State Industries SBD71 120, SBD85 500 User Manual 2

SERVICE HANDBOOK
®
SandBlaster
Self Cleaning Commercial Gas Water Heaters with Flue Damper and Electronic Ignition
MODELS COVERED
Part Number 317926-000
Printed in the U.S.A. - 0810
COMMERCIAL
The Expert’s Choice®
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
1
SBD
HANDBOOK
TABLE OF CONTENTS
PAGE PAGE
Troubleshooting (continued)
Introduction 1-2 Troubleshooting the Efflkal 28-30
Wire Harness Test 31 Installation 3 IID Module 32 Clearances 4 Pilot Spark 33 Air Requirements 5-8 Pilot Valve 34-35 Contaminated Air 9 Main Burner Test 36 Flammable 9 Flame Rectification 37 Gas Pressure 10 IID Module 38 Gas Valve 11 Main Gas Valve 39-40 Venting 12-15
Sequence of Operation
Mechanical 16 Service Charts and General Electrical 17-18 Questions and Answers 41-42
Troubleshooting Parts List 43-50 Transformer 19 High Limit 20-21 Component Part Information 51 Damper (on Standby) 22 PC Board 22-23 Service Check List 52-53 Thermostat 24 Effikal Damper 25 Comments 54
Effikal Harness Test 26 Normal Operation 26-27
SBD SERVICE HANDBOOK INTRODUCTION
This service
handbook is designed to aid in servicing and troubleshooting State SBD water heaters in the field. No duplication or reproduction of this book may be made without the express written authorization of the State Water Heater Company.
The following text and illustrations will provide you with a step by step procedure to verify proper installation, operation, and troubleshooting procedures. Additional quick reference data is included to assist you in servicing this product.
The information contained in this handbook is designed to answer common questions encountered in the operation of the SBD product line and is not meant to be all inclusive. If you are experiencing a problem not covered in this handbook, please contact the Technical Information Department at 1-800-365-0577 or your Local State Water Heater Sales Representative for further assistance. This handbook is intended for use by licensed plumbing professionals and reference should be made to the installation manual accompanying the product. This handbook contains supplemental information to the SBD installation and operat
ion manual.
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
2
Qualifications: Installation or service of this water heater requires ability equivalent to that of a licensed tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical testing skills are required.
Tools Required:
Phillips head screwdriver
standard screwdrivers
a 3/8 and 7/16 inch open end wrench
set of marked drill bits
an electrical multimeter tester capable of measuring continuity
gas pressure gauge or manometer
water pressure gauge
thermometer
1/2 inch socket with extension for removal of the clean out cover,
1 1/16 inch socket with extension for anode removal.
CUSTOM COMMERCIAL STORAGE TANK MODEL NUMBER BREAKDOWN
Model Breakdown
SBD 85 500 P E A CGA D
*Up to 8,000 Feet
S D 85
500
P
E
A DB
Sandblaster/Damper
85
Gallon
500,000
BTUH
Propane
3 Year
Warranty
ASME
Constructed
High
Altitude*
CGA
None=Standard
T=Tall
S=Short
Canadian
Product
(if applicable)
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
3
INSTALLATION
This portion of the handbook will review some often overlooked installation considerations, taking note of necessary installation requirements for the SBD 71120 through SBD 85500 model heaters. The installation manual covers most of these items in detail.
Clearance to Combustibles Table
MODEL A B C
120 - 200 1” (2.54CM) 1” (2.54CM) 1” (2.54CM) 250 - 305 2” (5.08CM) 2” (5.08CM) 2” (5.08CM) 365 - 400 3” (7.75CM) 3” (7.75CM) 3” (7.75CM)
500 5” (12.7CM) 5” (12.7CM) 5” (12.7CM)
A 24 inch clearance for all serviceable parts is recommended. Clearances may vary between SBD models – See instruction manual or the label on the heater, for clearances applicable to your specific model.
*20” (50.8CM) for 500 models.
CLEARANCES FROM COMBUSTIBLES
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
4
EXTERIOR CLEARANCE
This illustrates the exterior roof clearances for SBD units with natural draft venting. The vent shall extend at least 3 feet above the highest point where it passes through a roof of a building, and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet (for vents of 12" in diameter or less). (NFPA 54 ANSI Z 223.1 SEC
7.5.2a). (Sec 7.6.2a may allow reduction to 8 feet with a “ Listed vent cap”).
"Copyright by the American Gas Association. Used by permission of the copyright holder".
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
5
AIR FOR COMBUSTION
10 CUBIC FEET OF AIR PER 1,000 BTU
Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1000 BTUH input of the gas input. The National Fuel Gas Code also recommends an additional 2.5 cu.ft. of "excess" air. This 12.5 cu.ft minimum supply air per 1000 BTUH input applies to natural and propane gas models.
The National Fuel Gas Code also specifies minimum make-up air opening sizes for various building installations. (Ref: NFPA 54, ANSI Z223.1, sec 5.3)
2.5 CU. FT.
EXCESS
AIR
10 CU.
FT.
COMB.
AIR
(Minimum)
1,000
BTU
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
6
MAKE-UP AIR
DIRECT COMMUNICATION
A fresh supply of make-up air for combustion can be supplied to the heater through make­up air ducts which directly communicate with the out of doors. Two openings are required
- one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square inch per 4000 BTUH of the total input of all appliances within the enclosure.
The lower opening is primarily providing combustion air. The upper opening is providing vent dilution air and acts as a relief opening for flue gases should the vent become obstructed or a downdraft condition occur. Additionally, when the heater is installed in a confined space and communicating with the outdoor air, one permanent opening, commencing within 12 in. (30 cm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16 cm) from the front of the appliance. The opening
shall directly communicate with the outdoors and shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 sq. in. per 3000 BTU per hr (7 cm2 per kW) of the total input of all equipment
located in the enclosure, and
b. Not less than the sum of the areas of all vent connectors in the confined space.
1 Square Inch Per 4,000 BTUH
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
7
MAKE-UP AIR
VERTICAL DUCTS
Often it is more practical to install vertical make-up air ducts to the out doors. Again, two openings are required - one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square inch per 4000 BTUH of the total input of all appliances within the enclosure.
MAKE-UP AIR
HORIZONTAL DUCTS
When the heater is installed in an interior room with no roof access for vertical ducts, horizontal make-up air ducts should be installed. When using horizontal ducts, two openings are required - one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square inch per 2000 BTUH of the total input of all appliances within the enclosure.
1 Square Inch Per 4,000 BTUH
1 Square Inch Per 2,000 BTUH
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
8
INSUFFICIENT MAKE-UP AIR
BACKDRAFT
Insufficient make-up air is a major cause of combustion problems. One common example is in a restaurant installation where exhaust vent equipment was not considered in sizing make-up air requirements. This may result in air being backdrafted by the restaurant exhaust equipment through the heater causing flue gas spillage, flame roll out, improper combustion, inconsistent pilot operation, and/or erratic heater shut down.
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
9
CONTAMINATED AIR
Along with adequate make-up air, the quality of the air is important. Contaminants in combustion air can lead to premature heater failure. Vapors from bleaches, soaps, waxes, salts, etc. are drawn into the combustion chamber with the make-up air and, once fired, mix with water vapor in the gases to form extremely corrosive hydrochloric or hydrofluoric acid and other corrosive byproducts.
AIR FOR COMBUSTION
Flammable Items
Flammable items, pressurized containers or any other potentially hazardous articles must never be placed on or adjacent to the heater. Open containers of flammable material should not be stored or used in the same room with the heater.
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
10
GAS PRESSURE REQUIREMENTS
Natural Gas Propane Gas
Maximum Supply Pressure 10.5" W.C. 13.8" W.C.
Minimum Supply Pressure 5.0" W.C. 11" W.C.
Manifold Pressure 4.0 " W.C. 10" W.C.
The supply gas pressure is normally measured at the dirt leg or at the gas pressure tapping on the gas supply shutoff valve. This reading must be measured with 'flowing' gas.
The manifold gas pressure is measured at the manifold pressure tap of the gas valve when the gas is flowing.
Supply Gas
Dirt Leg
Manifold Gas Port
Manifold Pressure Tap
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
11
SBD GAS VALVE
The gas valves used on all SBD water heaters are 24 volt AC combination step opening gas valves. They incorporate the pilot valve, main valve, and gas pressure regulators into one body. The inlet view of the valve features a filter screen and the top knob. The top knob is a manual on/off gas control for both the pilot and main gas valves. When the top knob is placed on the black mark, gas is supplied only to the pilot valve.
On the top view, we see the pilot solenoid and pilot and main gas regulators. The top view also displays the “TH and “TR” terminals. The pilot gas regulator is found under its cover screw. It is factory preset at 3.5” W.C. but can be adjusted from
2.5 to 5 inches water column. The main gas regulator is found under its cover screw. It is factory preset to 3.5 inches W.C. and adjusts gas pressure output from 2.5 to 5 inches water column. The two electrical terminals are marked TH and TR. The TH terminal is the common between the pilot valve solenoid coil and the main valve
solenoid coil. The other wire emerging from the pilot solenoid connects to the pilot valve electrical output on the IID (terminal PV). The TR terminal connects directly to the main valve electrical output from the IID module (terminal MV).
On the outlet view of the gas valve, we see the pilot gas connection port, manifold gas connection port, a limited bleed vent port, the manifold gas and pressure tap.
See step 18 for SBD-500 gas valve illustration
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
12
VENTING
Atmospheric, Single, and Multiple Heaters
All SBD water heaters are classified by ANSI as category I (non-condensing, negative pressure venting) appliances. They are approved for type B vent.
For larger applications, SBD water heaters can be common vented together either in a tapered manifold or constant size manifold. (Follow National Fuel Gas Code requirements for sizing and installation.)
Combined Vents
When vents are combined, the area of the combined vent should be equal to area of the largest single vent, plus 50% of area of all others joining.
Nine Rules for Good Vents
1. The vent pipe should ALWAYS be the same size as the outlet of the draft diverter or factory supplied vent reducer.
Model SBD 120 are supplied with a 6” to 5” reducer.
Models SBD 250, 251 and 275 are supplied with a 8” to 6” reducer.
EXAMPLE: To combine two 6” vents with an 8” vent, the area of a combined vent should be one half area of two 6 inch vents (14 + 14) plus area of 8 inch vent (50) or 78 sq. inches. Referring to chart, 78 sq. inches require 10” diameter vent.
Vent Size
Area in Square
Inches Vent Size
Area in Square
Inches
5" 20 10" 79 6" 28 12" 113 7" 38 14" 154 8" 50 16" 201 9" 64 18" 254
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
13
Nine Rules for Good Vents (continued)
2. The diameter of a vent pipe should NEVER be reduced, no matter what the circumstances.
3. In some cases it may be necessary to run a vent larger than the draft diverter outlet.
4. Take the maximum vertical rise possible immediately above the draft diverter.
5.
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
14
Nine Rules for Good Vents (continued)
6. Horizontal pipe should be sloped upward at a minimum of ¼” per foot.
7. Horizontal elements should be limited to 75% of the vertical rise of the vent above the connection.
8. Flue gases must be kept hot for proper venting.
9. Obstructions can cause down drafts.
The vent pipe should be extended to meet local codes
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
15
POWER VENT KITS FOR SIDEWALL VENTING
SBD water heaters can be used with power vent kits for sidewall venting. State offers power vent kits for use on installations with a maximum of 100 equivalent feet of vent piping. The power vent kits also use type B vent materials. When power venting, specific exterior clearances must be maintained, as outlined in the National Fuel Gas Code. (NFPA 54, ANSI A223.1, sec 7.8)
Male plug to Cable
Female plug to Damper
40’, Power Venter cable with “Y” connect
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department Ashland City, TN ©2003
16
SBD SEQUENCE OF OPERATION
1. Thermostat calls for heat
2. Flue damper opens
3. Intermittent Ignition Control
5. Main gas valve opens
7. Thermostat satisfies
4. Pilot gas opens, Pilot sparks and flame proves
6. Main burner ignites
8. Main and pilot burners "OFF"
SEQUENCE OF OPERATION
To understand SBD tank type water heaters, an examination of their sequence of operation is necessary.
When the thermostat calls for heat, the relay in the draft hood assembly activates the flue damper motor. The damper opens and power flows to the IID (Intermittent Ignition Device). This activates the IID module to open the pilot valve and begin sparking at the pilot burner assembly. Once the pilot flame is established and confirmed back to the IID, the sparking is stopped and the main gas valve is opened, allowing gas flow to the main burner. When the thermostat satisfies, main and pilot gas is shut off. Damper is returned to closed position.
9. Flue damper closes
Loading...
+ 39 hidden pages