State Industries ROOFTOP SRT80 120NE User Manual

COMMERCIAL GAS W A TER HEA TER
GAS-FIRED POWER BURNER
FOR DOMESTIC HOT W A TER
• INST ALLA TION • OPERA TION • SERVICE • MAINTENANCE • LIMITED W ARRANTY
Thank you for buying this energy efficient water heater from State Industries. We appreciate your confidence in our products.
W ARNING: If the information in these instructions is not followed exactly , a fire or explosion may result causing property damage, personal injury or death.
– Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHL Y BEFORE INST ALLING AND USING THIS APPLIANCE.
– Installation and service must be
performed by a qualified installer, service agency or the gas supplier .
PLACE THESE INSTRUCTIONS ADJACENT TO HEA TER AND
NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED IN U.S.A. 1005 PART NO. 1 97242-000
1
500 Tennessee Waltz Parkway
Ashland City, TN 37015
www.statewaterheaters.com
SUPERSEDES PART NO. 196758-000
TOP VIEW
ROOFTOP SRT80-120NE ROUGH-IN-DIMENSIONS
RIGHT SIDE VIEW
LEFT SIDE VIEW
GAS VAL VE PIPING
SRT80-120 1/2" NPT
FRONT VIEW
T able 1. RECOVERY CAP ACITIES - NA TURAL GAS / L.P.
BTU Gallon
Model Input Capacity 30 40 50 60 70 80 90 100 110 120 130 140
SRT80-120
Recovery capacities are based on heater performance at 80% thermal efficiency .
120,000 80 388 291 233 194 166 145 129 116 106 97 90 83
35.17 kwh 303L (1469) (1102) (882) (734) (628) (549) (488) (439) (401) (367) (341) (314)
Approx.
TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR (LPH)
2
INST ALLA TION INFORMA TION
OUTBACK
Installation Information
Model: SRT 80-1 20NE series Input: 120,000 btuh Electrical: 120/24V AC/60 Hz/5 A Side Clearances: 0" Maximum Inlet Pressure: 14"WC T op Clearances: 1.50" Manifold Pressure: 4.50"WC Unit is Polarity Sensitive Minimum Inlet Pressure: 6.2"WC No external venting required
Warnings
Dummy hot return required if hot return from appliance is not used* Avoid flex gas line usage Avoid use of forklift truck to mount unit on outdoor stand Provide enough clearance to service unit
Available Kits
Anti-freeze kit Remote Interface kit
3
FOREWORD
This design complies with the current edition of ANSI Z21.10.3 as an automatic circulating tank type water heater and automatic storage water heater.
Detailed installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary. It is highly essential that all water, gas piping and wiring be installed as shown on the diagrams.
Particular attention should be given to the installation of thermometers at the locations indicated on the diagrams as these are necessary for checking the proper functioning of the heater.
TABLE OF CONTENTS
PAGE PAGE
ROUGH-IN DIMENSIONS .................................................................... 2
INST ALLATION INFORMA TION........................................................... 3
FOREWORD ....................................................................................... 4
FEATURES ......................................................................................... 5
Water Temperature Control........................................................... 5
High Limit Switch (E.C.O.) ............................................................. 6
Dishwashing Machine Requirement ............................................. 5
Circulating Pump............................................................................ 6
PLUMBING MANIFOLD ASSEMBL Y ................................................... 6
Flow Diagram ................................................................................ 5
Automatic Air Bleed Valve ............................................................ 5
Hot Return Recirculation Pump ..................................................... 7
Drain Valve.................................................................................... 7
AIR SYSTEM ASSEMBL Y .................................................................. 7
Blower Assembly.......................................................................... 7
Blower Plenum .............................................................................. 7
Air Hose ........................................................................................ 8
Flue Adapter.................................................................................. 8
Exhaust Vent ................................................................................. 8
CONTROL SYSTEM ........................................................................... 8
Blocked Outlet Switch .................................................................. 8
Blocked Inlet/Prover Switch .......................................................... 8
Low Gas Pressure Switch ........................................................... 9
On/Off Switch ............................................................................... 9
Hot Surface Igniter ........................................................................ 9
OIM - Outdoor Interface Module ................................................... 9
WR Ignition Control Board ............................................................. 9
Low Water Cutoff Board and Probe ............................................ 10
Thermostat/E.C.O. Probes ............................................................ 10
Transformer .................................................................................. 10
Junction Box ................................................................................. 10
TANK ASSEMBLY SYSTEM .............................................................. 10
T ank Insulation............................................................................... 10
CABINET ASSEMBLY......................................................................... 11
Cabinet Panels .............................................................................. 11
ADDITIONAL CONTROLS .................................................................. 11
Gas Valve ...................................................................................... 11
Flame Sensor ................................................................................ 11
INSTALLA TION INSTRUCTIONS ......................................................... 11
Required Ability ............................................................................. 11
Insulation Blankets ........................................................................ 11
Locating The Heater...................................................................... 11-12
Provide Unit Support ..................................................................... 12
Roof Curb ...................................................................................... 12-13
Rig and Place Unit ......................................................................... 13
Outdoor Stand ............................................................................... 14
Clearances .................................................................................... 14
Hard Water .................................................................................... 14
Air Requirements .......................................................................... 14
In addition to these instructions, the equipment shall be installed in accordance with all local codes. The authority having jurisdiction should be consulted before installing.
In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electric Code, NFPA 70. The former is available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131, and both documents are available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA
02269.
Chemical Vapor Corrosion ............................................................ 14
VENTING ............................................................................................ 15
Vent Terminals ............................................................................... 15
Pressure Switches ....................................................................... 15
Gas Piping ..................................................................................... 15-16
Connection of Gas Pipe ................................................................ 16
Purging .......................................................................................... 16
Gas Meter Size - City Gases Only ............................................... 16
Gas Pressure Regulation.............................................................. 16
Gas Valves .................................................................................... 17
SYSTEM CONNECTIONS ................................................................... 17
Thermometers ............................................................................... 17
Relief Valve ................................................................................... 17
Water Line Connections ............................................................... 17
Closed System .............................................................................. 17
Water (Potable) Heating and Space Heating ................................ 17
Water Heater Wiring...................................................................... 17-18
OPERATION........................................................................................ 19-20
Sequence of Operation ................................................................ 21
Error Codes ................................................................................... 21
Fault Conditions............................................................................. 21-22
PRIOR TO ST ART-UP ......................................................................... 22
Required Ability ............................................................................. 22
OPERATING INSTRUCTIONS.............................................................. 23
Adjustment Procedure (Initial Start-Up) ........................................ 23-24
Cathodic Protection....................................................................... 24
Precautions ................................................................................... 24
Lighting & Operating Label............................................................ 25
GENERAL INFORMA TION .................................................................. 26
Power Burner ............................................................................... 26
High Limit ....................................................................................... 26
High Altitude Installations .............................................................. 26
MAINTENANCE .................................................................................. 26
General.......................................................................................... 26
Maintenance Schedule ................................................................. 26
Flushing ......................................................................................... 26
Draining ......................................................................................... 26
Sediment Removal......................................................................... 26
Lime Scale Removal ...................................................................... 26-27
Anode Inspection and Replacement............................................. 27
Drain Valve and Access Panels ................................................... 27
Relief Valve ................................................................................... 27
Circulating Pump............................................................................ 27
Vent System .................................................................................. 27
INSTALLA TION DIAGRAMS ............................................................... 28-32
CHECKLIST AND SERVICE INFORMATION ........................................ 33
TROUBLE-SHOOTING........................................................................ 33-34
REPLACEMENT PARTS ...................................................................... 34
LIMITED WARRANTY......................................................................... 35
4
FEATURES
IMPORT ANT
IT IS REQUIRED THAT A QUALIFIED SERVICE TECHNICIAN PERFORM THE INITIAL FIRING OF THE HEATER.
A CHECKLIST AND SER VICE INFORMATION section are included at the rear of this manual. By using this checklist the user may be able to make minor operational adjustments and save himself unnecessary service calls. However, the user should not attempt repairs which are not listed in this section.
WA TER TEMPERA TURE CONTROL
DANGER
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. THE TEMPERATURE A T WHICH INJURY OCCURS V ARIES WITH THE PERSON’S AGE AND TIME OF EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, THE ELDERLY OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW THEIR OWN BATH W A TER. NEVER LEAV E A CHILD OR DISABLED PERSON UNATTENDED IN A BA THTUB OR SHOWER.
Figure 1 shows the approximate time-to-burn relationship for normal adult skin. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20°F/-1 1°C. If you experience this type of use, you should consider using lower temperature settings to reduce scald hazards.
Temperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
180°F / 82°C Nearly instantaneous 170°F / 77°C Nearly instantaneous 160°F / 71°C About 1/2 second 150°F / 66°C About 1-1/2 seconds 140°F / 60°C Less than 5 seconds 130°F / 54°C About 30 seconds 120°F / 49°C More than 5 minutes
FIGURE 1
Valves for reducing point-of-use temperature by mixing cold and hot water are available (see Figure 2). Also available are inexpensive devices that attach to faucets to limit hot water temperatures. Contact a licensed plumber or the local plumbing authority.
THE WA TER HEA TER SHOULD BE LOCA TED IN AN AREA WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS TO SET TEMPERATURES.
The water temperature is controlled using the Touch Pad Buttons on the Display at the front of the unit (See Figure 1). This control utilizes two temperature probes to determine the tank temperature. The upper temperature probe is located on top of the unit in the back and the lower probe is located on the front center axis of the tank.
The temperature may be adjusted from 70°F/21°C to 180°F/82°C. The thermostat was adjusted to 70°F/21°C before the heater was shipped from the factory. It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperature be set for the lowest temperature which satisfies your hot water needs. This will also provide the most energy efficient operation of the water heater and minimize scale formation.
SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C WILL REDUCE THE RISK OF SCALDS. Some states require settings at specific lower temperatures.
FIGURE 2
5
HIGH LIMIT SWITCH (E.C.O.)
The top immersion well of the upper probe also contains the high limit (energy cutoff) sensor. The high limit switch interrupts the main burner gas flow should the water temperature reach approximately 199°F/93°C.
Should the high limit switch activate, it must be reset by cycling power to the unit. The water temperature must drop below 180°F/ 82°C before the controller can be reset.
Continued manual resetting of the high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. For example, a malfunction of the control system allowing the gas valve to stay open could cause water temperature to rise until the high limit switch opens. Contact your dealer or servicer if continued high limit switch operation occurs.
DISHWASHING MACHINE REQUIREMENT
All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180°F (82°C) line to the dishwashing machine, and should be adjusted to deliver water between these limits.
The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 180°F (82°C) water at the point of take­off to the dishwashing machine. Adjust flow by means of the plug cock in the circulating line. (See INSTALLATION DIAGRAMS section.)
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the heater. Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current version of the National Electric Code NFPA No. 70.
All bronze circulators are recommended for use with commercial water heaters.
Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before being operated. Please refer to manufacturer's instructions.
PLUMBING MANIFOLD ASSEMBLY
FLOW DIAGRAM
FIGURE 3
AUTOMA TIC AIR BLEED V AL VE
The tank assembly utilizes an automatic air bleed valve. The purpose for this automatic air bleed valve is to allow air to escape the tank when the unit is filled with water. When the unit is drained, the opposite occurs with the valve allowing air to replace the drained water. It removes the pressure vacuum that occurs in the system causing incomplete drainage. This valve is automatic which allows it to sense when the tank assembly is filled with water, see Figure 4.
The plumbing manifold assembly is composed of several components with each having a unique function. Please see Figures 3, 5, and 6 to observe the water flow to the plumbing manifold assembly and the components that make it up.
FIGURE 4
6
HOT RETURN RECIRCULA TION PUMP
BLOWER ASSEMBLY
The hot return recirculation pump circulates the hot water through the hot water line to eliminate delays at plumbing fixtures, see Figure 5.
FIGURE 5
DRAIN V ALVE
The drain valve is used to drain the water from the tank assembly and plumbing manifold assembly, see Figure 6.
The blower assembly functions by pulling in air from outside the unit to supply to the burner assembly for proper combustion. The blower pushes the air through the burner assembly and heat exchanger where the flue gases then exit the exhaust system assembly, see Figure 8.
FIGURE 8
BLOWER PLENUM
FIGURE 6
AIR SYSTEM ASSEMBLY
The air system assembly is comprised of the blower assembly, blower plenum, air hose, and inlet vent terminal. This is where combustion air is acquired for combustion, see Figure 7.
The blower plenum is used to draw air into the blower inlet. The inlet of the air system must maintain enough height from the ground to take into account yearly snow levels to prevent possible inlet vent blockage. The air plenum allows the blower to pull air into the unit from a higher inlet location to provide protection required, see Figure 9.
FIGURE 7
FIGURE 9
7
AIR HOSE
CONTROL SYSTEM
The air hose is used to provide a flexible air path from the blower to the burner assembly. It is held in place with two standard hose clamps, see Figure 10.
FIGURE 10
FLUE ADAPTER
The flue adapter is made of a flat metal plate with an exhaust adapter to mate with the exhaust elbow. This is where the flue gases exit the heat exchanger. This is a very hot region and is covered with a layer of high temperature fiberglass insulation, see Figure 11.
The control system is comprised of an Outdoor Interface Module that monitors the functions of the WR ignition system, pressure switches, low water cutoff and temperatures in the tank.
FIGURE 13
BLOCKED OUTLET SWITCH
The Blocked Outlet Switch is set up to shut the unit off when a pressure buildup in the exhaust vent pipe occurs. This switch is a positive pressure switch that requires an increase in pressure to change the electrical contacts from normally closed to open. When this switch prevents the unit from igniting, most likely the exhaust is blocked. Check for obstructions in the exhaust venting and exhaust vent terminal, see Figure 14.
FIGURE 11
EXHAUST VENT
The exhaust vent elbow mates with the flue adapter. The elbow mates with the exhaust terminal to dispose the flue gases to the outdoors. This venting section is covered with a fiberglass insulated wrap to protect from heat and condensation. These pipes are sealed with a high temperature gasket integral to the vent pipe fittings, see Figure 12.
FIGURE 12
BLOCKED INLET/PROVER SWITCH
The Blocked Inlet/Prover Switch is set up to shut the unit off when a reduction in pressure in the intake vent occurs. This switch is a negative pressure switch that requires an increase in negative pressure to change the electrical contacts from normally open to closed. The switch is connected to the pressure tap connected to the housing of the blower. When this switch prevents the unit from ignition, most likely the intake is blocked. Check for obstructions in the inlet vent terminal, see Figure 14.
FIGURE 14
The blocked Inlet/Prover Switch has a second function. It is provided on the heater to verify that the fan is operating. When the fan increases in negative pressure, the electrical contacts close signaling that the blower is operational and is at peak performance. The controller requires that the electrical contacts on the switch close before it will allow the blower to come on.
8
LOW GAS PRESSURE SWITCH
OIM - OUTDOOR INTERFACE MODULE
The Low Gas Pressure Switch is a single pole, normally open pressure switch that will close its contacts when a rising pressure of 6.2 inches (1.53 kPa) w.c. is encountered. The contacts will open when the pressure falls below the fixed set point of 6.2 inches of w.c. The Low Gas Pressure Switch monitors the gas supply pressure to the heater. If the gas supply falls below the 6.2 inches of w.c., the main burner is extinguished (if heater is running) or the heater will not start up, see Figure 15.
FIGURE 15
ON/OFF SWITCH
The ON/OFF Switch is a single pole, single throw rocker switch. This switch provides 120V from the electrical source to the heater, see Figure 16.
The OIM is a device that monitors the control system. It monitors the ignition control assembly, the tank and outlet temperatures, the low water cutoff device, and the pressure switches. The display board provides operating information. It records and logs error messages for diagnostics. The module is equipped with a touch pad for easy access to observe menus and current status of control, see Figure 18.
FIGURE 18
WR IGNITION CONTROL BOARD
The WR Ignition Control Board performs the ignition sequence for the water heater. It controls the diagnostics of the system and monitors all the pressure switches, the flame sensing device, the thermostats, the E.C.O., and components that make up the control system. The difference between the WR Ignition Control Board is that the OIM board monitors all the controls and provides that information through the LCD display where the WR Ignition Control Board provides the means to control the complete sequence of operation and switches, see Figure 19.
FIGURE 16
HOT SURFACE IGNITER
The Hot Surface Igniter is a device that ignites the main burner by high temperature (1800°F). When the 120 VAC is applied to the igniter, sufficient heat is generated to ignite the main burner. Although improvements have been made to strengthen the igniter, it is still fragile and care must be taken when handling the igniter to prevent breakage, see Figure 17.
FIGURE 17
FIGURE 19
9
LOW WA TER CUT OFF BOARD AND PROBE
The Low Water Cutoff Board and Probe monitors the water level to confirm the tank is completely full. This function is very important when the unit is first filled with water and when complete loss of power is encountered during freezing temperatures (in case the unit drains while using the anti-freeze kit), see Figure 20.
FIGURE 20
THERMOST A T/E.C.O. PROBES
The Outback utilizes a two probe system. The upper probe located on top of the unit toward the back of the cabinet consists of a thermostat and E.C.O. The thermostat monitors the top temperature in the tank. The E.C.O. high limit switch interrupts the main burner gas flow should the water temperature reach approximately 205°F. The lower probe measures the water temperature in the lower half of the tank assembly.
grounding screw to tie into the metal panel to assure the unit is grounded, see Figure 23.
FIGURE 23
TANK ASSEMBLY SYSTEM
The Tank Assembly is an 80 gallon unit with a U-shaped heat exchanger. It incorporates two inlet tubes to control flow inside the tank. The heat exchanger is equipped with a stainless steel baffle which is non-removable. The working pressure is 150 psi, see Figure 24.
FIGURE 21
TRANSFORMER
The control system utilizes a 120/24 VAC step down transformer. Most of the control system utilizes 24 VAC for operation. See wiring diagram for those components utilizing 24 VAC and 120 VAC, see Figure 22.
FIGURE 22
FIGURE 24
TANK INSULA TION
The tank assembly is wrapped in foam insulation sealed inside a round jacket. The ends of the tank consist of high temperature fiberglass insulation and foam dams to prevent foam leakage, see Figure 25.
JUNCTION BOX
The junction box is where the 120 VAC is supplied to the unit and tied into the rest of the controls. The junction box provides a
FIGURE 25
10
CABINET ASSEMBLY
FLAME SENSOR
CABINET P ANELS
There are five panels that comprise the cabinet assembly. The ends of the cabinet allow access to all controls and plumbing. Please confirm all joints are attached correctly and sealed to prevent water leakage inside the cabinet, see Figure 26.
FIGURE 26
The flame sensor is used to sense the burner flame. When there is sufficient flame, and the burner is properly grounded, the flame sensor signals back to the ignition board that the burner is operating properly and to maintain the operation of the gas valve until the thermostat is satisfied.
FIGURE 28
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLA TION OR SERVICE OF THIS WA TER HEATER REQUIRES ABILITY EQUIV ALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING , AIR SUPPL Y , VENTING, GAS SUPPL Y AND ELECTRICAL WORK ARE REQUIRED.
INSULA TION BLANKETS
ADDITIONAL CONTROLS
GAS V AL VE
The gas valve is used to supply the gas to the unit during heat up periods. The ignition control board monitors the thermostat's call for heat and sends a signal to the gas valve when to open to allow gas flow, see Figure 27.
Insulation blankets available to the general public for external use on gas water heaters are not approved for use on your State water heater. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters. Yo ur State water heater meets or exceeds the ASHRAE/IES 90.1 b 1999 standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.
LOCA TING THE HEATER
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REP AIRED. FLAMMABLE V APORS ARE HEA VY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEA TER’S IGNITER OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERA TION OF GAS APPLIANCES IF INSTALLED 18 INCHES (46 cm) OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
FIGURE 27
DO NOT LOCATE THE HEATER WHERE NOISE FROM THE EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS INCLUDES LOCATIONS CLOSE T O OR ACROSS FROM WINDOWS AND DOORS.
11
Loading...
+ 25 hidden pages