 4.2 oz. (120 g) incl. sensor
Mounting position vertical
Storage temperature -40 to +176 °F (-40 to +80 °C)
Operating / Storage humidity max. 90 % RH (non-condensing)
Protection type IP20
Approvals UL File No. E164102, VDE, EAC
Note other versions (e.g. setting ranges and °C) on request
1
When connecting with stranded wires, wire end ferrules must be used.
max. AWG 12 (2.5 mm²)
AWG 16 (1.5 mm²);
Wiring example
Heater Thermostat DCT 010Wiring diagram
+
-
1
2
Part No. Max. switching capacity
01011.0-31 DC 13 A -22 °F to +122 °F (-30 °C to +50 °C) 14 to 122 °F - Contact maker (NO)
01011.0-32 DC 11 A -22 °F to +140 °F (-30 °C to +60 °C) 32 to 140 °F - Contact maker (NO)
01011.0-61 DC 13 A -22 °F to +122 °F (-30 °C to +50 °C) 14 to 122 °F 65 % RH pre-set Contact breaker (NC)
01011.0-62 DC 11 A -22 °F to +140 °F (-30 °C to +60 °C) 32 to 140 °F 65 % RH pre-set Contact breaker (NC)
2
Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.
Switching difference: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.
(relay output)
Operating temperature Primary switching function
setting range temperature
Secondary switching function²
humidity setting
Contact (primary)
­+
Loading...