PANEL-MOUNT FAN HEATER
HEATING
33
33
CR 130 |
6.6" (168mm)
950 W
7.2" (182mm)
3.9" (99mm)
> Compact design
> Built-in overheat protection
> Double insulated plastic housing
> Integrated adjustable thermostat or
fixed hygrostat
> Panel or DIN rail mounting
The compact CR 130 high performance fan heater prevents formation of condensation and provides an evenly
distributed interior air temperature in enclosures. This fan heater is available with an integrated thermostat
for temperature control or a pre-set hygrostat for humidity control. The CR 130 was designed as a stationary
unit for panel or DIN rail mounting. For footmounting on the bottom of an enclosure, the CR 030 fan heater is
recommended.
TECHNICAL DATA
Heating element High performance cartridge heater
Overheat protection with automatic reset and second-tier one shot fuse
Heater body extruded aluminum
Axial fan, ball bearing Service life 50,000 h at 77 °F (25 °C)
Air flow, free blowing 94 cfm (160 m³/h)
Connection 2-pole terminal AWG 16 max. (1.5 mm²) with strain relief,
Housing plastic, UL 94V-0, black
Mounting clip for 35 mm DIN rail, EN 60715 or M6 screws (not included)
Mounting position vertical airflow (air outlet up)
1
/ Storage temperature -49 to +158 °F (-45 to +70 °C)
Operating
Operating / Storage humidity max. 90 % RH (non-condensing)
Dimensions 3.9 x 6.6 x 7.2" (99 x 168 x 182 mm)
Weight approx. 3.1 lbs. (1.4 kg)
Protection class / Protection type II (double insulated) / IP20
1
Operating temperature of heater with integrated hygrostat: +32 to +140 °F (0 to +60 °C)
clamping torque 0.8 Nm max.
Part No. Operating
voltage
13059.9-00 AC 120 V, 50/60 Hz 950 W 10.0 A 32 to 140 °F UL File No. E234324 - EAC
13059.9-02 AC 120 V, 50/60 Hz 950 W 10.0 A none (no integrated controls) UL File No. E234324 - EAC
13051.0-00 AC 230 V, 50/60 Hz 950 W 6.3 A 0 to 60 °C UL File No. E234324 VDE EAC
13051.0-02 AC 230 V, 50/60 Hz 950 W 6.3 A 65 % RH, factory-set UL File No. E234324 VDE EAC
13051.0-03 AC 230 V, 50/60 Hz 950 W 6.3 A none (no integrated controls) UL File No. E234324 VDE EAC
² switching difference 12.6 °F ±7 °F tolerance (7 K ±4 K)
Heating
capacity
Recommended pre-fuse T
(time-delay)
Setting range
2
Approvals
Wiring diagram
07.09.2018 | Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.