VPH1011189230V1”1-1/4”1”15-1/2”6-1/2”14-1/2”56 lb.
VS210P
VA210P
VS215P1-1/222512.5230V1”1-1/4”1”18-1/8”9-1/4”15-1/8”76 lb.
All motors are single phase 60 Hz., 3450 RPM.
Motor can be changed to either 115V or 230V by following diagram on motor decal.
Pressure switch settings are 30 - 50 PSI for the above models.
HPSTG.
3/42189230V1”1-1/4”1”17”9-1/4”15-1/8”67 lb.
122110.5230V1”1-1/4”1”17-5/8”9-1/4”15-1/8”72 lb.
NAMEPLATE
MAX AMPS
115V230VDISCHG. SUCTION PRESS.HWLWT.
MOTOR
CONNECTED
FOR
TAPPING SIZE INCHESDIMENSIONS INCHES
EJECTOR SPECIFICATIONS AND WELL ADAPTER SELECTION CHART
EJECTOR
ORDER
NO.
SP20BL2” Brass, Leather
SP20CL
SP22CL
*129205 1-1/4” turned coupling required. Order separately.
EJECTOR
DESCRIPTION
2” Cast Iron,
Leather
2” Cast Iron,
Leather
EJECTOR
DROP PIPE
TAPPING
1” F
1-1/4” M
1” F2” x 1”
1-1/4” M2” x 1-1/4”
WELL SIZE /
DROP PIPE
2” x 1”
2” x 1-1/4”*
WELL ADAPTER
REQUIRED
PACKAGE
NO.
129719
127025
129720
129723
129719
127025
129720
129723
Rt. Angle
Rt. Angle
Rt. Angle
Rt. Angle
TYPE
Straight
Straight
Straight
Straight
READ THESE INSTRUCTIONS CAREFULLY
Read these installation instructions in detail before installing your pump. Be sure to check the following:
1. Be certain the motor is connected for the correct line voltage being used (check motor nameplate).
2. Be certain the pump is completely primed before starting. Otherwise damage may occur to the seal.
EVERY pump is tested before leaving the factory, and its performance depends largely on the installation.
GENERAL SAFETY INFORMATION
A. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC) and the Occupational
Safety and Health Act (OSHA).
B. Replace or repair damaged or worn cords immediately.
C. Do not kink power cable and never allow the cable
to come in contact with oil, grease, hot surfaces, or
chemicals.
D. Protect the power cable from coming in contact with
sharp objects.
E. Be careful when touching the exterior of an operating
motor--it may be hot enough to be painful or cause injury.
With modern motors, this condition is normal if operated
at rated load and voltage. Modern motors are built to
operate at higher temperatures.
F. Make certain that the power source conforms with the
G. Always disconnect power source before performing any
work on or near the motor or its connected load. If the
power disconnect point is out-of-sight, lock it in the open
position and tag it to prevent unexpected application of
power. Failure to do so could result in fatal electrical
shock.
H. Do not handle the pump with wet hands or when
standing in water, as fatal electrical shock could occur.
Disconnect main power before handling unit for ANY
REASON!
I. Unit must be securely and adequately electrically
grounded. This can be accomplished by wiring the unit
to a grounded metal-clad raceway system or by using a
separate ground wire connected to the bare metal of the
motor frame or other suitable means.
J. WARNING: Risk of electric shock. This pump has not
been investigated for use in swimming pool areas.
K. WARNING: This product contains chemicals known to
the State of California to cause cancer and birth defects
or other reproductive harm.
L. NOTE: Pumps with the “CSA” mark are tested to UL
standard UL778 and certified to CSA standard C22.2
No. 108.
2
PRELIMINARY CONSIDERATIONS
I. Location
A. Pump can be located at the well or can be offset some
distance away from the well. For best performance, it
should be located as close to the well as possible.
B. Location can be in the basement, a pit below ground, or
in a pump house above ground.
C. Ventilation and drainage must be provided to prevent
damage from moisture to the motor and pressure switch.
D. The pump and all piping must be protected from freezing.
E. Pump and pipe line must be drained when not in use if
there is any danger of freezing.
II. Well Conditions
A. New wells should be pumped clean of all sand and
foreign matter before installing the pump, or damage may
result to the operating parts.
B. The foot valve should be installed a minimum of five feet
from the bottom of the well to prevent sand, mud or other
foreign matter from entering the system.
C. The well must be capable of furnishing a sufficient
quantity of water to satisfy the demands of the pump and
personal needs. The water level must not draw down
below the maximum rated depth of the pump, or loss of
capacity and prime will result.
D. For weak well installations, see Paragraph A under Deep
Well (Double Pipe System) installations.
E. For sanitary reasons, install a well seal or pitless adapter
as required and in accordance with local and state
codes.
III. Piping
A. Old or badly scaled pipe should not be used, because
dislodged flakes of scale can cause stoppage of the
ejector nozzle and malfunction the entire system.
B. Use only pipe in good condition, free of rust and
scale. Threads should be sharp, cleanly cut and with a
minimum of two threads remaining when connection is
completely drawn up.
C. On galvanized steel pipe installations, the ends should
be reamed to ensure maximum capacity.
D. All joints and connections should be doped (male threads
only) and drawn up tightly.
CAUTION: THE ENTIRE SYSTEM MUST BE AIR
AND WATER TIGHT FOR EFFICIENT OPERATION
IV. Type of Pipe
A. Plastic or galvanized steel pipe may be used in the
installation of jet pumps.
B. Plastic pipe must have a minimum pressure rating of 160
P.S.I.
C. DO NOT USE PLASTIC PIPE IN THE WELL ON
SINGLE PIPE EJECTOR INSTALLATIONS.
V. Well To Pump Piping
A. All offset piping should slope upwards from well to pump.
B. Avoid dips or pockets in offset piping, or air will
accumulate at high points and make priming difficult.
C. Install unions at pump and at well to aid in servicing.
D. Allow enough room around pump and piping installation
for using pipe wrenches, and for service and installation.
E. Do not use piping of sizes smaller than those listed in
Application - Where the inside diameter of well is 3-1/2
inches or larger. (See illustration C & D).
A. Attach the foot valve to the ejector using a galvanized
steel or plastic nipple. Add sufficient pressure pipe (1”)
and suction pipe (1-1/4”) to submerge ejector 10 to 15’
below pumping water level, making certain foot valve is
at least 5 feet from bottom of well. If pressure pipe and
suction pipe of the same diameter are used, be sure to
identify them clearly so that they will be connected to the
proper tappings of the pump.
If a known weak well exists, replace nipple with 34 feet of
1” tail pipe between the ejector and the foot valve. This
will provide a continuous source of water for the pumping
system.
B. Check pipe and foot valve for leaks by filling pipes with
water. A continuous loss of water indicates a leak in the
piping, foot valve or unions, and must be corrected.
C. If no leaks are found, connect pressure and suction pipes
from well to pump using piping of the same diameter as
the suction pipe (1-1/4”) and pressure pipe (1” ) tappings
of the pump. For long offset distances, refer to Chart I.
for the proper pipe size.
D. Unions in suction and discharge piping near pump and
well will aid in servicing. Leave enough surrounding
room so that wrenches can be used without difficulty.
Application - Where the inside diameter of well is 2, 2-1/2 or
3 inches (See Illustration A & B).
A. Attach foot valve directly to bottom of ejector assembly
(tail pipe not used on single pipe installations). Ejector
is to be submerged 10 to 15 feet below pumping water
level, making certain foot valve is at least five feet from
bottom of well.
B. Attach foot valve and packer ejector to suction pipe
(presoak packer leathers for approximately two hours).
Start the assembly down the well. Some force may be
required to push the packer down the casing.
C. As each section is lowered, check for leaks by pouring
water into the suction pipe.
D. Attach well adapter to suction pipe, lower over casing top
and tighten adapter flange.
E. If pump is offset from the well, run suction and pressure
pipes from well to pump, using piping of the same
diameter as the suction tapping (1-1/4”) and pressure
tapping (1” of the pump. For long offset distances, refer
to Chart I for the proper pipe size.
F. Unions in suction and discharge piping near pump and
well will aid in servicing. Leave enough surrounding
room so that wrenches can be used without difficulty.
III. Pressure Tank Hook Up
A. Standard vertical pressure tanks require an air volume
control to ensure the proper air-to-water ratio in
the pressure tank. The air volume control tubing is
connected to the 1/4” tapping on the pump case (see
Illustration E).
B. Air-E-Tainer tanks are equipped with a diaphragm or
bladder that keeps the air and water from mixing. Since
these tanks are factory precharged with air, an air
volume control is not required.
C. On vertical tank installations, galvanized steel or plastic
pipe can be used to connect the pump to the tank. To
assist in servicing, place shut-off valve and union in line
between pump and tank (See Illustration E).
D. DO NOT install a check valve between pump and
pressure tank. This will cause the pressure switch to
malfunction.
IV. Wiring
A. All jet pump motors are suitable for use with 60 cycle
A.C. current only. Pumps with 3/4 thru 1-1/2 HP motors
are connected for 230 volt service.
B. All pumps (3/4 thru 1-1/2 HP) are dual voltage and may
be field connected for either 115 or 230 volt service.
C. Check the motor nameplate diagram if a voltage change
is required. Always use the higher voltage when
possible.
Your pump motor has built-in thermal overload that protects
the motor against burnout from overload of low voltage,
high voltage and other causes. The device is automatic
and resets itself once the temperature has dropped to a
safe point. Frequent tripping of the device indicates trouble
in the motor or power lines, and immediate attention is
needed. The device should never be tampered with, and
unless trouble is located and corrected, motor failure can
eventually be expected.
CHART II-A
RECOMMENDED WIRE AND FUSE SIZES
MAX. FUSE CAPACITYWIRE GAUGE
15A
20A
30A
45A
60A
14
12
10
8
6
CHART II-B
RECOMMENDED WIRE SIZES
Distance From
Motor To Meter
0-50’
115V
230V
50-100’
115V
230V
100-150’
115V
230V
150-200’
115V
230V
200-300’
115V
230V
HP Rating of Single Phase Motors
3/411-1/2
12 GA
14 GA
12 GA
14 GA
12 GA
14 GA
10 GA
14 GA
8 GA
14 GA
12 GA
14 GA
12 GA
14 GA
10 GA
14 GA
10 GA
12 GA
8 GA
12 GA
12 GA
14 GA
12 GA
14 GA
10 GA
12 GA
12 GA
10 GA
8 GA
6 GA
CAUTION: Never examine, make wiring changes or
touch the motor before disconnecting the main electrical supply switch. The thermal device may have
opened the electrical circuit.
D. Undersize wiring can cause motor failure (low voltage),
frequent cutout of motor overload protector, television
interference and even fire. Make certain the wiring
is adequately sized (Chart II-B), well insulated and
connected to a separate circuit outside the house in case
of fire. For added safety, the pump and motor should be
securely grounded to the well casing or to a separate
ground rod driven eight feet into the ground. Consult
local codes before attempting a wiring installation.
NOTE: Charts II-A and II-B assume copper wire to be
installed.
E. When fusing the pump service entrance box, consult
Chart II-A for proper fuse size. Use only the fuse that is
stipulated for your particular installation. Never use one
larger. Service should never be reinstated to the pump
motor by attempting to circumvent a blown fuse by any
other means.
F. The pressure switch is wired to the motor by connecting
the motor lead to the two inside terminals of the pressure
switch. Connect the power lines to pressure switch
terminals marked L-1 and L-2.
Motor
Load
LoadLoad
Line 1Line 1
Power
Supply
IL0199
PRIMING & ADJUSTMENT
CAUTION: Before starting motor, the pump body
must be completely filled with water. Running the
pump dry will cause seal damage.
I. Pumps With Fully Automatic Control Valve
A. Remove priming plug from pump. Fill pump body
completely with water until all air has been expelled.
Replace plug.
B. Start pump. If pump is properly primed, pressure will
build quickly and register on the pressure gauge. If
pressure does not build, repeat the priming operation.
ON DEEP WELL INSTALLATIONS, ALL AIR MUST BE
VENTED FROM THE DRIVE AND SUCTION PIPES AS
WELL AS THE PUMP BODY BEFORE THE PUMP WILL
PRIME. IT MAY BE NECESSARY TO FILL THE PUMP
BODY SEVERAL TIMES TO ACHIEVE PRIME.
C. Once prime is achieved, unit will adjust automatically to
the average operating pressure.
II. Pumps With Semi-Automatic Control Valve
A. Remove priming plug from pump. Fill pump body
completely with water until all air has been expelled.
Replace plug.
B. Screw adjusting stem on control valve all the way in, then
start the pump. If the pump is properly primed, pressure
will build quickly and register on the pressure gauge. If
pressure does not build, repeat the priming operation.
C. With the pump operating at high pressure and no
pressure in the tank (two or more faucets open) slowly
unscew the adjusting stem until maximum flow is
obtained. The case pressure at this point will be the
average operating pressure and should agree with the
chart shown below.
D. If the control valve is opened too far, a slight cavitation
noise will be noticeable and still further opening will
cause the pump to lose prime.
AVERAGE OPERATING PRESSURE
MODEL NO.
SETTING
VS, VA207P3/446 PSI
VS, VA210P157 PSI
VS, VA215P1-1/272 PSI
VPH10147 PSI
HPPRESSURE
NOTE: PUMP WILL NOT PRIME IF THERE IS ANY
LEAKAGE IN THE SUCTION PIPING.
III. Pumps Installed In A Horizontal Position
A. “VA” and “VS” pumps can be installed horizontally by
using the optional 135276 pump base.
B. If installed horizontally, prime through the priming port of
the pump body.
C. By following this procedure, the entire pump cavity can
be filled with water and air will be expelled more readily.
MAINTENANCE
A. LUBRICATION
The pumps and motors require no lubrication. The ball
bearings of the motor have been pre-lubricated and
under normal operating conditions should require no
further greasing.
B. FREEZING
Drain the entire system if there is danger of freezing. A
drain plug is provided at the bottom of the pump case for
this purpose.
ROTARY SEAL ASSEMBLY
REPLACEMENT
CAUTION: Make certain that the power supply is
disconnected before attempting to service the unit!
The rotary seal assembly must be handled carefully
to avoid damaging the precision lapped faces of
the sealing components.
A. Disengage pump body from motor and mounting ring.
B. Remove diffuser and unthread impeller from the pump
shaft.
NOTE: To prevent the shaft from rotating when removing
the impeller, use an 11/16” open end wrench on the hex
of the pump shaft.
C. The carbon seal face, friction ring, and stainless steel
shell & spring of the rotary seal will come loose at this
time. Use a screwdriver (or similar instrument) to pry the
ceramic seal and rubber gasket from the recess of the
mounting bracket.
CAUTION: Be careful not to damage the motor
shaft or recess surface.
(*) Standard hardware item
(†) For quantity required — See number of stages
(‡) Not shown
NOTE: For horizontal installations, use optional pump base 135276A