State Industries SBD30 199, SERIES 108, SBN85 390-A, SBN71 120, SBD30 150 User Manual

SERVICE HANDBOOK
SandBlaster
Self-Cleaning Induced Draft Multi Flue Commercial Gas Water Heaters
®
MODE L S COVERE D
SBN71 120 Through SBN85 390 (A)
Series 108 Models and
SBD30 150, SBD30 199
Booster Heaters
SBN Meets Low NOx Requirements of SCAQMD Rules 1121 & 1146.2
Printed in the U.S.A. - 0810
COMMERCIAL
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT1sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Table of Contents
SBN 71-120 thru 85-390, SBD30-150/199 SERVICE HANDBOOK INTRODUCTION.........2
QUALIFICATIONS..................................................................................................................3
TOOLS REQUIRED...............................................................................................................3
COMMERCIAL TANK TYPE GAS MODEL NUMBER BREAK DOWN..................................3
INSTALLATION CONSIDERATIONS - CLEARANCES.........................................................4
TOP AND FRONT VIEWS OF MINIMUM CLEARANCES TO COMBUSTIBLES..................4
MINIMUM CLEARANCE TO COMBUSTIBLES.....................................................................5
REQUIRED EXTERIOR CLEARANCES................................................................................6
REQUIRED EXTERIOR CLEARANCES................................................................................7
INSUFFICIENT MAKEUP AIR ........ NEGATIVE AIR PRESSURE .....DOWNDRAFTS........7
MAKE-UP AIR – DIRECT COMMUNICATION WITH OUTDOORS.......................................8
CONTAMINATED AIR............................................................................................................9
AIR FOR
COMBUSTION – FLAMMABLE ITEMS..................................................................9
GAS VALVE.........................................................................................................................10
GAS VALVE.........................................................................................................................11
VENTING.............................................................................................................................12
VENTING – MULTIPLE CATEGORY I GAS WATER HEATERS.........................................12
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT..................................................13
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT..................................................14
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT..................................................15
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT..................................................16
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT..................................................17
SBN /SBD30-150/199 SEQUENCE OF OPERATION.........................................................18
COMBINED VENTING.........................................................................................................19
9 RULES FOR GOOD VENTING.........................................................................................
20
9 RULES FOR GOOD VENTING.........................................................................................21
9 RULES FOR GOOD VENTING.........................................................................................22
DRAFT PROVING PRESSURE SWITCH - SETTINGS.......................................................23
THERMOSTAT AND IGNITION CONTROL BOARD VIEW.................................................24
WHITE RODGERS INTEGRATED CONTROL - THERMOSTAT........................................25
WHITE RODGERS IGNITION CONTROL BOARD..............................................................26
GAS CONTROL VALVE / BURNER AREA VIEW................................................................27
WIRING DIAGRAM..............................................................................................................28
ELECTRICAL SEQUENCE – SBN, SBD30-150/199...........................................................29
OPERATING SEQUENCE – FLOW CHART........................................................................30
DIAGNOSTIC SEQUENCE OF OPERATION – FLOW CHART..........................................31
PRE-SERVICE CHECK LIST...............................................................................................32
TEST 1 – 120VAC POWER
CHECK ...................................................................................33
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT2sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
This service handbook is a supplement to the SBN and SBD151/201 Installation and Operation Manual. The handbook provides information on servicing and troubleshooting State SBN/SBD30-150/199/ water heaters in the field. While this handbook is not intended to be all inclusive, it contains:
• step-by-step procedures with illustrations to verify proper installation, operation, and troubleshooting
• quick reference data to assist in servicing the product line
• answers to common questions encountered in the operation of the product line.
The handbook is intended to be used by licensed plumbing professionals. Reference should be made to the installation manual accompanying the product. If you are experiencing a problem not covered in this handbook, please contact the State Technical Information Department at 1-800-365-0024 or your local State Water
Heater representative for further assistance. No duplication or reproduction of this book may be made without the expressed written authorization of the State Water Heaters.
SBN 71-120 thru 85-390, SBD30-150/199 SERVICE HANDBOOK INTRODUCTION
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED
INTERPRETATION.............................................................................................................................33
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED
INTERPRETATION.............................................................................................................................34
TEST 2 – POLARITY CHECK.............................................................................................................35
TEST 3 - CONTINUITY CHECK OF HIGH LIMIT (ECO)....................................................................36
TEST 4 - UPPER TEMPERATURE PROBE CONTINUITY CHECK..................................................37
TEST 5 - CALLING FOR HEAT – NO INDUCER OPERATION.........................................................38
TEST 6 - INDUCER ON.............NO IGNITION..................................................................................39
TEST 7 – INDUCER ON, PROVER SWITCH AND LOW GAS PRESSURE SWITCH CLOSED
....................NO IGNITER OPERATION.............................................................................................40
TEST 8 – IGNITER HEATS .............. NO MAIN BURNER.................................................................41
TEST 9 – IG
NITER HEATS .......NO MAIN BURNER.........................................................................42
TEST 10 - MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS.............................................43
TEST 11 - WATER HEATER SHUTTING OFF BELOW SETTING....................................................44
DISPLAY LIGHTS ON INTEGRATED WATER HEATER CONTROL................................................45
PARTS SBN71-120 thru 85-390 series 100.......................................................................................46
PARTS SBN71-120 thru 85-390 series 100.......................................................................................47
PARTS SBN71-120 thru 85-390 series 100.......................................................................................48
PARTS SBN71-120 thru 85-390 series 108.......................................................................................49
PARTS SBN71-120 thru 85-390 series 108.......................................................................................50
PARTS SBN71-120 thru 85-390 series 108.......................................................................................51
PARTS SBD30-150/199NE.................................................................................................................52
PARTS SBD30-150/199NE.................................................................................................................53
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT3sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
QUALIFICATIONS
Installation or service of this water heater requires ability equivalent to that of a licensed
tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical testing skills are required.
TOOLS REQUIRED
Phillips head screwdriver
standard screwdrivers
3/8 and 7/16 inch open end wrench
• set of marked drill bits
electrical multimeter tester capable of measuring continuity, AC voltage and DC
voltage
• gas pressure gauge or manometer
• water pressure gauge
• thermometer (range 0 - 220 degrees F)
• 1/2 inch socket with extension for removal of the clean out cover
• 1-1/16 inch socket with extension for anode removal
Rev. 1 Adds SBD30-150 and 30-199 models with parts lists. Adds SBN series 108 parts list.
COMMERCIAL TANK TYPE GAS MODEL NUMBER BREAK DOWN
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT4sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
INSTALLATION CONSIDERATIONS - CLEARANCES
This portion of the handbook reviews some often overlooked installation considerations clearances, air supply, gas pressure requirements, and venting—taking note of necessary installation requirements for SBN and SBD30-150/199 . The installation manual covers most of these items in detail.
A 24-inch clearance for all serviceable parts is recommended. Clearances may vary between models. See instruction manual or the label on the heater for clearances applicable to your specific model.
TOP AND FRONT VIEWS OF MINIMUM CLEARANCES TO COMBUSTIBLES
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT5sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
MINIMUM CLEARANCE TO COMBUSTIBLES
Model Number "A" Right Side "B" Left Side "C" Back "D" Ceiling
SBN-120 thru 200A
2" 2" 2" 12"
SBN-250/A thru 310/A
3" 3" 3" 12"
SBN-366 6" 6" 6" 6"
SBN-390 4" 4" 4" 4"
SBD30-150/199 2” 2” 2” 12”
A, B, and C clearances to non-combustibles is “0” inches - a 12 inch clearance to cover remains unchanged.
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT6sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
REQUIRED EXTERIOR CLEARANCES
The illustration below shows the required clearances for venting units using natural draft venting. The vent must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet (for vents of 12 inches in diameter or less). References: NFPA 54 2006; ANSI Z 223.1 SEC 12.6.2 and Sec12.7.2 may allow reduction to 8 feet with a “listed vent cap.”
Copyright by the American Gas Association. Used by permission of the copyright holder”.
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
REQUIRED EXTERIOR CLEARANCES
tnemtrapeD gniniarT lacinhceT7sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
INSUFFICIENT MAKEUP AIR ........ NEGATIVE AIR PRESSURE .....DOWNDRAFTS
One common example is in a restaurant installation where exhaust vent equipment was not considered in sizing make-up requirements. This condition may result in air being back drafted by the restaurant exhaust equipment through the heater causing the draft proving switch to open and/or erratic heater shutdown.
Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1,000 BTUH of gas supplied. The National Fuel Gas code also recommends an additional 2.5 cubic feet of “excess” air. For information on minimum make-up air opening sizes for various building installations, refer to the National Fuel Gas Code NFPA 54, ANSI Z223.1, Sec. 5.3
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT8sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
A fresh supply of make-up air for combustion can be supplied to the heater through make-up air ducts, which directly communicate with the outdoors.(Not Direct Vent)
1 SQUARE INCH PER 4,000 Btu FOR EACH OPENING
Two openings are required: one within 12 inches of the top of the enclosure and one within 12 inches of the bottom of the enclosure. Each opening must have a free area of not less than 1 square inch per 4,000 BTUH of the total input of all appliances within the enclosure. The lower opening primarily provides combustion air. The upper opening provides vent dilution air and acts as a relief opening for flue gases should the vent become obstructed or a downdraft condition occur.
Additionally, when the heater is installed in a co
nfined space and communicating with the outdoor air, one permanent opening, beginning within 12 inches (30 cm) of the top of the enclosure, must be permitted where the equipment has clearances of at least 1 inch (2.5 cm) from the sides and back, and 6 inches (16 cm) from the front of the appliance. The opening must directly communicate with the outdoors and must communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and must have a minimum free area of a) 1
square inch per 3,000 BTUH (7cm2 per kW) of the total input of all equipment located in the enclosure and b) not less than the sum of the areas of all vent connectors in the confined space.
MAKE-UP AIR – DIRECT COMMUNICATION WITH OUTDOORS
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT9sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Along with adequate make-up air, the quality of the air is important. Contaminants in combustion air can lead to premature heater failure. Vapors from bleaches, soaps, waxes, salts, etc. are drawn into the combustion chamber with the make-up air and, once fired, mix with water vapor in the gases to form extremely corrosive hydrochloric or hydrofluoric acid and other corrosive by-products.
CONTAMINATED AIR
AIR FOR COMBUSTION – FLAMMABLE ITEMS
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT01sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
INLET VIEW
The supply gas pressure is normally measured at the gas valve inlet gas pressure tap, if available, when the gas is flowing. The manifold gas pressure is measured at the manifold pressure tap of the gas valve when the gas is flowing. Gas valves used are 24 volt AC combination-step opening gas valves. They incorporate the main valve and gas pressure regulator into one body. The Low Gas Pressure Switch, the Supply Gas Inlet, and the Supply Gas Pressure Tap are shown in the Inlet View to the right.
The top view of the gas valve, shown on the right, shows the Main Gas Regulator, Manifold Pressure Tap, Top Knob, and the Limited Bleed Vent Port. The main gas regulator is found under the silver cap (silver cap for Natural Gas or black cap for Propane) screw. It is factory preset to 3.5 inches W.C. and adjusts gas pressure output from 3.0 to 5 inches water column.
Caution: Always test the
manifold pressure at the outlet when the gas is flowing.
TOP VIEW
GAS VALVE
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT11sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
The outlet view of the Gas Valve, shown on the right, shows the Manifold Gas Outlet Connection, the two 24 volt Main Valve (MV) Solenoid connections, and the Manifold Pressure Tap. The two yellow wires from the 12-pin plug on the Ignition Board attach to the MV terminals.
OUTLET VIEW
GAS VALVE
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT21sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
All SBN and SBD water heaters are classified by ANSI as Category I (non-condensing, negative pressure venting) appliances. They are approved for type B vent. The draft inducer does not pressurize the exhaust.
VENTING
VENTING – MULTIPLE CATEGORY I GAS WATER HEATERS
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT31sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Multiple Gas Fired Tank-Type Heaters
When venting multiple Category I tank type heaters using Type B vent pipe, follow the installation tables below which give sizing and data based upon NFPA 54/ANSI Z223.1-2006.
Model: SBN 71-120
latoT.rh/utB 000,021:tupnI Vent Height (feet)
0010503025101865 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
120,000 1' 6 6 5 5 5 5 5 5
120,000 2' 5 5 5 5 5 5 5 5
120,000 3' 5 5 5 5 5 5 5 5
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
66666677000,0422
66677788000,0633
67788999000,0844
Model: SBN 154; SBD30-150
T.rh/utB 000,451/000,051:tupnI otal Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
150,000/154,000 1' 6 6 6 6 6 6 6 6
150,000/154,000 2' 6 6 6 6 6 6 6 6
150,000/154,000 3' 6 6 6 6 6 6 6 6
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2 300,000/ 308,000 7 7 6 6 6 6 6 6
3 450,000/ 462,000 8 8 7 7 7 6 6 6
4 600,000/ 616,000 9 9 9 8 8 7 7 6
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT41sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Model: SBN80-180; SBN100-199; SBN100-200; SBD30-199
Input:180,000, 190,000 and 199,000 Btu/hr. Total Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
180,000 1' 7 7 6 6 6 6 6 6
199,000/200,000 1' 7 7 7 6 6 6 6 6
180,000 2' 6 6 6 6 6 6 6 6
199,000/200,000 2' 7 7 6 6 6 6 6 6
180,000 3' 6 6 6 6 6 6 6 6
199,000/200,000 3' 6 6 6 6 6 6 6 6
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2
360,000
7 7 6 6 6 6 6 6
398,000/400,000
7 7 7 6 6 6 6 6
3
540,000
7 6 6 6 6 6 6 6
597,000/600,000
6 6 6 6 6 6 6 6
4
720,000
6 6 6 6 6 6 6 6
796,000/800,000
6 6 6 6 6 6 6 6
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT51sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Model: SBN100-275
latoT.rh/utB 000,572:tupnI Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
275,000 1' 8 8 7 7 6 6 6 6
275,000 2' 8 8 7 7 6 6 6 6
275,000 3' 7 7 7 7 6 6 6 6
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2 550,000 10 9 9 8 8 8 7 7
3 825,000 12 12 12 10 9 9 8 8
4 1,100,000 14 14 14 12 12 10 9 9
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT
Model: SBN100-250
latoT.rh/utB 000,052:tupnI Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
250,000 1' 8 8 7 7 7 6 6 6
250,000 2' 7 7 7 7 6 6 6 6
250,000 3' 7 7 7 7 6 6 6 6
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2 500,000 9 9 9 8 8 7 7 7
3 750,000 12 12 10 10 10 9 8 8
4 1,000,000 14 14 12 12 10 10 9 9
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT61sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Model: SBN 85-310
latoT.rh/utB 000,013:tupnI Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
310,000 1' 9 8 8 8 7 7 6 6
310,000 2' 8 8 8 7 7 7 6 6
310,000 3' 8 8 8 7 7 7 6 6
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2 620,000 10 10 9 9 8 8 7 7
3 930,000 14 12 12 12 10 9 9 8
4 1,240,000 14 14 14 12 12 12 10 9
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT71sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
Model: SBN 85-366NE, SBN 85-390NE
T.rh/utB 000,993/000,663:tupnI otal Vent Height (feet)
0010503025101866 :eziS rotcennoC tneV
Input Btu/hr Rise Vent Connector Diameter (inches)
366,000
399,000
1'
9 9 9 8 8 8 8 8
10 9 9 9 8 8 8 8
366,000
399,000
2'
9 9 8 8 8 8 8 8
9 9 9 8 8 8 8 8
366,000
399,000
3'
9 8 8 8 8 8 8 8
9 9 8 8 8 8 8 8
No. of Units Combined Input (Btu/hr x 1,000) Combined Vent/Manifold Diameter
2
732,000 12 10 10 9 9 9 8 8
798,000 12 12 10 10 9 9 8 8
3
1,098,000 14 14 14 12 12 10 9 9
1,197,000 14 14 14 12 12 10 10 9
4
1,464,000 16 16 14 14 14 12 12 10
1,596,000 16 16 16 14 14 12 12 10
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT81sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
SBN /SBD30-150/199 SEQUENCE OF OPERATION
Sequence
1. Thermistors (probes) call for heat.
2. Inducer fan starts and provides draft.
3. Hot surface igniter = 20 sec. warm-up.
4. Main gas valve opens 4 sec. trial for
ignition. (Maximum 5 trials.)
5. Main burner ignites and proves.
6. Thermostat reaches the temperature
setting.
7. Main burners “OFF” - Auto restart after
60 min. - 20 sec blower
6
1
4
2
1
5 & 7
3
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT91sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
COMBINING VENTS (MANIFOLDING
When vents are combined, the area of the combined vent should be equal to area of the largest single vent, plus 50% of area of all others joining.
EXAMPLE: To combine two 6” vents with an 8” vent, the area of a combined vent should be one half area of two 6 inch vents (14 + 14) plus area of 8 inch vent (50) or 78 sq. inches.
Referring to chart: 78 sq. inches requires a 10” diameter vent.
Vent Size Area in
Square Inches
Vent Size Area in
Square Inches
5" 20 10" 79
6" 28 12" 113
7" 38 14" 154
8" 50 16" 201
9" 64 18" 254
COMBINED VENTING
Maximize height from water heater vent connection to first elbow or tee.
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT02sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
1.The vent pipe should ALWAYS be the
same size as the outlet of the draft hood or
factory supplied vent reducer.
Model SBN71-120 is supplied with a 6” to 5” reducer.
2. The diameter of a vent pipe should
NEVER be reduced, no matter what the circumstances.
3. In some cases it may be necessary to
run a vent larger than the vent connector.
4. Take the maximum vertical rise (x)
possible immediately above the draft hood.
9 RULES FOR GOOD VENTING
VENT CONNECTOR
VENT PIPE
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT12sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
5.Use a 45° elbow in place of a 90° elbow where possible. Avoid the use of a 90° elbow
immediately above the draft hood. Allow the maximum vertical rise before any elbow.
6.Horizontal pipe should be sloped
upward at a minimum of ¼” per foot.
9 RULES FOR GOOD VENTING
HORIZONTAL RUN
VERTICAL RISE
EQUAL TO
1/4” PER FOOT OF
HOROZONTAL
RUN
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT22sretaeH retaW etatS
7002 © eessenneT ,ytiC dnalhsA
9.Obstructions can cause down drafts. The vent pipe should be extended to meet local
codes.
9 RULES FOR GOOD VENTING
7.Horizontal elements should be limited
to 75% of the vertical rise of the vent above the connection.
8.Flue gases must be kept hot for proper
venting. Single wall vent exposed to cold air may not vent properly.
HORIZONTAL
ELEMENTS
LIMITED TO
75% OF
TOTAL
VERTICAL
HEIGHT
VENT RUNS
BEYOND EXTERIOR
WALLS OR INTO
UNHEATED AREAS
SHOULD BE
DOUBLE WALL.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT32sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
DRAFT PROVING PRESSURE SWITCH - SETTINGS
Draft Proving Pressure Switch Table
SBN
Models
SBD
Models
Pressure Setting To Close Switch (Inches W.C.)
"01. ± 06.1 )-(663
"01. ± "00.2 )-(572
"01. ± "57,1 )-(013
"01. ± "04.2 )-(002/021
"01. ± "06.2 )-(081/451
30-150/199
NOTE: Pressure Switch Contacts are Normally Open “N.O.” and close on a fall in pressure.
(-) 2.50" ± .10"
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT42sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
THERMOSTAT AND IGNITION CONTROL BOARD VIEW
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT52sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
WHITE RODGERS INTEGRATED CONTROL - THERMOSTAT
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT62sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
WHITE RODGERS IGNITION CONTROL BOARD
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT72sretaeH retaW etatS
Ashland City, Tennessee 317927-0007002 ©
GAS CONTROL VALVE / BURNER AREA VIEW
HSI
Part Number 194405
Volts AC Nominal 80 VAC
Ohms Resistance 11.0 - 20.0 @ 77° F (25°
C)
NOTICE FLAME ROD CROSSES PATH OF FLAME .1 - .25”
SBN's
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT82sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
WIRING DIAGRAM
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT92sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
ELECTRICAL SEQUENCE – SBN, SBD30-150/199
1. Switch Power on to unit.
2. Thermostat calls for heat.
3. Ignition Control Board performs diagnostic check on system components.
4. On completion of diagnostics check, the Ignition Control Board sends signal to
Exhaust Inducer.
5. Exhaust Inducer begins drawing air through appliance closing the Prover Switch.
6. On completion of Prover Switch engagement, the Ignition Control Board begins
the ignition cycle.
7. The Ignition Control Board provides power to the Silicon Nitride Ignitor.
8. The Silicon Nitride Ignitor heats up for approximately 17 to 20 seconds.
9. At the end of Silicon Nitride Ignitor’s warm-up, the Ignition Control Board opens
the Gas Valve.
10. From the time the Gas Valve opens, the Ignition Control Board waits 3 seconds
and then shuts off power to the Silicon Nitride Ignitor.
11. From the time the Silicon Nitride
Ignitor’s power is shut off, the Ignition Control
Board waits 3 more seconds to monitor the Flame Sensor.
12. If the Flame Sensor does not detect a strong enough flame, the Ignition Control
Board shuts off the Gas Valve and allows the Exhaust Inducer to purge the unit for 20 seconds. At that time, the Ignition Control Board restarts with step
7. It will try and ignite the main burners 2 more times. If the unit does not light, the Ignition Control Board will wait one hour and then re-start at step 3. This cycle will continue until the unit lights or the power is shutoff to the unit.
13. If the Flame Sensor detects a strong flame, the Ignition ControlBoard will allow
the unit to operate until the thermostat is satisfied.
14. Once the unit is satisfied, the Ignition Control Board will shut off the Gas Valve
and the unit will be in standby mode until another call for heat is initiated by the thermostat.
.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT03sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
OPERATING SEQUENCE – FLOW CHART
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT13sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
DIAGNOSTIC SEQUENCE OF OPERATION – FLOW CHART
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT23sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PRE-SERVICE CHECK LIST
Use the following checklist BEFORE you begin servicing the water heater.
1. Have you removed the cover from the controls? ____________________________________________________ Did you take notice of the status lights on the upper water heater control? ____________________________________________________ Did you take notice of the red LED in the upper left corner of the lower ignition control? ____________________________________________________
2.Did you note conditions of the room? ____________________________________________________ Where does the supply air come from? ____________________________________________________ Is the room clean? ____________________________________________________ What is stored with the heater? ____________________________________________________ How is the heater vented? ____________________________________________________ Are all water and gas shut-off valves open? ____________________________________________________ Are there room exhaust or air intake fans? ____________________________________________________
3. Did you note the condition of the heater? ____________________________________________________ Is the ON/OFF switch “On”? ____________________________________________________ What is the temperature of the stored water? (Test at T&P valve or nearby faucet.) ____________________________________________________ Is the thermal expansion tank installed? ____________________________________________________
4. Did you write down the complete model and serial number of the water heater? If so, what are they? ____________________________________________________
5. Does the heater have a good ground wire connection? If not, the inducer will typically come on for a short time (3-5 seconds), then go off, and the re
d LED will flash 8
times.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT33sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED INTERPRETATION
TEST 1 – 120VAC POWER CHECK
No Green display “Power” LED on.
Plugs are in receptacles.
Supply power breaker is not “open”
On/Off heater switch is “On”.
White Rodgers Integrated Control
TEST 1
120 V. AC check to water heater ON/OFF switch
Check for 115-125 V. AC black wire to ground\ 115 V. AC check to E13 Terminal and 2B receptacle.
............nehT.........FI
voltage is not present from on/off switch center black wire to ground
Check conditions above Check wiring from switch to break box
Power is present from center on/off terminal Check power from on/off switch to ignition board terminal
E13
Voltage is not present at E13 to ground check wiring from on/off. Left-outside terminal to E13.
Replace on/off switch.
Power is present elcatpecer 2E lortnoc retaeh retaw ot 41E morf rewop kcehC31E ta
Voltage is not present from water heater control receptacle E2 black
to ground
Check wiring from ignition control board E14 to water heater control receptacle E2. Replace ignition control board.
.no eb dluohs DEL neerG.2E ta tneserp si rewoP
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT43sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED INTERPRETATION
Conditions:
Power On
Red, heater control “Call for Heat” LED – on
Red, ignition control board diagnostic LED – Flashing
Note LED Flash Code before resetting heater.
noitacidnIsutatS DEL
1 Flash System is in lock out.
2 Flashes Draft proving (pressure) switch failed to open within 5 seconds at the end of the last
cycle.
3 Flashes Draft proving (pressure) switch failed to close ( -2.1 inches of water column pressure)
within 5 seconds after the inducer was started. The low gas pressure switch )closes
at 5.2" ± .04" w. c.) may have remained open (Nat Gas only.)
4 Flashes Open on high temperature limit switch (ECO).
5 Flashes Not Used
6 Flashes 115-volt supply power connection is indicating reversed polarity.
7 Flashes Flam
e sensor reads a low flame signal for more than 4.25 sec.
8 Flashes No ignition sensed.
Continuous Flash Continuous flame sensed for more than 5 seconds without gas valve being energized.
Continuous ON Internal control board failure.
*Control system self adjusts to use a minimum voltage for ignition. Lower voltage results in lower IGNITOR temperature which results in longer IGNITOR life. IGNITOR voltage may vary from Nominal 80 VAC.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT53sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 2 – POLARITY CHECK
Conditions:
No hot water
Green “Power” LED is on.
Tank is more than 5° F below
temperature dial setting.
Red ignition control board diagnostic
LED is flashing 6 times between pauses.
Red, diagnostic “Call for Heat” LED-
OFF.
TEST 2
Polarity Check
Check from on/off switch center and white wire terminals to ground
115-125 VAC is not present see Test 1.
Voltage is present white (right terminal) to ground but not black (center terminal) to ground
reverse supply wire connections - polarity is reversed.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT63sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 3 - CONTINUITY CHECK OF HIGH LIMIT (ECO)
Conditions:
Power On – No Hot Water
Red, heater control “Call for Heat”
LED – on
Red ignition control board
diagnostic LED – 4 Flashing
Note LED Flash Code before
resetting water heater control.
See Description of diagnostic LED
Flashes.
Turn Power “Off”
0.0
Ohms
TEST 3
Continuity check of ECO (energy cut-off, high limit)
Black to Black wires of upper probe. Power is off.
.....neht fI
continuity is indicated (ZERO “0.0” Resistance) opens at 203° F; closes at 193° F. If water is
below 193° F, continuity is correct.
continuity is not present (meter reads “0.L”) replace ECO sensor, if water temperature is
below 193° F.
.no eb dluohs DEL sutats teserF °021 naht ssel si retaw
•replace heater control if control will not manually reset.
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT73sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 4 - UPPER TEMPERATURE PROBE CONTINUITY CHECK
Conditions:
Power On - Water below temperature
set point.
Red, water heater control “Reset
Status” LED-OFF
Call For Heat” LED off.
Ohms Resistance Table
° F Ohms
70° 11,884
120° 3,759
140° 2,488
180° 1,169
TEST 4
Upper Temperature probe continuity check
Red wire to red wire - Turn supply power "Off" for this test
.....nehtfI
Test indicates no continuity Replace probe.
Continuity smhO yfirev osla( yako eb dluohs eborPdetacidni si
resistance for water temperature). (Reading will be approximate.)
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT83sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 5 - CALLING FOR HEAT – NO INDUCER OPERATION
Conditions:
Power on
Plugs in Receptacles
Red “ Call for Heat” LED-ON
Inducer “Off”
Note flash code on ignition control board diagnostic LED
Water Heater Control - Thermostat
“call for heat”
LED Indicator
“diagnostic LED indicator”
120
........nehtfI
Pin 1 to ground check has no voltage reset control by interrupting power - note
possible reasons for this from flashing LED code
replace ignition board
Pin 1 to ground egatlov sah Proceed
Pin 3 to ground egatlov on sah •check wiring harness and plugs •replace inducer
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT93sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 6 - INDUCER ON.............NO IGNITION
Conditions:
Power on
Plugs in receptacles
Inducer operating
No power to Hot Surface IGNITOR
(HSI) Note LED flash code
TEST 6
24 VAC Check of Blower Prover/Low Gas Pressure Circuit
........nehtfI
ignition board receptacles E1, Pin 7 to ground shows no voltage replace Ignition board
E1, Pin 7 has 24 Volt recudni morf dna ot noitcennoc eriw kcehcdnuorg ot
voltage check of each blower switch terminal to ground shows voltage to only 1 terminal
Switch is open - check for proper draft (should also see LED 3 flash
code)...Check for blocked exhaust.... Check that blower outlet exhaust
damper is open....Replace blower (draft) proving switch
Natural Gas ONLY!
24V is present from each switch terminal to ground Check wiring from blower switch to low gas pressure switch
Voltage c
heck to each terminal of low gas pressure switch and
ground shows only voltage on 1terminal
Switch is open - test for a minimum of 5.2 ± " W.C. Natural Gas or
10.5" Propane, flowing supply gas pressure (should also see 3 Flash
LED code)..............Replace low gas pressure switch
Voltage is present to each pressure switch terminal and ground Check wiring from low gas pressure switch to ignition board
receptacles E1, Pin 10
INDUCER EXHAUST/ VENT CONNECTION
DRAFT PROVING PRESSURE SWITCH
LOW GAS PRESSURE SWITCH
INDUCER MOTOR
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT04sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 7 – INDUCER ON, PROVER SWITCH AND LOW GAS PRESSURE SWITCH
CLOSED ....................NO IGNITOR OPERATION
Conditions:
Power on
Plugs in receptacles
Inducer on
24V at ignition board E1, Pin
10
No Power to IGNITOR
Note:LED Flash code
TEST 7
Voltage check and continuity check of hot surface IGNITOR circuit
Continuity check - Power off- Plug removed from E4 receptacles. Nominal 80 VAC check - Plug in E4- Power "On".
If.......
then.......
Continuity is not indicated between E4plug pin 2 to 4. Check wiring and connection from E4 plug to HSI receiving
plug...................Replace HSI Assembly
Continuity is present Resistance should be between 11 and 20 Ohms at a
temperature of 77°F
Voltage is not present between E4, Pin 2 to ground Replace ignition board
Voltage Ctneserp si ontinue
Voltage is not present between E4, Pin 4 to ground Check wiring and plug connections to HSI.........Replace HSI
Voltage is present Note ignition board, Flash code LED...
..........HSI should work
CHECK E1PIN 10 TO GROUND – 24 V.
CONTINUITY TEST E4 PLUG
CHECK E4 PIN 4 TO GROUND
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT14sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 8 – IGNITOR HEATS .............. NO MAIN BURNER
TEST 8 IGNITOR HEATS......NO MAIN BURNER
........neht.......fI
short heat up time of IGNITOR
Check control box grounding.
Normal (Approximate 20 seconds) warm up - no ignition Check for 24V from E1, Pin 12 to ground during 4 second trial.
........Yes - Continue................No - Replace Ignition Board
No voltage present E4, Pin 12 to ground Replace ignition board
24 Volt was present from E1, Pin 12 to ground, but no main burner
Check that air has been purged from gas circuit........check that
wiring and connections to gas valve and E1, Pin 9 are correct
.........check fo
r 24 VAC at E1, Pin 9 to ground during 4 second
trial for ignition.
24 V.
E1 PLUG TO PIN 9
E1 PLUG TO PIN 12
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT24sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 9 – IGNITOR HEATS .......NO MAIN BURNER
Conditions:
Test 8 completed then:
Turn off power
Disconnect wires from gas valve
TEST 9 IGNITOR HEATS – NO MAIN BURNER
.....nehtfI
Meter reads 0 or 1
Check meter scale setting to read between 550 and 650 Ohms R
eplace Gas Valve
Meter indicates pilot and main coil have
continuity
Valve should be okay....still no gas to main burner, then coil
may be stuck .........Replace Gas Valve
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT34sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 10 - MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS
Conditions:
Power On – plug connected
Main Burner ignites for approximately 5
seconds then goes out.
Tests 8 and 9 completed
Note flash code on ignition board LED.
TEST 10
MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS
.........neht.......fI
No extended gulp ylbmessa ISH fo snoitcennoc gulp dna gniriw kcehCnoitingi renrub niam
and ignition board receptacles E1, Pin 2.......Check that HSI
assembly is not cracked or dirty......Check that flame prover
will be in main flame ......................Replace HSI assembly
Still no extended draob lortnoc noitingi ecalpeRnoitingi renrub niam
E1, Pin 2 - From Flame Proving Rod
Hot Surface IGNITOR
(Illustration of low NOx burner)
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT44sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
TEST 11 - WATER HEATER SHUTTING OFF BELOW SETTING
Conditions:
Main burner ignited
Stored water is below temperature setting more than 5° F (Tank
Average).
Power off
Plug disconnected from heater control board receptacle E3 and E4
TEST 11
WATER TEMPERATURE CIRCUIT CHECK - CONTINUITY
.....neht fI
continuity check pin to pin of lower temperature probe shows 1 or 0 (E4)
See Test 4 Check wiring and plug connections to heater control board receptacle E4 Replace lower temperature probe
continuity check red wire pin to red wire pin on upper temperature sensor shows 1 or 0 (E3)
see Test 4 Check wiring and plug connections to heater control board receptacle Replace upper temperature probe
.lortnoc retaeh retaw eht ecalpeR yako era skcehc evoba llA
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT54sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
DISPLAY LIGHTS ON INTEGRATED WATER HEATER CONTROL
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT64sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 100
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT74sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 100
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT84sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 100
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT94sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 108
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT05sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 108
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT15sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBN71-120 thru 85-390 series 108
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT25sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBD30-150/199NE
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL
GAS WATER HEATER SERVICE HANDBOOK
tnemtrapeD gniniarT lacinhceT35sretaeH retaW etatS
Ashland City, Tennessee 7002 ©
PARTS SBD30-150/199NE
COMMERCIAL
Prepared by the State Water Heaters Training Department.
For additional technical information call 800-365-0577.
©Copyright 2007 State Industries, Inc.
State Water Heaters
500 Tennessee Waltz Parkway Ashland City, TN 37015 800-365-8170 www.statewaterheaters.com
Loading...