ELECTRONIC HYGROSTAT
18.02.2020 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.
PRODUCT CATALOG - STEGO, Inc.
DCF 010 |
DC 20 to DC 56 V
2.09" (53mm) 1.73" (44mm)
3.66" (93mm)
> High DC switching capacity
> Adjustable humidity
> Small hysteresis
> Integrated switch module
> Precise measurement via an external
sensor
> Optical operating display (LED)
The electronic DC hygrostat with integrated switch module is used to control heating and cooling equipment, filter
fans or signal devices through the relay. The hygrostat measures the relative humidity and can switch a signal
current via an internal relay. The external sensor can be positioned freely anywhere in the control cabinet for precise
measurement of the atmospheric humidity. Additionally, this hygrostat is available in versions that not only
measure the relative humidity via the external sensor, but also the temperature.
TECHNICAL DATA
Switching difference (humidity) 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH
Reaction time approx. 5 sec.
External sensor cable 2 m with snap in connector (included in the delivery)
Contact type contact maker NO (MOSFET) or contact breaker NC (MOSFET)
Service life > 100,000 cycles
Operating voltage DC 20 to 56 V
Optical indicator LED
1
Connection 6-pole terminal: stranded wire
Mounting clip for 35 mm DIN rail, EN 60715
Housing plastic, UL 94V-0, grey (bicolor)
Dimensions 3.7 x 2.1 x 1.7" (93 x 53 x 44 mm)
Weight approx. 4.2 oz. (120 g) incl. sensor
Mounting position vertical
Storage temperature -40 to +176 °F (-40 to +80 °C)
Operating / Storage humidity max. 90 % RH (non-condensing)
Protection type IP20
Approvals UL File No. E164102, VDE, EAC
Note other versions on request
1
When connecting with stranded wires, wire end ferrules must be used.
max. AWG 12 (2.5 mm²)
Heater Hygrostat DCF 010Wiring diagram
AWG 16 (1.5 mm²);
Wiring example
-
1
2
+
Part No. Max. switching capacity
01012.0-20 DC 15 A -22 °F to +104 °F (-30 °C to +40 °C) 40 to 90 % RH +41 °F (+5 °C) pre-set Contact maker (NO)
01012.0-21 DC 13 A -22 °F to +122 °F (-30 °C to +50 °C) 40 to 90 % RH +41 °F (+5 °C) pre-set Contact maker (NO)
01012.0-22 DC 11 A -22 °F to +140 °F (-30 °C to +60 °C) 40 to 90 % RH +41 °F (+5 °C) pre-set Contact maker (NO)
2
Versions with secondary switching function can also register the temperature and therefore offer an additional protection for electronics.
Switching difference: 3 K (±1 K tolerance) at +77 °F (+25 °C), 50 % RH.
(relay output)
Operating temperature Primary switching function
setting range humidity
Secondary switching function²
Switch-on temperature
Contact (primary)
+