Steamist SM-46, SM-79 Installation Instructions Manual

Page 1
Electrical Installation Instructions
®
®
C
US
Steambath Generator Models: SM-46 and SM-79
The Steamist “SM” Generator operates with one or two controls appropriately located inside and/or outside the steamroom. It’s small enough in size to be tucked away using very little space in a vanity, closet, basement, or an insulated attic, but large enough to provide steam for most residential baths.
The Steamist “SM” Steambath Generator comes factory­assembled, carefully wired and tested.
NOTE: The TC-110, TC-125, TC-135, TC-150, DSC-425, and DSP Controls are designed to work with all Steamist “SM” Generators.
1. Pre-Installation
a) Proper electrical supply (208 or 240 Volt): See rating
label on Steam Generator and Chart on back page. Determine proper size of wire, voltage, amperage, and phase for the Steam Generator. Only UL rated 90°C wire can be used.
b) Dedicated overcurrent protection device, such as an
In-line fuse/circuit breaker required: Fuse/circuit breaker to be installed must be sized in accordance with chart on back page. Do NOT install a GFI (Ground Fault Interrupter) to this equipment (per article 210-8 in the National Electric Code).
c) Route power supply cable to the location where the
Steam Generator will be installed (before walls are closed).
IMPORTANT: The Dual Kilowatt Switch MUST be set to the proper kilowatt rating in accordance with the Generator Sizing Guide and Generator Specification Chart (back page).
a) Remove the two screws holding the electrical
access cover and remove cover.
b) Locate the supply line knockout. Mount proper
strain relief into knockout hole (see Figure 2: Internal Electrical Connections). c) Strip back power cable’s outer insulation jacket eight inches and insert into steam generator. Strip back insulation ½" from the three (3) incoming wires (two power and one ground). d) Connect incoming ground wire to floating green pigtail labeled “GND.”
CAUTION: Be sure the ground wire does not
come in contact with a live electrical part. e) Connect incoming power to floating black pigtail
leads labeled “L1” and “L2.” (see Figure 2: Internal Electrical Connections). f) The Steam Generator is ready for operation once the installation of the controls is completed (refer to separate Installation and Operating Instructions).
2. Electrical Rough-in
Figure 1 - Steam Generator
a) At this time read through the installation instructions for
the selected control(s).
b) Route appropriate power cable to the location the Steam
Generator will be installed. If receptacle is desired, mount the box for the receptacle near the location of the Steam Generator (see Figure 3: Typical Installation).
NOTE: The plug and receptacle require a rating of no
less than 250V and proper amperage. Refer to chart on page 4 for amperage rating.
After the walls are complete, the Steam Generator and
Control can be wired.
3. Steam Generator Electrical Installation
WARNING: All power to the Steam Generator must be
Electric
Panel Cover
Securing
Screws
Install Upright
and Level
Knockout for
Control Cable
Knockouts for
*Dual Kilowatt
Switch
Water Inlet
" Compression
Fitting
¾" Steam
Outlet
¾" Safety
Relief Valve
Identification
Plate
turned off.
WARNING: Elderly persons, pregnant women, or those suffering from heart disease, high blood pressure, diabetes, or who are otherwise not in good health, do not use this device unless directed to do so by a physician. Also, do not use steambath while under the influence of alcohol. For additional Important Safety Information, please see a separate
!
instruction Pub. No. 199.
IMPORTANT: The warranty of this product is voided if it is used in a commercial application or for anything other than a residential steambath installation. All electrical connections must be performed by a licensed electrician in accordance with Local and National Electric Codes.
03/09
- 1 -
Pub. No. 217-J
Page 2
Electrical Installation Instructions
Checklist Models: SM-46 and SM-79
Before starting, insure that the conditions of the following checklist have been met:
The proper size Steam Generator has been selected by using the sizing page in the “Full Line Brochure,” “Pricing Guide,” or “The Generator Sizing Guide” in the Residen­tial Systems/Steambath Product Information section of the Steamist website - www.steamist.com.
CAUTION: An improperly sized Steam Generator will NOT produce the amount of steam necessary to reach selected temperature.
The proper voltage Steam Generator has been selected (i.e., 208V or 240V). A 208V Generator operating on 240V will damage the heating element, and a 240V Generator operating on 208V will result in a 25% loss of power.
Figure 2 - Internal Electrical Connections
Optional Steamist
Splitter for Two
Controls
Black Plastic
Strain Relief
Clamp
Multi-Conductor
Control Cable
(25 feet)
The Steam Generator is installed in an upright position. The proper sized 90°C wire and circuit breaker have
been used. The circuit breaker is NOT a GFI (Ground Fault
Interrupter) type. The Steam Generator is properly grounded. The circuit breaker or disconnect switch is on. Water supply is open to the Steam Generator.
Protective
Plug
Covering
(Remove)
Modular Jack
Ground
Connection
03/09
- 2 -
L1 & L2 Power
Connections
Electrical
Supply Wire
208/240V
Steam Outlet
Safety Valve
Pub. No. 217-J
Page 3
Page 4
Electrical Installation Instructions
Wiring Diagram for SM-46 Generator Models: SM-46 and SM-79
119
SENSOR HEAT
START
TIME
STOP
TEMP
Typical Steamist
Control
W ater
Le v el
Probe
(Low V oltage)
Multi-Conductor
Cable*
WHT
GREY
L L C -1300-2 Circuit Board
P13
P4
L
P3
H
P5
XL
1 P
2 P
6 P
8 P
T H W
K L B
T ANK
Wiring Diagram for SM-79 Generator
119
SENSOR HEAT
START
TIME
STOP
TEMP
Typical Steamist
Control
W ater
Le v el
Probe
(Low V oltage)
Multi-Conductor
Cable*
WHT
GREY
T ANK
L L C -1300-2 Circuit Board
P13
P4
L
P3
H
P5
XL
2 P
6 P
8 P
T H W
D E R
K L B
Heating
Element
DS1
DS2
7 P
K L B
Heating
Element
DS1
DS2
1 P
7 P
K L B
DS3
DS4
9 P
Fuse 0.15 AMP
T H W
DS3
DS4
9 P
Fuse 0.15 AMP
T H W
D E R
S witch
See Chart
T est
S witch
See Chart
T est
D E R
T H W
GRN
P18
2 1 P
GRN
K L B
P18
2 1 P
K L B
T H W
K L B
1 1 P
1 1 P
T H W
P17
T H W
GRN GRN
P17
GRN GRN
0 1 P
P14
Dual
Kilowatt
Switch
0 1 P
P14
D E R
K L B
BLU
BLU
Dual
Kilowatt
Switch
BLU
BLU
NOTES: *Supplied with Controller.
**
Field Connections, see Specification Chart for proper wire size.
BLK BLK
GRN
W ater
Solenoid
V al v e
L1 L2
GND
NOTE: Check name plate for proper voltage, either 208 or 240 volts single phase.
Field
Connections**
NOTES: *Supplied with Controller.
**
Field Connections, see Specification Chart for proper wire size.
BLK BLK
GRN
W ater
Solenoid
V al v e
L1 L2
GND
NOTE: Check name plate for proper voltage, either 208 or 240 volts single phase.
Field
Connections**
Specication Chart
Model
No.
Max. Cu. Ft.
For Area Up To
60
SM-46
130
SM-79
220
300
03/09
Dual
KW
Volt Phase
240
4.5 208
240
6
208 240
7.5 208
240
9
208
East Coast Office: 25 E. Union Ave., East Rutherford, NJ 07073 • Tel: 800-577-6478 • Fax: 201-933-0746
®
West Coast Office: 315 W. Pondera St., Suite F, Lancaster, CA 93534 • Tel: 800-355-6478 • Fax: 661-940-1617
LED Color Chart
- 4 -
Line
Fuse
35 40 35 40
50 60 50 60
DS1 DS2 DS3 DS4
GRN
TIMER ON
YEL
HEAT ON
AMB
WATER FILL ON
RED
POWER ON
Pub. No. 217-J
Amps
1 1
1 1
1 1 1 1
Wire Size 90ºC
19 22
25 29
32 36 38 44
Copper AWG
8 8
8 8
8 6 8 6
Loading...