Stanley Dura-Glide 2000, Dura-Glide 5300, Dura-Glide 3000, Dura-Glide 5200, ProCare 8300A Installation And Operation Manual

iQ Controller
Installation and Operation Manual
204144
INCLUDES INSTRUCTIONS FOR
DURA-GLIDE™ 2000/3000, 5200/5300,
DURA-GUARD™, DURA-STORM™, DURACARE™, *5400-SERIES,
*PROCARE™ 8300A, AND DURACARE 7500A TL-FBO
AUTOMATIC SLIDE DOOR SYSTEMS
*Refer to product-specic Installaon Manuals for Wiring Diagrams as they contain the relevant system wiring.
Stanley Part Number 204144
REV B 01.2019
www.stanleymobileapps.com
Copyright 2019, Stanley Access Technologies, LLC. Prohibition on Copying: Any unauthorized reproduction, disclosure or distribution of copies by any person of any portion of this work may be a violation of copyright law of the United States of America and other countries, could result in the awarding of statutory damages of up to $250,000 (17 USC 504) for infringement, and may result in further civil and criminal penalties. All rights reserved.
Table of Contents
General Description ........................................................................................................... 2
Intended Use ............................................................................................................................................. 2
Applicability ............................................................................................................................................... 3
Prerequisites .............................................................................................................................................. 3
Precautions ................................................................................................................................................3
Installation Instructions .................................................................................................... 3
Installing the iQ Controller ................................................................................................................. 3
Wiring Instructions ............................................................................................................ 3
Evaluating Power Requirements ........................................................................................................ 3
Connecting Main Power Wiring ........................................................................................................4
Connecting Accessories (As Applicable) ......................................................................................... 4
Tune-In Instructions ........................................................................................................... 4
Handing for FIS Only .............................................................................................................................. 5
Tuning In the iQ Controller Using the Controller Pushbuttons ........................................... 6
Tables ............................................................................................................................................................ 7
Final Tune-In Adjustments .................................................................................................................18
Attachments ..................................................................................................................... 19
Attachment 1 - iQ Controls and Indicators .................................................................................19
Attachment 2 - iQ System Wiring Diagram ...............................................................................21
Attachment 3 - iQ Terminal Block Connections TB1-TB7 ..................................................... 31
Attachment 4 - ANSI/BHMA and UL Compliance Requirements for Sliding Doors ..32
Attachment 5 - Troubleshooting Aid ............................................................................................ 35
Attachment 6 - iQ Troubleshooting Aid ...................................................................................... 36
Attachment 7 - Fine Tuning Slide Doors .....................................................................................37
1
GENERAL DESCRIPTION
Intended Use
This manual provides installaon instrucons, wiring instrucons, and tune-in instrucons for the iQ Controller. It includes instrucons for Dura-Glide™ 2000/3000, 5200/5300, Dura-Guard™, Dura-Storm™,
All rights reserved. Reproduction
Dura-Max™ 5400-Series*, ProCare™ 8300A*, and DuraCare™ 7500A TL-FBO Automac Slide door systems.
On Dura-Glide sliding doors, the iQ Controller replaces the MC521 and MC521Pro, or both the microprocessor control box and the interface board on older models. The door acvaon devices (SU-100 moon sensors, carpets, control mats, push plates, etc.), lock, funcon switch, doorway holding beams, and door posion switches previously connected to the interface board must be connected to the iQ Controller.
Aachment 1 illustrates the iQ Controller controls and indicators. Aachment 2 illustrates system wiring for Dura-Glide series sliders. This manual supports the hardware and rmware at the me of this released revision.
Applicability
Copyright 2019 Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
This manual is applicable to the Dura-Glide series sliding doors used on Dura-Glide™ 2000/3000, 5200/5300, Dura-Guard™, Dura-Storm™, Dura-Max™ 5400-Series, ProCare™ 8300A, and DuraCare™ 7500A TL-FBO Automac Slide door systems.
Instrucons for connecng oponal accessories are not provided in this manual.
01.25.2019
2 Document # 204144 REV B • www.stanleyaccess • 1.800.7.ACCESS
iQ Control Box
Prerequisites
Special Items Required:
• Stanley Access Technologies document No. 203957, “SU-100 Moon Sensor Installaon and Operaon” (if installed).
• SU-100 tune-in remote control (if SU-100 Moon Sensor is installed).
• Stanley Access Technologies document No. 203768, “StanguardTM Threshold Sensor Installaon and Operaon” (if installed).
• Optex X Zone T or X Zone ST manufacturer’s installaon and tune-in instrucons (if installed).
• Hotron HR100 ST manufacturer’s installaon and tune-in instrucons (if installed).
• Bluetooth adapter or cable to connect compable handheld device to iQ Controller.
• Degreaser.
• Instrucons for any other device to be wired into the iQ Controller.
Precautions
All ANSI/BHMA and UL Requirements in Attachment 4 must be met before the door is put into operation.
2
INSTALLATION INSTRUCTIONS
Installing the iQ Controller
NOTE: This manual covers new door installaons in which the iQ is factory-installed and wired.
3
WIRING INSTRUCTIONS
Evaluating Power Requirements
• ENSURE power source is a dedicated 115 VAC, 50/60 Hz source with 20A circuit rang. If four operators are used, the source should have a 30A rang.
• ENSURE no more than four operators will be connected to one circuit.
• ENSURE power source is not shared with other equipment, i.e., cash registers, EAS systems, or other electromagnec interference generators.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 3
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Connecting Main Power Wiring
Warning: To prevent injury to personnel, incoming electrical power to the header must be de-energized
before connecng electrical service to the control box.
Warning: All electrical wiring must conform to Naonal Electrical Code Requirements.
1. DE-ENERGIZE incoming electrical power to header.
2. Refer to Aachment 2, and, using wire nuts, CONNECT incoming line, neutral, and ground wires to the controller power harness.
3. IF adhesive wire clamps will be used, DE-GREASE metal surfaces on inside of header cover where clamps will mount.
4. SECURE wiring to top of the header track tube, and ENSURE the following:
• All wires are clear of belts and belt brackets.
• Header cover opens and closes without interference.
Connecting Accessories (As Applicable)
Refer to Aachments 2 and 3, and CONNECT any of the following subsystems to the iQ Controller:
• Funcon switch (rotary, rocker and “POWER” switch wiring).
• StanguardTM threshold sensor.
• Doorway holding beam(s).
• Breakout switch.
• Solenoid lock.
• SU-100 moon sensor(s) wiring (refer to Stanley Document #203957).
• Optex X Zone T and X Zone ST Sensor(s) wiring.
• Push plate wiring.
• Door posion switch closed contact (with door closed).
• Hotron HR100 ST Sensor(s) wiring.
All rights reserved. Reproduction
4
TUNE-IN INSTRUCTIONS
Warning: The door path must be free of objects and remain clear unl the First Install Sequence (FIS)
is complete. During this sequence the sensors are inacve and the door has no SAFETY. To stop the door,
turn power off or put the doors into breakout.
NOTES:
1. Tune-In: The iQ Controller can be tuned-in using a handheld device or using the pushbuon switches located on the controller. Tune-in using a handheld device is the preferred method.
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
4 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
2. Status Codes: During normal operaon, the digital display indicates status codes. The “UP” and “DOWN” pushbuon switches can be used to enter and display data values. The user interface values are shown in Tables 2 through 4.
iQ Control Box
PULLEY ROTATES CCW WHILE OPENING USE RIGHT HAND IN FIS
PULLEY ROTATES CW WHILE OPENING USE LEFT HAND IN FIS
RIGHT HAND
LEFT HAND
HANDING
3. Solenoid Lock: If a solenoid lock is installed with no lock circuit board (new style), set Lock Logic to the actual lock type (Fail Safe or Fail Secure). If a Fail Safe or Fail Secure Lock is being installed with a lock circuit board (old style), the Lock Logic must be set to Fail Secure.
4. Handing (For purpose of FIS only): Manually open door nong rotaon of belt pulleys. If counter clockwise (CCW) use right hand during FIS. If clockwise (CW) use le hand during FIS. See gure below.
5. FIS: The rst installaon sequence (FIS) is used to perform the inial conguraon. Upon compleon of FIS, all setup parameters are stored in non-volale memory. Subsequent power cycles will reload the conguraon parameters that were congured during FIS.
6. Decimal points on digital display are encoder 1 signals. Rotang motor will cause decimal points to blink
and appear to dim.
7. Aer changing values, the values must be saved in non-volale memory by cycling the door to full open.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 5
01.25.2019
iQ Control Box
Tuning In the iQ Controller Using the Controller Pushbuttons
1. To change the INDEX and VALUE: To show the INDEX press and hold ENTER, the current INDEX will display. Once ENTER is released, the display will show the VALUE of that INDEX. Aer 2.5 seconds, the display will return to the current status code.
2. To change the INDEX:
Hold ENTER switch while pressing UP or DOWN to get desired INDEX.
3. To change a VALUE:
a. Unlock the keypad by seng index 99 to value 00.
b. Aer the desired INDEX is selected, release ENTER and within 2.5 seconds press UP or DOWN to get the
desired VALUE. (If the UP or DOWN buons are not pressed within 2.5 seconds of releasing the ENTER buon, the display will change from the VALUE back to the STATUS.)
4. To display STATUS CODE:
A few seconds aer the VALUE is selected, the display indicates the STATUS CODE.
5. Refer to Tables 2 and 3 for a list of index seng descripons and values. Read the descripons enrely before performing each step. Check the INDEX and VALUE aer each step.
6. To STORE CHANGES in permanent memory:
Cycling door open one me will store changes.
7. To LOCK keypad:
Lock keypad by seng index 99 to value 01 or by turning power OFF and then ON.
8. To ACCESS the door cycle counter funcon:
a. Ensure that the keypad is locked by seng index 99 to 01.
b. Ensure that the index is set to any index but 99.
c. Press the up or down key to access the door cycle counter.
The display will show “dc” followed by four pairs of digits, followed by “dc”.
Example: If the Door Count was 12345678 cycles the controller will display “dc” “12” “34” “56” “78” “dc”.
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
6 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 1. FIS Procedure using Pushbuttons
Step Description Display
Index Value Status Code
1 Set Funcon Switch to Closed.
2 Turn power on.
3 Unlock keypad. 99 00 00
4 Restart FIS. 96 01 A0
5 Select door type: Slide, 01 single motor or 02 dual motor. 00 01 (Single)
02 (Dual)
6 Select Handing: 00 Right or 01 Le.
Manually open door and note rotation of belt pulleys. If counterclockwise (CCW) use right hand during FIS. If clockwise (CW) use left hand during FIS.
01
7 Accept FIS. Display will go to A1. 03 01 A1
8 Make changes: Funcon Switch
11 01 (Rocker)
01 Rocker or 00 Rotary. The INDEX will start at 00.
9 Select Lock Logic: Lock Logic, 00 = Fail Safe; 01 = Fail Secure;
07 Lock Logic:
02 = Fail Safe Dura-Max; 03 = Fail Secure Dura-Max.
NOTE: For locks with circuit board, set to 01 Fail Secure.
For locks with no circuit board, set to Fail Safe or Fail Secure.
10
Warning: During this sequence the sensors are inactive and the door
has NO SAFETY. To stop the door, TURN POWER OFF or PUT THE DOOR INTO BREAKOUT.
Function Switch: Switch to OPEN, momentarily, then CLOSED/ LOCKED. The door opens fully, delays and then closes fully.
The iQ displays A2 when FIS is completed.
11 Aer FIS is complete it might be necessary to change index
11 (safety logic) and Index 20 (Safety Beam Type) to match the systems installed. Adjust any other index sengs as needed (refer to Table 3 for opons).
12 Lock keypad. 99 01 00
13 Final Tune-In.
Walk test doors to conrm compliance with applicable ANSI Standards and local codes.
00 (Right)
01 (Le)
00 (Rotary)
00 = Fail Safe 01 = Fail Secure 02 = Fail Safe Dura-Max 03 = Fail Secure Dura-Max
A0
A1
A2
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 7
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Table 2. Index List
Index Description
0 - 99 Sengs Values, see Table 3.
90 - 95 Reserved.
96 Command – Restart FIS. Entering “01” will cause FIS to restart.
97 Firmware – Entering “01” will display “FE” followed by two pairs of digits followed by “FE”. For example,
if the rmware was 0609 the controller will display “FE” “06” “09” “FE”.
98 Command – Restart auto conguraon. Entering “01” sets the Control Box to “A1” keeping all previous
values and then re-learns the encoder count.
99* Command – Lock. Entering “01” will lock all value inputs except this index. This prevents inadvertent
changes to input values. Values may be unlocked by entering “00” in this index.
Table 3. Settings
Index Min.
Value
0 1 99* Open
1 1 99* Close
All rights reserved. Reproduction
2 1 99* Open
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Max
Value
Speed
Speed
Check Speed
Open Speed is the speed used during normal operaon in the opening state (02).
This speed is set to change how long it takes the door
to open.
This parameter sets the target speed seng. Other parameters like open torque, open startup torque, open startup length, and open acceleraon as well as door properes like fricon, door length, and door weight aect door speed.
Close Speed is the speed used during normal operaon in the closing state (07).
This speed is set to change how long it takes the door to close.
This parameter sets the target speed seng. Other parameters like Close Torque, Close Startup Torque, Close Startup Length, and Close Acceleraon as well as door properes like fricon, door length, and door weight aect
door speed.
Open Check Speed is the speed used during normal operaon in the open check state (04) prior to arriving at full open.
This speed is set to determine how fast the door arrives at full open aer open speed.
This parameter sets the target speed seng. Other parameters like open check torque, open acceleraon, and open braking as well as door properes like fricon, door length, and door weight aect door speed.
Defaults
Single Dual
99 99
35 25
10 10
NOTE: With the iQ Toolbox, the Max Values are 125.
Table 3 Settings continued next page.
01.25.2019
8 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 3. Settings (continued)
Index Min
Value
Max
Value
Description Defaults
3 5 99 Open Check Length Open Check Length is the percent of door
length in which the door starts to slow down to open check speed.
This parameter typically is adjusted based on door weight and open speed seng.
4 5 99 Close Check Length Close Check Length is the percent of door length
in which the door starts to slow down to Close Check Speed.
This parameter typically is adjusted based on door weight and Close Speed seng.
5 1 99 Reduced Open
Length
Reduced Open Length is the percent of door length from the full open posion the door will stop at if in reduced open mode.
6 1 99 Hold Open Delay Delay that the door stays open aer all sensors
have cleared (0 to 25 seconds).
7 0 3 Lock Logic Select to choose desired Lock Logic.
NOTE: Dura-Max 5400 logic is dierent and has its own two opons:
00 = Fail Safe (unlocked when power is removed), 01 = Fail Secure (locked when power is removed), 02 = Dura-Max Fail Safe (unlocked when power is removed), 03 = Dura-Max Fail Secure (locked when power is removed).
8 1 99* Open Torque Open Torque is the torque used during normal
operaon following the end of open startup length.
Single Dual
40 25
15 15
1 1
15 15
1 1
40 45
This torque must be set to comply with BHMA/ ANSI door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjuncon with open speed.
Table 3 Settings continued next page.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 9
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Table 3. Settings (continued)
iQ Control Box
Index Min
Value
Max
Value
Description Defaults
9 1 99 Close Torque Close Torque is the torque used during normal
operaon following the end of Close Startup Length.
This torque must be set to comply with BHMA/ANSI door force equirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjuncon with Close Speed.
10 1 99 Close Check
Torque
Close Check Torque is the torque used during normal operaon in close check state.
This torque must be set to comply with BHMA/ANSI door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjunc­on with close check speed.
11 0 2 Funcon
Switch Type
00 = Double pole rotary 01 = Rocker 02 = ICU
12 0 1 2S Operaon; 00 = 2S mode disabled / normal
01 = Push switch to open, push switch to close;
Single Dual
30 25
35 25
1 1
0 0
13 1 60 Close
Obstrucon
Time
Close Obstrucon Time is the amount of me in increments of 0.025s the door applies force when almost stopped or stopped when the controller indicates a state of “07”.
All rights reserved. Reproduction
Before increasing this parameter, check mechanical issues, and speed and torque parameter sengs.
14 0 40 Open
Acceleraon
Open Acceleraon aects the rate at which the door gets to its target speed.
This parameter is used when the door is lagging open speed; open startup torque and open startup length should be invesgated prior to increasing.
This parameter aects all open moon speeds: open speed, open check speed, open learn speed, as well
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Table 3 Settings continued next page.
01.25.2019
10 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
as open braking.
50 50
30 30
iQ Control Box
Table 3. Settings (continued)
Index Min
Value
Max Value Description Defaults
15 1 10 Open
Braking
16 0 40 Close
Acceleraon
17 1 10 Close
Braking
The Open Braking parameter adjusts how quickly the door slows down prior to check speed.
Increasing this parameter increases braking power.
Close Acceleraon aects the rate at which the door gets to its target speed.
This parameter is used when the door is lagging close speed, close startup torque and close startup length should be invesgated prior to increasing.
This parameter aects all close moon speeds: close speed, close check speed, close learn speed, as well as close braking.
The Close Braking parameter adjusts how quickly the door slows down prior to check speed.
Single Dual
8 8
20 20
4 2
Increasing this parameter increases braking power.
18 0 6 Delayed Egress Special Locking Applicaon. See the
Delay Egress Instrucon Manual for use. 00 = O 01 = 15 sec delay 1 second nuisance 02 = 30 sec delay 1 second nuisance 03 = 15 sec delay 2 second nuisance 04 = 30 sec delay 2 second nuisance 05 = 15 sec delay 3 second nuisance 06 = 30 sec delay 3 second nuisance
19 0 5 Safety Logic 00 - Monitored 2 Sensors: Threshold
zone control (the threshold zone is enabled and disabled by the iQ). 1 - Monitored 4 Sensors: Threshold zone control (the threshold zone is enabled and disabled by the iQ). 2 - Monitored StanGuard™: (not recommended for Telescopic doors). 3 - Monitored 2 sensors. 4 - Non-monitored sensors. 5 - Monitored 4 sensors.
0 0
2 2
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Table 3 Settings continued next page.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 11
01.25.2019
Table 3. Settings (continued)
iQ Control Box
Index Min
Value
Max
Value
Description Defaults
20 0 1 Hold Beam Type 00 - Non-monitored Hold Beam
01 - Monitored Hold Beam
Selects the hold beam type to be used for monitored or non-monitored applicaons.
For Monitored Hold Beams: Photobeam Pro or Optex OSC12CT refer to wiring diagrams per applicaon.
21 1 50 Lock Delay This allows the lock to mechanically unlock
before door moon. Lock Delay in 0.1 second increments.
22 0 99 Open Stop Distance Distance from full open that the door will stop.
This will be in 0.25” increments.
23 1 99 Close Check Speed Close Check Speed is the speed used during
normal operaon in the close check state (09) prior to arriving at full closed.
This speed is set to determine how fast the door arrives at full closed aer close speed.
This parameter sets the target speed seng. Other parameters like close check torque, close acceleraon, and close braking as well as door properes like fricon, door length, and door weight aect door speed.
24 0 1 Access Control Pro
Enabled
Inside sensor lockout funcon. 00= OFF 01= ON When set to 01-On, the interior acvaon in­put is inhibited if the exterior acvaon input is acve. Acvaon override can be accomplished through TB2 pin 9 and 10.
25 0 5 Close Press Close Press aects how the doors press
All rights reserved. Reproduction
together at full closed. If the value selected is 0, the door does not press at the closed posion. A value of 1 will have a soer release of motor energy and a value of 5 will be a quicker release.
27 1 99 Lock Release Torque Lock Release Torque is the torque used on
lock release state. A closed posion switch is required, connected to TB-5.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force.
28 1 60 Close Check
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Obstrucon Time
Close Check Obstrucon Time is the amount of me in increments of 0.025s the door applies force when almost stopped or stopped when the controller indicates a state of “09”.
Before increasing this parameter, check
01.25.2019
mechanical issues, and speed and torque parameter sengs.
Single Dual
1 1
1 1
4 4
8 8
0 0
2 2
20 20
50 50
12 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 3. Settings (continued)
Index Min
Value
Max
Value
31 1 99* Close Learn
Speed
32 1 99 Close Learn
Torque
33 0 99 Close Startup
Length
Description Defaults
Close Learn Speed is the speed used on power up, during FIS and aer an obstrucon. The controller display may indicate either 07 or 09 as a door state and sll use Close Learn Speed based on the condions listed prior.
This speed is typically set higher than check speed, to allow faster door moon when not in the check zones, but sll slower door moon than normal operaon.
This parameter sets the target speed seng. Other parameters like close learn torque and close acceleraon as well as door properes like fricon, door length, and door weight aect door speed.
Close Learn Torque is the torque used on power up, during FIS, aer an obstrucon.
This torque must be set to comply with ANSI/ BHMA door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjuncon with Close Learn Speed.
Close Startup Length is the percent of door length in which Close Startup Torque parameter is used. These parameters are used to overcome fricon encountered at the begining of close door moon.
Single Dual
20 20
30 25
0 0
35 1 99 Close Startup
Torque
Table 3 Settings continued next page.
This parameter should be set as low as possible to ensure reliable operaon.
Close Startup Torque is the torque used when
35 25 entering the closing state (07). It is used for a congurable door length (determined by the Close Startup Length parameter). Aer this door length, the torque seng will revert to the Close Torque.
This torque should be set greater than Close Torque to ensure that the controller can start door moon, overcome stac fricon, and avoid obstrucons.
This torque must be set to comply with ANSI/BHMA door force requirements.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
This parameter sets the maximum current available to the motor which is directly proporonal to the door force.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 13
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Table 3. Settings (continued)
iQ Control Box
Index Min
Value
Max
Value
36 1 60 Open Check
Obstrucon
Time
37 1 99 Open Check
Torque
39 1 99* Open Learn
Speed
Description Defaults
Open Check Obstrucon Time is the amount of me in increments of 0.025s the door applies force when almost stopped or stopped when the controller indicates a state of “04”.
Before increasing this parameter, check mechanical issues, and speed and torque parameter sengs.
Open Check Torque is the torque used during normal operaon in open check state.
This torque must be set to comply with ANSI/BHMA door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjuncon with open check speed.
Open Learn Speed is the speed used on power up, during FIS, aer an obstrucon, and return from breakout. The controller display may indicate either 02 or 04 as a door state and sll use Open Learn Speed based on the condions listed prior.
Single Dual
50 50
40 40
25 25
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
40 1 99 Open Learn
Torque
41 1 60 Open
Obstrucon
Time
This speed is typically set higher then check speed, to allow faster door moon when not in the check zones, but sll slower door moon than normal operaon.
This parameter sets the target speed seng. Other parameters like open learn torque, and open acceleraon as well as door properes like fricon, door length, and door weight aect door speed.
Open Learn Torque is the torque used on power up, during FIS, aer an obstrucon, and return from breakout.
This torque must be set to comply with ANSI/BHMA door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force. This torque seng is used in conjuncon with open learn speed.
Open Obstrucon Time is the amount of me in increments of 0.025s the door applies force when almost stopped or stopped when the controller indicates a state of “02”.
Before increasing this parameter, check mechanical issues, and speed and torque parameter sengs.
48 25
50 50
Table 3 Settings continued next page.
01.25.2019
14 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 3. Settings (continued)
Index Min
Value
42 0 99 Open Startup
Max
Value
Length
Description Defaults
Open Startup Length is the percent of door length in which open startup torque parameter is used. These parameters are used to overcome fricon encountered at the begining of open door moon.
This parameter should be set as low as possible to ensure reliable operaon.
44 1 99 Open Startup
Torque
Open Startup Torque is the torque used when entering the opening state (02) and recycles. It is used for a congurable door length (determined by the Open Startup Length parameter). Aer this door length, the torque seng will revert to the Open Torque.
This torque should be set greater than Open Torque to ensure that the controller can start door moon, overcome stac fricon, and avoid obstrucons.
This torque must be set to comply with ANSI/BHMA door force requirements.
This parameter sets the maximum current available to the motor which is directly proporonal to the door force.
45 0 99 Recycle Speed Recycle Speed is the percent of open speed that is used
when recycling in the open check or open braking zone.
46 0 50 Lock Release
Time
The amount of me (seconds) that the door will press closed before going open when the lock needs to release at the closed posion. The value zero disables the lock release. A closed posion switch is required, connected to TB-5.
47 0 4 Fire Alarm
Mode
Allows a normally closed contact to force the door open or closed slowly, upon contact opening.
Single Dual
15 15
85 85
30 20
0 0
0 0
Used in conjuncon with Congurable I/O parameter.
Opons 00 to 04 are minimum and maximum values: 00 = Disabled, 01 = Open, 02 = Close, 03 = Open with Retry, 04 = Close with Retry.
Aer an obstrucon, retry modes (03 and 04) will retry with short delay.
Table 3 Settings continued next page.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 15
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Table 3. Settings (continued)
iQ Control Box
Index
Min
Value
Max
Value
Description Defaults
Single Dual
0 3 IO conguraon 0 0
48
00 (Default)
TB2-5 TB2-7 TB2-9
1 way / 2 way Reduced Access Control Pro acvaon override (highest priority
when selected).
4 Monitored Sensors (when selected).
Delay egress reset (default).
01 1 way / 2 way Reduced Fire Alarm.
02 1 way / 2 way Fire alarm Access Control Pro acvaon override (highest priority
when selected).
4 Monitored Sensors (when selected).
Delay egress reset (default).
03 Fire alarm Reduced Access Control Pro acvaon override (highest priority
when selected).
4 Monitored Sensors (when selected).
Delay egress reset (default).
IO Configuration Parameter Description
Allows the Fire Alarm to be used instead of funcons normally used with the selected input: 0 = Standard Funcons (NO Fire Alarm Input). 1 = Fire Alarm Input is TB2-9 (Removes Funcons: Access Control Pro acvaon override, Delayed Egress Reset,
and 4 Monitored Sensor capability). 2 = Fire Alarm Input is TB2-7 (Removes Reduced Open funcon). 3 = Fire Alarm Input is TB2-5 (Removes One-way funcon).
All rights reserved. Reproduction
Index
49
Min
Value
0 99 Open Power
Max
Value
Assist Torque
Descriptions Defaults
This parameter sets the current to the motor which is used to make the door feel easier to move open when in “Manual” mode. This value should be set only as high as is needed to reduce the force required to move the door. Seng this value too high can cause the door to move by itself.
Only available when index 11 is set to 02-ICU.
50 0 99 Close Power
Assist Torque
This parameter sets the current to the motor which is used to make the door feel easier to move closed when in “Manual” mode. This value should be set only as high as is needed to reduce the force required to move the door. Seng this value too
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
high can cause the door to move by itself.
Only available when index 11 is set to 02-ICU.
01.25.2019
16 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
Single Dual
60 60
50 50
iQ Control Box
Table 4. Status Codes
Status Code Description Remediation IF Necessary
00 Normal operaon—All OK
20 Breakout
33 System error See aachment 7
34 Internal communicaon error – Type 1 See aachment 7
35 Motor drive failure Replace controller
36 Internal communicaon error – Type 2 See aachment 7
0b Obstrucon
A0 First Installaon Sequence (FIS)
A1 Auto-conguraon sequence
A2 Auto-conguraon conrmaon sequence
b1 Encoder error > cable failure Verify magnet/encoder pair
b2 Encoder mismatch > wrong encoder/magnet Verify magnet/encoder pair
b3 Encoder fault > wrong encoder/magnet or
cable falure
bE Blocked egress
c1 Posion learn error
Ld Lock down (shear lock energized)
db Output control See Aachment 6, Sheet 2 of 2
dc Display door cycle counter
dE Delayed egress
d0 Free egress
E2 Door held open by any sensor input other than
the Hold Open switch on TB2-1.
E3 Door length error Re-do First Installaon Sequence (FIS)
E4 Presence sensor monitoring failure Verify sensor wiring and safety logic seng
E5 Motor drive failure
F0 Inside monitored sensor failure Verify sensor wiring and safety logic seng
F1 Outside monitored sensor failure Verify sensor wiring and safety logic seng
F2 Upper Monitored Photo Beam failure Check transmier, receiver, and hold beam type
F3 Lower Monitored Photo Beam failure Check transmier, receiver, and hold beam type
F6 Inside (2) monitored sensor failure Verify sensor wiring and safety logic seng
F7 Outside (2) monitored sensor failure Verify sensor wiring and safety logic seng
ho Door held open Check sensors and hold beam type
FA Fire Alarm Acve
uL Unlocked delay egress
Verify magnet/encoder pair
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 17
01.25.2019
iQ Control Box
Table 5. Door States
Door State Description
00 Door State is Closed
02 Door State is Opening
04 Door State is in Open Check
06 Door State is Full Open
07 Door State is Closing
09 Door State is in Close Check
10 Open Assist (manual mode door state)
11 Close Assist (manual mode door state)
12 Close Assist (manual mode door state)
14 Door Fault
15 Door State is in Open Stop
16 Door State is in Obstrucon while Closing
17 Door State is in Close Press
19 Lock Release (door state)
NOTE: If the current status code is “Normal operaon—All OK”, the iQ will show the current door state.
Otherwise, the iQ alternates between showing the current status code and the door state.
Final Tune-In Adjustments
1. Refer to ANSI/BHMA A156.10, “Standard for Power Operated Pedestrian Doors,” and aachment 4 and DETERMINE ANSI and UL door operang requirements.
2. IF StanguardTM threshold sensor is installed, refer to Stanley Access Technologies document No. 203768, “StanguardTM Threshold Sensor Installaon and Operaon,” and TUNE-IN StanguardTM threshold sensor. Ensure that the JP301 Jumper is properly installed for StanGuardTM Sensors.
3. IF SU-100 moon sensor(s) are installed, refer to Stanley Access Technologies document No. 203957,
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
“SU-100 Moon Sensor Installaon and Operaon,” and TUNE-IN SU-100 moon sensor(s).
4. IF Optex X Zone T or X Zone ST Sensors are installed, refer to the manufacturer’s installaon and tune-in instrucons.
5. If Hotron HR100 ST sensors are installed, refer to the manufacturer’s instrucons.
6. Aer all changes have been made, cycle the door to have the sengs stored in Non-Volale memory. Then turn power OFF and then back ON to ensure that all of the sengs are permanently stored.
• Verify that the correct Safety Logic has been selected for Sensor Monitoring and that the JP301 is in the
correct posion.
• DO NOT remove JP301 when Stanguard™ is installed. X Zone T, X Zone ST and HR100 ST monitored sensors
require JP301 to be removed.
7. This step only applies to the Stanley Automac ICU series doors: Refer to ANSI/BHMA A156.38, “American Naonal Standard for Low Energy Power Operated Sliding and Folding Doors” and Aachment 4 (Page 3 of 3) and determine ANSI and IBC-2018 door operang requirements.
01.25.2019
18 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 1
iQ Controls and Indicators
(Sheet 1 of 2)
NOTE: See next page for indicators and descriptions
1
2
3
4
SEE DETAIL A
5
6
7
8
15
15
9
9
11
11
1212
13
13
14
10
10
19
18
17
DETAIL A
16
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 19
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Attachment 1
iQ Controls and Indicators
(Sheet 2 of 2)
ITEM CONTROL/INDICATOR DESCRIPTION
1 Motor 2 Connector Motor No. 2 connector.
2 Power Connector Connecon point for incoming line, neutral, and common power wiring.
3 Fuse Controller fuse-- 5 Amp, 250V.
4 Motor 1 Connector Motor No. 1 connector.
5 Terminal Block Connector TB1 Connecon point for 24V power supply and solenoid lock.
6 Terminal Block Connector TB2 Connection point for function switch (rotary or rocker) and Fire
Alarm input.
7 Terminal Block Connector TB6 Push plate outside. Monitored Photo Beam and Test output.
8 Encoder 2 Connector Encoder # 2 Connector.
9 Two Digit Display Displays Controller Status. Also serves as the display for tune-in by
pushbuon switches and indicates encoder movement. High resoluon encoder may be dim.
10 Encoder 1 Connector Connecon point for motor encoder No. 1.
11 Up Pushbuon Switch Used for manual setup and tuning of door when handheld
is not available.
12 Down Pushbuon Switch Used for manual setup and tuning of door when handheld
is not available.
13 Enter Pushbuon Switch Used for manual setup and tuning of door when handheld is
14 RS232 RS232 connector. Connecon point for Bluetooth harness.
15 Jumper JP301 Keep jumper installed for StanguardTM installaons. See wiring diagrams
16 Terminal Block Connector TB7 Connecon for ECO Pro.
17 Terminal Block Connector TB5 Side screen sensor, door posion switch.
18 Terminal Block Connector TB4 Connecon point for INSIDE / OUTSIDE sensor and push plate.
All rights reserved. Reproduction
19 Terminal Block Connector TB3 Connecon point for StanguardTM, safety sensor and breakout switch.
not available.
to determine when to remove JP301 for monitored sensor installaons.
Using jumper wires across TB3 terminals 1 to 5 and 2 to 6, internal 24 VDC supplies power to mulple external sensors.
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
20 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 2
iQ System Wiring Diagram
(Sheet 1 of 10)
NOTE: JP 301 must be installed.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 21
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 2 of 10)
iQ Control Box
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
22 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 2
iQ System Wiring Diagram
(Sheet 3 of 10)
SEE NEXT PAGE
OR
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 23
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 4 of 10
iQ Control Box
SEE PREVIOUS PAGE
OR
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
24 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 2
iQ System Wiring Diagram
(Sheet 5 of 10)
STANLEY PHOTO BEAM
On the iQ: Set INDEX 20 to VALUE 01 (Monitored Beam).
TB6 COLOR DUAL HOLDING BEAM WIRING
1 YL OUTPUT UPPER RECEIVER
2 BK (-) UPPER RECEIVER
3 YL OUTPUT LOWER RECEIVER
4 BK (-) LOWER RECEIVER
5 OR TRANSMITTER CONTROL LOWER AND UPPER
6 -- NO CONNECTION
7 -- NO CONNECTION
8 RD (+) ALL RECEIVERS AND TRANSMITTERS
9 BK (-) LOWER AND UPPER TRANSMITTERS, JUMPER TO TB6-10
10 BK JUMPER FROM TB6-9
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 25
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 6 of 10)
iQ Control Box
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Program the OS-12 CT set to “D” - Acve High / N.C. On the iQ: Set INDEX 20 to VALUE 01 (Monitored Beam).
01.25.2019
26 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 2
iQ System Wiring Diagram
(Sheet 7 of 10)
TB3 COLOR PHOTO BEAM PRO BREAKOUT BEAM
1 RD JUMPER FROM TB3-5
2 BK JUMPER FROM TB3-6
3 -- NO CONNECTION
4 -- NO CONNECTION
5 RD JUMPER FROM TB3-1, (+) RECEIVER AND TRANSMITTER
6 BK JUMPER FROM TB3-2, (-) RECIEVER AND TRANSMITTER
7 -- NO CONNECTION
8 -- NO CONNECTION
9 YL OUTPUT RECEIVER
10 -- NO CONNECTION
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 27
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 8 of 10)
iQ Control Box
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
X-Zone ST
For Security Applicaons / 1-WAY Key DIP Switch sengs: 10 and 11 DOWN; 12, 13, 14, 15 and 16 UP.
X-Zone ST and X-Zone (ST) Key DIP Switch sengs: 10 and 11 DOWN; 12, 14 and 15 UP.
iQ
Remove JP301. Set index 19 to Value = 00 (Sensor Monitoring with Threshold Control).
X-Zone T Key DIP Switch sengs: 11 and 12 DOWN; 13 and 15 UP.
iQ
Remove JP301. Set index 19 to Value = 03 (Monitored 2 Sensors).
NOTE:: The X-Zone ST will replace the X-Zone (ST) in 2019.
01.25.2019
28 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 2
iQ System Wiring Diagram
(Sheet 9 of 10)
X-Zone ST
For Security Applicaons / 1-WAY Key DIP Switch sengs: 10 and 11 DOWN; 12, 13, 14, 15 and 16 UP.
X-Zone ST and X-Zone (ST) Key DIP Switch sengs: 10 and 11 DOWN; 12, 14 and 15 UP.
iQ
Remove JP301. Set index 19 to Value = 01 (Monitored 4 Sensors - Threshold Zone Control).
X-Zone T Key DIP Switch sengs: 11 and 12 DOWN; 13 UP and 15 UP.
iQ
Remove JP301. Set index 19 to Value = 05 (Monitored 4 Sensors).
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
NOTE: The X-Zone ST will replace the X-Zone (ST) in 2019.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 29
01.25.2019
Attachment 2
iQ System Wiring Diagram
(Sheet 10 of 10)
iQ Control Box
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
HR100 ST
Recommended DIP Switch sengs: DIP Switch X: (2, 3, and 4 = UP) (1 = DOWN). DIP Switch Y: (1, 2, 3 and 4 = UP) DIP Switch Z: (1, 2, 3 and 4 = UP) (5 and 6 = DOWN).
{UP = OFF} {DOWN = ON}
iQ Sengs
Remove JP301. Set index 19 to Value = 03 (Monitored 2 Sensors).
CAUTION: Tapered HR100 ST base plate must removed before sensor is installed for threshold sensor detecon.
01.25.2019
30 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
TB2
TB2
1
TB3
4
2
3
Attachment 3
iQ Terminal Block Connections -- TB1 through TB7
(Sheet 1 of 1)
2
4
6
8
5
9
7
10
1
TB7
5
3
8
6
7
9
10
VDC -
0
24 VDC +
EXT+
EXT-
COMMON (WH)
STANGUARD(GN)
EXT-
SEENOTE1
1
2
3
4
(ROTARYSWITCHWIRING)
COMMON (YL)
HOLD OPEN (BK)
1
COMMON (OR)
AUTOMATIC (RD)
3
2
4
COMMON (WH)
INT-
6
7
5
REDUCEDOPEN(GN)
ENTER-ONEWAY (BN)
6
7
5
BREAKOUT (GN)
OPTEXHOLDING BEAM (GN)
8
9
FIRE ALARM INPUT
8
9
COMMON (WH)
10
NOTE: Requires proper
setting of index 47 and 48.
Refer to Table 3 - Settings.
10
15 VDC +
1
TB6
PHOTO BEAM PRO UPPER RCVR
1
SEE NOTE 1SEE NOTE 1
VDC -
0
COMMON
COMMON
2
3
4
COMMON
PHOTO BEAM PRO LOWER RCVR
PHOTO BEAM PRO TEST OUTPUT
3
4
2
7
5
6
COMMON
OUT_SPARE2
7
5
6
COMMON
8
9
10
VDC -
0
24 VDC +
COMMON
8
9
10
(ROCKERSWITCHWIRING)
COMMON
HOLD OPEN (YL)
COMMON (OR)
AUTOMATIC (BN)
COMMON (BL)
COMMON(VI)
REDUCEDOPEN(VI )
ENTER-ONEWAY (BL)
EXT+
EXT-
EXT-
COMMON
SIDE SCREEN SENSOR
CH
VDC -
0
24 VDC +
INT-
COMMON
SEE NOTE 1
CLOSED POSITION SWIT
1
EXT+
2
EXT-
COMMON (WH)
EXT-
6
8
2
4
1
TB1
15 VDC +
5
3
SOLENOID LOCK (BL)
9
7
SOLENOID LOCK (BK)
10
TB TB54
VDC -
0
24 VDC +
POWER
INPUT
5
6
8
4
3
VDC -(BK)
0
24 VDC + (RD)
INSIDE SENSOR
COMMON (WH)
INT-
9
7
OUTSIDESENSOR(GN)
10
COMMON
PUSH PLATE
TO THE EXTERNAL POWER SUPPLY BUS (EXT).
NOTE 1. REMOVE JUMPERS ON TB3 IF EXTERNAL POWER SUPPLY IS USED.
JUMPERS ON TB3 CONNECT INTERNAL POWER SUPPLY (INT)
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 31
iQ Control Box
Attachment 4
ANSI/BHMA and UL Compliance Requirements for Sliding Doors
(Sheet 1 of 3)
Final adjustment and proper operaon of the door system must be and shall be performed in the eld.
NOTE: These instrucons are for informaonal purposes and do not substute for review against the current
revision of the referenced standards. Where a requirement exists in mulple standards, such as the ANSI/BHMA standard and the UL standard, the more restricve condion applies. Other local codes and re codes likely exist, and must also be followed.
ANSI/BHMA A156.10 Sliding Door Systems
Sliding door systems must be installed and adjusted for compliance with the current version of ANSI/BHMA A156.10, “American Naonal Standard for Power Operated Pedestrian Doors”.
Crical aspects of the installaon for compliance with ANSI/BHMA A156.10 include:
• Control mat size, layout, molding height, acve areas and sensivity.
• Sensor paern size, sensivity, and funcon.
• Knowing Act guidelines and secondary acvang zone.
• Entrapment protecon rules including door speeds, forces, and me delays.
• Signage. (Decals and applicaon instrucons are provided with the door system.)
NOTE: For Procare and Duracare series Automac series refer to the current version of ANSI/BHMA A156.38.
UL 325 Compliance
All power operated door systems must be installed in compliance with the current edion of UL 325, “Standard for Safety for Door, Drapery, Gate, Louver, and Window Operators and Systems”.
Wiring
1. To reduce the risk of electric shock proper and reliable grounding is mandatory. See Main Power Wiring instruc-
All rights reserved. Reproduction
ons and Wiring Diagrams in this guide for grounding techniques.
2. Permanent wiring is to be employed as required by the Naonal Electrical Code and/or local codes.
3. Connecon of external devices is shown in the wiring diagrams and terminal block layouts elsewhere in this guide. Refer to these gures for proper wiring of external devices to ensure compliance with UL 325.
Knowing Act
Doors acvated by a manual switch (Knowing Act switch in ANSI/BHMA terms) must have the switch installed in a locaon from which operaon of the door can be observed by the person operang the switch and not located in a positon where the user would be in the path of the moving door.
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
32 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 4
ANSI/BHMA and UL Compliance Requirements for Sliding Doors
(Sheet 2 of 3)
To ensure that a sliding door operates in accordance with UL 325 entrapment protecon criteria the following must be established:
• Manual opening force (sliding doors without breakout) or breakout force with power on or o must be less then 50 lbf (222.4 N).
• Closing force must be less than 30 lbf (133.4 N).
• A closing sliding door must not develop kinec energy in excess of 2.5 -lbf (3.39 J). This is achieved by proper seng of the closing speed. See secon entled “Closing Speed”.
• Maximum recommended door weight:
• Dura-Glide 5000 Series = 150 lbs (70 kg) per panel.
• Dura-Glide/Dura-Guard/Dura-Storm and similar 2000/3000 Series = 220 lbs (100 kg) per panel.
• IS10000/Double Diamond and similar Industrial Series = 300 lbs (90 kg) per panel
Closing Speed
Closing speed is measured over a travel distance of 2 or 3 feet. On smaller bi-part doors there may only be 2 feet of movement before the door system enters close-check (latch check). The me measurement should start once the door has achieved closing speed, usually 6 inches from full open. Mark this point on the oor with tape or other object. Measure from this point 2 or 3 feet toward the closed posion and mark the next point. Use a stopwatch to measure the me it takes for the sliding panel to travel this distance during normal closing cycles. Make sure the door system is not braking or entering close-check during the measurement. Repeat the measurement 3 mes and use the average value. The allowed me for a sliding panel to cover this distance during the closing cycle is given in the table below.
Door Weight
(pounds)
160 or less 2.0 3.0
161 to 180 2.1 3.2
181 to 200 2.2 3.3
201 to 220 2.3 3.5
221 to 240 2.4 3.7
241 to 260 2.5 3.8
261 to 280 2.6 4.0
281 to 300 2.7 4.1
Closing Time (seconds)
2 foot measurement
Closing Time (seconds)
3 foot measurement
NOTE: For low energy slide door applicaons refer to aachment 4 sheet 3 of 3.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 33
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Attachment 4
ANSI/BHMA and IBC Compliance Requirements for
Low Energy Power Operated Sliding Doors
(Sheet 3 of 3)
To ensure that a Low Energy Power Operated Sliding Door operates in accordance with ANSI/BHMA and the
the IBC-2018, the following must be established:
• Acvaon of the door must be by a Knowing Act.
• The Opening Time (speed) of the Door(s) shall be adjusted so that the door(s) open at a speed of 12 inches per second maximum, from fully closed to fully open.
• When powered open, the door shall remain at the fully open posion for not less than 5 seconds before starng the closing cycle.
• The Closing Time (speed) of Door(s) shall be adjusted so that the door(s) close at a speed of 6 inches per second maximum per leaf, from fully open to latch check.
• Latch check shall occur at no less than 2 inches from fully closed.
All rights reserved. Reproduction
The force required to prevent a stopped door from opening or closing shall not exceed 15 lbf (67 N).
• The required Signage must be present.
NOTE: In special applicaons where safety sensors or secondary acvaon sensors are used on
a low energy door, refer to ANSI/BHMA A156.10 for guidance on sensor performance criteria for the type of sensor selected.
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
34 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 5
Troubleshooting Aid (Sheet 1 of 1)
Terminal and Pin Descripon State
TB1-8 Solenoid Lock Output Dark = Unlocked
w/o PCB, fail secure Dark = Unlocked
w/o PCB, fail safe Dark = Locked
NOTE: Black color indicates a low signal (Approx. 0 VDC).
Rotary Function Switch States for TB2
Hold
Open
TB2-1
TB2-3
TB2-5 Don’t Care Don’t Care
TB2-7
Closed
Locked
Automac One Way Reduced Reduced
One Way
Rocker Function Switch States for TB2
Hold
Open
TB2-1
TB2-3
TB2-5 Don’t Care Don’t Care
TB2-7 Don’t Care Don’t Care
Terminal and Pin Descripon State
TB3-4 StanguardTM Input/Output Dark = triggered or detecng
TB3-8 & TB4-8
Non-Monitored Holding Beam Input Input and Outside Sensor (connected internally)
TB3-9 Breakout Input Dark = no breakout
TB4-4 & TB4-9
TB4-8 & TB3-8
TB4-9 & TB4-4
Inside Sensor Input and Push Plate Input (connected internally)
Inside Presence Sensor Input and Holding Beam Input (connected internally)
Push Plate Input and Inside Sensor Input (connected internally)
TB5-3 Side Screen Sensor Input Dark = detecng
TB5-7 Closed-Door Posion Switch Input Dark = closed
TB5-10 Spare
TB6-1 Monitored Beam Upper Holding Beam Dark = unobstructed White = detecng
TB6-3
Monitored Beam Lower Holding Beam
TB6-5 Photo Beam Pro Test Output Dark = tesng
TB6-7 Sensor Test Output Dark = normal operaon
Closed
Locked
Automac One Way Reduced Reduced
One Way
Dark = detecng
Dark = detecng
Dark = detecng
Dark = detecng
Dark = unobstructed White = detecng
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 35
Attachment 6
iQ Troubleshooting Aid
(Sheet 1 of 1)
Symptom Remedy
Use best pracces to troubleshoot using handheld device and
Door does not close and/or Status code displays ho/E2
NOTE: E2 indicates door held open by any sensor
input other than Hold Open Switch on TB-2.
Handheld will not update rmware Controller is not displaying 00. Re-FIS the door.
Door hits Open Stop/full open bumper Increase the Open Check Length (Index 3).
Door moon is not the same as the MC521/ MC521PRO for the same sengs
Status code displays E3
Status code displays E4
Status code displays F0-F1, F6-F7 Verify sensor wiring and safety logic seng.
Status code displays F2-F3
provided wiring diagrams.
Check hold beam type (index 20). Monitored beams should be set to “Monitored Beam” and non-monitored beams should be set to “Non-monitored Beam.”
Reference latest Photo Beam Pro Troubleshoong Tech Tip.
Parameters value for the iQ are not the same as MC521/ MC521PRO. Refer to Table 3.
Check mechanical issues, components.
Re-do rst installaon sequence (FIS).
Verify sensor wiring and safety logic seng.
Monitored beam Failure. Verify proper wiring and “holding beam type”(index 20 = appropraite seng, Monitored Beam or Non-Monitored Beam.
iQ Control Box
Door moves slowly on one cycle. Status code displays 33 or 34 or 36 momentarily (3 seconds).
Door moves slowly on several cycles.
All rights reserved. Reproduction
Status code displays 33 or 34 or 36 on slow cycles.
Door tuning issues
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Reference latest Photo Beam Pro Troubleshoong Tech Tip.
Note it. No acon required.
1. Reset Power.
2. If code does not clear, Call Tech Support.
Refer to parameter descripons for useful adjustments.
36 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Attachment 7
Fine Tuning Slide Doors
(Sheet 1 of 2)
Tuning the Stanley Automatic Door
Match your actual door to one from the list of doors described in the aachment. Start by installing these sengs.
Use the guide below to make adjustments to these sengs.
If the door:
OPENS TOO SLOWLY
If it is too slow
Increase Open Speed. Maximum seng is 99 with keypad or 125 with handheld.
Increase Open Torque
If it is too slow
NOTES: Max Values go to 125 via handheld.
Open Torque is also used to set the door open force.
HITS THE OPEN STOP
When the door braking and moon are under control, reduce the Open Check length as desired.
CLOSES TOO SLOWLY
If it is too slow
If it is too slow
NOTE: Close Torque is also used to set the door closing force.
Close Speed and Close Force cannot exceed the value specied by ANSI/BHMA 156.10.
Increase Open Acceleration
Increase Open Stop to 8 and Open Check Length to 45
Increase Open Brake unl there is good braking.
Increase or decrease unl there is good moon entering and in Open Check.
Increase Close Speed to 16
Increase Close Torque
Increase Close Acceleration
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 37
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Attachment 7
Fine Tuning Slide Doors
(Sheet 2 of 2)
Tuning the Stanley Automatic Door (Continued).
Match your actual door to one from the list of doors described in the aachment. Start by installing these
sengs. Use the guide below to make adjustments to these sengs.
If the door:
HITS THE CLOSE STOP too hard
Set Close Check Length to 50. Set Close Press to 1 and test. Increase the Close Brake seng unl there is good braking. Increase or decrease Close Check unl there is smooth moon enter­ing and in Close Check.
STALLS during opening without any mechanical reason. . .
Connues to stall and it seems
to happen at the transion
from Open Brake to Open Check
STALLS during closing without any obvious reason. . .
Connues to stall and it seems to
happen at the transion to Close
Check
SPEEDS UP during Close Check
Increase Obstruction Time from .5 seconds to 1.0 seconds
Make small increases to Open Brake.
Increase Obstruction Time
Increase Close Check one count at a me
Close Check Speed is set too high. Reduce Close Check one count at a me unl door moon is suitable.
Stanley Access Technologies 65 Scott Swamp Road Farmington, CT 06032
Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
Loading...