START-UP
NOTE: Make sure that all circuit breakers ahead of and at the
boiler are OFF.
Fill System
See Figures 4 through 6 for suggested purge valve and blocking valve. If system is filled but not purged, radiators must be
vented individually, to prevent air blocking of water flow. Fill
approximately 83 kPa (12 psi) (cold water), whether automatic
or manual fill is used. Do not apply full line pressure to system;
boiler and relief valve are rated at 207 or 345 kPa (30 or 50 psi)
(see rating plate). Suddenly applied main pressure can exceed
690 kPa (100 psi).
WATER CONTENT OF BOILER
All models EH-8 through EH-40 14.2 litres (3.75 U.S. Gallons)
Air Elimination
Diaphragm tank and air vent valve are recommended, see
Figures 4 through 6. Air remaining in system will vent from the
automatic vent valve during system operation. Valve cap must
be loose or removed to allow automatic venting. Open relief
valve briefly after filling to pressure, to make sure boiler is free
of air.
Bypass flow adjustment (Figure 5 & 6)
Close bypass valve. Turn down all zone thermostats. Inspect
all zone valves to be sure all are closed. Put a jumper on TT
terminals. Close ALL panels and turn on the 15 AMP control
circuit breaker ONLY. Be certain that the flow switch wires are
not connected to the flow switch terminals and the ends of
the wires are taped. Connect the ohmmeter or other continuity tester across the common terminal and the terminal that is
normally open during NO FLOW. Slowly open bypass valve
until continuity tester lights or ohmmeter kicks to zero: flow
switch now has closed contacts, indicating required minimum bypass flow rate when piping circuits are shut off.
Bypass valve should be locked at this position. Shut OFF
ALL circuit breakers ahead of and at boiler and open CONTROL PANEL (left hand FRONT COVER). Remove jumper on
“TT” terminals. Connect zone valve end switches (in parallel)
to thermostat “TT” terminals. See figure 7 and wiring diagram
on boiler. Connect flow switch wire to flow switch common
and N.O. terminals and to the “FF” terminals in the boiler.
Replace CONTROL PANEL COVER.
Check for Proper Boiler and System Operation
To check for proper boiler and system operation, perform the
following procedures:
1. Turn up all room thermostats.
2. There will be a delay of up to five minutes before all circuits
are energized.
3. Current may be checked by a qualified electrician at the
feeder panel and compared to the values shown in Table 2.
4. Water flow through the boiler should be sufficient to keep
the flow switch closed. The limit thermostat should also
remain closed. The LOW LIMIT of the dual limit aquastat is
factory set at a normal temperature of 180°F or 82°C; it may
be increased for the purpose of check-out if the load is very
low. The aquastat is located on the left end of the boiler
behind a round cover plate. Loosen screw and rotate cover
to view aquastat.
OPERATION
(Models equipped with Sequential Control System)
These models contain a "S" in the model number which is
located on the rating plate on the top surface of the boiler.
IMPORTANT:
DO NOT operate boiler until the following criteria have
been met:
1. Must be installed by qualified heating and electrical
contractors in accordance with instructions in this
manual.
2. Must be installed in compliance with local codes.
3. Must be inspected and approved by installing contractors and any local authority having jurisdiction, and be
approved for operation by them.
• Ask the installer to explain operation of the entire heating
system.
• Turn on all circuit breakers for boiler and circulator.
• Adjust wall thermostat to required temperature. If room
temperature is lower than the thermostat setting, the
first heater stage will go on immediately and the balance
of the heater stages will go on one at a time with a
delay of between several seconds and 1-1/2 minutes
between stages.
• In mild weather you may wish to reduce the total output of
heat. You may do this by turning off one or more of the
circuit breakers on the boiler. Do not turn off the 15 AMP
control circuit breaker.
IMPORTANT
You must turn on the circuit breaker marked "15" in order to
operate the boiler control system. You then may turn on any
one or more of the other circuit breakers (those marked 25,
30, 35, 50, or 60), depending on the amount of heat required.
PERIODIC INSPECTION
The hot water system, which includes the Monitron boiler, the
radiators and water control devices, should remain filled with
water at all times. DO NOT drain except to make repairs or to
prevent freeze-up during extended cold weather shutdown.
The pressure/temperature gauge on the Monitron should be
checked frequently: at the highest operating temperature,
pressure should be the same throughout the heating season.
If pressure (at a constant temperature) consistently rises or
falls over a period of time, a fill valve leak, a system leak or
compression tank malfunction is indicated. Leaks anywhere
in the system must be repaired without delay. Regular addition of fresh water to replenish leaks adds oxygen and lime.
Oxygen corrosion will cause further leaks and parts failure,
lime buildup on heating elements will cause element failure
due to overheating. If any leaks are found, or if pressure
changes, call for service immediately.
IMPORTANT
Under no circumstances should any electrical wiring or
internal controls be touched, except by an authorized
electrician (wiring and controls) or heating system service
expert (system service, repair, shutdown). Any mechanical adjustments to the heating equipment and system
must be made by a qualified heating serviceperson.
7