Stanley MAEVE Operation, Installation & Servicing Instructions

Page 1
MAEVE
STOVE RANGE
Operation, Installation & Servicing Instructions
IMPORTANT
Please read these instructions carefully and keep them in a safe place.
They will be needed when servicing this appliance.
STOVES REQUIRED TO HAVE THE GRILL OPTION MUST BE
STANDARD FLUE MEDIUM MAEVE STOVE WITHOUT GRILL
STANDARD FLUE MEDIUM MAEVE STOVE WITH GRILL
Country AT BE DK FI FR DE GR IS IE
Natural Gas
***** *
LPG **** **
Country IT LU NL NO PT ES SE GB
Natural Gas *** **** LPG * ******
WARNING
Do not attempt to burn rubbish in this stove. This stove must only be operated with the door secured firmly in position. The outer casting of this stove will become hot whilst in operation, it is therefore recommended that the appliance be guarded to protect the young and infirm using a suitable fire guard. Ensure that fabrics such as curtains are not positioned above or near to the stoves outer casting.
KEEP THESE INSTRUCTIONS IN A SAFE PLACE
Page 2
GAS CAT. GAS TYPE PRESSURE INPUT kW COUNTRY
AT, DK, ES,
I2 H G20 20MB 6.60 Gross FI, GB, IE, IT,
PT, SE.
I2L G25 25MB 6.00 Gross NL
I2E+ G20 20MB 5.94 Nett BE, FR
G25 25MB
ES, IT, IE
I3+ G30 29MB 6.25 Gross GB, PT
G31 37MB 5.62 Nett BE, FR
I3B/P G30 29MB 6.25 Gross DK, FI, IS
G31 NL, NO, SE
TECHNICAL SPECIFICATION
MEDIUM
INJECTOR SIZE NG 400
LPG 170
AERATION SIZE Ø
NG 11mm
Ø
I
2L 8mm
Ø
LPG 15.5 x 2
EFFICIENCY CLASS II
FLUE T.T.B SENSOR 100
o
C
FLUE OUTLET SIZE Ø
127mm
INLET CONNECTION SIZE Ø
8mm
150
150
225
1007
127
50
470
1
Fig.1
Fig.2
Fig.3
Fig.4
Fig.5
Fig.6
176
Page 3
1. GENERAL
1.1 Installation and servicing must only be carried out by a competent person.
1.2 In all correspondence, please quote the appliance type and serial number which can be found on the data badge located at the rear of the stove.
1.3 Ensure that curtains are not positioned above the stove, and that there is at least a clearance of 300mm between the sides of the stove and any curtains.
1.4 If any cracks are observed in the glass panel, do not use the appliance until the glass has been replaced.
2. LIGHTING THE STOVE
2.1 Ensure the control is pointing to the off
2.2 Depress control knob and rotate anti­clockwise until a click is heard and the
knob is pointing at the ignition symbol (
*
),
the pilot should now be lit.
2.3 Depress for 5 to 10 seconds and then release, the pilot should remain alight. If the pilot does not light, repeat the above procedure.
2.4 If it will not light after repeated attempts, contact the retailer or installer from whom the appliance was purchased.
2.5 The appliance may now be turned to the high position to ignite the main burner, then controlled between high and low as desired.
3. TURNING THE STOVE OFF
3.1 Depress the control knob and turn clock­wise until the knob is pointing at the off
NOTE: THE YELLOW FLAMES WILL APPEAR WHEN THE FIRE HAS GAINED SUFFICIENT HEAT - TYPICALLY 10 TO 20 MINUTES.
IF THE APPLIANCE IS EXTINGUISHED OR GOES OUT IN USE, WAIT 3 MIN­UTES BEFORE ATTEMPTING TO RE­LIGHT THE APPLIANCE.
4. CLEANING THE STOVE
4.1 Remove the ceramic coals and place on a dry, clean surface. Remove the front coal ceramic, please handle with care.
4.2 Clean the flame baffle ceramic piece and burner using a vacuum cleaner with soft brush attachment, ensure all debris are removed from the burner ports.
4.3 Replace the ceramics by referring to Section 5.
5. ARRANGEMENT OF FUEL-BED COM­PONENTS
The major ceramic components can be found inside the firebox, remove the cast iron door and remove all the protective packaging from these components.
NOTE: THE CAST IRON DOOR IS HEAVY, TAKE EXTREME CARE WHEN HANDLING.
The loose coals should be arranged as specified in the following steps, care should be taken to ensure that there is sufficient space between the coals to allow flames to pass through.
5.1 Place the flame baffle onto the shelf at the rear of the tray and push up against the rear ledge, see Fig 11.
5.2 Locate the front coal moulding in front of the flame baffle ensuring that the end legs sit flat against the burner skin, see Fig 12.
5.3 Place three large coals on the front coal so that they lean against the flame baffle, and four large coals on the flame baffle so that they sit on the fingers, see Fig 13.
5.4 Place two small coals at each end of the front coal so that they lean against the flame baffle, and a further two large coals on the flame baffle, one at each end, see Fig 14.
5.5 Place five small coals along the rear of the flame baffle, resting against the rear ledge, see Fig 15.
NOTE: ENSURE THAT THE COALS ARE POSITIONED, AS DETAILED ABOVE. ONLY USE THE CORRECT AMOUNT OF COALS, AS SPECIFIED IN THE DIA­GRAMS.
INSTRUCTIONS FOR USE
2
position (
).
position (
).
Page 4
6. THE FLAME FAILURE DEVICE
6.1 This is a safety feature incorporated in all WATERFORD fires which automatically switches off the gas supply if the pilot light goes out and fails to heat the thermo­couple.
7. 'RUNNING IN'
7.1 The surface coating on the coals used in your WATERFORD fire will "burn off" dur­ing the first few hours of use, producing a harmless and temporary odour. This will disappear after a short period of use. If the odour persists, ask your installer for advice.
8. SERVICING
8.1 The fire must be serviced every 12 months by a qualified Gas Engineer. In all correspondence, always quote the appli­ance type and the serial number, which may be found on the data badge.
9. ENAMEL CLEANING
General cleaning must be carried out when the stove is cool.
If this stove is finished in a high gloss vitreous enamel, to keep the enamel in the best condition observe the following tips:
9.1 Wipe over daily with a soapy damp cloth, followed by a polish with a clean dry duster.
9.2 For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel.
9.3 Use only products recommended by the Vitreous Enamel Association, these prod­ucts carry the vitramel label.
9.4 DO NOT USE ABRASIVE PADS OR
OVEN CLEANSERS CONTAINING CIT RIC ACID ON ENAMELLED SURFACES. ENSURE THAT THE CLEANSER MANU FACTURERS INSTRUCTIONS ARE ADHERED TO.
3
ASSOCIATION
Page 5
NOTE: IF IT IS INTENDED TO FIT THE STOVE INTO AN EXISTING BRICK CHIMNEY, A 127mm LINER MUST BE USED.
2.2 The minimum effective height of the flue or chimney must be 3 metres (10ft).
2.3 The chimney or flue must be free from any obstruction. Any damper plates should be removed or secured in the fully open posi­tion, and no restrictor plates should be fit­ted.
2.4 The chimney should be swept immediately prior to the installation of the appliance. However, where it can be seen that the chimney is clean and unobstructed through-out its entire length, it need not be swept.
3. VENTILATION & COMBUSTION AIR REQUIREMENTS
This stove has a heat input of less than 7 kW and therefore does not normally require any additional ventilation. However, consideration must be given to the local rules in force.
3.1 Any air vent must either be connected direct to an outside air supply or to adja cent rooms having a permanent vent to the outside.
3.2 If there is another combustion appliance fitted in the same or adjacent room, it will be necessary to refer to the rules in force
to calculate the additional air supply.
3.3 If there is an air extraction fan fitted in the room or adjacent rooms where this appli­ance is fitted, additional air vents may be required to elleviate the possibility of spillage of products of combustion from the appliance/flue while the fan is in oper­ation. Refer to the rules in force.
3.4 Where such an installation exists, a test for spillage should be made with the fan or fans and other gas burning appliances in operation at full rate.
3.5 If spillage occurs following the above oper­ation, an additional air vent of sufficient size to prevent this occurrence should be installed.
4. INSTALLATION OF THE GAS SUPPLY
4.1 Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compati­ble.
IMPORTANT: ENSURE THAT THE APPLI ANCE IS CORRECTLY ADJUSTED FOR THE GAS TYPE AND CATEGORY APPLICABLE IN THE COUNTRY OF USE. REFER TO DATA BADGE AND TECHNI CAL SPECIFICATIONS AT THE FRONT OF THE BOOKLET.
FOR DETAILS OF CHANGING BETWEEN GAS TYPES, REFER TO SECTION 18.
1. SAFETY PRECAUTIONS
1.1 This appliance must be installed in accor­dance with the rules in force, and used only in a sufficiently ventilated space. Please read these instructions before installation and use of this appliance.
1.2 These instructions must be left intact with the user.
1.3 Do not attempt to burn rubbish in this appliance.
1.4 In your own interest, and those of safety, this appliance must be installed by com­petent persons in accordance with local and national codes of practice. Failure to install the appliance correctly could lead to prosecution.
1.5 Keep all plastic bags away from young children.
1.6 Do not place any object on or near to the stove. Allow adequate clearance above the stove. See Figs 7, 8, 9.
1.7 The stove is fitted with the Waterford Flue T.T.B System which will act to cut off the gas supply to the appliance in the event of incorrect operation of the flue. If the sys­tem acts to shut off the gas supply, this indicates that there is insufficient flue pull. Continued operation of this safety device means that there may be a serious prob­lem with the flue system, and this should be inspected by a qualified gas engineer.
Do not use the stove until an engineer says it is safe to do so.
The Waterford T.T.B System must not be tampered with. Use only genuine Waterford replacement parts when servic ing the system - refer to section 16.
2. FLUE AND CHIMNEY REQUIREMENTS
2.1 The chimney or flue system must comply with the rules in force, and must be a mini­mum of 127mm (5”) in diameter.
INSTRUCTIONS FOR INSTALLATION & SERVICING
4
Page 6
4.2 Ensure that the gas supply is capable of delivering the required amount of gas, and is in accordance with the rules in force.
4.3 Soft copper tubing and soft soldered joints can be used but must not be closer than 50mm (2”) to the base of the tray.
4.4 A means of isolating the gas supply to the appliance must be provided independent of any appliance control.
4.5 All supply gas pipes must be purged of any debris that may have entered, prior to con­nection to the appliance.
5. APPLIANCE LOCATION
5.1 This appliance must stand on a non-com­bustible hearth that is at least 12mm thick; the minimum dimensions are shown in Fig.7.
5.2 This appliance must not be installed in a room that contains a bath or shower.
5.3 This stove is not suitable for installation onto a combustible wall; all combustible materials must be removed from the area behind the stove.
5.4 Ensure that all clearances to combustible materials are complied with, in particular, there must be 50mm clearance to any rear wall and 150mm either side of the stove. If there is any combustible materials directly above the unit, a minimum distance of 225mm must be maintained. See Fig. 8 &
9.
NOTE: ATTENTION MUST BE GIVEN TO ALLOWING ADEQUATE CLEARANCE AT THE SIDES AND REAR OF THE STOVE, SO THAT A SPILLAGE TEST CAN BE PERFORMED.
6. INSTALLATION OF THE STOVE
6.1 Remove the outer carton, take the stove off the pallet, and remove the accessory car­ton. It will now be necessary to decide upon top or rear flue exit, the stove is fac­tory built for rear flue exit, but it may be changed to top exit by simply interchanging the flue spigot and blanking plate located on the stove.
6.2 Position the stove ensuring all appropriate clearances are observed.
NOTE: THE STOVE LID IS LOOSE, BE CAREFUL WHEN MOVING THE UNIT.
6.3 Having run the gas supply to the stove, PURGE THE SUPPLY PIPE, this is essen­tial to expel any debris that may block the
gas controls. Connect the gas supply to the 8mm-compression elbow at the right hand rear corner of the stove, see Fig.10.
6.4 Check the pull of the flue system by apply­ing a lighted smoke pellet to the flue sys­tem opening. If there is a definite flow into the chimney, proceed with the installation, if not; warm the chimney for a few minutes.
IF THERE IS STILL NO DEFINITE FLOW, THE FLUE MAY REQUIRE ATTENTION ­SEEK EXPERT ADVICE.
6.5 The flue system may now be connected to the stove, ensure that all joints are sealed with a suitable fire resistant sealant. It is also recommended that a physical reten­tion method be used at the flue spigot joint, self-tapping screws being favoured.
6.6 Connect a suitable pressure gauge to the test point located on the inlet fitting, and turn the gas supply on. Light the appliance and check all gas joints for possible leaks. Turn the appliance to maximum and check that the supply pressure is as stated on the data badge. Turn the gas off and replace the test point screw, turn the gas on and check the test point for leaks.
7. FUELBED ARRANGEMENT
The major ceramic components can be found inside the firebox, remove the cast iron door using the tool provided, and remove all the protective packaging from these components.
NOTE: THE CAST IRON DOOR IS HEAVY, TAKE EXTREME CARE WHEN HANDLING.
The loose coals should be arranged as specified in the following steps, care should be taken to ensure that there is suf­ficient space between the coals to allow flames to pass through.
7.1 Place the flame baffle onto the shelf at the rear of the tray and push up against the rear ledge, see Fig. 11.
7.2 Locate the front coal moulding in front of the flame baffle ensuring that the end legs sit flat against the burner skin, see Fig.12.
7.3 Place three large coals on the front coal so that they lean against the flame baffle, and four large coals on the flame baffle so that they sit on the fingers, see Fig.13.
7.4 Place two small coals at each end of the front coal so that they lean against the
5
Page 7
flame baffle, and a further two large coals on the flame baffle, one at each end, see Fig. 14.
7.5 Place five small coals along the rear of the flame baffle, resting against the rear ledge, see Fig. 15.
NOTE: ENSURE THAT THE COALS ARE POSITIONED, AS DETAILED ABOVE. ONLY USE THE CORRECT AMOUNT OF COALS, AS SPECIFIED IN THE DIAGRAMS.
7.6 Ensure that the fibreglass seal on the back of the door is intact, locate the door on the four studs and slide back to the firebox. Secure in place using the four brass dome nuts, do not overtighten the nuts. See Fig.17.
NEVER OPERATE THE STOVE WHEN THE DOOR IS REMOVED.
7.7 The top flue blanking plate is fitted to the stove (see Fig.16). If rear exit is chosen, top blanking plate must be kept in place.
8. COMMISSIONING
NOTE: LIGHTING INSTRUCTIONS ARE GIVEN IN SECTION 2 OF THE INSTRUC­TIONS FOR USE CHAPTER.
8.1 Close all openable doors and windows in the room, ignite the stove and operate on maximum for 5 minutes. Position a lighted smoke match just inside the draught divert­er opening and check that all the smoke is drawn into the opening, see Fig.18. If there is any doubt, run the stove for a fur­ther 10 minutes, and repeat the test.
8.2 If there are any extractor fans in the room of adjacent rooms, the test must be repeat­ed with the fans running on maximum.
IF SPILLAGE PERSISTS, DISCONNECT THE APPLIANCE AND SEEK EXPERT ADVICE.
SERVICING
9. GENERAL
9.1 This appliance must be serviced at least once a year by a competent person.
9.2 All principal components can be replaced without removing the stove from its instal­lation, although it is essential that the gas supply to the appliance is turned off at the isolation device before proceeding further.
10. PILOT UNIT
10.1 Turn the gas supply off at the isolation
6
device, remove the door and place to one side, carefully remove the ceramic fuelbed components.
10.2 Undo the pilot compression nut, remove the ignition lead from the electrode by gen­tly pulling downwards, and undo the ther­mocouple from the back of the gas valve , see Fig 19. Undo the main injector compression nut and pull pipe clear of the injector, see Fig 23.
10.3 Remove the two pozidriv screws which retain the burner and remove the burner unit, see Fig 20. Remove the two screws holding the heat shield in place to reveal the pilot unit.
10.4 Remove the two screws holding the pilot, and replace with a new unit. Replace the heat shield and secure the burner unit in position ensuring that the front of the tray sits on top of the tabs at the sides of the firebox. Reconnect the thermocouple, igni­tion lead and pilot pipe, turn the gas supply on and check the joints for any leaks.
10.5 Replace the ceramic components by refer ring to Section 7, replace the door and secure in position.
11. IGNITION LEAD AND PIEZO
Due to the method of manufacture, these components can only be replaced as an integral unit.
11.1 Turn the gas supply off at the isolation device. Pull the control knob off the gas valve spindle to reveal the piezo securing screw access holes. Using a small pozidriv screwdriver, remove the two screws, see diagram 26.
11.2 Pull the piezo body down and remove from the valve, disconnect the ignition lead from the electrode, see diagram 24.
11.3 Replace the assembly with a new unit, refit the screws and connect the ignition lead to the electrode. Check the operation of the new piezo, turn the gas supply on and with the pilot running, check for leaks, especial­ly where the two halves of the valve join. Replace the control knob.
NOTE: WHILST PERFORMING THE PIEZO REPLACEMENT, YOU WILL BE BREAKING THE SEAL BETWEEN THE TOP AND BOTTOM HALVES OF THE VALVE. ENSURE THAT THIS JOINT IS CORRECTLY SECURED AND LEAK TESTED.
Page 8
12. GAS FILTER
The gas filter is located just inside the inlet boss of the control valve, to replace the fil­ter, proceed as follows:
13.1 Turn the gas supply off at the isolation device. Undo the inlet compression nut and pull the pipe clear of the valve, see Fig
22. Prise the small retaining ring out and remove the filter.
13.2 Replace with a new filter and push into position ensuring that it sits on the shoul­der, replace the retaining ring and push into position.
13.3 Replace the inlet pipe, turn the gas supply on and check for leaks.
14. MAGNETIC SAFETY VALVE
14.1 Turn the gas supply off at the isolation device. Undo the thermocouple connec­tion from the back of the gas valve, pull the sensor leads clear and remove the inter­ruptor block.
14.2 Undo the mag valve retaining nut at the back of the control valve, gently tap out the mag valve and replace with a new unit. Replace the retaining nut and tighten, see Fig.22.
14.3 Reassemble the interrupter block and leads, secure in place with the thermocou­ple. Turn the gas supply on and check the entire pipework and valve joints for any leaks.
15. MAIN INJECTOR
15.1 Turn the gas supply off at the isolation device. Locate the main injector on the left hand side of the airbox, undo the compres­sion nut and pull the pipe clear of the injec­tor body, see Fig.23.
15.2 Rotate the injector until it is fully removed, and install the correct replacement injector. Reassemble and turn the gas supply on, check for any leaks.
16. WATERFORD FLUE T.T.B SYSTEM
If the stove has been installed in a restric­tive location, it may be necessary to remove the stove from its location.
16.1 Locate the sensor in the draught diverter opening, and gently pull the two wires off the terminals. Undo the two taptite screws and remove the sensor and the two plastic spacers, see Fig.24.
16.2 Refit a new sensor ensuring that the spac­ers are located between the sensor and the bracket, replace the two leads.
7
If it has been necessary to remove the stove, ensure that all disturbed gas joints are leak tested when reinstalled, and repeat the flue clearance test as detailed in section 9.
17. PRIMARY AERATION PLATE
17.1 Turn the gas supply off at the isolation device.
17.2 Locate the aeration plate on the underside of the airbox and remove the Nyloc nut, see Fig.25.
17.3 Remove the plate and replace with the cor­rect size, ensure that the hole(s) in the plate align correctly with the holes in the underside of the airbox and replace the Nyloc nut.
18. CHANGING BETWEEN GAS TYPES
In order to change between gas types, it will be necessary to change the following items:
* Pilot Unit * Control Valve * Injector * Aeration Plate * Data Badge
The relevant parts can be ordered from the parts list, always quote the appliance type
and serial number when ordering spare parts.
19. SHORT SPARES LIST
Component Medium
Stove
NG LPG
Pilot Unit P10036 P10037
Injector IN0007 IN0006
Aeration Plate ME1096 ME0834 Gas Valve GC0056** Flue Sensor EL0001
Sensor Lead EL0064
Interrupter GC0026
Mag Unit GC0016
Piezo and GC0062 Ignition Lead
Gas Filter GC0065
Rear Panel -
Flame Baffle CE0120
Front Coal CE0124 Coal Set CE0136
Note: The Control Valve is Factory preset for the correct gas type and model, a new unit will need to be ordered when changing between gas types.
Page 9
FAULT CAUSE POSSIBLE REMEDY
Pilot will not light Various Refer to Ignition
Functional Check 1
No Spark Various Refer to Ignition
Functional Check 2
Pilot will not stay lit or goes Various Refer to Flame Failure
out in use Check 2-
Stove goes out while Flue blockage Insufficient flue pull or
warming or in operation Sensor has been activated partial blockage - flue must be
checked by an engineer.
Uneven flame pattern Ceramics not Check front coal and flame
positioned correctly baffle are positioned as shown
in Section 7.
Coals not laid correctly The coals may require slight
adjustment, see Section 7.
Debris in burner Clean burner ports, refer to
ports Users Manual for guidance.
Blue Flame Warming Up Stove will burn blue until run
ning temperature has been
achieved - typically 20 minutes.
Aeration plate Ensure that the aeration plate
is tight and sits flat.
Insufficient gas pressure Check the gas pressure and
correct if necessary.
Airbox QC label removed Ensure QC seal on front of air-
box is correctly sealed.
Low flame height Blockage in supply pipe Disconnect pipe and purge,
ensure no debris has entered
the stove pipework.
Blocked gas filter Replace filter - refer to
Section 12
Insufficient gas pressure Check the gas pressure and
correct if necessary.
Empty supply tank or LPG only - ensure adequate
clylinder supply of gas in cylinders.
Short pilot flame length (see Insufficient gas Check the gas pressure and
diagram 26) pressure correct if necessary.
Blocked pilot flame Replace Unit - refer to section 10
IGNITION FUNCTIONAL CHECK 1
PILOT WILL NOT LIGHT
Ensure there is no debris around the pilot assembly e.g. coal, soot, etc
which could short the spark, clean the area.
There is a blockage in the system, check the inlet test point, the mag
seating, valve and pilot filter.
Operate the valve.
Is there a spark?
Is the control being
operated correctly?
Consult users book
and retry
Will the pilot light
with a match?
Is the gas turned on to
the appliance?
Check isolation tap and
gas meter, retry
Correct and retry.
Is the gas pressure
correct?
Has the system got any
air in it?
Purge the gas pipes
and retry.
GO TO THE NEXT
CHART IGNITION
FUNCTIONAL CHECK
SYSTEM OK
Ensure gap between
electrode and thermo-
couple is 3.5mm and
retry. If the gap is OK
then first change the
ignition lead and retry, if
still no good then change
the piezo.
Does the pilot light?
YES
YES
NO
NO
YES
YES
YES
NO
YES
NO
NO
NO
YES
NO
8
Page 10
IGNITION FUNCTIONAL CHECK 2
NO SPARK
Ensure there is no debris around the pilot assembly e.g. coal, soot, etc
which could short the spark, clean the area.
From Ignition Fault
Finding Chart Pt 2
Is the valve being
operated correctly?
Operate the valve to light
the pilot, does the valve
‘click?
Reset the electrode
gap, retry.
Correct and retry.
Has ignition lead
become detached or is
connection poor?
Remove the electrode
lead from electrode with
insulated pliers hold the
tip 3.5mm from the pilot
pipework, is there a
spark when the valve
‘click’?
Check for defective or damaged
control knob spindle or cam
operation. Check for correct
location of piezo components.
Correct and retry
Remove the electrode lead from
the piezo. Operate the valve.
Does a spark jump from the
piezo to the valve body?
Is the electrode wire
detachable from piezo in
the valve?
Replace the combined
lead and piezo, retry.
Replace the pilot unit
Replace the electrode
lead and retry
Replace the piezo and
retry.
Is the gap between
electrode and
Thermocouple 3.5mm?
Consult the users
instructions, retry.
NO
YES
YES
YES
NO
NO
NO
NO
YES
YES
YES
YES
NO
FLAME FAILURE FUNCTIONAL CHECK
PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USE
If the appliance goes out in use continually, this may mean that
the Waterford Flue T.T.B System has been activated. The
appliance should not be used until the cause has been found
and rectified.
Ensure there is no debris around the pilot assembly, e.g. coal,
soot, etc which could short the spark, clean the area.
Light the pilot and keep the control knob pushed in at least 10
seconds before letting go.
With the fire
running on full is
the gas at the
pressure started
on the data
badge?
Will pilot
stay alight?
With the pilot running
is the gas pressure as
stated on the data
badge?
Is the pilot flame
of the correct
length?
See Diagram 26
Problem is with
the pipework or
fittings which
lead to the fire.
Correct and
retry.
Is thermocouple
connection good
in back of valve
Run for 3 mins, turn off,
time interval until mag
unit shuts with a click.
Is this greater than 7
seconds?
Change the
pilot unit
Replace pilot unit
will pilot stay alight?
Change mag unit
Tighten the
connection and retry.
SYSTEM OK
Run for 3 mins,
turn off, time
interval until
mag unit shuts
with a click. Is
this greater than
7 seconds?
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
9
Page 11
AB
Medium 1007 470
A = 225mm B = 150mm
A = 50mm B = 150mm
10
DIAGRAMS
Fig.7
Fig.8
Fig.9
Page 12
11
Fig.10
Fig.11
Fig.12
Fig.13
Fig.15
Fig.14
COAL LAYOUT
Page 13
12
Fig.16
Fig.17
Fig.18
Page 14
13
Fig.19
Fig.21
Fig.20
Page 15
14
Fig.22
Fig.23
Fig.24
Fig.26
Fig.25
Page 16
Rev: 004 DP 070129
INSTALLATION CHECK LIST
Flue System
1. The flue height should not be less than 3 metres and no more than 11 metres.
2. If connecting to an existing chimney, the appliance should be connected to a 125mm (5”) diameter continuous, rigid or flexible flue pipe that terminates in excess of 0.6 metres from the nearest point on the roof measured vertically, and in excess of 2.3 metres measured horizontally.
3. If using an external flue, the appliance should be connected to a 125mm (5”) diameter rigid insulated flue pipe that terminates in excess of 0.6 metres from the nearest point on the roof measured vertically and in excess of 2.3 metres measured horizontally.
4. Any horizontal flue sections should not exceed 300mm (12”).
5. The chimney serving this appliance should not serve any other appliance.
6. A suitable flue terminal should be fitted at the flue termination point.
7. If using an internal flue or chimney, closure-clamping plates should be used to seal the top & bottom of the chimney.
8. Access should be provided to the chimney serving the appliance to allow for cleaning.
9. If the flue passes through a combustible wall, a twin wall insulated connector must be used and come flush to the external surface of the wall.
10. The flue should be capable of producing a continuous draught of between 0.06” w.g. during normal operation.
Location
1. Clearance to combustible materials must be adhered to as described in the Clearance to Combustibles section.
2. The stove should be installed as to allow adequate air circulation around the stove and to allow access for installation & servicing.
3. The stove must be installed on a non-combustible insulated floor protector that covers the area of 1007mm x 470mm around and under the stove.
Ventilation & Combustion Air Requirements
1. The room in which the appliance is located should have an air vent of adequate size to support correct combustion, including all other air using devices fitted in the same or adjacent rooms. (see Ventilation & Combustion Air Requirement Section for specific details).
Gas Supply
1. A 8mm rigid gas supply pipe must be used to connect directly from the gas meter to the stove. In the event of a number of appliances using the same supply pipe, the pipe size may need to be increased.
2. A shut off valve must be used to connect the gas supply as close as possible to the stove and should be accessible at all times.
3. A soundness test must be conducted to check all joints for gas tightness.
Tick
15
Manufactured by
Waterford Stanley Ltd.,
Unit 210, IDA Industrial Estate, Cork Road,
Waterford, Ireland.
Tel: (051) 302300 Fax (051) 302315
Loading...