State Water Heaters TPD-140-140, TPG-600-2500, TPG-140-140, TPD-600-2500, TPO-140-140 Instruction Manual

...
MODELS TPG-140-140 thru 600-2500
INCLUDING TPX/TPO & TPD
COMMERCIAL GAS, OIL AND GAS/OIL TANK-TYPE WATER HEATERS
INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY
ASME
CAUTION
WARNING – PROPANE MODEL
Water heaters for propane gas are different from natural gas models. A natural gas heater will not function safely on propane gas and no attempt should be made to convert a heater from natural gas to propane gas.
Propane gas must be used with great caution. It is highly explosive and heavier than air. It collects first in the low areas making its odor difficult to detect. If propane gas is present or even suspected, do not attempt to find the cause yourself. Ventilate the room, then call your gas supplier or service agent. Keep area clear until a service agent has been called.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE
PRINTED IN U.S.A. 1202 PART NO. 09063370T
1
FOREWORD
This manual is intended to be used in conjunction with other literature provided with the heater. This includes power burner and related gas control information. It is important that this manual and the additional publications be reviewed in their entirety before beginning any work.
The installation should be made in accordance with the regulations of the local code authorities and utility companies, which pertain to this type of water heating equipment.
MAKE SURE the fuel on which the heater will operate is the same
as that specified on the heater model and rating plate.
THESE HEATERS MUST NOT BE INSTALLED ON COMBUSTIBLE FLOORS.
Instructions for periodic testing of various water heater safety devices are included in section titled COMBUSTION
TABLE OF CONTENTS
PAGE
FOREWORD ................................................................................ 2
IDENTIFICATION ......................................................................... 2
GENERAL SAFETY INFORMATION ........................................... 3
Precautions ............................................................................. 3
Grounding Instructions ............................................................ 3
Improper Combustion .............................................................. 3
Liquid Petroleum Models ......................................................... 3
Extended Non-Use Periods (TPG Models Only) ..................... 3
Insulation Blankets .................................................................. 3
High Altitude Installations ........................................................ 3-4
FEATURES .................................................................................. 4
Water Temperature Control ..................................................... 4
INSTALLATION INSTRUCTIONS ................................................ 4
Required Ability ....................................................................... 4
Uncrating ................................................................................. 4-5
Locating the Heater ................................................................. 5
Leveling ................................................................................... 5
Clearances .............................................................................. 5
Air Requirements ..................................................................... 5-6
Thermal Expansion (Closed System) ...................................... 6
Venting .................................................................................... 6
Vent Connector........................................................................ 6
Barometric Draft Control Assembly ......................................... 6-7
Water Line Connections .......................................................... 7
Thermometers (Not Supplied) ................................................. 7
Relief Valve ............................................................................. 7
ARRANGEMENT REQUIREMENTS AND SERVICE RECOMMENDATIONS.
In the absence of local codes, the installation must comply with the instruction as outlined in the latest publication of ANSI booklet NFPA-54/ANSI Z223.1
“NATIONAL ELECTRICAL CODE”, or Canadian Gas
70
“NATIONAL FUEL GAS CODE”, NFPA No.
Association booklet CAN 1-B149.1 or CAN 1-B149.2 for Canadian Installations also be followed.
These manuals can be purchased from the American Gas Association Laboratories, 8501 East Pleasant Valley Road, Cleveland, OH 44131 or the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269-9101, or Canadian Gas Association Laboratories, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B 2R3.
PAGE
Gas Piping ............................................................................... 7-8
Purging .................................................................................... 8
Gas Meter Size (City Gases Only) .......................................... 8
Gas Pressure Regulator .......................................................... 8
Wiring ...................................................................................... 8-11
TWO UNIT MANIFOLD INSTALLATION ..................................... 11
OPERATION ................................................................................ 11
Important ................................................................................. 11
General .................................................................................... 11
Filling ....................................................................................... 11
Combustion Air Requirements
And Service Recommendations .............................................. 11-12
MAINTENANCE ........................................................................... 12
General .................................................................................... 12
Flushing ................................................................................... 12
Draining ................................................................................... 12
Sediment Removal .................................................................. 12
Lime Scale Removal ............................................................... 12-13
Relief Valve ............................................................................. 13
Power Burner ........................................................................... 13-14
Cleaning Flues - TPO & TPD Only .......................................... 14
Vent Systems .......................................................................... 14
Barometric Draft Control ......................................................... 14
TROUBLESHOOTING ................................................................. 14-15
Replacement Parts .................................................................. 15
LIMITED WARRANTY ................................................................. 16
This manual is supplemented by the power burner manual. All information, including start-up and
maintenance relating to the burner, can be found in that manual.
IDENTIFICATION
The heater and burner mounted identification plates provide valuable information. When ordering parts or inquiring about a unit, be sure to include serial number, model number and type of fuel.
2
GENERAL SAFETY
INFORMATION
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDERWATER. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE BEEN MADE BY A QUALIFIED SERVICEMAN.
The venting of the water heater should be inspected by a qualified service technician at the time of installation and periodically thereafter to ensure a down-draft condition does not exist.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION.
LIQUID PETROLEUM MODELS
Water heaters for propane or liquefied petroleum gas (LPG) are different from natural gas models. A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas.
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER. 4 SOOTING.
Heater must be protected from freezing downdrafts during shutdown periods.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the National Electric Code and/or local codes. These must be followed in all cases.
This water heater must be connected to a grounded metal, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater.
CHEMICAL VAPOR CORROSION
WARNING
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS WHICH BREAK DOWN INTO ACIDS AT HIGH TEMPERATURE. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
LP gas must be used with great caution. It is highly explosive and heavier than air. It collects first in the low areas making its odor difficult to detect at nose level. If LP gas is present or even suspected, do not attempt to find the cause yourself. Ventilate the area, then call your gas supplier or service agent. Keep area clear until a service call has been made.
The presence of LP gas may be difficult to detect. The use of a propane gas detector is recommended.
Only trained LP professionals should conduct the required safety checks in accordance with industry standards.
EXTENDED NON-USE PERIODS
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE. To reduce the risk of injury under these conditions,
it is recommended that a hot water faucet be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. THERE SHOULD BE NO SMOKING OR
OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals and typical compounds which are potentially corrosive. Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions).
IMPROPER COMBUSTION
WARNING
ATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE POISONING AND DEATH.
OPERATING OF THESE FANS CAN PRODUCE A DOWN DRAFT IN THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY OR VENT PIPE.
INSULATION BLANKETS
Insulation blankets available to the general public for external use on gas water heaters are not approved for use on your State water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your State water heater meets or exceeds the ASHRAE/ IES 90.1b-1992 standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary.
WARNING
The application of an insulation blanket will void the warranty for this water heater. Furthermore, the application of an insulation blanket may interfere with the operation of this water heater, possibly resulting in property damage, injury, or death.
HIGH ALTITUDE INSTALLATIONS
Your State water heater has been designed to operate at altitudes above 2000 feet, provided that requirement was specified at the time of order. The firing rate will be specified on the water heater rating plate.
3
Note: Some gas utility companies derate the heating value of the supplied gas at high elevations. Your authorized State Start-Up Agent must adjust for actual heating valve of the gas at the time of start-up.
FEATURES
WATER TEMPERATURE CONTROL
The water temperature is controlled by two thermostats. One thermostat is located near the top of the tank and the other is in the lower part of the tank. The upper thermostat must be set at least 5°F higher than the lower thermostat. In the case where the water heater has electronic thermostats, this differential has been factory set and cannot be changed.
The thermostat temperature dials are accessible by opening the control compartment cover.
WARNING
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/ OR DEATH. THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE HOT WATER TAP, OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET TEMPERATURES.
SETTING THE WATER HEATER TEMPERATURE AT 120°F WILL REDUCE THE RISK OF SCALDS. Some states or provinces
require settings at specific lower temperatures.
Below you will find listed the appropriate time-to-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F (11°C). If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards.
Temperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
180°F (82°C) Nearly Instantaneous 170°F (77°C) Nearly Instantaneous 160°F (71°C) About 1/2 Second 150°F (65°C) About 1-1/2 Seconds 140°F (60°C) Less than 5 Seconds 130°F (54°C) About 30 Seconds 120°F (49°C) More than 5 Minutes
Valves for reducing point-of-use temperature by mixing cold and hot water are available. Also available are inexpensive devices that attach to faucets to limit hot water temperatures. licensed plumber or the local plumbing authority.
Contact a
FIGURE 1
A high limit switch interrupts the power burner operation should the water temperature reach 200°F.
The high limit switch must be manually reset by depressing the red button on the front of the control when water temperature drops to about 180°F. The manual reset high limit can be found inside the control compartment.
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER IS REQUIRED TO BE PERFORMED BY AN AUTHORIZED STATE STARTUP AGENT. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
UNCRATING
The heater should be moved in the crate as close as possible to the installation site. Depending upon size, shipping weights range from about 1,300 to 4,500 pounds.
The installer should be guided by the instructions furnished with the heater, local codes and utility company requirements. Preference should be given to codes and requirements where they differ from the heater furnished instructions.
Additional publications, which should guide the installer, include:
The latest version of the from American Gas Association Laboratories, 8501 East Pleasant Valley Road, Cleveland, OH 44131.
In Canada – CGA No. B149 (latest version), from Canadian Gas Association Laboratories, 55 Scarsdale Road, Don Mills, Ontario, Canada M3B 2R3.
Code for the installation of Heat Producing Appliances (latest version), from American Insurance Association, 85 John Street, New York, NY 11038.
National Fuel Gas Code, ANSI Z223.1,
4
The latest version of the National Electrical Code, NFPA No.
70. In Canada refer to Canadian Electrical Code C 22.1, from National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269-9101.
A clearance of 24” should be maintained from serviceable parts, such as relief valve, power burner, thermostat and drain valve.
MINIMUM INST ALLATION CLEARANCES
LOCA TING THE HEATER
When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERA TED OR REPAIRED. FLAMMABLE V APORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S IGNITION SYSTEM OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION.
SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IF INST ALLED 18 INCHES OR MORE ABOVE THE FLOOR. THIS MA Y REDUCE THE RISK IF LOCA TION IN SUCH AN AREA CANNOT BE AVOIDED.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
TPG/TPX TPO/TPD
FRONT - 18 Inches FRONT - 18 Inches
BACK - 0 Inches Back - 6 Inches
TOP - 5 Inches Top - 12 Inches
LEFT SIDE - 0 Inches LEFT SIDE - 6 Inches
RIGHT SIDE - 0 Inches RIGHT SIDE - 6 Inches
NOTE: If a chimney connector is used, the minimum clearance from the top of the unit to the connector is 18 inches.
AIR REQUIREMENTS
WARNING
FOR SAFE OPERATION, AN AMPLE SUPPLY OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILATION AIR IN ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILATION, OF THE FUEL GAS CODE, NFPA-54/ANSI Z223.1 OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES. AN INSUFFICIENT SUPPLY OF AIR WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE HEAT EXCHANGER AND CREA TING A RISK OF ASPHYXIATION. DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILA TION AIR.
UNCONFINED SP ACE
NATIONAL
WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.
LOCATE HEATER NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCA TED IN AN AREA WHERE LEAKAGE FROM
THE TANK OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE A VOIDED, A SUIT ABLE METAL DRAIN PAN, ADEQUATELY DRAINED, SHOULD BE INSTALLED UNDER THE HEATER. Such pans should be fabricated with sides at least 2” deep, with length and width at least 2” greater than the diameter of the heater and must be piped to an adequate drain. The pan must not restrict combustion air flow.
This unit must be installed on a non-combustible surface.
LEVELING
The heater shall be installed level. If it is necessary to adjust the heater, use metal shims under the channel-type skid base.
In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion.
If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood dilution must be obtained from outdoors or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
CONFINED SPACE
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btu/hr of the total input of all appliances in the enclosure, but not less than 100 square inches.
If the confined space is within a building of tight construction, air for combustion, ventilation and draft dilution must be obtained from outdoors. When directly venting with the outdoors or venting with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btu/hr of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btu/hr of the total input of all appliances in the enclosure.
CLEARANCES
Provide ample clearance on all sides for installation, adjustment and replacement of burner, control components and other parts.
Where an exhaust fan is installed in the same room with the boiler, sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY OR OTHER
5
UNDESIRABLE OPENINGS, CAUSING POOR COMBUSTION. SOOTING MAY RESULT WITH AN INCREASED RISK OF ASPHYXIATION.
THERMAL EXPANSION (CLOSED SYSTEM)
Thermal expansion occurs in any hot water system when system water is heated or “recovered” during periods of non-use.
If the system is operated in an “open” condition such as being connected directly to the city main, the volume of expanded water generated during the recovery periods can be dissipated back through the “open” connection to the city main so pressure cannot increase.
However, once a back flow preventer is installed to isolate system water from the public supply; or a pressure reducing valve is installed to protect a water meter; or any device preventing flow back into the cold water supply, the “open” condition becomes “closed”. During periods of temperature recovery and no usage, water expands and the pressure increases until a relief valve opens spilling hot water.
A relief valve opening on pressure will flow small amounts of water, whereas relieving on temperature releases large amounts of water. Consult the section under “High Water Temperature” to determine the cause of the relief valve to open due to temperature.
Since the water is not compressible, some provision must be made for THERMAL EXPANSION to protect the system from excessive pressures. Two options are:
VENT CONNECTOR
The chimney vent connector diameter should be the same size as the heater flue outlet, see table 1. A minimum rise of 1/4” per foot of horizontal connector length must be maintained between the heater and chimney opening, fig. 2. The connector length should be kept as short as possible.
TABLE 1
TPG/TPX/TPO/TPD FLUE OUTLET
INPUT (KBTUh) (INCHES)
140, 199 5
255, 270, 300 6
400 7
540, 600 8
720, 800, 1000 10
1250, 1500 12 1750, 2000 14 2250, 2500 16
BAROMETRIC DRAFT CONTROL ASSEMBLY
A double-acting barometric draft control assembly is provided with each unit. This assembly must be attached to the heater as shown in figure 2. The direction in which the outlet to the draft control assembly faces is arbitrary. This assembly must be fitted to the jacket cover such that it is plumb and level to the ground. Fasten the draft control assembly to the top cover using sheet metal screws at three locations, or more, as required.
1. Install an expansion tank properly and adequately sized for the expanding volume of water.
2. Install a pressure relief valve in the cold water supply line having a setting of at least 10lbs. located at or near a suitable drain. This valve will open at each heat cycle when there is no hot water demand on the system.
Service problems or parts failure due to excessive pressure are NOT covered under warranty.
The pressure and temperature relief valve supplied with the water
IS NOT considered to be protection against thermal
heater expansion.
below the system working pressure,
VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Heater must be protected from freezing downdrafts during shutdown periods.
Remove all soot or other obstructions from chimney, which will retard free draft.
Refer to the instructions provided with the barometric damper for complete installation requirements.
Dampers or other obstructions must not be installed between the heater and the barometric draft control assembly.
Barometric draft control counterweights can be adjusted for installation conditions by an authorized State Start-Up Agent. Any readjustment must be by authorized State Start-Up agent.
PROPER DRAFT CONTROLLER AND
VENT PIPE INSTALLATION - FIGURE 2
VENT CONNECTION
Venting materials used for this category 1 appliance must be in accordance with the National Fuel Gas Code and all state and local requirements.
NOTE: A NEGATIVE DRAFT MUST BE MAINTAINED IN VENT PIPING (-0.02 to -0.06).
Vent connections must be made to an adequate stack or chimney. Refer to the National Fuel Gas Code or to the vent pipe manufacturer’s gas vent and chimney sizing table to properly design and size the venting system. Refer to Table 2 for the vent pipe size required for installation to the barometric draft control assembly outlet.
6
TABLE 2
CAPACITY OF PIPE - NATURAL GAS IN CUBIC FEET PER HOUR
Maximum Based Upon Pressure Drop of 0.3” w.c. and Specific Gravity
of 0.60 and Maximum Gas Pressure of .5 psig.
Pipe Length Pipe Size - Inches (IPS)
In Feet 1 1 1/4 1 1/2 2 2 1/2 3 4
10 520 1050 1600 3050 4800 8500 17500 20 350 730 1100 2100 3300 5900 12000 30 285 590 890 1650 2700 4700 9700 40 245 500 760 1450 2300 4100 8300 50 215 440 670 1270 2000 3600 7400 60 195 400 610 1150 1850 3250 6800 70 180 370 560 1050 1700 3000 6200 80 170 350 530 990 1600 2800 5800
90 160 320 490 930 1500 2600 5400 100 150 305 460 870 1400 2500 5100 125 130 275 410 780 1250 2200 4500 150 120 250 380 710 1130 2000 4100 175 110 225 350 650 1050 1850 3800 200 100 210 320 610 980 1700 3500
NOTE: Use Multiplier at right for other specific gravities and pressure drops.
CORRECTION FACTORS
Specific Gravity Pressure Drop Other than 0.60 Other than 0.3
Specific Multplier Pressure Multiplier
Gravity Drop
0.50 1.10 0.1 0.577
0.60 1.00 0.2 0.815
0.70 0.926 0.3 1.00
0.80 0.867 0.4 1.16
0.90 0.817 0.6 1.42
1.00 0.775 0.8 1.64
Propane - Air 1.0 1.83
1.10 0.740 2.0 2.58
Propane 3.0 3.16
1.55 0.622 4.0 3.65
6.0 4.47
8.0 5.15
Where an existing chimney or vent is to be used, be sure that the chimney or vent has adequate capacity for the number and sizes of gas appliances being vented through it. Inspect the chimney or vent and remove all soot or other obstructions, which will retard free draft.
Vent piping making horizontal runs must have a minimum upward slope toward the chimney or vent of 1/4” per foot. Vent pipe length should be kept as short as possible. Be sure that the vent pipe does not extend beyond the inside wall of a chimney.
In venting systems, where a continuous or intermittent back (positive) draft is found to exist, the cause must be determined and corrected. In some cases, a special vent cap may be required.
WATER LINE CONNECTIONS
The water heater may be installed by itself, or with a separate storage tank, on both single and two-temperature systems. When used with a separate storage tank, the circulation may be either by gravity or by means of a circulating pump.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported.
THERMOMETERS (Not supplied)
WARNING
THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSIONS, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF VALVE AND THE TANK.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
Your local code authority may have other specific relief valve requirements.
GAS PIPING
Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.
Thermometers should be obtained and field installed as shown in the installation diagrams.
Thermometers are installed in the system as a means of detecting the temperature of the outlet water.
RELIEF VALVE
This water heater has been provided with an ASME rated pressure and temperature relief valve.
In addition to the appliance relief valve, each remote storage tank, which may be used in conjunction with this appliance, shall also be installed with a properly sized, rated and approved temperature (ANSI) and pressure (ASME) relief valve(s).
Size the main gas line in accordance with Table 3. The figures shown are for straight lengths of pipe at 0.3 in. w.c. pressure drop, which is considered normal for low-pressure systems. Note that fittings such as elbows and tees will add to the pipe pressure drop.
Equivalent lengths of standard pipe in feet for listed fittings (add below values to Table 3).
Install vent lines from main gas regulator and (if applicable) a diaphragm gas valve. Vent line should be run to the outside of the building, terminating clear of windows or fresh air intakes. Outside terminal of vent should have a screen to prevent insects from building nests in vent pipe. The vent should terminate in a manner, which will preclude the possibility of water, snow, dirt or other matter from entering the line.
7
TABLE 3
EQUIVALENT LENGTH OF FITTINGS IN FEET
Pipe Size (IPS) 1 1.25 1.5 2 2.5 3 4 Std. Tee through side 5.5 7.5 9.0 12.0 14.0 17.0 22.0 Std. E11 2.7 3.7 4.3 5.5 6.5 8.0 12.0 45°F E11 1.2 1.6 2.0 2.5 3.0 3.7 5.0 Plug Cock 3.0 4.0 5.5 7.5 9.0 12.0 16.0
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 13.8” WATER COLUMN (1/2 POUND PER SQUARE INCH) SUPPLY GAS PRESSURE. HIGHER GAS PRESSURE REQUIRES SUPPLEMENTAL REDUCING SERVICE REGULATION. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR DURING ICE STORMS.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEANED ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING. THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipes to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG. GAS SUPPLY LINE MUST BE CAPPED WHEN
DISCONNECTED FROM THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG OR LESS, THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. USE SOAP AND WATER SOLUTION OR
OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING GAS LEAKS. DO NOT USE MATCHES, CANDLES,
FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
NATIONAL FUEL GAS CODE.
PURGING
Gas line purging is required with new piping or systems in which air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE. TO AVOID RISK OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED.
GAS METER SIZE – CITY GASES ONLY
Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, request the gas company to install a meter having adequate capacity.
GAS PRESSURE REGULATOR
DO NOT SUBJECT COMBINATION GAS VALVE TO INLET GAS PRESSURE OF MORE THAN 14 I.W.C. A SERVICE REGULATOR IS NECESSARY IF HIGH GAS PRESSURES ARE ENCOUNTERED.
The gas pressure regulator vent line must be vented to the outside of the building.
POWER BURNER
For information relating to the power burner supplied with this water heater, refer to the power burner manual provided.
LIFTING LUGS
This water heater is supplied with lifting lugs. Prior to lifting, insure that the lugs are threaded into their receptacles as tight as possible.
These lugs may be removed after installation. Sheet metal covers are provided to cover the receptacle openings.
WIRING
The rating plate provides the electrical information needed to size the water heater branch supply circuit.
Typical water heater electrical diagrams are provided in this manual (pages 9 and 10). The actual diagram, corresponding to each water heater, is provided with each water heater, and may differ from the diagrams shown in this manual.
The TPG unit burner is wired to the water heater control compartment as shown in the following diagram. The electrical service should be connected to the N & L Terminals located in the control compartment. Ground from control compartment to suitable ground.
All electrical work must be installed in accordance with the Electrical Code (latest version) and local requirements. AN
ELECTRICAL GROUND IS REQUIRED TO REDUCE THE RISK OF ELECTRICAL SHOCK. DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE HEATER TANK IS FILLED WITH WATER.
National
8
TYPICAL WIRE DIAGRAM
TPG, 270 - 2,500 KBTUH TPO, 800 - 2,500 KBTUH TPD, 400 - 2,500 KBTUH
TYPICAL WIRE DIAGRAM
TPG, 140 - 255 KBTUH
9
TYPICAL WIRE DIAGRAM
TPD, 140 - 300 KBTUH
TYPICAL WIRE DIAGRAM
TPO, 140 - 720 KBTUH
10
TWO UNIT MANIFOLD
INSTALLATION
The time to ask any questions you may have about your unit is when the State Authorized TPG/TPO/TPD Start-Up Agent is there. Please do not hesitate to ask the agent any questions which you may have regarding the units start-up, operation or maintenance.
Assure water flow balance of all units. Without this balance, the full water heating and storage potential of the system cannot be achieved. Otherwise, the units with the higher water flow may have a shortened life.
Dimensions shown are for minimum space occupied by complete assemblies. Service space in front of units must be included.
MODEL MANIFOLD SIZE
TPX/TPG/TPO/TPD - 140 2” TPX/TPG/TPO/TPD - 200 2 1/2” TPX/TPG/TPO/TPD - 300 2 1/2” TPX/TPG/TPO/TPD - 400 3” TPX/TPG/TPO/TPD - 600 3”
A MAINTENANCE section is included at the rear of this manual. Any service required should be performed by an Authorized State Service Agent.
GENERAL
NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER.
CAUTION
Before proceeding with the operation of the unit make sure the water heater and system are filled with water and all air is expelled.
FILLING
1. Close the heater drain valve by turning handle clockwise.
2. Open a nearby hot water faucet to permit the air in the system to escape.
3. Fully open the cold water inlet pipe valve allowing the heater and piping to be filled.
4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.
OPERATION
IMPORTANT
AUTHORIZED START-UP REQUIRED. Start-up by a State Authorized TPG/TPX/TPO/TPD Start-Up Agent is required on the models covered in this manual. Start-up and Operation of the units covered by this manual by other than a State Authorized TPG/TPX/TPO/TPD Start-Up Agent will void the warranty.
If you have not already done so, contact your local State Sales Representative or Authorized TPG/TPX/TPO/TPD Start-Up Agent and set-up a date for the start-up service.
The Authorized Start-Up Agent will when they come out to start-up the unit(s) complete one of the following forms for each unit you have and submit it to State Industries to activate your warranty:
Start-Up Covering Models
Form No.
09063511 TPG Models, 140 - 255 kBTUH 09063510 TPG Models, 270 - 2500 kBTUH 09063512 TPD Models, 140 - 2500 kBTUH 09063514 TPO Models, 140 - 2500 kBTUH 09063515 TPX Models, 400 - 2000 kBTUH
COMBUSTION AIR REQUIREMENTS AND
SERVICE RECOMMENDATIONS
1. In order to fire correctly, the burner requires an adequate supply of combustion air. Ventilation to the boiler room should be provided on the basis of one square inch of free air opening for each 1000 BTU/HR input. This excludes the requirements for any other fired equipment in the room. The boiler room should not become excessively hot and under no circumstances should be under negative pressure.
2. The burner must be set up initially and serviced at regular intervals (suggested semi-annually) by a trained serviceman using the proper instruments. During this semi-annual service, primary safety devices should be tested under operating conditions. Failure to routinely test primary safety devices may cause hazards. Suggested test procedures are listed in the following paragraphs. Failure to maintain the correct burner settings may result in inefficient gas consumption, premature wear of burner components, or explosion hazard.
3. The correct test instruments are:
•CO
CO indicator
Stack thermometer
Draft gauge or inclined manometer
U-tube manometer or calibrated 0-10” and 0-35” w.c.
Combination volt/ammeter.
indicator or 02 analyzer
2
pressure gauge
11
Suggested safety device test procedures are:
DRAINING
A. While heater is operating, turn valve, main burner and pilot
gas line manual gas cocks to the OFF position. Burner should shutdown within 3-4 seconds and lockout on flame failure, requiring reset of the flame safeguard device.
B. While heater is operating, lower the setting of each of (2)
operating thermostats (one at a time). During this setting change, the burner should shutdown when the called for temperature is less than the temperature indicated on the thermometer. Restore the settings to original values and burner should restart.
Should any of the above operating test fail, replace the involved component.
MAINTENANCE
GENERAL
Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale. The power burner should be inspected and adjusted to maintain proper combustion. Refer to the following table. A periodic inspection of the venting system should be made. Where used, the water heating system circulating pump should be oiled.
KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
FLUSHING
1. Turn off the heater electrical disconnect switch.
• For convenience, the switch on the outside of the control compartment can be used.
2. Open the drain valve and allow water to flow until it runs clean.
The heater must be drained if it is to be shut down or exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater.
1. Tun off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.
3. Open a nearby hot water faucet to vent the system.
4. Open the heater drain valve.
5. If the heater is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.
• Follow FILLING instructions when restoring hot water service
SEDIMENT REMOVAL
Waterborne impurities consist of fine particles of soil and sand which settle out and form a layer of sediment on the bottom of the tank.
For convenience, sediment removal and lime scale removal should be performed at the same time.
LIME SCALE REMOVAL
The amount of calcium (lime) released from water is indirect proportion to water temperature and usage. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.
Lime accumulation not only reduces the life of the equipment but also reduces efficiency of the heater and increases fuel consumption.
3. Close the drain valve when finished flushing.
4. Turn on the heater electrical disconnect switch.
MAINTENANCE SCHEDULE
Component Operation Interval Required
Flushing Monthly
Sediment
Tank Removal Semi-Annually
Lime Scale UN•LIME
Removal As Required Delimer
Relief Valve Inspect Semi-Annually
Power Burner SAE No. 20
Motor(1) Inspect Quarterly non-detergent
motor oil
Power Burner Combustion
and Ignition Inspection Semi-Annually test kit &
Device(2) test
specifications
Main Burner Check Flame Annually
Flue Baffle
Pipe(3) Cleaning As Required Wire Brush
Vent System
and Barometric Inspect Semi-Annually Draft Gauge
Damper
(1) If furnished with oiling provisions (2) If flange gasket is damaged, it must be repaired. (3) TPO and TPD Only.
®
The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.
12
The depth of lime build-up should be measured periodically. Heaters will have about 3” of lime build-up when the level of lime has reached the bottom of the cleanout opening or about 1” of lime build-up if it has reached the drain valve opening. A schedule for deliming should be set-up; based on the amount of time it would take for a 1” build-up of lime.
Example 1 = Initial inspection, after 1 year, shows 1/2” of lime
accumulation. Therefore, the heater can be delimed once a year.
check the relief valve, lift the lever at the end of the valve several times. The valve should seat properly and operate freely.
CAUTION
BEFORE MANUALLY OPERATING THE VALVE, MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN. FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT OF THE VALVE DURING THIS CHECKING OPERATION.
Example 2 = Initial inspection, after 1 year, shows 2” of lime
accumulation. Therefore, the heater should be delimed every 3 months.
Following are the instructions for performing some of the recommended maintenance. Power burner inspection and adjustment should be performed by a competent technician.
Heater failure due to excessive lime build-up voids the warranty.
Sediment and lime scale removal may be accomplished through the cleanout opening furnished on the heater. The heater must be drained, see DRAINING, before removing cleanout cover on tank.
To dissolve and remove the more stubborn mineral deposits, UN•LIME Professional Delimer should be used.
UN-LIME Delimer is an easy to handle patented food grade acid formulated specifically for lime scale removal from all types of water using equipment. Available in 1 gallon (part no. 4763) and 5 gallon (part no. 4813) sizes. Hydrochloric acids are not recommended for use on glass-lined tanks.
Form no. 4800, entitled, “Why, When and How”, describes tank cleaning methods and materials. UN•LIME and the booklet may be obtained through your State dealer or distributor.
To clean heater through cleanout opening, proceed as follows:
1. Turn off water inlet valve, the heater electrical disconnect switch and open drain valve.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove plug from cleanout opening.
• Place a short pipe nipple into the tank to extend beyond the heater jacket.
If the temperature and pressure relief valve on the heater discharges periodically or continuously, it may be due to the thermal expansion of water in a closed water supply system, or it may be due to a faulty relief valve.
Thermal expansion is the normal response of water when it is heated. In a closed system, thermal expansion will cause the system pressure to increase until the relief valve actuation pressure is equaled. Then, the relief valve will open, allowing some water to escape slightly lowering the pressure. (See THERMAL EXPANSION Section of pages 5 and 6).
Contact your water supplier or local plumbing inspector on how to control this situation.
ABOVE ALL, DO NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE. THIS IS NOT A SOLUTION AND CAN CREATE A HAZARDOUS SITUATION.
POWER BURNER
KEEP THE AREA AROUND THE BURNER CLEAR AND FREE OF COMBUSTIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS. DO NOT OBSTRUCT BURNER AIR OPENINGS OR VENTILATION GRILLES FOR COMBUSTION AIR. REMOVE LINT ACCUMULATION FROM AIR INTAKE GRILL.
At least annually, contact a qualified service agency for burner cleaning and other routine maintenance.
CLEANING FLUES-TPO & TPD ONLY
The following describes how to gain access to the tank flues for cleaning if necessary.
1. Turn off the heater electrical disconnect switch.
4. Remove lime, scale and sediment using care not to damage the glass coatings inside the tank.
5. Remove the nipple.
6. Replace cleanout plug.
7. Follow filling instructions when restoring hot water service..
8. Check for water leakage and correct as necessary.
9. Replace outer jacket cover plate.
RELIEF VALVE
At least twice a year, the temperature and pressure relief valve should be checked to ensure that it is in operating condition. To
The switch on the outside of the control compartment may be used.
2. Remove the vent connector from on top the heater.
3. Remove the jacket top from the heater by taking out the screws and lifting it off.
The insulating pad should then be lifted out.
4. Take out the screws holding the flue gas collector top to the tank and lift off.
5. The flue baffles may now be removed by lifting out.
The flue baffles are flexible enough to bend for removal
within headroom.
13
6. Using a wire brush, remove soot from flue passages in heater tank.
• If the heater was installed when incoming water temperature was warm, colder water creates the effect of less hot water.
CAUTION
While cleaning tank flue passages, care must be taken that brush does not come in contact with the combustion chamber lining as damage could occur.
• If burner flue collector flange gaskets are damaged, replace.
VENT SYSTEMS
Examine the vent system every six months for obstruction and/or deterioration of vent piping. Remove any soot or obstructions and replace damaged vent piping.
BAROMETRIC DRAFT CONTROL
The heater is equipped with a double acting barometric draft control. The damper gate must pivot freely in the ring guides.
5. Look for hot water wastage and leaking or open hot water faucets.
6. Sediment or lime scale may be affecting water heater operation. Refer to MAINTENANCE for details.
7. Heater or burner may be dirty.
• Clean all heater flue pipes and flue connector, see
MAINTENANCE.
• Have burner properly cleaned and readjusted.
8. Burner may not be firing at proper rate.
• Check gas pressure, see burner manufacturer’s instruction
manual.
9. Burner fan wheel may be dirty.
10.Draft regulator may be stuck.
• Check to see if vane swings freely. Clean, if vane is stuck.
11.Reset button or burner flame safeguard primary control has operated.
FIGURE 3
To test gate for operation, gently tap gate and observe. DO NOT
OIL.
The red solid fuel tabs supplied with the draft regulator must be
removed (See instructions supplied with Draft Regulator).
TROUBLESHOOTING
NOT ENOUGH OR NO HOT WATER
1. Be certain the electrical disconnect switch serving the water heater is in the ON position.
• The outside of the control compartment and the power burner
housing also have switches.
2. Check the fuses
• The electrical disconnect switch usually contains fuses.
3. The capacity of the heater may have been exceeded by a large demand for hot water.
WATER IS TOO HOT
1. Water temperature control may be set too high.
2. If lowering the control setting does not reduce the water temperature, contact your dealer.
WATER HEATER MAKES NOISE
1. Sediment or lime scale accumulations cause noises when the heater is operating.
• The sounds are normal, however, the tank bottom should
be cleaned. Refer to MAINTENANCE for details.
2. Some of the electrical components of the water heater make sounds, which are normal.
• Contacts click or snap as the heater starts and stops.
• Transformers often hum.
WATER LEAKAGE IS SUSPECTED
1. Check to see if the water heater drain valve is tightly closed. Also check the cleanout-opening plug for leakage.
2. The apparent leakage may be condensation, which forms on cool surfaces of the heater and piping.
3. If the outlet of the relief valve is leaking it may represent:
• Large demands require a recovery period to restore water temperature.
4. Colder incoming water temperature will lengthen the time required to heat water to the desired temperature.
• Excessive water pressure.
• Excessive water temperature.
• Faulty relief valve.
14
Excessive water pressure is the most common cause of relief valve leakage. It is often caused by a “closed system”. If a check valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main. The relief valve must release this water or the water heater or plumbing system will be damaged.
When such a condition is encountered, local codes or inspection agency should be consulted to determine which system is acceptable in your area. These may consist of:
• Installation of a second relief valve with lower setting than the primary relief valve.
• An expansion tank of suitable size and pressure rating and
provision to avoid water logging.
REPLACEMENT PARTS
Replacement parts may be ordered through authorized servicers or distributors, refer to your local Yellow Pages for where to call or contact State Water Heaters, 500 Lindahl Parkway, Ashland City, TN 37015. When ordering parts, be sure to state the quantity, part number and description of the item including the complete model and serial number as it appears on the product. Refer to the parts list for more information.
For additional troubleshooting information, refer to the power burner manual.
15
Model TPG/TPX/TPO/TPD Limited Warranty
CERTIFIED FACTORY START - UP REQUIRED
To activate your warranty, contact your local sales representative or Authorized Start-up Agent to arrange for a FREE Certified Start-up.
State Water Heaters, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.
1. THE TANK If the glass lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable water therein, during the first THREE years after initial installation, the warrantor will at its option, provide a replacement State water heater of equivalent
size and current model, less burner and controls. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit sale of a model of equivalent size and construction, State Water Heaters will provide a model which complies with the regulations of your area, in which case the consumer will be charged the difference in price between the like replacement and the energy efficient model required. The warranty on the replacement water heater will be limited to the unexpired term of the original warranty.
2. ALL OTHER PARTS If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor will repair such part or portion at its option.
3. CONDITIONS AND EXCEPTIONS This warranty shall apply only if a certified factory start-up was performed and if the water heater is installed in accordance with local plumbing and building codes, ordinances and regulations, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, approved by the American Society of Mechanical Engineers, must have been installed.
a) This warranty shall apply only when the heater is:
(1) owned by the original purchaser. (2) sized in accordance with proper sizing techniques for commercial water heaters. (3) bearing a rating plate which has not been altered, defaced or removed except as required by the warrantor. (4) used in an open system, or in a closed system with a properly sized and installed thermal expansion tank. (5) fired with the fuel for which it was factory built. (6) fired at the factory rated input. (7) used at temperatures not exceeding the maximum setting of its thermostat; (8) used at water pressure not exceeding the working pressure shown on the water heater;
(9) used when operated free from the damaging effects of uncontrolled water hammer; (10) used when filled with potable water, free to circulate at all times and the tank free of damaging water sediment or scaled deposits; (11) in a non-corrosive and not-contaminated atmosphere; (12) in its original installation location; (13) used with factory approved anode(s) installed; (14) in the United States, its territories or possessions, and Canada.
b) Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, or any attempt to repair tank leaks will void this warranty. c) This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater is connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times. The relief valve installed on the heater is not an acceptable method.
4. SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs. Such costs may include but are not limited to: a) Labor charges for service removal, repair or reinstallation of the water heater or any component part;
b) Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and returning the claimed defective heater or part to such distributor. c) All cost necessary or incidental for any material and/or permits required for installation of the replacement heater or part.
5. LIMITATIONS ON IMPLIED WARRANTIES Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year duration for the heater or any of its parts. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you.
6. CLAIM PROCEDURE Any claim under the warranty should be initiated with the dealer who sold the heater, or with any other dealer handling the warrantor’s products. If this is not practicable, the owner should contact:
State Water Heaters 500 Lindahl Parkway Ashland City, TN 37015
a) The warrantor will only honor replacement with identical or similar water heater or parts thereof, which are manufactured or distributed by the
warrantor.
b) Dealer replacements are made subject to in-warranty validation by warrantor.
7. DISCLAIMERS NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE HEATER. THE WARRANTOR SHALL NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT. a) Some states do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or exclusions may not apply to you b) This warranty gives you specific legal rights, and you may also have other rights, which may vary, from state to state.
Fill in the following for your own reference. KEEP IT. Registration is not a condition of warranty. The model and serial number are found on the heater’s rating plate.
Model No. _____________________ Serial No. ______________________________________ Date Installed ___________________ Dealer’s Name __________________________________________________________________________________________________________
Dealer’s Address __________________________________________________________________Phone Number _________________________
City and State _____________________________________________________________________ Zip _________________________________
KEEP THIS WARRANTY POSTED ADJACENT TO THE HEATER FOR FUTURE REFERENCE.
16
Loading...