State Industries GPG85 540 NEA User Manual

For Additional Technical Information,
PHONE 800-365-0024
STATE WATER HEATERS 500 Tennessee Waltz Parkway, Ashland City, TN 37015 www.statewaterheaters.com
TITAN
Low-NOx Commercial Gas Water Heaters
For medium-demand commercial applications, State Titan™ (GPG and GPV) commercial gas water heaters offer precise powered-burner performance, plus flexible venting options including conventional atmospheric venting, sidewall venting or direct venting. Professional start-up service is also available from State on these Titan units to help ensure optimum performance.
Powered Gas Low-NOx Burner (Natural Gas Only)
• Premix burner operation includes internal Flue Gas Recirculation (FGR)
• Safety features: Internal blocked flue sensor, separate pilot system, internal thermal cutoff and anti-flashback barrier
Three Venting Options
• Conventional atmospheric vertical venting on GPG models, with barometric draft regulating damper. Order Vent Kit Part # 170777-005
• Horizontal atmospheric sidewall venting or direct venting on GPV models
• For sidewall venting order Vent Kit Part # 192049-000
• For direct-venting order Vent Kit Part # 192050-002
Automatic Controls
• Safety shut-off, high-temperature limit control
• Dual thermostat for accurate temperature adjustment from 120ºF to 180ºF
Patented “Dome Design” Combustion
• Draft-equalizing dome balances pressure inside combustion chamber for optimum flue loading and efficient heat transfer
Adjustable Damper for High-Altitude Installations
• Air intake damper easily reset for high-altitude installation by authorized start-up agent
ASME Tank Construction – Rated Working Pressure 160 psi
Factory-Installed AGA/ASME Temperature and Pressure Relief Valve
Glass-Lined Tank
• With multiple anode rods for long-term protection against corrosion
Flame Inspection Port
Handhole Cleanout
• For easy removal of sediment from tank bottom
Meets ASHRAE/IESNA 90.1-1999 Requirements
• Also meets SCAQMD low-NOx Rule 1146.2
Three-Year Limited Tank Warranty
• For complete warranty information, consult written warranty shipped with water heater, or contact State Water Heaters
Page 1 of 2
SCGSS00205
March 2007R
For Additional Technical Information,
PHONE 800-365-0024
STATE WATER HEATERS 500 Tennessee Waltz Parkway, Ashland City, TN 37015 www.statewaterheaters.com
SCGSS00205 © 2005 State Industries, Inc. Printed in U.S.A.
March 2007R
For complete information on limited warranties, consult written warranty, or contact the State Customer Care Center, 1-800-365-0024.
State Industries, Inc. reserves the right to make product changes or improvements without prior notice.
TITAN
Low-NOx Commercial Gas Water Heaters
DIMENSIONS AND WEIGHT – ALL MODELS
CAPACITY, INPUT AND OUTPUT
SUGGESTED SPECIFICATION
Water heater(s) shall be State Model ________________ or equal, with maximum storage capacity of 85 gallons, an input rating of ___________________ BTU/Hr., a recovery rating of ____ GPH at 100ºF temperature rise, and minimum thermal efficiency of 80%. Heater(s) shall meet ASHRAE/IESNA 90.1-1999 requirements for thermal efficiency and standby loss, and meet SCAQMD R1146.2 low-NOx requirements. In addition, heater(s) shall: 1) Include a powered gas burner, redundant main gas valves, gas pressure regulator and flame inspection port. 2) Include a high-temperature limit control, dual-bulb thermostat for accurate temperature control and anti­stacking compensation and a factory-installed AGA rated temperature and pressure relief valve. 3) Be equipped with 1-1/2" NPT water inlet and outlet and a boiler-type handhole cleanout. 4) Shall be constructed and stamped in accordance with ASME Boiler and Pressure Vessel Code and be so marked for a maximum working pressure of 160 psi. 5) Have a glass-lined steel tank with multiple anodes for corrosion protection, and polyurethane foam insulation. 6) Tank shall have a 3-year limited warranty against corrosion as outlined in the written warranty.
Venting: GPG heater(s) shall be supplied with a Barometric Draft Regulator for conventional atmospheric venting. GPV heater(s) shall be supplied with an optional vent kit allowing for horizontal sidewall venting or direct venting.
Burner and Controls: Burner(s) shall be pre-mix design, with internal FGR and thermal cutoff, separate spark pilot ignition system, integral blocked flue sensor, glass view port, main gas regulator, automatic gas valve, manual test cock and manual gas shutoff. Burner(s) must be factory-installed, tested and started by an Authorized State Start­up Agent before being placed into operation.
Based on 80% Thermal Efficiency obtained in State engineering laboratories. To compensate for effects of high altitude above 2,000 feet, recovery ratings should be reduced 5% for every 1,000 feet above sea level. Current Draw (120V, 60Hz, 1 Phase): 6.0 Amps
*D dimension is for atmospheric vent size (GPG models). **E dimension is for direct and sidewall vent size (GPV models). ***Minimum gas supply pipe is 1-1/4". See Reference Manual, Table 7 for gas supply pipe size.
MODEL
NUMBER
GPG85 540 NEA GPV85 540 NEA
GPG85 650 NEA GPV85 650 NEA GPG85 740 NEA GPV85 740 NEA
FIRST HOUR
RATING
100° F
RISE
583
2206.7
690
2611.7 778
2944.7
TAN K
SIZE
85
321.7
85
321.7 85
321.7
BTU
INPUT
PER
HOUR
540,000
650,000
740,000
Gallons
or
Litres
U.S. Gallons
Litres
U.S. Gallons
Litres
U.S. Gallons
Litres
GPH
or
LPH
GPH
LPH
GPH
LPH
GPH
LPH
40°F
4°C
1309
4954.6
1579
5976.5 1794
6790.3
100°F
56°C
523
1979.6
630
2384.6 718
2717.6
140°F
78°C
374
1415.6
450
1703.3 512
1937.9
RECOVERY-GALLONS
PER HOUR AT °F
TEMPERATURE RISE
Inches
or
CM
Inches
CM
950 Lbs.
431.8 Kg
GAS
CONN.***
1
˝
-
A
80-3/4
205.1
B
73
185.4
C
32-1/4
81.9
D
9
22.9
E
26-1/2
67.3
F
26-1/2
67.3
G
93
236.2
H
29-1/2
74.9
I
48-1/2
123.2
DIMENSIONS
SHIPPING
WEIGHT
Page 2 of 2
Loading...