StarTech.com PDU02IPSC User Manual

2 Port Remote Power Control IP PDU (Power Distribution Unit)
2 Port Remote Power Control IP PDU with Console and Sensor Ports
*PDU02IP shown in photo
DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com ES: Guía del usuario - es.startech.com IT: Guida per l'uso - it.startech.com NL: Gebruiksaanwijzing - nl.startech.com PT: Guia do usuário - pt.startech.com
For the most up-to-date information, please visit: www.startech.com
Manual Revision: 01/02/2014
FCC Compliance Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit dierent from that to which the receiver
is connected.
Consult the dealer or an experienced radio/TV technician for help.
Use of Trademarks, Registered Trademarks, and other Protected Names and Symbols
This manual may make reference to trademarks, registered trademarks, and other protected names and/or symbols of third-party companies not related in any way to StarTech.com. Where they occur these references are for illustrative purposes only and do not represent an endorsement of a product or service by StarTech.com, or an endorsement of the product(s) to which this manual applies by the third-party company in question. Regardless of any direct acknowledgement elsewhere in the body of this document, StarTech.com hereby acknowledges that all trademarks, registered trademarks, service marks, and other protected names and/or symbols contained in this manual and related documents are the property of their respective holders.
Instruction Manual
Table of Contents
Product Diagram ....................................................................................1
Rear View ...................................................................................................................................................... 1
Front View ....................................................................................................................................................1
Introduction ............................................................................................2
Packaging Contents ................................................................................................................................. 2
LED Indicators .........................................................................................2
Reset Button ...........................................................................................2
Installation .............................................................................................3
Hardware Installation .............................................................................................................................. 3
Logging In for the First Time ................................................................................................................. 4
Web Console Operation ........................................................................6
Power Switch Operation .........................................................................................................................6
Monitor Section ......................................................................................................................................... 7
UPS Status (PDU02IPSC Only) ............................................................................................................... 9
Dry Contact Input Indication (PDU02IPSC Only) ........................................................................... 10
System Section ........................................................................................................................................... 10
Firewall Section .......................................................................................................................................... 15
Account Section ........................................................................................................................................ 17
TimeSync Section ...................................................................................................................................... 18
Event Section .............................................................................................................................................. 19
Instruction Manual
i
Firmware Upgrade Procedure ..............................................................22
Specications ..........................................................................................23
Technical Support .................................................................................. 24
Warranty Information ............................................................................24
Instruction Manual
ii

Product Diagram

Rear View

Front View

PDU02IP
Reset Button
PDU02IPSC
Reset Button
Instruction Manual
RJ45 LAN
LED Indicators
RJ45 LAN RS232 UPS Console
LED Indicators
Dry Contact Input
1

Introduction

Packaging Contents

• 1 x 2 Port PDU
• 1 x Power Cable
• 1 x Instruction Manual (CD)

LED Indicators

Port Indicators
(Top Row)
Reset Indicator
(Bottom Left)
Power Indicator
(Bottom Right)
LED #1 is illuminated when output receptacle #1 is ON.
LED #2 is illuminated when output receptacle #2 is ON.
Reset LED will ash when the Reset function is being performed.
Utility Power LED is illuminated when there is an acceptable AC voltage Present.

Reset Button

If you need to reset the PDU back to factory defaults, the Reset Button is located next to the LED panel. Insert a paperclip to gently press and hold the Reset Button for at least 3 seconds, then release.
Reset Button
LED Indicators
The IP address will be reset back to 192.168.1.10
The user name and password will be reset back to admin.
All other settings will be unchanged.
Instruction Manual
RJ45 LAN
2

Installation

Hardware Installation

1. Connect the power cord to the power inlet and to a wall outlet
2. Plug your equipment into the two output receptacles
3. Connect an Ethernet cable from the PDU to your network
4. Turn the power switch to the ON position
Instruction Manual
*Optional connections - PDU02IPSC only
3

Logging In for the First Time

The minimum requirement to operate the PDU is to setup the IP Address, subnet mask, and default gateway, which can be done through your web browser or using the IP Search Utility application on the CD.
Default Settings:
IP address: 192.168.1.10
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.1
User name / Password: admin / admin (lower case)
Web Browser Method
NOTE: The workstation and the PDU must be on the same LAN
1. Open a web browser and input the default IP address (192.168.1.10)
2. After the login screen appears enter admin / admin for the User name and Password
3. Click on the System tab from the menu bar of the web interface and then click on Network to set the IP address and network info of this device
Instruction Manual
4
IP Search Utility
NOTE: The workstation and the PDU must be on the same LAN for the IP Search Utility
to detect it, and the Windows Firewall must also be turned o.
1. Open the Windows Control Panel
2. Select Windows Firewall
3. Select O and then click the OK button
4. Insert the provided CD in the CD-ROM drive
5. Launch the IP Search Utility program
6. Click on the Refresh button to search for all PDU02IPxx units on the LAN
7. Click on the detected PDU and congure the IP address, Gateway and Net Mask, then click the Congure button twice. You will see the values you specied populate in the main window
8. Repeat step 7 for each device if you have multiple PDU02IPxx units connected
9. Once all devices are congured, close the IP Search Utility program and turn the Windows Firewall back on
Instruction Manual
5

Web Console Operation

Power Switch Operation

The global outlet controls can be used to either turn all outlets on, or all outlets o, while each individual outlet allows for On / O / Reboot controls.
• Double clicking the ALL ON button will turn ON both outlets. Double clicking on the ALL OFF button will turn OFF all of the outlets.
• Double clicking the switch for Port 1 or Port 2 will ip the switch to the opposite state (ON/OFF) for that individual outlet.
• If you want to Reboot (cycle o, then back on) an individual outlet, check the Reboot box and then double click on the switch.
ON OFF No Power
Instruction Manual
Not Authorized
(User account
restruction)
6

Monitor Section

The Monitor section shows you the current status of each outlet and allows you to modify the power state of each outlet individually, or make global changes to both. From the Monitor tab you can also Schedule events and congure the Auto-Ping feature.
Conguration Tab
Click on the Set button located on the top corner of each outlet to modify an individual outlet. When the Set button is orange, the outlet is ready to be congured.
Description: Allows you to give each outlet a more meaningful name if desired
Start Delay Time: Each outlet can be programmed to startup at dierent time
intervals instead of both of them starting up at the same time.
Shutdown Delay Time: Each outlet can be programmed to shutdown at dierent time intervals instead of shutting both of them down at the same time.
Save: Saves all changes.
Instruction Manual
7
Schedule Tab
Congure scheduled actions for each outlet. Click on the Set button located on the top corner of each outlet to modify an individual outlet. When the Set button is orange, the outlet is ready to be congured.
Recurrence: An Action can be scheduled to occur yearly, monthly, weekly or daily at a specic time for each individual outlet.
Time: Set the time (hours and minutes) when you want the action to occur.
Action: Set the action you want the outlet to perform, ON, OFF or Reboot.
ADD: Click the ADD button to add this action.
Delete: To delete a scheduled action, double-click on the “X”.
Save: Saves all changes.
Network Tab
Congure the Auto-PING feature to ping an IP-addressable device and detect when that device has stopped communicating. Click on the Set button located on the top corner of each outlet to modify an individual outlet. When the Set button is orange, the outlet is ready to be congured.
Detect: Check this box to enable the Auto-Ping function.
Equipment Network Address: Enter the IP address of the connected equipment.
PING Interval Time: Set the time Interval to PING the connected device.
Detect Times: If a device fails to respond to a ping continuously and exceeds the
specied amount of attempts, the PDU02IPxx can notify selected personnel via email or SMS.
Reboot: Check this box to reboot the outlet for the failed connected device.
Re-detect Time: The time interval before restarting the Auto-Ping function after the
connected device has been rebooted.
Save: Saves all changes.
Instruction Manual
8

UPS Status (PDU02IPSC Only)

The UPS Status information will display to the left of the power switches on the Monitor Tab. If you have connected an APC Smart UPS series device to the RS232 port on the PDU02IPSC, you can monitor the following information about your UPS.
Alive - Displays the state of the UPS device as either Normal (1) or Oine (0).
Model - Displays the connected UPS model.
AC Fault - Displays if there is an AC fault causing the equipment to function on UPS
battery power – Normal (0), AC Fault (1)
Output Overload - Displays either Normal (0) or Overload (1) state - Overload is shown if the power draw exceeds the output limit set by the UPS when operating on battery power.
Battery Level(%) - Displays the remaining battery capacity as a percent value.
Battery Run Time (Min) - Displays the remaining battery capacity in minutes.
Battery Low - Displays either Normal (0) or Low (1) state – the Low state threshold is
set by the UPS.
Replace Battery - Displays either Normal (0) or Needs Replacement (1) - the Needs Replacement state threshold is set by the UPS.
Instruction Manual
9

Dry Contact Input Indication (PDU02IPSC Only)

The dry contact status information will display to the right of the power switches on the Monitor Tab. If you have connected and congured the Detectors information (located in System > Detectors section – explained in the following pages), you will see a Normal or Abnormal indication.
Status Illustration: Normal Abnormal

System Section

Network Tab
Congure the PDU with a Static IP address or use DHCP.
Instruction Manual
10
Http Port: Assign the desired HTTP port (default is port 80) for connecting to the PDU via a web browser. If you change the HTTP port, enter the IP address followed by the new HTTP port into your browser address bar (e.g. http://192.168.1.10:8080).
Save: Saves all changes.
Mail Server Tab
Congure the Mail Server settings to send notications when an event has occurred.
SMTP Server Address: Enter the Hostname or IP address of the SMTP Mail Server that will be used to send emails from the PDU. If entering a Hostname, you will also be required to enter the DNS Address on the Network tab.
SMTP Port: Enter the port number for the SMTP server. The default port is 25.
Sender Mail Address: This must be a legitimate email address.
Mail Subject: Enter a subject line to easily identify the device.
SMTP Auth: Check this box if the Mail Server requires authentication to send emails.
SMTP Account: Enter the account name if SMTP authentication is required.
SMTP Password: Enter the password if SMTP authentication is required.
Mail Test: This is used to verify that the email works properly.
Save: Saves all changes.
Instruction Manual
11
SMS Server Tab
Congure the SMS Server settings to send text notications when an event has occurred.
Server Address: Enter the SMS server address.
Port: Enter the port number for the SMS server. The default value is 2500.
Equipment Name: Enter a name/subject to identify the device.
Account: Enter the account name if required.
Password: Enter the password if required.
Send SMS: Check this box if SMS Server requires authentication to send messages.
SMS Test: This is used to verify that the SMS works properly.
Save: Saves all changes.
Instruction Manual
12
SNMP/SysLog Tab
Congure SNMP Traps and System Logs to be sent to dierent Network Management Stations (NMS).
System Name: Enter the name of the SNMP device.
System Contact: Enter the name of the System Administrator.
System Location: Enter the location of the SNMP device.
Receiver IP Address: The IP Address of the NMS of where the Traps should be sent.
Receiver Port: The port that will be used to receive the Traps. The default value is 162.
Community: Low-level password of the associated IP address with the access type set
by the administrator.
Enabled: Enables the SNMP Traps to be sent.
SNMP Test: This is used to verify that the Trap notication works properly.
Syslog Server Address: The IP Address of the Server to which the System Logs should
be sent.
Syslog Server Port: The port that will be used to receive the System Logs.
Save: Saves all changes.
Instruction Manual
13
Detectors Tab (PDU02IPSC Only)
Other Tab
Set the outlets on the main tab to default to a reboot action, instead of ON/OFF.
Reboot Option: Check this box to default to rebooting the outlet instead of just turning the outlet ON/OFF. The Reboot check box on the Monitor screen will be checked when this option is selected.
Reboot Device: Selecting this option will immediately reboot the outlets.
Save: Saves all changes.
Instruction Manual
14

Firewall Section

This menu allows the administrator to congure user privileges and prevent unauthorized access to the device.
IP Filter Tab
Congure the range of IP addresses that are able to access the PDU.
IP Filter Enable: Check this box to enable the IP address lter.
Allow IP Address: The rst four sections are the beginning of the IP range. The last
section is the ending of the IP range that is being given access to the device.
E.g. To authorize the IP range from 192.168.1.110 - 192.168.1.120, input as shown in the image above
ADD: Click ADD to place the entered address range in the table.
Delete: To delete a specic IP address range, click on the “X”.
Save: Saves all changes.
Instruction Manual
15
MAC Filter Tab
Congure a specic list of MAC addresses that are able to access the PDU.
MAC Filter Enable: Check this box to enable the MAC address lter.
Allow MAC Address: Enter the MAC address of the user(s) that you want to have
access to the PDU. The default MAC address is the MAC address of the computer that you initially used to setup the device.
ADD: Click ADD to place the entered address in the table.
Delete: To delete a specic MAC address, click on the “X”.
Save: Saves all changes.
Instruction Manual
16

Account Section

This menu allows the administrator to setup authorized user accounts and other privileges. The administrator can assign specic access levels for each user account. Example: The administrator can assign user “A” to have access to outlet number 1 and receive email notications when an event occurs to that specic outlet. Smart Power 2S allows administrator to set up 2 accounts for management.
Account: Enter the user id for each user account.
Password: Enter the password for each user account.
Cell phone: Enter the contact phone number of the user that will receive the SMS text
message once an event has occurred.
Mail Address: Enter the contact email address of the user that will receive the email notication once an event has occurred.
1 | 2: Mark the outlet(s) that the account can control.
Del (Column): Check account(s) to be deleted.
Delete (Button): Delete checked account(s).
Save: Saves all changes.
Instruction Manual
17

TimeSync Section

This menu allows the administrator to set the date and time for the PDU.
Equipment Date: Displays the date. This eld is not editable.
Equipment Time: Displays the time in 24-hour format. This eld is not editable.
Sync with PC: Check the Sync with PC button to synchronize the PDU’s date and time
with the PC.
PC Date: The current PC system date.
PC Time: The current PC system time.
Sync with NTP Server: Check the Sync with NTP Server button to synchronize the
PDU’s date and time with an NTP server.
NTP Server Address: There is a drop-down list of some available NTP servers. Select the desired NTP server and then click Save. If your desired NTP server is not on the list, click on the New button and then enter your desired NTP server address, then click OK.
Instruction Manual
18
Manual Setup: Check the Manual Setup button to manually setup the date and time.
Date: Please enter the date with correct format.
Time: Please enter the time with correct format.
Time Zone: Adjust the time dierence between Greenwich Mean Time and your
country into this format.
Save: Saves all changes.

Event Section

This menu displays the events that have occurred with the PDU.
Refresh: Check for new events.
Download: Save the event log information (.csv format).
Delete: Clear the event log.
Instruction Manual
19
To Download / save the conguration le:
1. Click the Download button, then select Save from the window that pops up
2. Select the location you would like to place the le (.bin format), then click Save
Instruction Manual
20
To upload a previously saved conguration le:
1. Click the Browse button
2. Navigate to the location of your previously saved cfg.bin le, the click Open
3. Click the Upload button to begin. Once the upload is complete, the PDU will restart automatically
Instruction Manual
21

Firmware Upgrade Procedure

1. Open the rmware_upgrade.exe program located on the included CD
2. Input the IP Address of the PDU
3. Click on the GetVersion button
4. Click on the browse (…) button to select the new rmware le (.bin)
5. Input the password (default is admin)
6. Click on the Upgrade button to start the process
7. Once the rmware upgrading process is complete, the PDU will reboot
8. Once the reboot is complete click the OK button
Instruction Manual
22
Specications
PDU02IP PDU02IPSC
Ports 2
1 - IEC 60320 C14 Power
Connectors
2 - NEMA 5-15 Power (North
Max. Current load
per Port
Max. Total Current
Output
Power Consumption 4.5 W
Enclosure Material Steel
Operating
Temperature
Storage
Temperature
Humidity 0~85% RH (Non-Condensing)
Dimensions 182 x 125 x 44 mm
Weight 780g 820g
Plug
1 - RJ-45 Female
America) Receptacle
12 A
0°C to 40°C (32°F to 104°F)
0°C to 70°C (32°F to 158°F)
1 - IEC 60320 C14 Power Plug
1 - DB-9 (9 pin; D-Sub) Male
2 - RJ-45 Female
2 - NEMA 5-15 Power (North
America) Receptacle
8 A
Instruction Manual
23

Technical Support

StarTech.com’s lifetime technical support is an integral part of our commitment to provide industry-leading solutions. If you ever need help with your product, visit www.startech.com/support and access our comprehensive selection of online tools, documentation, and downloads.
For the latest drivers/software, please visit www.startech.com/downloads

Warranty Information

This product is backed by a two year warranty.
In addition, StarTech.com warrants its products against defects in materials and workmanship for the periods noted, following the initial date of purchase. During this period, the products may be returned for repair, or replacement with equivalent products at our discretion. The warranty covers parts and labor costs only. StarTech.com does not warrant its products from defects or damages arising from misuse, abuse, alteration, or normal wear and tear.
Limitation of Liability
In no event shall the liability of StarTech.com Ltd. and StarTech.com USA LLP (or their ocers, directors, employees or agents) for any damages (whether direct or indirect, special, punitive, incidental, consequential, or otherwise), loss of prots, loss of business, or any pecuniary loss, arising out of or related to the use of the product exceed the actual price paid for the product. Some states do not allow the exclusion or limitation of incidental or consequential damages. If such laws apply, the limitations or exclusions contained in this statement may not apply to you.
Instruction Manual
24
Hard-to-nd made easy. At StarTech.com, that isn’t a slogan. It’s a promise.
StarTech.com is your one-stop source for every connectivity part you need. From the latest technology to legacy products — and all the parts that bridge the old and new — we can help you nd the parts that connect your solutions.
We make it easy to locate the parts, and we quickly deliver them wherever they need to go. Just talk to one of our tech advisors or visit our website. You’ll be connected to the products you need in no time.
Visit www.startech.com for complete information on all StarTech.com products and to access exclusive resources and time-saving tools.
StarTech.com is an ISO 9001 Registered manufacturer of connectivity and technology parts. StarTech.com was founded in 1985 and has operations in the United States, Canada, the United Kingdom and Taiwan servicing a worldwide market.