Stanley Tara Boiler, Tara Non Boiler, Tara DHW Installation And Operating Instructions Manual

Page 1
Tara Boiler / Non Boiler & DHW
Solid Fuel Stove
INSTALLATION AND OPERATING INSTRUCTIONS
WARNING: This appliance is hot while in operation and retains its heat for a long period of time after use. children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
When using the boiler stove in situations where children, aged and/or infirm persons are present a fire­guard must be used to prevent accidental contact with the stove. The fireguard should be manufactured in accordance with
BS 8423:2002.
Page 2
TABLE OF CONTENTS
PAGE NO.
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fire Cement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Asbestos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Metal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Pre-Installation Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3. Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Flues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5. Flue Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6. Top Flue Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Rear Flue Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8. Ventilation & Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
9. Permanent Air Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Extractor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
10. Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
11. Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
12. Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
13. Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Boiler Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DHW Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Non Boiler Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
14. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
15. Plumbing (Boiler Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
16. Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
17. Gravity Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
18. Interlink System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
19. DHW Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
20. Injector Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
21. Water Circuit Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
22. Domestic Hot Water System (DHW Model Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
23. Safety Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
24. Direct Domestic Cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
25. Indirect Domestic Cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
26. Pipe Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
27. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
28. Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
29. Suitable Fuels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
30. Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
31. Important Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
32. Primary Air Settings - Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
33. Primary Air Settings - Outside Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2
Page 3
TABLE OF CONTENTS
PAGE NO.
34. Recommended Fuels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
35. Air Wash Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
36. Secondary Air /System Control (Dry Model Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
37. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
38. Overnight Burning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
39. Re-fuelling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
40. De-Ashing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
41. Disposal of Ashes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
42. To Clean Chimney Outlet (Boiler / Non Boiler Model ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
43. To Replace Fire Grate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
44. Fire Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
45. Vitreous Enamel Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
46. Glass Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
47. Glass Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
48. Data Plaque Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
49. CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
50. Exploded View - HPB Stove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
51. Exploded View - NB Stove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
52. Exploded View - DHW Stove . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
53. Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3
Page 4
TARA SOLID FUEL CENTRAL HEATING STOVE INSTALLATION & OPERATING INSTRUCTIONS
GENERAL
When installing, operating and maintaining your Tara Stove respect basic standards of fire safety. Read these instructions carefully before commenc­ing the installation. Failure to do so may result in damage to persons and property. Consult your local Municipal office and your insurance representative to determine what regulations are in force. Save these instructions for future reference.
Please note that it is a legal requirement under England & Wales Building Regulations that the installation of the stove is either carried out under Local Authority Building Control approval or is installed by a Competent Person registered with a Government approved Competent Persons Scheme. HETAS Ltd operate such a scheme and a listing of their Registered Competent Persons can be found on their website at www.hetas.co.uk.
Special care must be taken when installing the stove such that the requirements of the Health & Safety at Work Act are met.
Handling
Adequate facilities must be available for loading, unloading and site handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of contact with the skin wash immediately with plenty of water.
Asbestos
This stove contains no asbestos. If there is a possi­bility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment.
Metal Parts
When installing or servicing this stove care should be taken to avoid the possibility of personal injury.
“IMPORTANT WARNING”
This stove must not be installed into a chimney that serves any other heating appliance.
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room.
4
The complete installation must be done in accor­dance with current Standards and Local Codes. It should be noted that the requirements and these publications may be superseded during the life of this manual.
Fig.1
CHIMNEY
Do not connect to a chimney serving another appliance.
The stove is a radiant room heater and must be con­nected to a chimney of the proper size and type. The chimney must have a cross-sectional area of at least 30 square inches 18150sq. mm or a diameter of at least 6” (150mm). It is best to connect to a chimney of the same size, as connection to a larger size may result in a somewhat less draught. Do not connect to a chimney serving another appliance.
Minimum chimney height 15’(4.1 meters) from floor on which stove is installed. An existing masonry chimney should be inspected and if necessary repaired by a competent mason. The stove must be connected to a chimney with a minimum continuous draft of .06 wg. Poor draft conditions will result in poor performance.
PRE INSTALLATION ASSEMBLY
1. After removing the stove from its pack, open the front door and remove the contents.
2. Fit the front door handle using the M8 screw, as shown in Fig.1.
3. Remove the stove from the wooden pallet.
4. Fit the front ash tray by slotting into place on the front and secure it using the screws provided.
Page 5
In adverse weather conditions, down drafts may be experienced causing smoke or fumes to spill into the room. If this occurs shut the appliance down by closing the air controls. If the problem persists seek the advice of a chimney sweep.
Fig 2
FLUES
Flues should be vertical wherever possible and where a bend is necessary, it should not make an angle of more than 45
o
with the vertical. Horizontal flue runs should be avoided except in the case of a back outlet appliance, when the length of the hori­zontal section should not exceed 150mm.
In order to minimise flue resistance and to make sweeping easier it is recommended to use 2 x 45
o
bends rather than a 90obend.
The flue termination point must be located to min­imise any wind effects. Wind effects of suction, pressure zones and turbulence can be created by the roof and adjacent objects. Wind effects can also be created by natural land contours.
To minimise the wind effects, the flue termination point should be located a minimum of 1000mm from the roof measured vertically and 2300mm measured horizontally. Where this termination point does not suffice it may be necessary to extend the flue pipe so that the termination point is above the apex. (See Fig.3)
2300
1000
Soot Door
Appliance
Fig 3
FLUE PIPES
A flue pipe should only be used to connect an appli­ance to a chimney and should not pass through any roof space.
Flue pipes may be of any of the following materials:
(a) Cast iron as described in BS 41: 1973
(1981), or
(b) Stainless steel with a wall thickness of
at least 1mm and as described in BS EN 10095:1999 Specification for stainless and heat resisting steel plate, sheet and strip, for Grade 316 S11, 316 S13, 316 S16, 316 S31, 316 S33, or the equivalent Euronorm 88-71 designation, or
(c) Vitreous enamelled steel complying with BS
6999: 1989.
Flue pipes with spigot and socket joints should be fit­ted with the socket uppermost.
Clearance to combustibles must be adhered to when fitting the flue pipe.
The appliance is suitable for continuous operation on solid mineral fuel and intermittent operation on wood logs.
5
Page 6
TOP FLUE EXIT
For top outlet configuration remove the hob from the top of the stove, turn the hob upside down and place it on the floor, taking care not to damage it. Remove the hob blanking plate by unscrewing the two screws from underneath the hob.
Next remove the flue blanking plate from the top of the stove by unscrewing the two screws, connect this blanking plate to the rear flue outlet at the back of the stove. Replace the hob in the correct position.
Connect the connector pipe (not supplied) into the top flue outlet socket at the top of the stove and cement into place using approved fire cement ensur­ing that no cement blocks the flue passageway.
6
Fig 4
VENTILATION & COMBUSTION AIR REQUIRE­MENTS
It is imperative that there is sufficient air supply to the stove in order to support correct combustion.
The air supply to this appliance must comply with B.S. 8303: Part 1.
The minimum effective air requirement for this appli­ance is 21cm
2
(3.25in2). When calculating combus­tion air requirement for this appliance use the fol­lowing equation: a total free area of at least 550mm
2
per kW of rated output above 5kW shall be provid­ed.
If there is another air using appliance fitted in the same or adjacent room, it will be necessary to cal­culate additional air supply.
All materials used in the manufacture of air vents should be such that the vent is dimensionally stable and corrosion resistant.
The effective free area of any vent should be ascer­tained before installation. The effect of any screen should be allowed for when determining the effective free area of any vent.
Air vents direct to the outside of the building should be located so that any air current produced will not pass through normally occupied areas of the room.
An air vent outside the building should not be locat­ed less than the dimensions specified within the Building Regulations from any part of any flue termi­nal. These air vents must also be fire proofed as per Building Regulations.
Air vents in internal walls should not communicate with bedsits, toilets, bathrooms or rooms containing a shower.
Air vents traversing cavity walls should include a continuous duct across the cavity. The duct should be installed in such a manner as not to impair the weather resistance of the cavity.
REAR FLUE EXIT
For rear flue outlet configuration push in flue con­nector pipe (not supplied) into flue outlet socket at the rear of the stove and cement into place using approved fire cement ensuring that no cement blocks the flue passageway.
It is recommended that a minimum clearance of 100mm be maintained from the sides and rear of the appliance to a tiled fireplace or masonry wall, espe­cially on the right of the appliance as access is required for the controls.
Fig. 5
Page 7
7
Fig.6
It is recommended that this appliance is sited next to and on a non-combustible surface. A minimum all round clearance of 100 mm will allow air circulation and not impede the performance of the stove.
The connector may pass through walls or partitions constructed of combustible materials provided the connector is either listed for wall pass-through or is routed through a device listed for a wall pass­through and is installed in accordance with the con­ditions of the listing. Any unexposed metal that is used as part of a wall pass-through system is exposed to flue gases shall be constructed of stain­less steel or other equivalent material that will resist corrosion, softening, or cracking from flue gas at temperatures up to 982
o
C.
FLOOR PROTECTION
It is recommended that this appliance is installed on a solid, level, non- combustible hearth conforming to current Building Regulations.
The hearth should extend at least 127mm from the sides and rear of the stove and 460mm from the front. See Fig. 6.
Joints between air vents and outside walls should be sealed to prevent the ingress of moisture. Existing air vents should be of the correct size and unob­structed for the appliance in use.
Where such a installation exists, a test for spillage should be made with the fan or fans and other appli­ances using air in operation at full rate, (i.e. extrac­tion fans, tumble dryers) with all external doors and windows closed.
If spillage occurs following the above operation, an additional air vent of sufficient size to prevent this occurrence should be installed.
PERMANENT AIR VENT
The stove requires a permanent and adequate air supply in order for it to operate safely and efficiently. In accordance with current Building Regulations the installer will have fitted a permanent air supply vent into the room in which the stove is installed to pro­vide combustion air. This air vent should not under any circumstances be shut off or sealed.
Extractor Fan
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room.
LOCATION
There are several conditions to be considered in selecting a location for your Tara Stove.
a. Position in the area to be heated, central
locations are usually best.
b. Allowances for proper clearances to
combustibles.
INSTALLATION CLEARANCES
Clearance to combustible materials (Boiler Model)
From the front - 36” From the sides - 6” From the back - 6” From the flue pipe - 24”
Clearance to combustible materials (Non Boiler Model)
From the front - 36” From the sides - 20” From the back - 15” From the flue pipe - 24”
Page 8
Fig 7
SPECIFICATION
DHW STOVE
8
Fig 7A
BOILER STOVE
Page 9
NON BOILER STOVE
TECHNICAL DATA
MODEL BOILER NON BOILER DHW
Fuel Coal Wood Coal Wood Coal Wood
Parameter
Max Heat Output (kW) 10 10 8 8 10 10
Nominal Heat Output (kW) 7.4 7 4.1 5.5 9.1 9.2
Output to Room (kW) 1.5 2.1 4.1 5.5 6.5 6.3
Output to Water (kW) 5.9 5.4 N/A N/A 2.7 3
Typical Refuel Interval To Achieve Nominal Outputs (h)
4.15 1 4 1.5 1 0.75
Mean Flue Gas Temp. (oC) 264 240 250 250 245 286
Gross Weight (kg) 147 135 135
Max Water Pressure (Bar) 2 N/A 2
Flue Outlet Diameter (mm) 152 152 152
Wood Log Size (mm) N/A 300 N/A 300 N/A 300
Note: Dimensions stated are in millimetres and may be subject to a slight +/- variation.
Fig 7B
9
Page 10
10
PLUMBING (BOILER MODEL)
REGULATIONS
The plumbing must be in accordance with all relevant regulations and practices. It must include a gravity circuit with expansion pipe, open to the atmosphere. The central heating will normally be pump-driven as with other types of boilers.
GRAVITY CIRCUIT
The gravity circuit consists of the domestic hot water tank of 135 litres indirect cylinder, fixed in an upright position, recommended for hot water storage and it should be connected to the boiler by 28mm diame­ter flow and return piping. The pipes should not exceed 7.8 meters (25ft) in length and cylinder and pipework should be fully lagged. The shorter the run of pipe work the more effective the water heating.
Fig.8
WARNING: DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE SPIN VALVE AT THE FRONT OF THE STOVE
There must be no gate valves on this circuit and it must have an expansion pipe exhausting to atmos­phere. Cylinder and pipe work should be lagged to minimise heat loss.
This diagram illustrates the basic principal of water heating systems and must not be regarded as a working drawing.
PLUMBING
INTERLINK SYSTEM
Fig. 9
Page 11
11
Fig.10
DHW PLUMBING SYSTEM in the unlikely event that the appliance is not operat-
ing in freezing conditions the water must be drained from the boiler to prevent frost damage.
DOMESTIC HOT WATER SYSTEM (DHW MODEL ONLY)
The DHW Model must be connected to a gravity system. Care should be taken to ensure that the domestic hot water installation is correctly installed and that it complies with all relevant codes of prac­tice. If this appliances is being connected to an exist­ing system, it is strongly recommended to check the following:
(a) That the system is sound. (b) That the pipe work is adequately insulated. (c) Are there any modifications necessary to make the domestic hot water system more efficient.
SAFETY VALVE
A non-adjustable 3 bar safety valve must be fitted to the primary flow pipe adjacent to boiler connection ensuring that any discharge will not create a hazard to occupants or cause damage to electrical compo­nents or property.
NOTE: We strongly advise the use of pipe lagging if the installation is likely to be exposed to situations where the temperatures will drop to a level consis­tent with frost.
Only competent personnel should be employed to carry out any work on your domestic hot water sys­tem.
DIRECT DOMESTIC CYLINDER
A 227 Litre (60 Gallon) direct domestic cylinder can be connected to this cooker using copper or stain­less steel 28mm O.D. (1”) flow & return pipes. We recommend that the cylinder is lagged along with the pipework. We do not recommend the use of a direct cylinder in areas where there is a high concentration of lime or minerals in the water.
INDIRECT DOMESTIC CYLINDER
A 227 Litre (60 Gallon) indirect domestic cylinder can be connected to this cooker using copper or stainless steel 28mm O.D (1”) flow and return pipes. We recommend that the cylinder is lagged along the pipework.
INJECTOR TEE
Where the gravity and central heating circuits join together to return to the stove we recommend the use of an injector tee connection, situated as close to the unit as possible. This type of tee encourages a stable flow of water through both circuits and helps to prevent priority being given to the stronger flow, which is most commonly the pumped central heating circuit.
WATER CIRCUIT TEMPERATURE
The return water temperature should be maintained at not less than 40°C so as to avoid condensation on the boiler and return piping. Fitting a pipe thermo­stat to the flow pipe of the gravity circuit and wiring it into the pump control will ensure rapid circulation of the hot water.
In some circumstances it may be possible to over­heat the appliance and the water inside will boil. This will be evident by the sound of a knocking noise coming from the appliance and pipes around the house. If this occurs close off all air controls and manually start the central heating pump if fitted. One radiator on the heating circuit should be uncon­trolled to act as a heat leak in the event that the appliance overheats and has nowhere to discharge a build up of hot water should the heating circuit be satisfied. Be aware that steam and boiling water willl be expended from any open vent from the heat­ing system probably in the roof space at the expan­sion tank.
Page 12
PIPE THERMOSTAT
The fitting of a pipe thermostat to the flow pipe is essential in order to activate the water circulation pump when the water reaches the selected temperature.
When the water temperature falls below the select­ed temperature the pipe thermostat will cut off the water circulation pump in order to allow the boiler to recover.
12
Fig.11
HANDOVER
On completion of the installation allow a suitable period of time for any fire cement and mortar to dry out, when a small fire may be lit and checked to ensure the smoke and fumes are taken from the stove up the chimney and emitted safely to the atmosphere. Do not run at full output for at least 24 hours.
Ensure that the operating instructions for the stove are left with the customer. Ensure to advise the cus­tomer on the correct use of the appliance with the fuels likely to be used on the stove and warn them to use only the recommended fuels for the stove.
Advise the user what to do should smoke or fumes be emitted from the stove. The customer should be warned to use a fireguard to BS 6539 in the pres­ence of children, aged and/or infirm persons.
OPERATING INSTRUCTIONS
SUITABLE FUELS
COAL, ANTHRACITE, PEAT, WOOD SYNTHETIC LOGS, OR OTHER FUELS. “Never use gasoline” gasoline type lantern fuel, kerosene, charcoal lighter fluid or similar liquids to start or ‘freshen up’ a fire in this heater. Keep all such liquid well away from the heater at all times. Operate stove only with fuelling door closed. This heater is hot whilst in operation. Keep children, clothing and furniture a safe distance away.
Fig.12
Page 13
LIGHTING
1. Before lighting the stove, ensure that any build up of ashes in the fire box has been removed and that the ashpan has been emptied.
2. Open the firebox and cover the grate with crumpled pieces of paper.
3. Lay pieces of kindling on top of the paper towards the back of the fire box.
4. Open the primary air inlet by turning the spin valve at the front of the stove anticlockwise.
5. Open the secondary air control by sliding the control knob located over the top of the fire door to the left.
6. Ignite the paper and close the firedoor.
7. When the kindling is well alight, open the fire door and add more kin­dling of a larger size to sustain the fire. Close the firedoor.
8. Never use inflammable liquid i.e. gasoline, petrol paraffin etc. to
start or “freshen up” afire in this heater.
9. When a hot bed of fuel is established, add the normal fuel and adjust the spin valve to the required setting.
10. To shut the fire down, do not add fuel, make sure that the firedoor is properly closed and that the primary and secondary air controls are all in the closed position. Cutting off the air supply will reduce the heat output.
11. Following a prolonged shutdown of the appliance perhaps after the summer break, ensure the flueway is free from obstruction prior to re-lighting.
Re-fuelling -Open the firedoor and reload, close the firedoor.
13
Before lighting the stove check with the installer that the installation work and commissioning checks described in the installation instructions have been carried out correctly and that the chimney has been swept clean, is sound and free from any obstructions. As part of the stove’s handover the installer should have demonstrated how to operate correctly.
Page 14
IMPORTANT NOTES
Now that your Stanley Solid Fuel Stove is installed and no doubt you are looking forward to many comforts it will provide, we would like to give you some tips on how to get the best results from your stove.
1. We would like if you could take some time to read the operating instructions/hints, which we are confident, will be of great benefit to you.
2. Do not burn fuel with a high moisture content, such as a damp peat or unseasoned timber. This will only result in a build up of tar in the stove and in the chimney.
3. Clean the flue-ways of the stove every week and ensure that there are no blockages. Check flueways before lighting especially after a shut down period. Please refer to manual for instructions.
4. Before loading fresh fuel into the firebox, riddle fully to remove all ashes this will allow better and cleaner burning. See Re-Fuelling Section.
5. Never allow a build up of ashes in the ash pan, as this will cause the grate to burn out prema­turely. Empty the ashpan when re-fuelling.
6. Allow adequate air ventilation to ensure plenty of air for combustion.
7. Do not use as an incinerator burning rubbish/household waste.
8. Do not leave ash-door open for long periods as this will over heat the unit causing unnecessary damage. Close the ash door between removing and replacing the ashpan.
9. Clean the chimney at least twice a year.
10. Burning soft fuels such as timber and peat will stain the glass. Regular cleaning will prevent per­manent staining. Clean with soapy water when cool.
11. Keep all combustible materials a safe distance away from unit, please consult manual for clear­ance to combustible table.
12. For safety reasons never leave children or the elderly unaccompanied while stove is in use. Use a fire guard.
13. Avoid contact with unit when in use as stove reaches very high operating temperatures.
14. This appliance should be regularly maintained by a competent service engineer.
Use only replacement parts recommended by Stanley. Making unauthorised modifications, or using unauthorised parts will invalidate your guarantee and may cause damage or injury.
FUEL CALORIFIC VALUES - SOLID FUELS
Anthracite 25-50mm C.V.: 8.2kW/Kg 14,000 BTUs/lb
House Coal 25-75mm C.V.: 7.2kW/Kg 12,000 BTUs/lb
Timber - Firebox size C.V.: 5.0kW/Kg 8,600 BTUs/lb
Peat Briquettes C.V.: 4.8kW/Kg 8,300 BTUs/lb
14
AN ODOUR WILL EMIT FROM STOVE ON FIRST FIRING, WHEN FIRE REACHES MAXIMUM TEMPERATURE OVER A NUMBER OF HOURS THE ODOUR WILL SUBSIDE. IT IS BEST ADVISED TO OPEN WINDOWS DURING THIS PERIOD.
THE ODOUR IS UNPLEASANT BUT NOT TOXIC. YOU MAY WISH TO VACATE THE ROOM WHILE THE PAINT CURES.
Page 15
15
Fig.13
Fig.14
PRIMARY AIR SETTINGS - STANDARD
The spin valve (Part No. 12), located at the bottom end of the door controls the primary air supply to the stove. For maximum heat output and burn rate rotate the spin valve (Part No. 12) fully in an anti­clockwise direction and for a minimum heat output and burn rate rotate the spin valve clockwise until fully closed. You will soon learn spin valve settings to best suit your requirements.
PRIMARY AIR SETTINGS - OUTSIDE AIR
The spin valve will be locked closed. The primary air can now be controlled using the knob on the top of the rear of the stove (See Fig.15). The knob can be rotated from setting 0 - 6, 0 is outside air inlet closed and 6 is maximum air setting.
IMPORTANT: The first few fires should be relatively small to permit the refractory to set properly and to season the stove.
RECOMMENDED FUELS
All fuels should be stored under cover and kept as dry as possible prior to use.
This appliance has been tested using seasoned wood logs and manufactured briquetted smokeless fuel (Ancit) for closed appliances, sized between 20g and 140g. Other fuels are commercially avail­able and may give similar results. Wood logs up to 406mm long are suitable. All fuels should be stored under cover and kept as dry as possible prior to use. Do not use fuels with a Petro-coke ingredient as this may cause the grate to overheat, causing damage. Reduced outputs will result when fuels of lower calorific values are used. Never use gasoline or gasoline type lantern fuel, kerosene, charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater. Keep all such liquid well away from the heater at all times. Operate the stove only with the fuelling door closed except for re-fuelling.
This stove has obtained HETAS Ltd approval for burning natural and manufactured smokeless fuels and wood logs only as detailed in recommended fuels below. HETAS Approval does not cover the use of other fuels either alone or mixed with the rec­ommended fuels listed, nor does it cover instructions for the use of other fuels.
Fig.16
Fig.15
AIR WASH SETTINGS
The following settings should be observed for the Air Wash Shutter (Fig.16) when burning the speci­fied fuels.
Note: Always use operating tool when opening and closing the Air Wash Shutter.
OPEN When burning coal, timber or peat. CLOSE When burning anthracite and
smokeless fuels.
SECONDARY AIR / SYSTEM CONTROL (Dry Model Only)
The Tara Non Boiler has a Secondary Air System located at the top under the roof baffle and connect­ed to an air feed ducting on the right hand side and controlled by a push pull slider assembly, located at the bottom right hand side.
Open
Closed
Page 16
WARNING:
Properly installed, operated and maintained this stove will not emit fumes into the dwelling. Occasional fumes from de-ashing and re-fuelling may occur. However, persistent fume emission is potentially dangerous and must not be tolerated. If fume emission does persist, then the following immediate action should be taken -
(a) Open doors and windows to ventilate room.
(b) Let the fire out or eject and safely dispose of
fuel from the stove.
(c) Check for flue or chimney blockage and clean
if required.
(d) Do not attempt to relight the fire until the cause
of the fume emission has been identified and corrected. If necessary seek expert advice.
The most common cause of fume emission is flue­way or chimney blockage. For your own safety these must be kept clean at all times.
WARNING: Failure to comply with the Installation and Operating Instructions outlined above may result in carbonmonoxide entering the house rather than being drawn up the chimney.
bustion chamber. Add fuel to the fire, close fire door and re-set spin valve to required setting.
DE-ASHING
Never allow ashpan to over fill as it will cause dam­age to fire fence. When ash build-up becomes excessive in the fire chamber riddle the fire until all dead ash has fallen through to the ashpan.Open the front door (Part No.2) and remove ashpan (Part No.17) using the operating tool (Part No.15). Close the front door (Part No. 2). When the ash is dis­posed of, replace the empty ashpan.
OPERATION
To operate the Secondary Air, push to open and pull to close. Open secondary air slider only when the fire is established.
Note: Close off the secondary air for overnight burn.
OVERNIGHT BURNING
To achieve an overnight or a low burn rate, close the Air Wash Shutter fully, close the front spin valve fully or leave it open about half a turn depending on draught conditions. If the fuel load is too small or the draught too strong the spin valve may need to be closed even further to sustain the low burn rate.
REMEMBER: Coal gases are toxic.
RE-FUELLING
Riddle the fire by connecting the grate operating tool onto the rocker connection located at the bottom front of the stove, then gently pull and push the rock­er arm until all dead ash has fallen through into the ashpan. Before opening the door, open the spin valve by turning it anti-clockwise, as this will help to eliminate any smoke or fly ash resident in the com-
Fig.17
DISPOSAL OF ASHES
The ashpan must be emptied every day.
If ashes are allowed to build up to grate level the fire­box insert could be damaged by overheating. We recommend that you remove ashes after you have riddled the fire.
Ashes should be placed in a metal or other non­combustible container with a tight fitting lid. The closed container of ashes should be placed on a non-combustible material, pending final disposal. If ashes are buried in soil, or otherwise dumped they should be retained in the closed container until they are thoroughly cooled.
Fig.18
16
Page 17
TO CLEAN CHIMNEY OUTLET (Boiler Model)
Remove baffle underneath the boiler cross flow chamber by lifting it upwards and pulling it outwards and insert cleaning brush. Replace baffle before lighting fire.
When fitted correctly the baffle should fall forward to close onto the bottom of the boiler. The appliance will not function correctly with this baffle misaligned or missing.
Fig.19
17
Replace any damaged parts and replace firebox insert and grate ensuing that the pull rod is inserted back through the opening on the left hand side of the boiler and also through the hole on the front panel.
Replace the pull rod knob and the 3 fire fence before relighting.
FIRE SAFETY
To provide reasonable fire safety, the following should be given serious consideration.
1. Do not over fire the stove.
2. Overfiring will also damage painted or enamel finish.
3. Install a smoke detector in the room.
4. A conveniently located class “A” fire extin­guisher to contend with small fires resulting from burning embers.
5. A practical evacuation plan.
6. A plan to deal with a chimney fire as follows:-
(a) Notify the fire department. (b) Prepare occupants for immediate
evacuation.
(c) Close all openings into the stove.
(d) While awaiting the fire department watch
for ignition to adjacent combustibles from overheated stove pipe or from embers or sparks from the chimney.
VITREOUS ENAMEL CLEANING
General cleaning must be carried out when the stove is thoroughly cool.
If this stove is finished in a high gloss vitreous enamel, to keep the enamel in the best condition observe the following tips:
1. Wipe over daily with a soapy damp cloth, followed by a polish with a clean dry duster.
2. For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel.
3. Only products recommended by the Vitreous Enamel Association, these products carry the Vitramel label.
(Non Boiler Model)
Remove the fire bricks on each side. Remove sec­ondary air pipe by removing the retaining screw on left hand side. Remove the baffle by first lifting it up and pulling it forward, then rotate it down around the baffle supports. Replace the baffle, the firebricks and the secondary air pipe before the fire is lit. Ensure the secondary air pipe is sealed to the right hand side with fire cement.
TO REPLACE FIRE GRATE
Remove the 3 fire fence at the front of the stove, unscrew the pull rod knob from the pull rod bar locat­ed at the front of the stove in the bottom left hand corner. Pull the circular firegrate in the centre of the stove upwards to the right as far as is possible. Then twist the circular firegrate so that the front edge is lifted up and the back edge is moved down through the hole in the firebed insert. Push the cir­cular firegrate down through the firebed insert.
The circular firegrate can then be removed by push­ing it to the rear of the stove to relieve the pull rod bar and then putting it out under the firebox insert. The firebox insert can be removed by fitting the fire­box insert up at the front, then rotate the firebox insert until it can slide diagonally forward through the opening in the front panel.
Page 18
18
4. DO NOT USE ABRASIVE PADS OR OVEN
CLEANSERS CONTAINING CITRIC ACID ON ENAMELLED SURFACES. ENSURE THAT THE CLEANSER MANUFACTUR­ERS INSTRUCTIONS ARE ADHERED TO.
GLASS CLEANING
The glass will self clean when there is sufficient heat generated by the burning fuel. If a build-up of cre­osote occurs on the glass it may be due to draft con­ditions, poor quality fuel or very low burning for a long time. It is best to clean the glass when it is thoroughly cooled.
Fig.20
GLASS REPLACEMENT
(a) Open the front door fully. (b) Remove the four corner screws and clips
and carefully remove the broken glass. (c) Clean the glass recess in the door. (d) Attach adhesive thermal tape to the
perimeter of the replacement glass. (e) Place the thermal tape side of the glass into
the door recess and replace the four corner
clips. (f) Tighten screws. (g) Replace glass only with ceramic glass 5mm
thick.
DATA PLAQUE POSITION
The data plaque is positioned at the back of the stove, See Fig.21.
Fig.21
CO ALARM
Waterford Stanley recommend the fitting of a CO Alarm in the same room as the appliance, this is a requirement under UK Building Regulations. Further guidance on the installation of a carbon monoxide alarm is available in BS EN 50292:2002 and from the alarm manufacturers instructions.
Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance of the appliance and chimney system.
WARNING:-
If the CO Alarm sounds unexpectedly:-
1. Open Doors and windows to ventilate the room and then leave the premises.
2. Let the fire go out.
Page 19
TARA HPB EXPLODED VIEW
1. OPERATING TOOL - B00009DZZ
2. SPIN VALVE - B00012AZZ
3. LEG - B00077BZZ
4. HOB - B00209AZZ
5. HOB BLANKING PLATE - B00210AZZ
6. SIDE PANEL - B00211BZZ
7. FRONT PANEL - B00257GZZ
8. FRONT DOOR - B00258BZZ
9. ASHTRAY FRONT - B00259AZZ
10. DOOR GLASS CLIP - F00003AXX
11. ASHPAN - F01076AXX
12. PULL ROD BOX - F01077AXX
13. TARA BOILER ASSY - L00125AXX
14. SECONDARY AIR WASH SHUTTER - Q00247AXX
15. AIR WASH PLATE - Q00564AXX
16. FLUE BLANKING PLATE - Q00624AXX
17. GLASS WINDOW - T00009BXX
18. DOOR HANDLE (LONG) - U00009AXX
19. 2” HINGE - U00010AXX
20. AIR WASH KNOB - U00077AXX
21. DOOR HANDLE AXLE - V00022BXX
22. DOOR LATCH - V00023AXX
23. SPACER TO DOOR HANDLE - V00035AXX
24. SPRING (RS 751-584) - V00151AXX
25. AIR WASH SHUTTER SHAFT - V00158AXX
26. M8 X 44 SPINDLE - V00763AXX
27. PULL ROD - V00992AXX
28. SPLIT PIN 3/32” X 1” - W00608AXX
29. WASHER DOUBLE COIL SPRING 5/16” - W00801AXX
30. TOP BAFFLE - Z00017AXX
31. FIRE FENCE - Z00020AXX
32. GRATE - Z00036AXX
33. GRATE SUPPORT - Z00046AXX
19
Page 20
TARA NB EXPLODED VIEW
1. OPERATING TOOL - B00009BZZ
2. SPIN VALVE - B00012AZZ
3. FLUE BLANKING PLATE - B00064AZZ
4. LEG (LONG) - B00077BZZ
5. HOB - B00209AZZ
6. HOB BLANKING PLATE - B00210AZZ
7. SIDE PANEL - B00211BZZ
8. FRONT PANEL - B00257JZZ
9. FRONT DOOR - B00258CZZ
10. ASHTRAY FRONT - B00259AZZ
11. DOOR GLASS CLIP - F00003AXX
12. ASHPAN - F00221AXX
13. PULL ROD BOX - F00223BXX
14. DRY SHELL - F00238DXX
15. WS PLUG - F00506AXX
16. RATING PLATE BRACKET - F00879BXX
17. BLANKING PLATE - F01029AXX
18. SIDE BRICK - H00070BXX
19. TARA BRICK FOR DRY SHELL - H00197AXX
20. SERIAL NUMBER PLATE - N00234BXX
21. DATA PLAQUE - N00442AXX
22. OSA DAMPER GASKET - P00101AXX
23. SECONDARY AIR WASH SHUTTER - Q00247AXX
24. DRY SHELL PROTECTION PLATE - Q00250AXX
25. AIR WASH PLATE - Q00564AXX
26. GLASS WINDOW - T00009AXX
27. DOOR HANDLE LONG - U00009AXX
28. SECONDARY AIR CONTROL - U00018AXX
29. AIR WASH KNOB - U00077AXX
30. HINGE - U00153AXX
31. DOOR HANDLE AXLE - V00022BXX
32. DOOR LATCH - V00023AXX
33. SPRING (RS 751-584) - V00151AXX
34. AIR WASH SHUTTER - V00158AXX
35. SECONDARY AIR DAMPER - V00161AXX
36. SECONDARY AIR TUBE - V00162AXX
37. PULL ROD - V00393AXX
38. BADGE - V00730BXX
39. M8X44 SPINDLE - V00763AXX
40. FIRE BOX INSERT - Z00016BXX
41. FLUE CLEANING PLATE - Z00019BXX
42. FIRE FENCE - Z00020AXX
43. GRATE - Z00025BXX
20
Page 21
TARA DHW EXPLODED VIEW
1. OPERATING TOOL - B00009BZZ
2. SPIN VALVE - B00012AZZ
3. LEG - B00077AZZ
4. HOB - B00209AZZ
5. HOB BLANKING PLATE - B00210AZZ
6. SIDE PANEL - B00211BZZ
7. FRONT PANEL - B00257HZZ
8. FRONT DOOR - B00258BZZ
9. ASHTRAY FRONT - B00259AZZ
10. DOOR GLASS CLIP - F00003AXX
11. ASHPAN - F00221AXX
12. PULL ROD BOX - F00223BXX
13. DRY SHELL - F00238DXX
14. TARA DHW BOILER - F00948AXX
15. SIDE BRICK - H00070BXX
16. TARA BRICK FOR DRY SHELL - H00197AXX
17. SECONDARY AIR WASH SHUTTER - Q00247AXX
18. DRY SHELL PROTECTION PLATE - Q00250AXX
19. AIR WASH PLATE - Q00564AXX
20. FLUE BLANKING PLATE - Q00624AXX
21. GLASS WINDOW - T00009BXX
22. DOOR HANDLE (LONG) - U00009AXX
23. 2” HINGE - U00010AXX
24. KNOB SECONDARY AIR DAMPER - U00018AXX
25. AIR WASH KNOB - U00077AXX
26. DOOR HANDLE AXLE - V00022BXX
27. DOOR LATCH - V00023AXX
28. SPACER TO DOOR HANDLE - V00035AXX
29. SPRING (RS 751-584) - V00151AXX
30. AIR WASH SHUTTER SHAFT - V00158AXX
31. SECONDARY AIR DAMPER - V00161AXX
32. SECONDARY AIR TUBE - V00162AXX
33. PULL ROD - V00393AXX
34. M8 X 44 SPINDLE - V00763AXX
35. SPLIT PIN //32” X 1” - W00608AXX
36. WASHER DOUBLE COIL SPRING 5/16” - W00801AXX
37. BRASS NUT FLANGED - W00910AXX
38. FIRE BOX INSERT - Z00016BXX
39. FIRE FENCE - Z00020AXX
40. GRATE - Z00025BXX
21
Page 22
22
INSTALLATION CHECK LIST
Flue System
1. Minimum Flue Height of 4.5 metres (15 feet).
2. Appliance should be connected to a minimum of 1.8 metres (6 feet) of 150mm (6”) flue pipe with a horizontal run not exceeding 150mm (6”).
3. Appliance should be connected to a chimney of less than 200mm (8”) in diameter (otherwise the chimney must be lined with a 6” flue liner).
4. The chimney venting position must be above the main ridge of the roof or adjacent outside obstructions.
5. The chimney serving this appliance should not serve any other appliance.
6. Access should be provided to the chimney serving the appliance to allow for cleaning.
Location
7. Clearance to combustible materials must be adhered to as described in the Clearance to Combustible section.
8. The stove must be installed on a floor protector that covers the area under the stove and extends 18” to the front & 8” to the sides and back.
Plumbing
9. Appliance must be connected to a gravity circuit using 1” ID flow & return piping.
10. The length of pipes from the cylinder to the cooker should not exceed 7.8 metres (25
1
/2
feet).
11. A circulation pump should be fitted to the return pipe of the radiator circuit and controlled by a pipe stat fitted to the flow pipe of the gravity circuit to the cylinder. (Not applicable to DHW Model).
Ventilation & Combustion Air Requirements
12. The room in which the appliance is located should have an air vent of adequate size to support correct combustion (see Ventilation & Combustion Air Requirement Section for specific details).
Tick
Page 23
23
NOTES
Page 24
NOTES
REV:002 DP 150309
N00154AXX
Manufactured by
Waterford Stanley Ltd.,
Unit 401-403, IDA Industrial Estate, Cork Road,
Waterford, Ireland.
Tel: (051) 302300 Fax (051) 302315
www.waterfordstanley.com
24
Loading...