Steamist SM-12, SM-15 Installation Instructions Manual

Page 1
Steambath Generators
Models: SM-12 and SM-15
®
C
Electrical Installation Instructions
LISTED 995C
WARNING: Elderly persons, pregnant women, or those suffering from heart disease, high blood pressure, diabetes, or who are otherwise not in good health, do not use this device unless
!
IMPORTANT: the warranty of this product is voided if it is used in a commercial application or for anything other than a residential steambath installation. All electrical connections must be performed by a licensed electrician in accordance with Local and National Electric Codes.
directed to do so by a physician. Also, do not use steambath while under the influence of alcohol.
US
The Steamist “SM” generator operates with one or two controls appropriately located inside and/or outside the steamroom. It’s small enough in size to be tucked away using very little space in a vanity, closet, basement, or an insulated attic, but large enough to provide steam for most residential baths.
The Steamist “SM” Steambath Generator comes factory-assembled carefully wired and tested.
NOTE: The TC-110, TC-135, DSC-425, and DSP Controls are designed to work with all Steamist “SM” Generators.
1. Pre-Installation
Proper electrical supply (208 or 240 Volt): See rating
a)
label on Steam Generator and Chart on back page. Determine proper size of wire, voltage, amperage, and phase for the Steam Generator. Only UL rated 90°C wire can be used. In-line fuse/circuit breaker required: Fuse/circuit
b)
breaker to be installed must be sized in accordance with chart on back page. Do NOT install a GFI (Ground Fault Interrupter) to this equipment (per article 210-8 in the National Electric Code). Route power supply cable to the location where the
c)
Steam Generator will be installed (before walls are closed).
2. Electrical Rough-In
3. Steam Generator Electrical Installation
WARNING: All power to the steam generator must
be turned off.
a)
Remove the six screws holding the electrical access cover and remove cover.
b)
c)
Strip back power cable’s outer insulation jacket eight inches and insert into steam generator. Strip back insulation ½” from the three (3) incoming wires (two power and one ground).
d)
Insert ground wire into grounding lug located on the right side of the electrical compartment and secure.
CAUTION: Be sure the ground wire does not come in contact with a live electrical part.
e)
Locate the terminal block in the upper portion of the electrical box. Insert power wires into the power lugs on the right of the terminal block and secure.
4. Optional Auto Drain Valve Connection
Open knockout for Auto Drain Valve conduit
a)
connection. Route flexible conduit from valve to knockout and
b)
secure. Connect two wires from valve to the two place
c)
terminal strip provided (See figure 2).
a)
Route appropriate power cable to the location the Steam Generator will be installed. If receptacle is desired, mount the box for the receptacle near the location of the Steam Generator (See Figure 3: Typical Installation).
NOTE: The plug and receptacle require a rating of no less than 250V and proper amperage. Refer to chart on page 4 for amperage rating.
After the walls are complete, the Steam Generator and Control can be wired.
07/07
- 1 -
Knock-out for Control Cable
Electrical
Panel Cover
Figure 1
Steam Generator
Install Upright and Level
Knock-outs for
Electrical Supply Line
¾“ Steam
Outlet
¾“Safety
Relief Valve
Water Inlet
⅜“ Compression
Fitting
Optional Auto
Drain Installed
Pub. No. 323-H
Page 2
Checklist
Before starting, insure that the conditions of the following checklist have been met:
The proper size Steam Generator has been selected by using the sizing page in the “Full Line Brochure,” “Pricing Guide,” or “The Generator Sizing Guide” in the Residential Systems/Steambath Product Information section of the Steamist web site - www.steamist.com. CAUTION: An improperly sized Steam Generator will NOT produce the amount of steam necessary to reach selected temperature.
The proper voltage Steam Generator has been selected (i.e., 208V or 240V). A 208V generator operating on 240V will damage the heating element and a 240V Generator operating on 208V will result in a 25% loss of power.
Optional Steamist Splitter
for two Controls
Protective Covering
Plug
“Remove Before
Installation”
The Steam Generator is installed in an upright position.
The proper sized 90°C wire and circuit breaker have been used.
The circuit breaker is NOT a GFI (Ground Fault Interrupter) type.
The Steam Generator is properly grounded.
The circuit breaker or disconnect switch is on.
Water Supply is open to the Steam Generator.
Power Supply
L1 and L2
Water
Level
Probe
Printed
Circuit
Board
Modular Jack
Ground
Contactor / Relay
Single Phase
Connections Shown
Knock-Out
for Auto Drain
¾“ Steam
Outlet
Safety
Relief Valve
Water Inlet
⅜“ Compression
Fitting
07/07
Terminal Strip
for Auto Drain
Connection
Optional Auto
Drain Connection
- 2 -
½“ Out
When not equipped
with Auto Drain leave
drain line capped
and closed
Pub. No. 323-H
Page 3
NOTE: Unit must be wired with 90°C wire in a suitable raceway, or, if local codes allow, provide twist lock plug on a 90°C wire cord from generator to a 250V 2 pole, 3-wire grounding receptacle (amperage rating as required).
Outside Installation
TC-110 or
DSP Timer Only
The Electrical Instructions must be given to the homeowner for future use.
Inside Installation
Control should be mounted four
feet from the floor. Select a
location convenient to the
bather but not in a direct line of
Shower or Body Sprays and not
directly above the steamhead.
30
START
TIMER
STOP
TIMER
Appropriately fuse protected 208/240V field
wiring to Steam
generator.
Control Cable
Route from
Control to Steam
Generator in a
¾” conduit.
TC-135, DSC-425, and
DSP Temperature Control
MUST be installed inside
the shower.
115
START
TEMP
STOP
TEMP
07/07
IMPORTANT: Run the Control Cable through a ¾” conduit. Remove protective cap when making the final connection to Control.
Figure 3: Typical installation
- 3 -
Pub. No. 323-H
Page 4
SM-12/15 SINGLE PHASE SCHEMATIC
119
SENSOR HEAT
START
TIME
STOP
TEMP
Typical Steamist
Control
(Low Voltage)
Multi-Conductor
Cable*
LLC-1300-3 Circuit Board
P13
P4
L
P3
P5
YEL
P6
H
XL
P8
P2
RED
WHT
GREY
Test
P18
P11
P14
P10
BRN
RED
P17
GND
DS1
Switch
DS3
See
DS2
P1
P7
YEL
RED
Chart
DS4
Fuse 0.15 AMP
P9
P16
P15
P12
Water
Level
Probe
GRN
Heating
Elements
TANK
Model
No.
SM-12
Max. Cu. Ft.
For Area Up To
450 12
SPECIFICATION CHART
KW Volt Phase
240 208 240 208
240 208
15 550 SM-15
240 208
Amps
50
1
58
1 3
29
3
33
1
63
1
72
3
36
3
42
NOTES: * Supplied with Controller.
** Field Connections, use 90ºC wire, gauge No. See Chart Copper.
Wire Size 90ºC
Copper AWG
6 4
8 8 4 4 8 6
SM-12/15 THREE PHASE SCHEMATIC
119
SENSOR HEAT
START
TIME
STOP
TEMP
Typical Steamist
Control
(Low Voltage)
Multi-Conductor
Cable*
Water
Level
Probe
TANK
LLC-1300-3 Circuit Board
P13
P4
L
P3
P5
P6
YEL
Heating
Elements
H
XL
P8
RED
WHT
GREY
East Coast Office: 275 Veterans Blvd., Rutherford, NJ 07070 Tel: (800) 577-6478 Fax: (201) 933-0746
West Coast Office: 315 W. Pondera St., Suite F, Lancaster, CA 93534 Tel: (800) 355-6478 Fax: (661)940-1617
P2
RED
DS1
DS3
DS2
Fuse 0.15 AMP
P1
P7
YEL
DS4
P9
Test
P18 P17
Switch
See Chart
P16
BLK
BLK
BLK
P15
P12
P10
GND
BLU
BLU
GRN
P14
P11
NOTES: * Supplied with Controller.
** Field Connections, use 90ºC wire, gauge No. See Chart Copper.
GRN
BRN RED
GND
GRN
BLU
BLU
Line
Fuse
70 80 40 45
80 90 45 60
GND
Water
Solenoid
Valve
ORG
Fuse Block
RED
ORG
ORG
BLK
BLK
BLK
Terminal
RED
Block
Auto-Drain
ORG
Sensor
Water
Solenoid
Valve
Terminal
Block
Auto-Drain
Thermostat
BLK
DS1
DS2
DS3 DS4
Terminal Block
L1 L2 L3
Contactor / Relay
BLK
GND
L1
L2
Field
Connections
Contactor / Relay
L1
L2
L3
L4
BLK
COIL
Noise Filter
T1
T2
T3
T4
Optional
Auto-Drain
Valve
LED COLOR CHART
GRN
TIMER ON
YEL
HEAT ON
AMB
WATER FILL ON
RED
POWER ON
GND
L1
Field
L2
Connections
L3
T3
L3
COIL
L2
L1
BLK
T2
T1
Noise
Filter
Optional
Auto-Drain
Valve
**
**
07/07
- 4 -
Pub. No. 323-H
Page 5
Steambath Generators
Models: SM-12 and SM-15
®
C
Plumbing Installation Instructions
LISTED 995C
WARNING: Elderly persons, pregnant women, or those suffering from heart disease, high blood pressure, diabetes, or who are otherwise not in good health, do not use this device unless
!
directed to do so by a physician. Also, do not use steambath while under the influence of alcohol.
IMPORTANT: the warranty of this product is voided if it is used in a commercial application or for anything other than a residential steambath installation.
US
The Steamist “SM” Generator comes factory assembled, carefully wired and tested.
The Plumbing Installation must conform to local and national codes. All electrical power should be turned OFF when working with Steam Generator.
1. Pre-Installation
a)
Be sure that the proper size Steam Generator has been selected by using the sizing page in the “Full
Line Brochure,” “Pricing Guide,” “The Generator Sizing Guide,” Architectural Guidelines,” or in the
Residential Systems/Steambath Product Information section of the Steamist web site ­www.steamist.com.
CAUTION: An improperly sized Steam Generator may NOT produce the amount of steam necessary to reach selected temperature.
IMPORTANT: Refer to page 4 for model required for cubic foot rating.
b)
The Steam Generator should be located as close as possible to the Steam Room/Shower or tub enclosure. Steam pipe should NOT exceed twenty-five feet in length. If the steam pipe exceeds ten feet, use an appropriate pipe insulation rated for a minimum of 212°F. Possible locations include Vanity, Closets, Attic (insulated), or Basement near bath area. The serial number plate should be visible and the Steam Generator should be accessible for service. Refer to Installation Suggestion on the page
4. Do NOT install Generator outdoors, in a moist humid area, or in an area where parts may freeze or corrode. Also, do NOT install near flammable
c)
materials such as paints, thinners, gasoline, etc. The steam line and safety valve reach a temperature of 212°F during operation and should be appropriately protected to prevent personal injury by accidental contact.
2. Plumbing Rough-In
Plumbing rough-in is required for the water supply and steam line, this should be completed before the walls are closed. For operation, the “SM” Steam Generator
requires a ⅜” O.D. copper tubing to the fitting on the
generator for water inlet and ¾” copper or brass pipe for steam outlet.
NOTE: Safety Valve should be connected to a minimum ¾” indirect waste or as required by local plumbing codes. In the unlikely event this valve should open, the discharge must be directed to prevent damage to the home.
a)
Water Inlet - A water line should be roughed-in from
existing ½” hot or cold water pipe. Using a ½” x ⅜”
tee, cut and solder tee into the existing water line.
(See Figure 3 on page 3). Solder a piece of ⅜”
copper tubing into tee. Rough-in for water supply is now complete.
b)
Steam Outlet - Rough-in the steam line using a minimum of a ¾” copper or brass pipe, do NOT use black iron or galvanized pipe, it will rust and discolor the wall of the steam bath. The steamhead location should be 18” above the shower floor or 6” above the rim of the bathtub, as far from the seating area as possible.
CAUTION: No shut-off valve can be installed in the steam line. Do NOT create traps or valleys in this line which would trap condensation and block the flow of steam. The steam pipe should be pitched toward the Steam Generator allowing condensation to run back toward the Steam Generator (preferred), or toward the steamhead.
Knock-out for Control Cable
Knock-outs for
Electrical Supply Line
¾“ Steam
Outlet
Electrical
Panel Cover
Figure 1
Steam Generator
Install Upright and Level
¾“Safety
Relief Valve
Water Inlet
⅜“ Compression
Fitting
Optional Auto
Drain Installed
07/07
- 1 -
Pub. No. 324-G
Page 6
3. Steam Generator Installation
The Steam Generator should be mounted in a location convenient for hook-up and service by the Plumber and Electrician.
CAUTION: The steam generator is designed to be used ONLY in an upright and level position, to do otherwise would damage the unit and void the warranty.
a)
The steam generator can be mounted to a wall or set on the floor. However, the unit must be secured. To secure the unit to a vertical wall, loosen the two screws holding the electrical access cover, remove cover (see Figure 1). Located inside the cabinet near the top left and right corners are mounting holes. Place top cover back and secure.
b)
Connect the 3/8” water supply, described in Section 2 to the Steam Generator by first soldering a 3/8” valve into the previously installed water line. The valve must be kept in an open position during normal operation. In areas where high water pressure may be a problem a water hammer arrestor or a pressure regulator should be installed. Complete water supply by connecting 3/8” copper tubing from the valve to the water inlet compression fitting. Refer to Plumbing Diagram below.
IMPORTANT: Do NOT use a “saddle valve” or piercing type valve for water connection.
c)
Connect the steam line from rough-in location described in Section 2 to the ¾” nipple on the steam generator using a union.
d)
In the shower, place the center of the escutcheon onto the steam pipe and screw the steamhead into place. Care must be taken not to scratch the steamhead or escutcheon with wrench. Be sure the steam slot in the steamhead is facing down. After the plumbing connections are complete the electrician may finish wiring the unit.
Steam Generator
Electric Water
Solenoid Valve
Free Flowing
Steam Line
Union
(Required)
Water Level Probe
Hot or Cold
Incoming Water
Supply
Shut-off
Valve
Installation Instruction for Steamhead & Escutcheon
(Supplied with control package)
1.
Be sure the steam pipe is installed with the proper length pipe protruding through the wall.
2.
Apply silicone sealant around the pipe to seal the pipe to the wall.
3.
Slip the Escutcheon over the steamhead loosely.
4.
Screw on the steamhead making sure the steam opening is facing down.
5.
Hold the Escutcheon against the wall and tighten the retaining screw facing down.
Steam Pipe
Escutcheon
Steamhead
Apply silicone around
the steam pipe to form
a water tight seal
Tighten the screw to the
steamhead with the screw
to face down
WARNING: When installing a steam pipe into a steam room made out of Acrylic, Cultured Marble, Corian, Swanstone, Resin, Plastic or an equivalent type of material, consult the manufacturer of the material for their recommendation on location of the steam pipe. Verify that the type of material used for the construction of the steam room is rated for a steam room environment. When installing a steam pipe, in the mentioned material type rooms, it is very critical in making sure that when the steam pipe protrudes into the steam room that it is centered in its 1¼” hole and does not touch the edge of the wall material around the steam pipe.
IMPORTANT: An optional steam diffuser (Not Included) is strongly recommended for small steam rooms. This option helps to better diffuse the steam and makes the steambath more comfortable. This option may not be necessary in larger steam rooms where the bather is sitting a few feet away from the steamhead.
IMPORTANT: Install
steam head 18” above
the shower floor or 6”
above the rim of the
Bathtub.
07/07
Optional Auto Drain Valve
Connect to Indirect Waste
or as Required by Local Codes.
Pressure Safety Valve
Connect to Indirect Waste
or as Required by Local Codes.
- 2 -
Figure 2: Plumbing Diagram
Pub. No. 324-G
Page 7
WARNING: When installing the Steamist Unit in conjunction with an acrylic modular tub/shower unit, please consult the “manufacturer of the module” for location of the steamhead.
Outside Installation
TC-110 or
DSP Timer Only
The Plumbing Instructions must be given to the homeowner for future use.
Slope ceiling 2” per foot
TC-135, DSC-425, and
DSP Temperature Control
MUST be installed inside
the Steam Room.
30
START
TIMER
STOP
TIMER
Required
Safety Valve
Connect ¾” pipe to an
indirect waste or as
required by Local Codes.
⅜” Shut-off Valve
Keep in open
position during
normal operation.
Union
½“ x ½” x ⅜” Tee.
Using existing Hot or
Cold water supply.
A ⅜” air gap is recommended below the
door and the door should incorporate a
splashguard. The top and sides of the
shower opening must be sealed.
115
START
TEMP
STOP
TEMP
Steamhead Installation
Steamhead should be mounted
18” above the finished floor or
6” above the rim of the tub as
far from the bather as possible.
07/07
Steam Outlet Pipe - Use a minimum of a ¾” Copper or Brass pipe. CAUTION: Do NOT install a Shut-off valve on the Steam outlet pipe. Do NOT
create traps or valleys in this line which would prevent the flow of steam. The steam outlet pipe should be pitched toward the Steam Generator (preferred), allowing condensation to run back into the Steam Generator or toward the steam head. If the steam pipe exceeds ten feet, use an appropriate pipe insulation rated
for a minimum of 212°F.
Figure 3: Typical installation
- 3 -
Pub. No. 324-G
Page 8
Access Requirements
Optional Auto Drain
35”
Use 35” with
Select a location for mounting the Steam Generator that is accessible for installation and service. The access requirement indicates the minimum space for convenient access to Steam Generator.
28”
Installation Suggestions
18”
CAUTION: All models must be installed INDOORS, in a DRY, NON-FREEZING location away from flammable materials such as: Gasoline, Paints, Thinners, Etc...
IMPORTANT: Steam Generator must be installed upright and level.
20”
Model
SM-12
SM-15
No.
For Area Up To
* Max. Cu. Ft.
* Refer to the Steamist Sizing Guide for actual Cu. Ft. capacity.
Alternate Attic Location
(Insulate to Prevent Freezing)
SPECIFICATION CHART
KW Volt Phase
240
450
550
208
12
240 208
240 208
15
240 208
Wire Size 90ºC
Amps
1 1
3 3
1 1
3 3
50 58
29 33
63 72
36 42
Copper AWG
6 4
8 8
4 4
8 6
Line
Fuse
70 80
40 45
80 90
45 60
Steam
Generator
in Vanity
30
START
TIMER
STOP
TIMER
122
TEMP
START
STOP
TEMP
Alternate
Closet
Location
Alternate Basement Location
(Insulated and Dry)
07/07
East Coast Office: 275 Veterans Blvd., Rutherford, NJ 07070 Tel: (800) 577-6478 Fax: (201) 933-0746
West Coast Office: 315 W. Pondera St., Suite F, Lancaster, CA 93534 Tel: (800) 355-6478 Fax: (661)940-1617
- 4 -
Pub. No. 324-G
Page 9
Master/Slave Installation Instructions
Introduction:
The System-30 consists of one SM-15 Master and one SM-15 Slave. The Master/Slave generators are 15 kilowatts each. This instruction sheet is to be used in conjunction with the standard SM-15 Electrical and Plumbing instructions (Pub. No. 323 and 324). All connections both plumbing and electrical must be kept completely separate.
Danger: To reduce the risk of explosion. DO NOT interconnect the steam outlets.
Operation: The Master/Slave generators operate as two completely separate generators. The steam bath controls are connected to the Master Generator. When the Master Generator is started up from the controller, it then turns on the Slave Generator and both units produce steam at the same time.
NOTE: The following specifications apply to each of the two Generators, wired and plumbed separately.
Slave
Steambath Generators
System-30
®
C
LISTED 995C
Master
US
Electrical
Note: See separate electrical instruction. Pub. No. 323.
Main Power Connection: Each Steam Generator
requires a separate incoming power service.
Important: The System-30 consists of two 15 kilowatt Steam Generators, therefore reference Specification Chart below.
Master/Slave Interconnection: The only common connection between the Master/Slave generators is as follows: Connect the cable (supplied with Slave Unit) from Telco receptacle at Slave Unit to same at the Master Unit (See diagram on back).
Control Connection: The controls are to be connected to the Master Generator as described in the control installation instructions.
SPECIFICATION CHART
Max. Cu. Ft.
For Area Up To KW Volt Phase
1100 2 @ 15
240 208 240 208
Plumbing
Note: See separate electrical instruction. Pub. No. 324.
Water Connection: The two Generators may be
connected to a single water line with a tee connection to the water inlet of each Generator.
Steam Connection: Each Generator must be connected to a separate Steamhead using ¾” brass or copper pipe.
Drain Connection: When the optional drain connection is made, it must be completely separate from the each Generator.
Safety Valve Connection: The Safety Valve must be connected per the local plumbing code. Then its connection must be completely separate from each Generator.
Amps
1 1
3 3
2 @ 63 2 @ 72
2 @ 36 2 @ 42
Wire Size 90ºC
Copper AWG
2 @ 4 2 @ 4
2 @ 8 2 @ 6
Line
Fuse
2 @ 80 2 @ 90 2 @ 45 2 @ 60
07/07
- 1 -
Pub. No. 563-C
Page 10
To Slave
Unit
To Control
Diagram 1
When using one Control
Splitter supplied
with Slave Unit
IMPORTANT: System-30
will NOT work with a
TC-110 by itself
(a Thermostatic Control is
needed for this application)
To Slave Unit
Diagram 2
When using
two Controls
To Controls
Splitter
supplied
with control
Splitter
supplied
with Slave
Generator
Modular Jack
From
Master
Unit
Optional Auto Drain
for installation instructions
(see Pub. No. 577)
Master
Slave
Plug
Modular Jack
Slave Interface
Board
East Coast Office: 275 Veterans Blvd., Rutherford, NJ 07070 Tel: (800) 577-6478 Fax: (201) 933-0746
West Coast Office: 315 W. Pondera St., Suite F, Lancaster, CA 93534 Tel: (800) 355-6478 Fax: (661)940-1617
Each generator requires it’s own steamhead. When a system is purchased you receive (2) steamheads. (1) with the control and (1) with the slave generator. You must not install these steamheads any closer than 6”. Steamheads must be 18” from the finished floor or 6” above the rim of the tub.
07/07
- 2 -
Pub. No. 563-C
Page 11
InstaMist
Info
Warning: Do not turn on the power to the steam generator until the installation is
complete and the unit is ready to test/use. If the steam generator will not be in use for long periods of time (over 6 months) the power to the steam generator should be turned off.
Important: In order for the InstaMist feature to function, water must always be in the tank. For this reason the Optional Auto-Drain can NOT be used with any InstaMist generators.
The Steamist InstaMist Feature (-IM) is only available as a factory installed option on the following Models: SM-5, SM-7, SM-8, SM-11, SM-12, SM-15, System-18, System-24, and System-30.
Live Power
Connecon
The Steamist InstaMist generators feature pre-heat function, which provides a generous volume of steam in under a minute. This new feature maintains an average water temperature of 180°F in the stainless steel reservior. When the steam generator is activated, the pre-heated water inside the steam generator quickly reaches the boiling point, allowing steam to flow out in under a minute.
All Steamist steam generators with or without InstaMist are factory assembled and tested. There are no additional Plumbing or Electrical requirements needed in the field for generators with the InstaMist feature. The installation instructions for the plumber and the electrician are provided with the steam generator and need to be followed.
125 Wa
Heater
Hi-Limit
Switch
Thermostat
07/07
Pub. No. 124-A
Loading...