State Water Heaters 196114-000, 65 Installation, Operation, Service, Maintenance, Limited Warranty

Page 1
COMMERCIAL GAS WATER HEATER
Glass-Lined Tank-Type Water Heater
Instruction Manual
INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY
AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMA TION RELATIVE TO YOUR SAFETY. BEFORE INSTALLING AND USING THIS APPLIANCE.
PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER
1
CAUTION
PLEASE READ THOROUGHLY
PART NO. 196114-000
Page 2
ROUGH-IN-DIMENSIONS
DIMENSIONS
Model A B C D E F G H J
65
In. 63 1/2 61 26 22 4 8 3/4 1/2 53 3/4
mm 1613 1550 660 559 106 203 NPT NPT 1,365
RECOVERY CAP ACITIES
U.S. Gallons/Hrs. and Litres/Hr. at TEMPERATURE RISE INDICATED
Type
o f Input Approx. 20F° 30F° 40F° 50F° 60F° 70F° 80F° 90F° 100F° 110F° 120F° 130F° 140F°
Model Gas Btuh KW Capacity 11C° 17C° 22C° 28C° 33C° 39C° 44°C 50C° 56C° 61C° 67C° 72C° 78C°
65
65
Natural
Propane
65,000 65 US Gals. GPH 299 200 150 120 100 86 75 67 60 54 50 46 43
19.0 246 Litres LPH 1133 756 567 453 378 324 283 252 227 206 189 174 162
55.000 65 US Gals. GPH 253 169 127 101 84 72 63 56 51 46 42 39 36
16.1 246 Litres LPH 959 639 479 384 320 274 240 213 192 174 160 48 137
RECOVERY CAP ACITIES
FOREWORD
The design of Model 65 complies with the latest version of ANSI Z21.10.1/CSA 4.1 M98 as automatic storage type water heater.
Installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping necessary. It is highly essential that all water and gas piping be installed as shown on the diagrams.
In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction
should be consulted before installations are made. The installation must conform to these instructions and the local
code authority having jurisdiction. In the absence of local codes, the installation must comply with the latest editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, in Canada CAN/CSA B 149.1-00. Both are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131. For Canadian customers, 178 Rexdale Blvd., Rexdale (Toronto), Ontario, Canada M9W 1R3. The National Fuel Gas Code, ANSI Z223.1/NFPA 54 is available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
2
Page 3
TABLE OF CONTENTS
Page
ROUGH-IN DIMENSIONS ....................................................................... 2
FOREWORD .......................................................................................... 2
GENERAL SAFETY INFORMA TION ...................................................... 3
Precautions....................................................................................... 3
Liquid Petroleum ............................................................................... 3
Chemical Vapor Corrosion ............................................................... 3
Improper Combustion........................................................................ 3
Extended Non-use Periods ..............................................................3-4
Insulation Blankets............................................................................ 4
INSTALLA TION INSTRUCTIONS ............................................................ 4
Required Ability ................................................................................ 4
Locating The Heater ......................................................................... 4
High Altitude Installations ................................................................. 4-5
Clearances ....................................................................................... 5
Hard Water ....................................................................................... 5
Air Requirements.............................................................................. 5
Combination Water (Potable) Heating and Space Heating ..............5-6
Venting.............................................................................................. 6
Thermometers (Not Supplied) .......................................................... 6
Relief Valve....................................................................................... 6-7
Page
Gas Piping......................................................................................... 7-8
Purging.............................................................................................. 8
Gas Pressure Regulation ................................................................ 9
OPERATION.......................................................................................... 9
Precautions...................................................................................... 9
Lighting Instructions ........................................................................ 10
T emperature Regulation .................................................................. 11
High Temperature Limit Switch........................................................ 11
Checking Venting.............................................................................11-12
SERVICE INFORMATION ...................................................................... 12
Pilot and Main Burner....................................................................... 12
Checking Gas Input .........................................................................12-13
Vent System .................................................................................... 13
Relief Valve...................................................................................... 13
Hot Water Odor ............................................................................... 13
Anode Rod Inspection ..................................................................... 13
Winter Protection ............................................................................. 13
Replacement Parts .......................................................................... 13
CHECKLIST ..........................................................................................13-14
LIMITED WARRANTY............................................................................Insert
GENERAL SAFETY
INFORMATION
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY P ART HAS BEEN UNDER WATER. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEA TER UNTIL ALL CORRECTIVE STEPS HA VE BEEN MADE BY A QUALIFIED SERVICEMAN.
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER.
4. SOOTING
LIQUID PETROLEUM MODELS
WARNING
Water heaters for propane or liquified petroleum gas (LPG) are different from natural gas models. A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas.
sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of the water heater is due to a corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions.)
IMPROPER COMBUSTION
WARNING
ATTIC AND/OR EXHAUST F ANS OPERA TING ON THE PREMISES WITH A WATER HEA TER CAN RESULT IN CARBON MONOXIDE POISONING AND DEATH.
OPERA TION OF THESE FANS CAN PRODUCE A NEGA TIVE DRAFT IN THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY OR VENT PIPE.
The venting of the water heater should be inspected by a qualified service technician at the time of installation and periodically thereafter to ensure a down-draft condition does not exist.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERA TION.
CHEMICAL VAPOR CORROSION
WARNING
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and
EXTENDED NON-USE PERIODS
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT W ATER SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED FOR A LONG PERIOD OF TIME (GENERALL Y TWO WEEKS OR MORE). HYDROGEN GAS IS EXTREMEL Y FLAMMABLE. T o reduce the risk
of injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins
3
Page 4
THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR
to flow.
THE FAUCET A T THE TIME IT IS OPEN.
INSULATION BLANKETS
Insulation blankets available to the general public for external use on gas water heaters are not necessary with your commercial water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Your commercial water heater meets or exceeds the ASHRAE/IES 90.1b­1992 standards with respect to insulation and standby loss requirement making an insulation blanket unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater, you should follow these instructions. Failure to follow these instructions can result in fire, asphyxiation, serious personal injury or death.
Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood.
Do not cover the outer door, thermostat or temperature &
• pressure relief valve.
Do not allow insulation to come within 2" (51 mm) of the floor to prevent blockage of combustion air flow to the burner.
Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
Do obtain new warning and instruction labels from for placement on the blanket directly over the existing labels.
Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the
water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches (76 mm) in any direction. If the heater is installed in a carpeted alcove or closet, the entire floor shall be covered by the panel. Also, see the drain requirements.
THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.
THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such pans should be fabricated with sides at least 2" (51 mm) deep, with length and width at least 2" (51 mm) greater than the diameter of the heater and must be piped to an adequate drain. The pan must not restrict combustion air flow.
Drain pans suitable for these heaters are available from your distributor.
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLA TION OR SER VICE OF THIS WA TER HEA TER REQUIRES ABILITY EQUIV ALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING, AIR SUPPL Y, VENTING AND GAS SUPPLY WORK ARE REQUIRED.
LOCATING THE HEATER
When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRA VEL ALONG THE FLOOR AND MA Y BE IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION.
APPLIANCES IF INSTALLED 18 INCHES (457 mm) OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE A VOIDED.
SOME LOCAL CODES PERMIT OPERA TION OF GAS
For appliance installation locations with elevations above 2000 feet (610 meters), refer to HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure.
HIGH ALTITUDE INSTALLATIONS
WARNING
INSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIRE REPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCE WITH SECTION 8.1.2 OF THE NA TIONAL FUEL GAS CODE (ANSI Z223.1). FOR CANADIAN INSTALLA TIONS CONSUL T CANADIAN INSTALLATIONS CODES AND CAN/CSA B149.1-00. F AILURE TO REPLACE THE ORIFICE WILL RESULT IN IMPROPER AND INEFFICIENT OPERA TION OF THE APPLIANCE RESULTING IN THE PRODUCTION OF INCREASED LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD RESUL T IN SERIOUS PERSONAL INJUR Y OR DEATH.
You should contact your gas supplier for any specific changes which may be required in your area.
As elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply. Failure to make this reduction would result in an overfiring of the heater causing sooting, poor combustion and/or unsatisfactory heater performance.
4
Page 5
U.S. REQUIREMENTS
Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610 m). For elevations above 2000 feet (610 m), ratings must be reduced at the rate of 4% for each 1000 feet (305 m) above sea level. For example, if a heater is rated at 65,000 Btuh (19 Kw) at sea level, to rate the heater at 4000 feet (1219 m), you subtract 4 (once for each thousand feet) x.04 (4% input reduction) x 65,000 (original rating) from the original rating. Therefore, to calculate the input rating at 4,000 feet (1219 m): 4 x .04 x 65,000 = 10,400 Btuh (3.0 Kw), 65,000 (19 Kw) - 10,400 (3.0 Kw) = 54,600 Btuh (16 Kw). At 6000 feet (1829 m) the correct input rating should be 49,400 Btuh (14.5 Kw).
CANADIAN REQUIREMENTS
Appliances with inputs up to and including 400,000 BTU must be factory equipped with orifices for operation at specific elevations. Standard (sea level) orifices permit operation up to 2000' (610 m) elevation. For operation between 2000' (610 m) and 4500' (1370 m) specify "HIGH ALTITUDE OPERATION" when ordering the heater(s). For operation above 4500' (2370 m) consult factory before ordering.
Field conversion for operation at altitudes other than that specified on the heater rating plate is not permitted.
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MA TERIALS, GASOLINE AND OTHER FLAMMABLES, V APORS AND LIQUIDS.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR VENTILA TING AIR.
WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPL Y OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN AIR CONT AMINA TION THA T MA Y BE HAZARDOUS TO LIFE. SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION.
Where an exhaust fan is supplied in the same room with a heater, sufficient openings for air must be provided in the walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION. SOOTING MA Y RESULT IN SERIOUS DAMAGE TO THE HEA TER AND RISK OF FIRE OR EXPLOSION.
UNCONFINED SPACE
The input reduction is primarily achieved by reducing the size of the main burner orifices. To do this, the main burner orifices require replacement with orifices sized for the particular installation elevation. Contact your local gas supplier for further information.
Upon completion of derating of the heater, adjustment to the gas pressure regulator may be required. See CHECKING THE INPUT section in this manual for inlet and manifold pressure requirements.
Also due to the input rating reduction required at high altitudes, the output rating of the appliance is reduced and should be compensated for in the sizing of the equipment for application.
CLEARANCES
These heaters are approved for installation on combustible flooring in a closet having a ceiling 18" (457 mm) above top cover and with clearances to combustible construction of 6" (152 mm) from flue or vent connector, 1" (25 mm) at the sides and rear and 4" (102 mm) to front to prevent a possible fire hazard condition. A minimum of 4" (101.6 mm) shall be allowed for installation of serviceable parts.
HARD WATER
Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.
Contact your dealer or qualified service technician for more information on this product.
In buildings of conventional frame, brick, or stone construction, unconfined spaces may provide adequate air for combustion, ventilation and draft hood dilution.
If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood dilution must be obtained from outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.
CONFINED SPACE
When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings, ONE IN OR WITHIN 12 INCHES (30.50 cm) OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES (30.50 cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh (2202.8 mm input of all appliances in the enclosure, but not less than 100 square inches (645 cm2).
If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh (550.7 mm appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh (1101.4 mm in the enclosure. For Canadian installations consult CAN/CSA B149.1-00.
2
/KW) of the total input of all appliances
2
/KW) of the total input of all
2
/KW) of the total
AIR REQUIREMENTS
REFER TO THE LA TEST EDITION OF THE "NA TIONAL FUEL GAS CODE" ANSI Z223.1/NFP A 54. FOR CANADA CONSULT CAN/CSA B149.1-00.
COMBINA TION WATER (POTABLE)
HEA TING AND SPACE HEATING
1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water.
5
Page 6
2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.
3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than required for domestic water
purposes, a tempering valve must be installed (See Fig. 3).
CAUTION
A closed system will exist if a check valve (without bypass), pressure reducing valve (without bypass), or a water meter (without bypass) is installed in the cold water line between the water heater and street main (or well).
Excessive pressure may develop in such closed systems, causing premature tank failure or intermittent relief valve operation. not a warranty failure. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of the water.
This is
FIGURE 2
DRAFT HOOD
The draft hood furnished with this heater must be installed without alteration. Provision must be made if it is installed in confined space or a small room to accommodate draft hood spillage and avoid risks described in previous steps. The upper air opening called for in the AIR REQUIREMENTS section of this manual is for this purpose.
Locate draft hood as seen in Figure 1. Position draft hood over the flue tube. Align the draft hood legs with four holes surrounding the flue. Insert tabbed end of legs into the corresponding holes and twist to lock the draft hood in place.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and to the local code authority having jurisdiction. Good practice requires that all heavy piping be supported.
VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIA TION.
Heater must be protected from freezing downdrafts. Remove all soot or other obstructions from the chimney that will
retard a free draft. Type B venting is recommended with these heaters. This water heater must be vented in compliance with all local
codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables. In Canada, venting shall conform to the requirements of the current CAN/CSA B149.1-00 installation code.
If any part of the vent system is exposed to ambient temperatures below 35 degrees F (2 degrees C) it must be insulated to prevent condensation.
Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.
Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe.
When installing vent piping, secure the vent pipe to the draft hood using at least three sheet metal screws in the draft hood outlet.
VENT CONNECTION
Vent connections must be made to an adequate stack or chimney. Size and install proper size vent pipe. Do not reduce pipe size to less than that of the draft hood outlet.
Horizontal runs of vent pipe must have a minimum upward slope toward the chimney of 1/4 inch per foot (20 mm per meter). Dampers or other obstructions must not be installed in between the heater and the draft hood. Be sure that the vent pipe does not extend beyond the inside wall of the chimney.
Where a continuous or intermittent back draft is found to exist, the cause must be determined and corrected. A special vent cap may be required. If the back draft cannot be corrected by the normal methods or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.
THERMOMETERS (Not Supplied)
Thermometers should be obtained and field installed. Thermometers are installed in the system as a means of detecting
the temperature of the outlet water supply.
RELIEF VALVE
This water heater is equipped with a combination temperature­pressure relief valve that complies with the standard for relief valves and automatic gas shut-off devices for hot water supply system, ANSI Z21.22, for Canada see CAN/CSA 149.1-00. FOR SAFE
OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED OR PLUGGED.
ASME ratings cover pressure relief capacities. A.G.A. ratings cover release rate with temperature actuation.
6
Page 7
SINGLE TEMPERATURE
VACUUM RELIEF
VALVE
* INSTALL PER
LOCAL CODES
CIRCULATING RETURN LINE CONNECTIONS TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A". STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO COLD WATER INLET.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW PREVENTER, CHECK VA L VE OR WA TER METER WITH CHECK V A L VE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED.
FIGURE 3
In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s).
WARNING
THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE SCALDING A T FIXTURES, T ANK EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE RELIEF V AL VE AND T ANK.
Your local code authority may have other specific relief valve requirements.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF V AL VE T O DIRECT DISCHARGE TO A SAFE LOCA TION TO A VOID SCALDING OR WA TER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH THE V AL VE AND LINE.
See SERVICE INFORMATION section for procedure and precautions.
WARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE TEMPERATURE REGULA TION ON PAGE 11. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
Size the main gas line in accordance with Table 1. The figures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the latest version of the National Fuel Gas Code. For Canadian installations consult Canadian Installation Code CAN/CSA B149.1-00.
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 10.5" W.C.(2.61 kPa) - NATURAL GAS, or 13.0" W.C.(3.23 kPa) -PROPANE GAS SUPPL Y GAS PRESSURE. EXPOSURE TO HIGHER SUPPL Y PRESSURE MAY CAUSE DAMAGE TO THE GAS VALVE WHICH COULD RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS V ALVE MUST BE CHECKED FOR SAFE OPERA TION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT V AL VES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MA Y OCCUR DURING ICE STORMS.
IT IS IMPORT ANT TO GUARD AGAINST GAS VAL VE FOULING FROM CONTAMINANTS IN THE GAS WA YS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
The type, size and location of the relief valve(s) must be in accordance with local codes. The location of the relief valve shown in Figure 3 is typical. The heater has a factory installed high temperature limit switch.
For circulating heaters, the separate storage vessel must have a temperature and pressure relief valve installed. This valve shall comply with the standard for relief valves and automatic gas shut­off devices for hot water supply systems.
GAS PIPING
Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MA TERIAL IN THE GAS SUPPL Y LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORA TED IN THE PIPING (SEE FIG.
4). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE LA TEST VERSION OF THE
NA TIONAL FUEL GAS CODE. For Canadian installations consult Canadian Installation Code CAN/CSA B149.1-00.
7
Page 8
TABLE 1 - GAS SUPPLY LINE SIZES (IN INCHES)*
MAXIMUM CAPACITY OF PIPE IN
CUBIC FEET PER HOUR
LENGTH NORMAL IRON PIPE SIZES (INCHES)
IN INPUT IN THOUSANDS BTU/HR
FEET 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990 1900 3000 5300 10900 50 73 151 285 580 900 1680 2650 4750 9700 60 66 138 260 530 810 1520 2400 4300 8800 70 61 125 240 490 750 1400 2250 3900 8100 80 57 118 220 460 690 1300 2050 3700 7500
90 53 110 205 430 650 1220 1950 3450 7200 100 50 103 195 400 620 1150 1850 3250 6700 125 44 93 175 360 550 1020 1650 2950 6000 150 40 84 160 325 500 950 1500 2650 5500 175 37 77 145 300 460 850 1370 2450 5000 200 35 72 135 280 430 800 1280 2280 4600
PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 Kpa). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45 Kpa) OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE ISOLA TED FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS Shut-off VAL VE.
PURGING
Gas line purging is required with new piping or systems in which air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE. TO A VOID RISK OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SP ACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILA TED AND ALL SOURCES OF IGNITION MUST BE INACTIV A TED OR REMOVED.
LENGTH NORMAL IRON PIPE SIZES (INCHES)
IN INPUT IN KW
METERS 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
3 51 105 199 410 615 1160 1845 3221 6735 6 35 73 142 278 428 805 1277 2255 4626
9 28 59 110 225 346 644 1031 1830 3748 12 24 50 94 193 290 556 878 1552 3192 15 21 44 83 170 264 492 776 1391 2840 18 19 40 76 155 237 445 703 1259 2577 21 18 37 70 143 220 410 659 1142 2372 24 17 35 64 135 202 381 600 1083 2196 27 16 32 60 126 190 357 571 1010 2108 31 15 30 57 117 182 337 542 952 1962 38 13 27 51 105 161 299 483 864 1757 46 12 25 47 95 146 278 439 776 1610 53 11 23 42 88 135 249 401 717 1464 61 10 21 40 82 126 234 375 688 1347
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS LEAKAGE. Use soap and water solution or other material
acceptable for the purpose in locating the leaks. DO NOT USE
MA TCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
GAS METER SIZE — NATURAL GAS ONLY
Be sure the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity.
FIGURE 5 -THERMOSTA T FOR NA TURAL GAS
GAS PRESSURE REGULATOR
The gas pressure regulator is built into the gas valve and is equipped to operate on the gas specified on model and rating plate. The regulator is factory adjusted to deliver gas to burner at correct water column pressure allowing for a nominal pressure drop through the controls.
FIGURE 4 - GAS PIPING AND DIRT LEG INSTALLATION
DISCONNECT THE HEA TER AND ITS MANUAL GAS Shut-off V AL VE FROM THE GAS SUPPL Y PIPING SYSTEM DURING ANY SUPPL Y
The minimum gas supply pressure for input adjustment is
5.0" W.C. (1.24 kPa) for natural gas or 11.0" W.C. (2.74 kPa) for propane gas.
Do not subject the combination gas valve to inlet gas pressures of more than 10.5" W.C. (2.61 kPa) - natural gas or 13.0" W.C. (3.23 kPa) - propane gas. A service regulator is necessary if higher gas pressures are encountered.
Gas pressure specified in Table 2, refer to flow pressure taken at pressure tap of automatic gas valve while heater is operating.
8
Page 9
TABLE 2
MANIFOLD PRESSURE SETTING
Model Type of Manifold
Number Gas Input Pressure
65 Natural 65,000 Btu/hr 4.0 in. W.C.
16.7 KW/hr 1.0 Kpa
65 Propane 55,000 Btu/hr 10.0 in. W.C.
16Kw 2.49kPa
OPERATION
Entire system filled with water.
Air purged from all lines and no leaks (gas and water).
All gas and water lines open.
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY P ART HAS BEEN UNDER WATER. The heater must be replaced.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT OPERATE HEA TER UNTIL ALL CORRECTIVE STEPS HA VE BEEN MADE BY A QUALIFIED SERVICEMAN:
It is recommended that a qualified person perform the initial firing of the heater. At this time the user should not hesitate to ask the individual any questions which he may have in regard to the operation and maintenance of the unit.
WARNING
THE GAS V AL VE MUST HA VE BEEN IN THE OFF POSITION FOR AT LEAST 5 MINUTES. This waiting period is an important safety step. Its purpose is to permit gas that may have accumulated in the combustion chamber to clear. IF YOU DETECT GAS ODOR A T THE END OF THIS PERIOD DO NOT PROCEED WITH LIGHTING. RECOGNIZE THA T GAS ODOR, EVEN IF IT SEEMS WEAK, MAY INDICATE PRESENCE OF ACCUMULA TED GAS SOMEPLACE IN THE AREA WITH RISK OF FIRE OR EXPLOSION. SEE THE FRONT P AGE FOR STEPS TO BE T AKEN.
Before lighting the pilot and operating the heater, the following conditions must exist:
1. EXTERNAL FIRE.
2. PHYSICAL DAMAGE.
3. FIRING WITHOUT WA TER.
4. SOOTING. NEVER OPERATE THE HEA TER WITHOUT FIRST BEING CERT AIN
IT IS FILLED WITH WATER AND AN A.G.A. TEMPERATURE AND PRESSURE RELIEF V AL VE IS INST ALLED IN THE RELIEF V AL VE OPENING OF THE HEA TER.
SHOULD OVERHEA TING OCCUR OR THE GAS SUPPL Y F AIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
A checklist is included in the SERVICE INFORMATION section of this manual. By using this checklist the user may be able to make minor operational adjustments and save himself unnecessary service calls. However, the user should not attempt repairs which are not listed in this section.
9
Page 10
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppliers instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read safety information above on this label.
2. Set the thermostat to lowest setting by turning the water temperature dial clockwise ( ) to its lowest temperature setting (with arrow on dial) as shown.
DO NOT FORCE.
3. Remove outer door.
4. Turn gas control knob clockwise to “OFF” position. Knob cannot be turned from “PILOT” to “OFF” unless knob is depressed slightly. DO NOT FORCE.
5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above on this label. If you don't smell gas, go to next step.
6. Remove (or open) inner door located below gas control unit.
7. Find pilot - follow metal tube from gas control. The pilot is located in front of the burner or on the right hand side of the burner.
PILOT
BURNER
8. If you don’t smell gas, turn knob on gas control counter clockwise to “PILOT” position.
OR
PILOT
BURNER
*THERMOCOUPLE
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
9. Push in control knob all the way and hold down. Immediately light the pilot with a match. Continue to hold control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 3 through 8.
• If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after several tries, depress and turn the gas control knob clockwise to “OFF” and call your service technician or gas supplier.
10. Replace (or close) inner door. Replace outer door if door does not cover gas control on/off knob or temperature adjustment knob.
11. At arms length away, turn gas control knob counter- clockwise to the full “ON” position. WARNING: Do not use gas control
knob to regulate gas flow.
12. At arms length away, set the thermostat to desired setting. The mark ( ) indicative of approximate 120°F is preferred starting point. Some local laws may require a lower starting point. If hotter water is desired, see instruction manual and “warning” below.
13. Replace the outer door if not replaced in step 10.
Hotter water increases the risk of scald injury. Before changing temperature setting see instruction manual.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting by turning the water temperature dial clockwise ( ) to its lowest temperature setting (with arrow on dial) as shown. DO
NOT FORCE.
WARNING
2. Turn gas control knob clockwise to “OFF” position. Knob cannot be turned from “PILOT” to “OFF” unless knob is depressed slightly. DO NOT FORCE.
3. Replace outer door (if removed).
10
Page 11
TEMPERATURE REGULATION
DANGER
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE PAINFUL SCALDING WITH POSSIBLE SERIOUS AND PERMANENT INJUR Y . THE TEMPERA TURE A T WHICH INJURY OCCURS V ARIES WITH THE PERSON’S AGE AND THE TIME OF THE EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BA TH WA TER. NEVER LEA VE A CHILD OR DISABLED PERSON UNA TTENDED IN A BATHTUB OR SHOWER.
THE WA TER HEA TER SHOULD BE LOCA TED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HA VE ACCESS. IF A SUIT ABLE AREA IS NOT A VAILABLE, A COVER SHOULD BE INSTALLED OVER THE THERMOSTAT TO PREVENT TAMPERING.
are available from your distributor.
It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperature dial be set for the lowest temperature which satisfies your hot water needs. This will also provide the most energy efficient operation of the water heater. The water temperature adjusting dial was factory set at the lowest temperature; all the way clockwise to the mechanical stop. Turning the dial counterclockwise
reduces temperature.
SETTING THE WA TER HEA TER TEMPERA TURE A T 120°F (49°C) (APPROX. " THE RISK OF SCALDS. Some states require settings at specific lower temperatures.
Figure 6 shows the approximate water temperatures produced at various thermostat dial settings. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30°F (17°C). If you experience this type of use you should consider using lower temperature settings to reduce scald hazards.
Valves for reducing point of use temperature by mixing cold and hot water are available. Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority.
SHOULD OVERHEA TING OCCUR OR THE GAS SUPPL Y F AIL TO SHUT OFF , TURN OFF THE MAIN MANUAL GAS Shut-off V AL VE TO THE APPLIANCE.
" MARK ON FACE OF THERMOSTA T) WILL REDUCE
increases temperature and clockwise
Suitable covers
T emperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
VERY HOT = APPROX.180°F (82°C) Nearly instantaneous
D = APROX. 160°F (71°C) About 1/2 second C = APPROX.150°F (66°C) About 1 1/2 seconds B = APPROX.140°F (60°C) Less than 5 seconds A = APPROX.130°F (54°C) About 30 seconds
= APPROX.120°F (49°C) More than 5 minutes
LOW = APPROX.100°F (38°C) - - - - - - - -
FIGURE 6
HIGH TEMPERATURE LIMIT SWITCH
(Single-Use T ype Energy Cut Off)
The thermostat has a built-in limit switch which will extinguish the pilot light in case of excessive water temperatures. The pilot cannot be relit until the entire thermostat (labeled as single use type) is replaced. It is important that a serviceman be called to determine the reason for limit operation and thus avoid repeated thermostat replacement. Lower the temperature adjustment dial setting on new control.
CHECKING VENTING
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 or the CAN/CGA B149 Installation codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods
11
Page 12
and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers.
4. Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so appliance shall operate continuously.
5. Test for draft hood spillage at the relief opening after 5 minutes of main burner operation.
WARNING
SOOT BUILD-UP INDICATES A PROBLEM THAT REQUIRES CORRECTION BEFORE FURTHER USE. CONSULT WITH A QUALIFIED SERVICE TECHNICIAN.
Should the main burner or burner air openings require cleaning, remove the burner and clean with a soft brush. Clean main burner orifice with a suitable soft material. Do not disassemble burner head unless necessary.
6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINA TION AND UNSAFE CONDITIONS.
If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.
SERVICE INFORMATION
The installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER, it is recommended that only qualified servicemen, using appropriate test equipment, be allowed to service the heater.
FOR YOUR SAFETY AND SATISFACTORY OPERATION, IT IS RECOMMENDED THAT THIS HEATER BE CHECKED ONCE A YEAR BY A COMPETENT SERVICE PERSON.
USERS OF THIS APPLIANCE SHOULD BE AWARE THAT GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME. THE GAS CARRYING COMPONENTS OF THIS APPLIANCE SHOULD BE INSPECTED FOR PROPER OPERATION PERIODICALLY BY A QUALIFIED SERVICE TECHNICIAN.
PILOT AND MAIN BURNER
CHECK FOR GOOD FLOW OF COMBUSTION AND VENTILA TING AIR TO THE UNIT. MAINTAIN A CLEAR OPEN AREA AROUND THE HEATER AT ALL TIMES. DO NOT STORE COMBUSTIBLES OR FLAMMABLE LIQUIDS NEAR OR AROUND AN APPLIANCE.
PILOT AND MAIN BURNER
FIGURE 7
CHECKING GAS INPUT
For appliance installation locations with elevation above 2000 ft.(610m) refer to HIGH ALTITUDE INST ALLATIONS section of this manual for input reduction procedure.
With this heater in operation, determine whether it is receiving the full rated input of gas. This may be done by timing the gas meter and measuring gas pressure with a gauge or manometer. When the heater is operating at full capacity (full gas input) it should consume approximately 1 cubic foot of gas in the time shown in table 3.
T ABLE 3
INPUT CHECK TIME REQUIRED TO
CONSUME 1 CU. FT . OF GAS
Time Required T o
T ype of BTU Per Consume 1 Cu. Ft.
Model Gas Cu. Ft. of Gas
65 Natural 1050 58.2 sec. 65 Propane 2500 163.7 sec.
Check pilot, figure 7, and main burner at least every 6 months for proper flame characteristics. The main burner should display the following characteristics:
1. Provide complete combustion of gas.
2. Cause rapid ignition and carryover of flame across entire burner.
3. Give reasonably quiet operation during ignition, burning and extinction.
4. Cause no excessive lifting of flames from burner ports.
If preceding burner characteristics are not evident, check for accumulation of lint or other foreign material that restricts or blocks the air openings to the heater or burner.
Use this formula to “clock” the meter. Be sure that other gas consuming appliances are not operating during this interval.
3,600 X H = Btuh T
T = Time in seconds needed to burn one cubic foot of gas. H = Heating value of gas in Btu’s per cubic foot of gas.
Btuh = Actual heater input rate. Example: (Using 65 heater)
T = 58.2 seconds/ft H = 1,050 Btu/ft3 (natural gas)
Btuh = ?
3,600 X 1,050 = 64.948 Btu/hr (19.0 KW)
58.2
12
3
Page 13
Compare the actual input rate to that given on the heater’s rating plate. In the example, the 65 full input rate should be 65,000 Btuh (19.0 KW) for natural gas.
VENT SYSTEM
Examine the venting system every 6 months for obstructions and/ or deterioration of vent piping.
RELIEF VALVE
At least once a year the temperature and pressure relief valve should be checked to ensure that it is in operating condition. (During manual operation of this valve, avoid any contact with hot water and take preventive steps for water damage). Lift the lever at the top of the valve several times until the valve seats properly and operates freely.
WARNING
THE WATER PASSING OUT OF THE VALVE DURING THIS CHECKING OPERATION MAY BE EXTREMELY HOT. AVOID CONTACT AND DISCHARGE SAFELY TO PREVENT WATER DAMAGE.
diameter core wire is visible as this means that the anode material has been expended in the control of corrosion.
NOTE: Anode rod inspection may need to be made more frequently in areas subject to acid rain that obtains their water supply from surface water as the low pH will accelerate anode activity.
CAUTION: Close cold water inlet valve serving heater and open nearby hot water faucet to relieve the pressure in the heater before attempting to remove anode(s) for inspection.
WINTER PROTECTION
In regions where freezing weather is encountered, all water must be drained from unit and piping when out of service (water shut off). Drain valve must be left open until unit is returned to service.
REPLACEMENT PARTS
Now that you have purchased this water heater, should a need ever exist for repair parts or service, simply contact the company it was purchased from or direct from the manufacturer listed on the rating plate on the water heater.
If the temperature and pressure relief valve on the heater discharges periodically or continuously, a problem exists. This may be due to unusually high water temperatures or pressures in the system, or to a faulty relief valve. Contact your dealer or a qualified service technician to find the cause of the problem and to correct it. This may also be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT PLUG THE TEMPERATURE
AND PRESSURE RELIEF V ALVE.
WARNING
SHOULD OVERHEA TING OCCUR OR THE GAS SUPPL Y F AIL T O SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE APPLIANCE.
HOT WATER ODOR
On occasion, hot water may develop a strong odor. If this occurs drain the heater completely, flush thoroughly, and refill. If the problem persists, chlorination of the heater and replacement of the factory installed magnesium anode with an aluminum anode may correct the condition.
Occasionally water softener companies recommend removal of heater anodes for odor reasons.
CAUTION
Unauthorized removal of heater anode will void the warranty. Replace the anode as necessary to maintain corrosion protection. For further information contact your dealer.
ANODE ROD INSPECTION
Be sure to provide all pertinent facts when you call or visit. Selling prices will be furnished on request or parts will be shipped
at prevailing prices and you will be billed accordingly. The model number of your gas water heater will be found on the
rating plate located above the gas control valve. WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE
FOLLOWING INFORMATION:
MODEL NUMBER
TYPE GAS (NATURAL OR PROPANE [L.P.])
SERIAL NUMBER
PART DESCRIPTION
CHECKLIST
Before contacting your dealer, check the water heater to see if the apparent malfunction is caused by some external fault. Consulting this checklist may eliminate the need for a repair call and restore hot water service.
NOT ENOUGH OR NO HOT WA TER
1. Check to see if the pilot flame is lit.
To relight the pilot, follow the instructions on the heater or in this manual.
Check to see if the main gas Shut-off valve in the gas supply pipe is partially closed or the water temperature dial is set too low.
The heater tank is equipped with an anode rod to provide corrosion control. At least once a year the anode rod should be checked to determine if replacement is necessary. Initially the anode rod is approximately 7/8" (22mm) in diameter with a 1/8" (3mm) diameter steel core wire running down the center of the anode material. THE ANODE SHOULD BE REPLACED when the 1/8" (3mm)
2. Look for leaking or open hot water faucets. Check for excessive usage.
3. Your gas company can check the gas input to the heater to see that it is correct. An underfired heater will not produce hot water at its normal recovery rate.
13
Page 14
4. If the heater was installed when incoming water temperatures were warm, colder incoming temperatures will create the effect of less hot water.
5. The thermostat water temperature adjusting dial may be set too low.
6. If you cannot determine the cause of the problems, contact your dealer.
WA TER TEMPERA TURE IS TOO HOT
1. The thermostat water temperature adjusting dial may be set too high.
2. If lowering control setting does not reduce the water temperature contact your dealer.
GAS SMELL A T THE HEA TER
1. Close the main Shut-off valve in the gas supply pipe near the heater, see fig. 4 on page 8. The thermostat includes a gas control (top knob) which can also be closed.
quantities of water are drawn, chilling the tank bottom. This too can result in condensation.
Condensation, appearing in the vent pipe (water dripping from draft diverter) during heater operation is evidence of poor vent action. Possible causes are too long a vent pipe or improper chimney operation.
3. If the leakage is from the temperature and pressure relief valve or its discharge pipe, it may represent a normal condition. However, see RELIEF VALVE section on page 12. DO NOT PLUG THE TEMPERA TURE AND PRESSURE RELIEF V AL VE. Also, the leakage could be due to unusually high water pressures or temperatures in the system, or to a faulty relief valve. Your dealer or a qualified service technician should be called to determine the cause of the problem and to correct it.
4. If you cannot identify or correct the source of water leakage:
Close the main Shut-off valve in the gas supply pipe at the heater. See fig. 4, page 8.
Close the valve which feeds water to the cold water inlet at the top of the heater.
2. Call your gas company.
WA TER LEAKAGE IS SUSPECTED
1. Check to see if the heater drain valve is tightly closed.
2. The apparent leakage might be condensation. In warm or humid locations, condensation can accumulate and run from within the heater or its piping.
When a water heater is first installed and filled, the bottom of the tank might condense water. The water accumulation, if excessive, can drip into the floor shield. Also, during normal operation there may be occasions when large
Contact your dealer.
WA TER HEA TER MAKES SOUNDS
1. Occasional excessive condensation, as explained under LEAKAGE, can cause a sizzling sound as the moisture is vaporized by the gas flame. This is a normal sound and may be disregarded.
2. Sediment and water scale accumulations may cause rumbling noises. Contact your dealer for details of flushing the heater.
3. If you cannot identify or remedy the condition, contact your dealer.
14
Page 15
NOTES
15
Page 16
16
Loading...