Wire an external zone valve transformer to the "A-B" terminals if zone valves are used. These terminals provide a
constant 120 volts and can alternately be used to power the
circulator if constant circulation is desirable. Use 90°C (75°F)
minimum wire, copper or aluminum.
2. Service Connections and Electrical Ratings
A. All circuit breakers ahead of and at boiler must be OFF.
Remove the Service Connection Panel (right hand front)
cover by removing 5 screws from the top, bottom and
side flanges (see wiring diagram on back of the Service
Connection Panel and Figure 2 & 3).
B. Draw power feeder cable (90°C [75°F]minimum) and
conduit through service K.O. provided on side, top
or bottom.
C. Connect hot lines to main lugs on breaker base (S
models) or to black and red or to black, red and blue
leads (LB models) provided in service compartment. A
ground lead should be drawn and wired to the ground
lug in the service compartment. If rating plate indicates
boiler is a single phase 3-wire or 3-phase 4-wire model,
draw a neutral wire #12 AWG maximum, 90°C (75°F).
minimum and connect to neutral lug or white wire lead
provided in service compartment. See Tables 1 and 2 for
lug sizes and current ratings.
Main * Lug Grounding Lug Wire Size
Wire Size Small Holes Large Holes
Model Phase CU-AL† CU-AL† CU AL†
EH-40 1 2-250 MCM CU DO NOT USE 6-2/0
EH-28 thru 32 1 2-250 MCM DO NOT USE 14-4 6-4
EH-8 thru 24 1 6-2/0 14-8 14-4 6-4
EH-8 thru 40 3 6-2/0 14-8 14-4 6-4
Neutral Lug Wire Size: For 3-wire single phase and 4-wire 3 phase models
equipped with circuit breakers
Small Holes accommodate: #14-12 Solid CU or AL † and #12 stranded CU or AL†
Large Holes accommodate: #14-8 Solid CU, #10-4 Stranded CU and #6-4 AL †
The maximum wire size of the neutral should not exceed 12 AWG in order for 51 mm (2”)
conduit to accommodate incoming power feeder, plus the neutral wire and a ground conductor for the larger models.
Table 1. Lug Sizes
* For models with circuit breakers only.
† ALUMINUM conductors may be used, lug size, conduit size, ampacity and all applicable
codes permitting. However, aluminum conductors may NOT be used for model EH-40 single phase.
SINGLE PHASE 3 WIRE THREE PHASE, 4 WIRE
120/208V, 120/240V‡ 120/208V-WYE
CIRCUIT ONLY‡
Basic Heater Basic Heater
Model Amperes* Model Amperes†
No. @240V No. @208V
EH-8 33
EH-9 38
EH-10 42
EH-12 50 EH-12 25
EH-15 63
EH-16 67 EH-16 38†
EH-18 75
EH-20 83 EH-20 48†
EH-24 100 EH-24 60†
EH-25 104
EH-28 117 EH-28 60†
EH-30 125
EH-32 133 EH-32 73†
EH-35 146
EH-40 167 EH-40 95†
Table 2. Current Ratings
* For current values @ 208V, multiply current @ 240V by 0.867.
† Leg with the highest value of line current of an unbalanced 3-phase load.
‡ 125 VAC maximum rating of all hot conductors.
Flow Switch Minimum
Model McDonnell Pipe Length of
No. & Miller No. Size Straight Pipe*
mm in. mm in.
EH-40 FS8V 32 1-1/4 216 8-1/2
EH-8 thru
EH-35 FS4-3T3-1 25 1 165 6-1/2
Table 3. Flow Switch Size Selection
* Both upstream and downstream of flow switch
3