StantFin Monitron EH, Monitron EH EH8-135S, Monitron EH-40-135S, Monitron EH-12-345S, Monitron H-40-345S Operation And Installation Instructions Manual

MODEL EH ELECTRIC BOILER
EH8-135S through EH-40-135S 3 wire 120/208V, 120/240V single phase EH-12-345S through EH-40-345S 4 wire 120/208V three phase WYE
OPERATION AND INSTALLATION INSTRUCTIONS
IMPORTANT:
This manual must be left with owner and should be hung on or adjacent to the boiler for reference.
Publication No. EH-40
Part No. 79-0820
Rev.B
Heating Contractor
Address
Phone Number
Boiler Model Number
Boiler Serial Number
Installation Date
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Air Eliminator and Expansion Tanks . . . . . . . . . . . . . . . . . . 2
Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Wall Thermostat Flow Switch and Circulator . . . . . . . . . . . 2
Service Connections and Electrical Ratings . . . . . . . . . 3–4
Typical Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Zone Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Fill System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Air Elimination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Bypass Flow Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Check for Proper Boiler and System Operation . . . . . . . . 7
Operation (models equipped with seq. control system) . . . . . . 7
Periodic Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Appendix A & B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DESCRIPTION
The Monitron boiler is a low pressure hot water heating electric boiler. The heating elements are sheathed resistance type. The heat exchanger is cast-iron. The heat exchanger is constructed, inspected, and stamped in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code. In addition, the Monitron Boiler is equipped with a safety relief valve and an integral dual limit con­trol, conforming to ASME requirements. The Monitron boiler is CSA listed.
MOUNTING
The Monitron is intended for wall mounting, utilizing the wall brackets attached to the boiler (see Figure 1). Allow sufficient space for piping and service. The boiler may be installed in an enclosed space (see Figure 1). The boiler must be INSTALLED LEVEL.
PIPING Air Separator and Expansion Tanks
The recommended piping arrangement is shown in figures 4 through 6. Note that there is a built-in air eliminator in the heat exchanger (air vent, however, is by others). The air vent tapping is 13mm (1/2”). A bushing (by others) to suit the size of the air vent thread is required. Additional air vents should be installed at points just upstream from all drops in elevation of the piping system (high points).
Relief Valve Discharge Piping
Use same size or larger piping than valve outlet. Must terminate 152mm ( 6”) minimum from floor with a plain ( no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping.
Flow Switch
THE INSTALLATION OF A FLOW SWITCH IS STRONGLY RECOM MENDED. It is intended to prevent the burnout of heater elements should the circulator fail, or should air accumulate in the boiler due to faulty air elimination (see Table 3 for flow switch size required). FLOW SWITCH MUST BE INSTALLED IN HORI­ZONTAL POSITION. IF A FLOW SWITCH IS NOT USED JUMPER THE “FF” TERMINALS (JUMPER NOT SUPPLIED.)
Bypass
The bypass shown must be set so that a sufficient amount of water can circulate through the boiler when all zone valves are closed. (See Figure 5 & 6.)
Multi-zone Balancing
Raise all zone thermostat settings and verify that all zone valves are open (bypass valve should be closed). Close all electrical panels. Turn on 15 amp control circuit breaker ONLY. Pump should operate. Note the pressure reading on the pump dis­charge. Lower each zone thermostat setting to close correspond­ing zone valve. Adjust the corresponding balancing valve to maintain pump discharge pressure. The pump discharge pres­sure should remain the same when all zones are in bypass or when all zones are open or any combination of opened and closed. (See Figure 5 & 6.)
WIRING
To wire the electric boiler, perform the following procedures:
1. Wall thermostat, flow switch, outdoor thermostat,
circulator and external transformer
All circuit breakers ahead of and at the boiler must be OFF. Remove the Control Panel (left-hand front cover) by removing 5 screws from top, bottom and side flanges. The centre compartment contains a 24V control terminal board marked, "FF/TT/1-2" (see figure 2 or figure 3.) Wire a 24V, two-wire heating thermostat or the auxiliary end switch terminals from zone valves (see Figure 7) to "TT". The "FF" terminals are for a flow switch. Do not connect the wires to the flow switch "FF" terminals until the by-pass flow adjustments are completed. Refer to "By­pass Flow Adjustment" (page 7) for wiring and adjustment procedures. The flow switch wires should be taped at the boil­er until they are to be connected to "FF".
The left compartment contains a 120V terminal board marked "A-B/Circulator". Wire the circulator and connect wires and conduit through the 13 mm (1/2") knockout (pro vided on the bottom left hand corner of the cabinet) to the terminal board "Circulator" terminals. These terminals supply 120 volts to the circulator only when there is a call for heat.
2
NOTES:
1. MAY BE TOTALLY ENCLOSED.
2. ALL ABOVE CLEARANCE DIMENSIONS ARE MINIMUM.
3. ALL DIMENSIONS ARE IN METRIC (INCHES).
424mm
(16-11/16”)
475mm
(18-11/16”)
Figure 1. Boiler Mounting
Wire an external zone valve transformer to the "A-B" termi­nals if zone valves are used. These terminals provide a constant 120 volts and can alternately be used to power the circulator if constant circulation is desirable. Use 90°C (75°F) minimum wire, copper or aluminum.
2. Service Connections and Electrical Ratings
A. All circuit breakers ahead of and at boiler must be OFF.
Remove the Service Connection Panel (right hand front) cover by removing 5 screws from the top, bottom and side flanges (see wiring diagram on back of the Service Connection Panel and Figure 2 & 3).
B. Draw power feeder cable (90°C [75°F]minimum) and
conduit through service K.O. provided on side, top or bottom.
C. Connect hot lines to main lugs on breaker base (S
models) or to black and red or to black, red and blue leads (LB models) provided in service compartment. A ground lead should be drawn and wired to the ground lug in the service compartment. If rating plate indicates boiler is a single phase 3-wire or 3-phase 4-wire model, draw a neutral wire #12 AWG maximum, 90°C (75°F). minimum and connect to neutral lug or white wire lead provided in service compartment. See Tables 1 and 2 for lug sizes and current ratings.
Main * Lug Grounding Lug Wire Size
Wire Size Small Holes Large Holes
Model Phase CU-AL† CU-AL† CU AL†
EH-40 1 2-250 MCM CU DO NOT USE 6-2/0 EH-28 thru 32 1 2-250 MCM DO NOT USE 14-4 6-4 EH-8 thru 24 1 6-2/0 14-8 14-4 6-4 EH-8 thru 40 3 6-2/0 14-8 14-4 6-4
Neutral Lug Wire Size: For 3-wire single phase and 4-wire 3 phase models
equipped with circuit breakers Small Holes accommodate: #14-12 Solid CU or AL † and #12 stranded CU or AL† Large Holes accommodate: #14-8 Solid CU, #10-4 Stranded CU and #6-4 AL †
The maximum wire size of the neutral should not exceed 12 AWG in order for 51 mm (2”) conduit to accommodate incoming power feeder, plus the neutral wire and a ground con­ductor for the larger models.
Table 1. Lug Sizes
* For models with circuit breakers only. † ALUMINUM conductors may be used, lug size, conduit size, ampacity and all applicable
codes permitting. However, aluminum conductors may NOT be used for model EH-40 single phase.
SINGLE PHASE 3 WIRE THREE PHASE, 4 WIRE
120/208V, 120/240V‡ 120/208V-WYE
CIRCUIT ONLY‡
Basic Heater Basic Heater
Model Amperes* Model Amperes†
No. @240V No. @208V
EH-8 33
EH-9 38 EH-10 42 EH-12 50 EH-12 25 EH-15 63 EH-16 67 EH-16 38† EH-18 75 EH-20 83 EH-20 48† EH-24 100 EH-24 60† EH-25 104 EH-28 117 EH-28 60† EH-30 125 EH-32 133 EH-32 73† EH-35 146 EH-40 167 EH-40 95†
Table 2. Current Ratings
* For current values @ 208V, multiply current @ 240V by 0.867. † Leg with the highest value of line current of an unbalanced 3-phase load. ‡ 125 VAC maximum rating of all hot conductors.
Flow Switch Minimum Model McDonnell Pipe Length of No. & Miller No. Size Straight Pipe*
mm in. mm in.
EH-40 FS8V 32 1-1/4 216 8-1/2
EH-8 thru EH-35 FS4-3T3-1 25 1 165 6-1/2
Table 3. Flow Switch Size Selection
* Both upstream and downstream of flow switch
3
Loading...
+ 5 hidden pages