Servicing should only be performed by a Qualified Service Agent 198152-002
INTRODUCTION
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
The service handbook is designed to aid in
servicing and trou bleshooting S tate W ater
Heaters Ultra Force SUF commercial water
heaters i n t he f ield. No duplication or
reproduction of t his bo ok m ay be m ade
without the ex press w ritten authorization o f
State Water Heaters .
The fol lowing tex t and i llustrations w ill
provide you with a step by step procedure to
verify pr oper i nstallation, opera tion, and
troubleshooting procedures. Additional quick
reference da ta i s i ncluded to ass ist you in
servicing these products.
The information contai ned i n this handbook
is designed to answer co mmonly face d
situations enc ountered in the ope ration of
this product l ine and is not meant to be all
QUALIFICATIONS
inclusive. If you are experiencing a problem
not covered in this handbook, please contact
State Water Heaters Technical Information at
1-800-365-0024, by email at
help@statewaterheaters.com
or your local
State Water Heater representative for further
assistance.
Our website:www.statewaterheaters.com
is also a resource for installation and service
information. Thi s handbook i s i ntended for
use by licensed plumbing professionals and
reference should be made to the installation
manual accom panying the prod uct. This
handbook contains supplemental information
to the produ ct’s i nstallation and ope ration
manual.
ANSI Z223.1 Sec 3.3.83
"Qualified Agency"
"Any individual, firm, corporation or company
that ei ther i n person o r through a
representative i s e ngaged i n an d i s
responsible for (a) the installation, testing or
replacement of g as p iping or (b) the
connection, i nstallation, testing, re pair or
servicing of appliances and equipment; that
is experienced i n such work; that is familiar
with all precautions required; and that has
complied w ith al l the re quirements o f the
authority having jurisdiction."
Service of this water heater requires ability
equivalent to th at of a Qual ified S ervice
Agent (l icensed t radesman) i n the fi eld
involved. Installation skills such as plumbing,
air supp ly, vent ing, gas s upply, e lectrical
supply are r equired i n addition to electrical
testing ski lls. S ome pro ducts m ay requ ire
combustion testi ng equipment and
certification. If you do not possess these
skills or do not h ave the pr oper t ools y ou
should not attem pt to serv ice thi s w ater
heater.
Servicing should only be performed by a Qualified Service Agent 198152-002
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
TOOLS REQUIRED
●ELECTRICAL MULTIMETER CAPABLE OF MEASURING CONTINUITY/ OHMS, AC
& DC VOLTS, AMPERES, MICROAMPERES, MILLIVOLTS, and FREQUENCY(Hz)
○UEi Model DL289 or equivalent
●DIGITAL MANOMETER + 60” W. C. in .01” increments
Note: A digital manometer is required for testing pressure switches and can replace
a gas pressure gauge, draft gauge or slack tube manometer for checking gas
pressure.
○UEi model EM200 or equivalent
●WATER PRESSURE GAUGE w/ LAZY HAND AND HOSE BIBB CONNECTION
●THERMOMETER
●1-1/16 INCH SOCKET WITH EXTENSION FOR ANODE REPLACEMENT
Servicing should only be performed by a Qualified Service Agent 198152-002
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
GENERAL INFORMATION
INSTALLATION REQUIREMENTS FOR THE
COMMO NWEALTH OF MASSACHUSETTS
For al l side w all terminated, hor izontally vented
power v ent, direct vent, and power direct v ent gas
fueled w ater heat ers installed i n ev ery dwelling,
building or structure used in w hole or i n p art for
residential pur poses, including t hose ow ned or
operated by the Commonwealth and where the side
wall exhaust vent termination is less than seven (7)
feet above finished grade in the area of the venting,
including but not limited to decks and porches, the
following requirements shall be satisfied:
INSTA LLATION OF CARBON MONOXIDE
DETECTORS
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gas fitter s hall observe that a hard wired carbon
monoxide detector with an alarm and battery backup is in stalled on t he f loor le vel wh ere t he g as
equipment is t o b e i nstalled. In add ition, t he
installing plumber or gas fitter shall obs erve t hat a
battery operated or har d w ired carbon monoxide
detector w ith an al arm i s i nstalled on eac h
additional level of the dwelling, building or structure
served by the sidewall horizontal vented gas fueled
equipment. It s hall b e the re sponsibility o f the
property owner to secure t he services of q ualified
licensed pr ofessionals for the i nstallation of har d
wired carbon monoxide detectors. In the event that
the s ide wall hor izontally v ented gas fueled
equipment is installed i n a c rawl space or an attic,
the hard wired carbon monoxide detector with alarm
and battery back-up may be installed on the nex t
adjacent f loor l evel. I n t he e vent t hat the
requirements of this subdivision can not be met at
the t ime of c ompletion o f i nstallation, t he ow ner
shall have a period of thirty (30) days to comply with
the a bove requirements p rovided t hat dur ing said
thirty ( 30) day p eriod, a bat tery op erated carbon
monoxide detector with an alarm shall be installed
APPROVED CARBON MONOXIDE DETECTORS
Each carbon monoxide de tector as r equired in
accordance with the above provisions shall comply
with N FPA 720 and be AN SI/UL 20 34 listed and
CSA certified.
SIGNAGE
A m etal or p lastic i dentification plate s hall b e
permanently mounted to the exterior of the b uilding
at a minimum height of eight ( 8) feet ab ove grade
directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2”) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR
OF ALL OBSTRUCTIONS.”
GAS PRESSURE SPECIFICATIONS
MODELS
Maximum Gas Supply Pressure
Nominal Gas Suppl y Pressure
Minimum Gas Supply Pressure
(Low Gas Press. Switch
Setting)
Servicing should only be performed by a Qualified Service Agent 198152-002
Propane
120-150
14.0“WC
( 3.45kPa)
11.0“WC
( 2.74kPa)
8.5“WC
( 2.12kPa)
10.0“WC
(2.49 kPa)
Natural
199-250
10.5“WC
(2.59kPa)
7.0“WC
(1.74kPa)
4.8”WC
(1.20kPa)
0“WC
( 0 kPa)
Propane
199-250
14.0“WC
( 3.45kPa)
11.0“WC
( 2.74kPa)
8.5“WC
( 2.12kPa)
0“WC
( 0 kPa)
Natural
300/400/500
11.0”WC
(2.74kPa)
7.0”WC
(1.74kPa)
5.2”WC
(1.54kPa)
4.00“WC
( 1.25kPa)
Propane
300/400/500
14.00”W C
(3.49kPa)
11.0”WC
(2.74kPa)
11.0“WC
( 2.74kPa)
10.0“WC
( 2.49kPa)
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
INSTALLATION QUICK TIPS – SUF 120 and 150 GAS PRESSURE
ADJUSTMENT PROCEDURE:
GAS PRESSURE
SUF120 AND 150 MODELS
a. Attach a pressure gauge (manometer) to the
manifold pressure tap and refer to page 4 for correct
pressure.
Main line gas pressure to the water heater for natural
gas should be between a maximum of 10.5"W.C.
(2.59kPa) for natural gas, 14.0"W.C.(3.45kPa) for
propane and a minimum of 4.8W.C.(1.18kPa) for
Natural Gas, and 8.5"W.C. (2.08kPa) for Propane
Gas.
A supply gas pressure regulator
(service regulator) must be installed on
the gas supply line within 10' (305 cm)
of the unit.
Also see gas pressure specification table on page 4.
1.Check gas line pressure with a manometer.
2.Check manifold pressure gauge (manometer)
connected to the manifold pressure tap on the gas
control valve,
If full rate adjustment is required, remove cover screw
from top of the gas control valve. Using a small
screwdriver, turn adjusting screw clockwise to
increase or counterclockwise to decrease gas
pressure to obtain 4.0" W.C.(1 K pa) for natural gas
and 10.0" W.C. (2.5 kPa) for L.P. Gas.
3. Cycle the burner on and off several times to check
its operation.
4. Check the operation of the limit and operating
controls.
5. Check the vent system seams and joints and
ensure that there is no discharge of flue products into
the room.
6. Check the input rate.
HIGH ALTITUDE INSTALLATIONS
SUF 120 - 150
For appliance installation locations with elevations
above 6,500 feet (1982 meters) consult the “High
Altitude Installation” section of the owners manual.
b. Use this formula to “clock” the meter. Be sure
other gas consuming appliances are not operating
during this interval.
Btuh = 3600 X H/ T
T = Time in seconds to burn 1 cubic foot of gas.
(With a stopwatch read the gas meter and measure
the amount of time required for the heater to consume
1 cubic foot of gas.)
H = Heating value of gas (in Btu’s per cubic foot of
gas).
Btuh = Actual heater input rate, in Btuh.
EXAMPLE: (Using SUF-150 heater)
T = 25.25 seconds
H = 1050 Btu/ft.3
BTUH = ?
Compare result to the de-rated input required for
the elevation at the installat ion location.
Should it be necessary to adjust the gas pressure to
the burner, to obtain the full input rate, the steps below
should be followed:
c. Remove the pressure regulator cover screw and
adjust the pressure by turning the adjusting screw with
a small screwdriver. Do not exceed 4.0" (1 kPa)
natural gas models and 10.0" w.c. (2.5kPa) on the
propane models. Clockwise to increase gas pressure
and input rate. Counterclockwise to decrease gas
pressure and input rate.
d. “Clock” the meter as in step (b) above.
e. Repeat steps (c) and (d) until the specified input
rate is achieved.
f. Turn the manual gas valve to “OFF”. Replace the
pressure regulator cover screw. Remove the pressure
gauge or manometer from the manifold pressure tap.
Replace the set screw in the manifold pressure tap. If
the gas pressure regulator cannot be adjusted to give
the full input rating with sufficient gas pressure at the
valve, check to ensure the unit is equipped with the
correct orifice.
Servicing should only be performed by a Qualified Service Agent 198152-002
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
INSTALLATION QUICK T IPS - SUF 199 AND 250 GAS PRESSURE
ADJUSTMENT PROCEDURE:
GAS PRESSURE
SUF 199 AND 250 MODELS
IMPORTANT NOTE
THE SUF 199 AND 250 MODELS
INCORPORATE A NEW GAS CONTROL,
WHICH OPERATES AT A MANIFOLD
PRESSURE OF 0" W.C. (0 kPa) FOR BOTH
NATURAL AND PROPANE GAS. SEE T HE
GAS PRESSURE CHART ON PAGE 4.
THESE MODELS ARE CONFIGURED
PRIOR TO BEING SHIPPED FROM THE
FACTORY AND NO ADJUSTMENTS ARE
NECESSARY PRIOR TO STARTUP. THE
CONTROLLER MONITORS T HE AIR FLOW
AND MAKES ADJUSTMENTS TO THE FAN
SPEED WHICH IN EFFECT CONTROLS
THE AMOUNT OF GAS FLOW.
THEREFORE, THE UNIT WILL SELF
ADJUST TO ACQUIRE THE CORRECT
AMOUNT OF INPUT.
"Supply gas pressure to the water heater
must not exceed a maximum of 10.5" w.c.
(295kPa) for natural gas, or 14" w.c. (3.45
kPa) for propane. The minimum supply gas
pressure is 4.8" w.c. (1.20 kPa) for natural
gas and 8.5" w.c. (2.12 kPa) for propane
gas."
HIGH ALTITUDE INSTALLATION
The SUF 199 and 250 models are suitable
for installation up to 10,100 feet above sea
level with no adjustments.
GAS ORIFICE
The SUF 199 and 250 models do not have a
natural gas orifice. A .230” orifice is used on
LP gas models.
Venturi
Gasket
w/o orifice
Gas Control Without Orifice
Natural Gas
Venturi
Gasket w/
LP Gas
Orifice
(.230”
Brass)
Gas Control with .230” LP Orifice
Once the unit is installed and filled with water
and the inlet pressures confirmed, simply
turn the switch "on" and observe operation.
Cycle the unit "off" and "on" several times to
ensure proper operation.
A supply gas pressure regulator
(service regulator) must be installed on
the gas supply line within 10' (305 cm)
of the unit.
Servicing should only be performed by a Qualified Service Agent 198152-002
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
INSTALLATION Q UICK TIPS - SUF 300, 400 GAS PRESSURE
ADJUSTMENT PROCEDURE:
GAS PRESSURE
SUF 300,400,
A minimum dynamic gas suppl y pressure of
5.2" w.c. (1.29 kPa) for Natural Gas and 11"
w.c. (2.74 kP a) for LP Gas is requir ed befo re
making any adjustment to th e gas control
pressure regulator. Attempts to adjust the
regulator during periods of low gas supply
pressure could result in over firing of the water
heater when the gas supply pressure returns to
normal.
1. Check gas line pressure with a manometer,
adjust the gas supply line pressure Gas Pressure
table on page 4.
2. Check manifold pressure using a pressure
gauge (manometer) connected to the manifold
pressure tap on the gas control valve, If full rate
adjustment is required, remove cover screw from
top of the gas control valve. Using a small
screwdriver, turn adjusting screw clockwise to
increase or counter clockwise to decrease gas
pressure to obtain 4.0" w.c. (0.996 kPa) for
Natural Gas and 10" w.c. (2.49kPa) for LP gas.
3. Cycle the burner on and off several times to
check its operation.
4. Check the operation of the limit and operating
controls.
5. Check the vent system seams and joints and
ensure that there is no discharge of flue products
into the room.
6. Check the input rate as shown on page 5.
HIGH ALTITUDE ADJUSTMENT
SUF 300,400,
For high altitude adjustments, contact the
help line on the front of the water heater or
contact help@statewaterheaters.com .
Servicing should only be performed by a Qualified Service Agent 198152-002
ULTRAFORCE COMMERCIAL GAS WATER HEATER
SUF 120 thru 400 SERVICE HANDBOOK
VENTING TABLES SUF 120 – 250
Maximum equivalent feet of intake and vent pipe using 3” PVC is 50 feet (15.2m). Equivalent feet
must include any 90° elbows (two 45° elbows equal one 90° elbow). Three inch diameter 90° elbows
are equivalent to 5' (1.5m) of pipe.
Maximum equivalent feet of intake and vent pipe using 4” PVC is 120 feet (36.6m).
Equivalent feet must include any 90° elbows (two 45° elbows equal one 90° elbow). Four inch
diameter 90° elbows are equivalent to 5' (1.5m) of pipe.