State Industries 184748-001 User Manual

Instruction Manual
RESIDENTIAL HUD SIDE PLUMBING ELECTRIC
WATER HEATERS
FOR POTABLE WATER
HEATING ONLY
NOT SUITABLE FOR
SPACE HEATING
LISTED
GAMA certification applies to all residential electric water heaters with capacities of 20 to 120 gallons. Input rating of 12 Kw or less.
ALL TECHNICAL AND W ARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WA TER HEA TER WAS PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLA TE ON THE WA TER HEA TER.
KEEP THIS MANUAL IN THE POCKET ON HEA TER FOR FUTURE REFERENCE
WHEN EVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
PRINTED IN THE U.S.A. 1004 PART NO. 184748-001
1
supersedes 184748-000
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
W ARNING
CAUTION
hazardous situation which, if not avoided, could result in death or injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
IMPORTANT DEFINITIONS
Qualified Installer: A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing, and electrical installation of these appliances. This would include a thorough understanding of the requirements of the National Electrical Code and applicable local electrical and plumbing codes (and tools necessary to confirm proper installation and operation of the water heater) as they relate to the installation of electric water heaters. The qualified installer must have a thorough understanding of the water heater Instruction Manual.
Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing, and electrical installation of these appliances. This would include a thorough understanding of the requirements of the National Electrical Code and applicable local electrical and plumbing codes (and tools necessary to confirm proper installation and operation of the water heater) as they relate to the installation of electric water heaters. The service agency must have a thorough understanding of the water heater Instruction Manual.
2
GENERAL SAFETY
3
INTRODUCTION
Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.
Abbreviations Found In This Instruction Manual:
• ANSI - American National S tandards Institute
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturers Association
• NEC - National Electrical Code
• NFPA - National Fire Protection Association
• UL - Underwriters Laboratories Inc.
PREP ARING FOR THE INSTALLA TION
1. Read the “General Safety” section of this manual first and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODIL Y INJURY AND/OR PROPERTY DAMAGE.
This manual contains instructions for the installation, operation, and maintenance of the electric water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety . Since we cannot put everything on the first few pages, READ THE ENTIRE MANUAL BEFORE
ATTEMPTING T O INST ALL OR OPERATE THE W ATER HEA TER.
This appliance has been Listed as complying with U.L. Standard for Safety UL 174.
2. The installation must conform with these instructions and the local code authority having jurisdiction and the requirements of the power company . In the absence of code requirements follow the current edition of the NEC, National Electrical Code, NFPA-70 which may be ordered from: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
3. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local utility or the manufacturer whose name appears on the rating plate.
4. Carefully plan the place where you are going to put the water heater. INSTALLA TION OR SER VICE OF THIS WA TER HEA TER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD INVOLVED. PLUMBING AND ELECTRICAL WORK ARE REQUIRED.
Examine the location to ensure the water heater complies with the “Facts to Consider About the Location” section in this manual.
5. For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Office of the St ate Architect, 400 P S treet, Sacramento, CA 95814.
6. Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR 5.00.
TABLE OF CONTENTS
SAFE INST ALLA TION, USE AND SERVICE .... .. .................2
GENERAL SAFETY............................................................... 3
INTRODUCTION .................................................................. 4
Preparing for the New Installation .................................. 4
TABLE OF CONTENTS ........................................................ 4
TYPICAL INSTALLA TION......................................................5
MIXING VAL VE USAGE......................................................... 6
LOCA TING THE NEW W ATER HEATER............................. 7
Facts to Consider About Location................................... 7
Insulation Blankets ........................................................... 7
INSTALLING THE NEW WATER HEA TER.......................... 7
Water Piping .................................................................. 7-8
Water Piping Pressure Test............................................. 8
Temperature-Pressure Relief Valve ........................... 8-9
Filling the Water Heater ................................................... 9
T & P Valve and Pipe Insulation (Selected Models)..10
WIRING DIAGRAMS ........................................................... 11
WIRING ............................................................................... 12
TEMPERATURE REGULATION......................................... 13
Temperature Adjustment ............................................... 13
FOR YOUR INFORMA TION................................................ 14
Thermal Expansion ........................................................ 14
Strange Sounds ............................................................ 14
Operational Conditions .................................................. 14
Smelly Water ................................................................ 14
“Air” in Hot Water Faucets ........................................... 14
High Water Temperature Shut Off System ................. 14
PERIODIC MAINTENANCE ............................................... 15
Anode Rod Inspection .................................................... 15
Temperature-Pressure Relief Valve Operation ...........15
Draining ........................................................................... 15
Thermostat Removal/Replacement ....................... 15-16
Element Cleaning/Replacement ............................. 16-18
Drain Valve Washer Replacement................................ 18
Service ............................................................................. 18
LEAKAGE CHECKPOINTS ................................................ 19
TROUBLESHOOTING GUIDELINES ................................ 20
REPAIR PARTS LIST.......................................................... 21
NOTES .......................................................................... 22-23
WARRANTY................................................................... Insert
4
TYPICAL INSTALLATION
INSTALL SUITABLE DRAIN PANS UNDER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE. REFER TO WATER HEATER LOCATION ON PAGE 8.
INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES.
FIGURE 1.
5
INSTALL THERMAL EXP ANSION T ANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM.
MIXING VALVE USAGE
FIGURE 2.
Water (Potable) Heating: All models are considered suitable for
water (potable) heating only.
LOCATING THE NEW WATER HEATER
FACTS TO CONSIDER ABOUT THE LOCA TION
HOTTER WA TER CAN SCALD: Water heaters are intended to produce hot water. W ater heated to a
temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly , children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a *mixing valve, shall be used at the hot water taps used by these people or at the water heater. Mixing valves are available local plumbing contractor. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “T emperature Regulation” section in this manual.
Carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance.
Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed:
1. Select a location indoors as close as practical or centralized to the water piping system as possible. The water heater should be located in an area not subject to freezing temperatures.
2. Selected location must provide adequate clearances (4”) for servicing parts such as the thermostats, drain valve and relief valve. Adequate clearance for servicing this appliance should be considered before installation, such as changing the anodes, etc.
6
LOCATING THE NEW WATER HEATER
Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the flow will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan should be installed under the water heater. Drain pans are available from your local plumbing contractor. Such a drain pan must have a minimum length and width of at least 2 inches (51 mm) greater that the water heater dimensions and must be piped to an adequate drain.
Water heater life depends upon water quality , water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However , unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.
• Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply .
Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle.
INSULA TION BLANKETS
Insulation blankets are available to the general public for external use on electric water heaters but are not necessary with this product. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Y our water heater meets or exceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you should follow these instructions below. Failure to follow these instructions can result in fire, serious personal injury , or death.
Do not cover the temperature and pressure relief (T & P) valve with an insulation blanket.
Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
Do obtain new warning and instruction labels for placement on the
blanket directly over the existing labels.
INSTALLING THE NEW WATER HEATER
WATER PIPING
HOTTER WA TER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly , children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a *mixing valve, shall be used at the hot water
taps used by these people or at the water heater. V alves for reducing point of use temperature by mixing cold and hot water are also available.
Consult a Qualified Installer or Service Agency . Follow manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “T emperature Regulation” section in this manual.
This water heater shall not be connected to any heating systems or component(s) used with a non-potable water heating appliance.
T oxic chemicals, such as those used for boiler treatment shall not be introduced into this system.
Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc. to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it exp ands (thermal expansion) and closed systems do not allow for the expansion of heated water.
7
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater’s temperature-pressure relief valve is reached, the valve will relieve the excess pressure. The temperature-pressure
relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.
It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank or device to relieve the pressure built by thermal expansion in the water system. Expansion tanks are available for ordering through a local plumbing contractor. Contact the local water supplier and/or a
service agency for assistance in controlling these situations.
When testing the water ways, H.U.D. Standards state: “Water distribution system: All water piping in the water distribution system shall be subjected to a pressure test. The test shall be made by subjecting the system to air or water at 100 psi for 15 minutes without loss of pressure. When air pressure is used, the water heater
shall not be connected during the test.”
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that di-electric unions or couplings be installed on this water heater when connected to copper pipe.
Figure 3 shows the typical attachment of the water piping to the water heater. The water heater is equipped with 3/4 inch NPT water connections.
NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the cold water inlet connection. Do not solder the cold water supply line directly to the cold water inlet, it will harm the dip tube and damage the tank.
• If water piping system is to be air pressure tested, the water heater must be disconnected from the water piping system.
• Failure to disconnect the water heater during air pressure testing of the water system could result in DEA TH, SERIOUS BODIL Y INJURY , OR PROPERTY DAMAGE.
FIGURE 3.
WA TER PIPING PRESSURE TEST
This section is only for the manufacturer installing the water heater when the installation is to comply with H.U.D. Standards.
FIGURE 4.
TEMPERATURE-PRESSURE RELIEF VAL VE
This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.
8
The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief V alves and Automatic Gas Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.
If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.
For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 mm) above, or at any distance below the structural floor. Be certain that no cont act is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury , hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
FIGURE 5.
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.
FILLING THE WATER HEA TER
• Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.
• Shall terminate beneath the manufactured home.
• Shall not have any valve between the relief valve and tank.
The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.
Never use this water heater unless it is completely full of water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” electrical supply to the water heater.
9
To fill the water heater with water:
1. Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when the water heater is in use.
3. T o insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant flow is obtained. This will let air out of the water heater and the piping.
4. Check all water piping and connections for leaks. Repair as needed.
T&P VALVE and PIPE INSULATION (On Selected Models)
Remove insulation for T&P V alve and pipe connections from carton. Fit pipe insulation over the incoming cold water line and the hot water
line. Make sure that the insulation is against the side jacket of the heater.
Secure all insulation using tape.
Fit T&P V alve insulation over valve. Make sure that the insulation does not interfere with the lever or outlet of the T&P valve.
FIGURE 6.
10
WIRING DIAGRAMS
TURN OFF THE HEA TER ELECTRICAL SUPPL Y BEFORE SERVICING ANY ELECTRICAL COMPONENTS.
FIGURE 7.
11
WIRING
1. Provide a way to easily shut off the electric power when working on the water heater. This could be with a circuit breaker or fuse block in the entrance box or a separate disconnect switch.
2. Install and connect a circuit directly from the main fuse or circuit breaker box. This circuit must be the right size and have its own fuse or circuit breaker.
3. If metal conduit is used for the grounding conductor:
Never use water heater unless it is completely full of water. To prevent damage to the tank and heating element, the tank must be filled with water. W ater must flow from the hot water faucet before turning on power.
You must provide all wiring of the proper size outside of the water heater. Y ou must obey local codes and electric comp any requirements when you install this wiring.
If you are not familiar with electric codes and practices, or if you have any doubt in your ability to connect the wiring to this water heater, obtain the service of a competent electrician. Contact a local electrical contractor and/or the local electric utility.
A. The grounding electrode conductor shall be of copper, aluminum,
or copperclad aluminum. The material shall be of one continuous length without a splice or joint.
B. Rigid metal conduit, intermediate metal conduit, or electrical,
metallic tubing may be used for the grounding means if conduit or tubing is terminated in fittings approved for grounding.
C . Flexible metal conduit or flexible metallic tubing shall be permitted
for grounding if all the following conditions are met:
The length in any ground return path does not exceed 6 feet.
The circuit conductors contained therein are protected by overcurrent devices rated at 20 amperes or less.
The conduit or tubing is terminated in fittings approved for grounding.
For complete grounding details and all allowable exceptions, refer to the current edition of the National Electrical Code NFPA 70.
4. A standard 1/2” conduit opening has been made in the water heater junction box for the conduit connections.
5. Use wire nuts and connect the power supply wiring to the wires inside the water heater’s junction box.
6. The water heater must be electrically “grounded” by the installer. A green ground screw has been provided in the water heater’s junction box. Connect ground wire to this location.
WA TER HEA TERS EQUIPPED FOR ONE VOLT AGE ONL Y: This water heater is equipped for one type voltage only . Check the rating plate near the bottom access panel for the correct voltage. DO NOT use this water heater with any voltage other than the one shown on the model rating plate. Failure to use the correct voltage can cause problems which can result in DEATH, SERIOUS BODIL Y INJUR Y , OR PROPERTY DAMAGE. If you have any questions or doubts consult your electric company .
If wiring from your fuse box or circuit breaker box was aluminum for your old water heater, replace it with copper wire. If you wish to reuse the existing aluminum wire, have the connection at the water heater made by a competent electrician. Contact a local electrical contractor and/or the local electric utility.
7. Replace the wiring junction cover using the screws provided.
FIGURE 8.
12
TEMPERATURE REGULATION
Due to the nature of the typical water heater, the water temperature in certain situations may vary up to 30°F (16.7 °C) higher or lower at the point of use such as, bathtubs, showers, sink, etc.
Any water heater’s intended purpose is to heat water. Hot water is needed for cleansing, cleaning, and sanitizing (bodies, dishes, clothing). Untempered hot water can present a scald hazard. Depending on the time element, and the people involved (adults, children, elderly , infirm, etc.) scalding may occur at different temperatures.
HOTTER WA TER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a mixing valve, shall be used at the hot water taps used by these people or at the water heater. Mixing valves are available from your local plumbing contractor. Follow manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “T emperature Regulation” section in this manual.
TEMPERATURE ADJUSTMENT
T o change the temperature setting: NOTE: It is not necessary to adjust the upper thermostat. However, if it
is adjusted above the factory set point (120°F (49°C)/HOT) it is recommended that it not be set higher than the lower thermostat setting.
Turn “OFF” the heater electrical supply . Do not attempt to adjust
1. thermostat with power on.
2. Remove the thermostat outer doors and insulation covers from the thermostats. Do not remove the plastic personnel protectors covering the thermostats.
3. Using a flat tip screwdriver, rotate the adjustment knob to the desired temperature setting.
4. Replace the insulation covers and outer doors and turn “ON” heater electrical supply.
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT WATER TEMPERATURES DESIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALDS RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. THE TEMPERA TURE A T WHICH INJURY OCCURS V ARIES WITH THE PERSON’S AGE AND THE TIME OF THE EXPOSURE. THE SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW SMALL CHILDREN TO USE A HOT WA TER TAP , OR TO DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED PERSON UNA TTENDED IN A BA THTUB OR SHOWER.
It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperature thermostat be set for the lowest temperature which satisfies your hot water needs, see Figure 9. This will also provide the most energy efficient operation of the water heater . Thermostat(s) are factory set at 120°F (49°C) unless specified differently by state requirements.
KEEPING THE THERMOSTA T SETTING AT 120°F (49°C) WILL REDUCE THE RISK OF SCALDS.
Figure 9 shows the approximate time-to-burn relationship for normal adult skin.
TEMPERA TURE SETTINGS
It is recommended that the dial be set lower whenever possible.
Temperature Time to Produce 2nd & 3rd
Setting Degree Burns on Adult Skin
160°F (71°C) About 1/2 second 150°F (66°C) About 1-1/2 seconds 140°F (60°C) Less than 5 seconds 130°F (54°C) About 30 seconds 120°F (49°C) More than 5 minutes
FIGURE 9.
13
FOR YOUR INFORMATION
THERMAL EXP ANSION
Water supply systems may, because of such events as high line pressure, frequent cut-offs, the effects of water hammer among others, have installed devices such as pressure reducing valves, check valves, back flow preventers, etc. to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it exp ands (thermal expansion) and closed systems do not allow for the expansion of heated water .
The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of the water heater’s temperature-pressure relief valve is reached, the valve will relieve the excess pressure. The temperature-pressure
relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.
It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank or device to relieve the pressure built by thermal expansion in the
system. Expansion tanks are available for ordering through a
water
local plumbing contractor. Cont act the local water heater supplier or service agency for assistance in controlling these situations.
STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions.
“AIR” IN HOT WA TER F AUCETS
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these conditions, we recommend the hot water faucet, located farthest away, be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open.
HIGH WA TER TEMPERATURE SHUT OFF SYSTEM
A non-adjustable high temperature limit control operates before steam temperatures are reached. The high limit is in the same area as the upper thermostat and must be reset manually when it operates. BECAUSE THE HIGH LIMIT OPERATES ONLY WHEN ABNORMALLY HIGH W A TER TEMPERA TURES ARE PRESENT, IT IS IMPORT ANT THAT A QUALIFIED SER VICE AGENT BE CONT ACTED TO DETERMINE THE REASON FOR OPERA TION BEFORE RESETTING.
OPERA TIONAL CONDITIONS
SMELL Y WA TER
In each water heater there is installed at least one anode rod (see parts sections) for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a “rotten egg smell” in the hot water. This odor is derived from hydrogen sulfide gas dissolved in the water. The smell is the result of four factors which must all be present for the odor to develop:
A. A concentration of sulfate in the supply water . B. Little or no dissolved oxygen in the water. C . A sulfate reducing bacteria which has accumulated within the water
heater (this harmless bacteria is nontoxic to humans).
D. An excess of active hydrogen in the tank. This is caused by the
corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active material, and then chlorinating the water heater tank and all hot water lines. Contact the local water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment. If the smelly water persists after the anode replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem.
Do not remove the anode leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided.
• Turn “OFF” the heater electrical supply. Do not attempt to reset thermostat with power on.
• Remove the two screws securing the outer door and remove door.
• Remove the insulation block and pad to expose the reset button opening.
• Reset the high limit by pushing in the red button marked “RESET”.
• Replace the insulation block and pad so that it completely covers the thermostat and element.
• Replace the outer door.
• Turn “ON” electric power to the water heater.
14
PERIODIC MAINTENANCE
ANODE ROD INSPECTION
The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrifices itself to protect the tank. Instead of corroding the tank, water ions attack and eat away the anode rod. This does not affect the water’s taste or color. The rod must be maintained to keep the tank in operating condition.
Anode deterioration depends on water conductivity , not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often then an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period.
TEMPERA TURE-PRESSURE RELIEF VAL VE OPERATION
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.
If the temperature-pressure relief valve on the appliance weeps or discharges periodically , this may be due to thermal expansion. You may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or service agency for further information. Do not plug the temperature-pressure relief valve.
DRAINING
The water heater should be drained if being shut down during freezing temperatures. Also periodic draining and cleaning of sediment from the tank may be necessary .
1. Turn electrical supply “OFF”.
The temperature-pressure relief valve must be manually operated at least once a year.
When checking the temperature-pressure relief valve operation, make sure that (1) no one is in front of or around the outlet of the temperature­pressure relief valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot, see Figure 10.
2. CLOSE the cold water inlet valve to the water heater.
3. OPEN a nearby hot water faucet and leave open to allow for draining.
4. Connect a hose to the drain valve and terminate to an adequate drain.
5. OPEN the water heater drain valve to allow for tank draining.
NOTE: If the water heater is going to be shut down and drained for an extended period, the drain valve should be left open with hose connected allowing water to terminate to an adequate drain.
6. Close the drain valve.
7. Follow the instructions in the “Filling the Water Heater” section.
THERMOST A T REMOVAL / REPLACEMENT
FIGURE 10.
15
1. Turn “OFF” the electric power supply to the water heater .
4. Remove the two wires attached to the thermostat.
2. Remove the outer door, insulation block and pad in the order they are installed.
3. A. Models with lower thermostat without high limit: Lift
out the tab as shown below to unclip the terminal cover from the thermostat. The terminal cover can now be removed from the thermostat.
5. Remove the thermostat from behind the thermostat bracket.
6. Disconnect wires from thermostat and slide out of the bracket.
7. Place the new lower thermostat in the bracket making sure it fits firmly against the tank.
8. Attach the wires to the new thermostat.
NOTE: Some of the terminals may require straight-in wiring through an eye-opening. If wires are now looped, recut and strip wire 3/8” to a straight length and insert.
9. Put plastic terminal cover back in place.
10.Replace the insulation block and pad to cover the thermostat.
1 1.Replace outer door then turn the electric power “ON”.
ELEMENT CLEANING / REPLACEMENT
NOTE: These instructions are written for element cleaning and element replacement for the lower element.
FIGURE 11.
B. Models with Upper or Lower Thermostat with High
Limit: Lift out the tab as shown below to unclip the terminal
cover from the thermostat. The terminal cover can now be removed from the thermostat.
T o remove the element from the tank in order to clean or replace it:
1. Before beginning turn “OFF” the electric power supply to the water heater.
2. Turn off the water supply to the water heater at the water shut-off valve or water meter.
FIGURE 13.
3. Attach a hose to the water heater drain valve and put the other end in a floor drain or outdoors. Open the water heater drain valve. Open a nearby hot water faucet which will relieve pressure in the water heater and speed draining.
FIGURE 12.
FIGURE 14.
16
The water passing out of the drain valve may be extremely hot. To avoid scalding, make sure all connections are tight and that the water flow is directed away from any person.
4. Remove the two screws securing the outer door, and remove door.
B. Models with Upper or Lower Thermostat with High
Limit: Lift out the tab as shown below to unclip the terminal cover from the thermostat. The terminal cover can now be removed from the thermostat.
FIGURE 15.
5. Remove the insulation block and pad.
FIGURE 16.
6. A. Models with lower thermostat without high limit: Lift
out the tab as shown below to unclip the terminal cover from the thermostat. The terminal cover can now be removed from the thermostat.
FIGURE 18.
7. Disconnect the two wires on the element and unscrew the old element from the tank.
FIGURE 19.
8. Clean the area around the element opening. Remove any sediment from or around the element opening and inside the tank.
FIGURE 17.
9. If you are cleaning the element you have removed, do so by scraping or soaking in vinegar or a deliming solution.
NOTE: Replacement elements must (1) be the same voltage and (2) no greater wattage than listed on the model rating plate affixed to the water heater.
10. A new gasket should be used in all cases to prevent a possible water leak. Place the new element gasket on the threaded side of the cleaned or new element and screw into tank, securing tightly using an element wrench.
FIGURE 20.
17
11. Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater.
12. Open the cold water supply valve to the water heater .
NOTE: The cold water supply valve must be left open when the water heater is in use.
13. To insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a const ant flow is obtained. This will let air out of the water heater and the piping.
FIGURE 22.
DRAIN VALVE WASHER REPLACEMENT
(See Figure 23)
1. Follow “Draining” instructions.
Never use this water heater unless it is completely full of water. To prevent damage to the tank and heating element, the tank must be filled with water. W ater must flow from the hot water faucet before turning “ON” power.
14. Check element for water leaks. If leakage occurs, tighten element or repeat Steps 2 and 3, remove element and reposition gasket. Then repeat Steps 10 through 14.
15. Reconnect the two wires to the element and then check to make sure the thermostat remains firmly against the surface of the tank.
FIGURE 21.
16. Replace terminal cover on thermostat making sure the locking tabs on the terminal cover are in place.
17. Replace the insulation block and pad so that it covers the thermostat and element, see Figure 21.
18. Replace outer door.
19. Turn “ON” electric power to water heater .
2. Turning counter clockwise ( screw handle.
3. Remove the washer and put the new one in place.
4. Screw the handle and cap assembly back into the drain valve and retighten using a wrench. DO NOT OVER TIGHTEN.
5. Follow instructions in the “Filling The Water Heater” section.
6. Check for leaks.
), remove the hex cap below the
FIGURE 23.
SERVICE
If a condition persists or you are uncertain about the operation of the water heater contact a service agency .
Use this guide to check a “Leaking” water heater. Many suspected “Leakers” are not leaking tanks. Often the source of the water can be found and corrected.
If you are not thoroughly familiar with your water heater and safety practices, contact a qualified installer to check the water heater .
18
LEAKAGE CHECKPOINTS
Read this manual first. Then before checking the water heater make sure the electrical power supply has been turned “OFF” before checking the tank for leakage.
*A. Condensation and dripping may be seen on pipes if the water
temperature is low in humid weather or pipe connections may be leaking.
*B. The anode rod fitting may be leaking.
C . Small amounts of water from temperature-pressure relief valve
may be due to thermal expansion or high water pressure in your area. If the valve is not piped to an open drain the released water could be mistaken for a leaking heater .
FIGURE 24.
*D . The temperature-pressure relief valve may be leaking at the tank
fitting.
E . The element may be leaking at the tank fitting. Turn electrical power
“OFF”, remove outer door, insulation block and pad. If leaking around the element, follow proper draining instructions and remove element. Reposition or replace gasket on element. Place element into opening and tighten securely. Then follow “Filling the W ater Heater” instructions in the “Installing the New Water Heater” section.
F. Water from a drain valve may be due to the valve being slightly
opened.
*G . The drain valve may be leaking at the tank fitting.
*H. Water in the water heater bottom or on the floor may be from
condensation, loose connections, or the relief valve. DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken.
Leakage from other appliances, water lines, or ground seepage should also be checked.
* T o check where threaded portion enters t ank, insert cotton swab
between jacket opening and fitting. If cotton is wet, follow “Draining” instructions in the “Periodic Maintenance” section and then remove fitting. Put pipe dope or teflon tape on the threads and replace. Then follow “Filling the Water Heater” instructions in the “Installing the New Water Heater” section.
19
TROUBLESHOOTING GUIDELINES
These guidelines should be utilized by a qualified service agent.
Problem Cause Solution
(See Leakage Checkpoints on 19)
WA TER LEAKS
LEAKING TEMPERA TURE
AND PRESSURE
RELIEF VAL VE
HOT WA TER ODORS
(CAUTION: UNAUTHORIZED REMOVAL OF THE
ANODE(S) WILL VOID THE WARRANTY FOR
FURTHER INFORMATION, CONT ACT YOUR
DEALER)
NOT ENOUGH
OR
NO HOT WA TER
HOT W A TER TOO HOT
Improperly sealed, hot or cold supply connection, relief valve or drain valve.
Leakage from other appliances or water lines.
Thermal expansion in closed water system.
Improperly seated valve.
High sulfate or mineral content in water supply. Bacteria in water supply.
Power supply to heater is not on.
Thermostat set too low. Heater undersized. Incoming water is unusually cold (Winter). Leaking hot water from pipes or fixtures. High temperature limit switch activated.
Thermostat set too high.
Tighten threaded connections.
Inspect other appliances near water heater.
Install thermal expansion tank (DO NOT plug T&P valve).
Check relief valve for proper operation (DO NOT plug T&P valve).
Drain and flush heater thoroughly, then refill. Chlorinate water supply.
Turn disconnect switch on or contact electrician.
Refer to temperature regulation. Reduce hot water use. Allow more time for heater to reheat water. Have plumber check and repair leaks.
Contact dealer to determine cause. See temperature regulation.
Refer to temperature regulation.
WA TER HEA TER SOUNDS
High temperature limit switch activated.
Scale accumulation on elements. Sediment build-up on tank bottom.
Contact dealer to determine cause. See temperature regulation.
Contact dealer to clean or replace elements. Drain and flush thoroughly, then refill.
20
REPAIR PARTS LIST
MANUFACTURED (MOBILE) HOME ELECTRIC MODELS
Key No. Part Description
1 Temperature-Pressure Relief Valve 2 Outlet Nipple Assembly 3 Inlet Nipple 4 Conduit Bracket 5 Junction Box Cover 6 Upper and Lower Element 7 Element Gasket 8 Thermostat Bracket (ea.) 9 Lower Thermostat 2 Pole
10 Terminal Cover
11 Lower Thermostat w/Hi Limit 4 Pole (Used in place of 9)
* Not Applicable to
19.9 Gallon Models.
** Not Illustrated.
Key No. Part Description
12 Terminal Cover (Used in place of 10) 13 Lower Outer Door 14 Upper Outer Door 15 Upper Thermostat w/Hi/Limit 16 Anode Rod 17 Drain Valve (30 Gallon Model Only) 18 Base Pan w/Side Drain 19 Pipe Insulation* 20 T & P Insulation*
** Instruction Manual
Now that you have purchased this water heater, should a need ever exist for repair parts or service, simply contact the company it was purchased from or the manufacturer listed on the rating plate on the water heater.
Be sure to provide all pertinent facts when you call or visit.
Selling prices will be furnished on request or parts will be shipped at prevailing prices and you will be billed accordingly .
The model number of your Water Heater will be found on the rating plate located above or adjacent to outer door.
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION:
• MODEL NUMBER
• SERIAL NUMBER
• VOL TAGE AND ELEMENT WATT AGE
• P ART DESCRIPTION
THIS IS A REP AIR P ARTS LIST, NOT A P ACKING LIST.
21
NOTES
22
NOTES
23
24
Loading...