*Refer to product-specic Installaon Manuals for Wiring Diagrams as they contain the relevant system wiring.
Stanley Part Number 204144
REV B 01.2019
All manuals can be found at
www.stanleymobileapps.com
Copyright 2019, Stanley Access Technologies, LLC.
Prohibition on Copying: Any unauthorized reproduction, disclosure or distribution of copies by
any person of any portion of this work may be a violation of copyright law of the United States
of America and other countries, could result in the awarding of statutory damages of up to
$250,000 (17 USC 504) for infringement, and may result in further civil and criminal penalties.
All rights reserved.
Table of Contents
General Description ........................................................................................................... 2
Intended Use ............................................................................................................................................. 2
Attachment 1 - iQ Controls and Indicators .................................................................................19
Attachment 2 - iQ System Wiring Diagram ...............................................................................21
Attachment 3 - iQ Terminal Block Connections TB1-TB7 ..................................................... 31
Attachment 4 - ANSI/BHMA and UL Compliance Requirements for Sliding Doors ..32
Attachment 5 - Troubleshooting Aid ............................................................................................ 35
Attachment 6 - iQ Troubleshooting Aid ...................................................................................... 36
Attachment 7 - Fine Tuning Slide Doors .....................................................................................37
1
GENERAL DESCRIPTION
Intended Use
This manual provides installaon instrucons, wiring instrucons, and tune-in instrucons for the iQ
Controller. It includes instrucons for Dura-Glide™ 2000/3000, 5200/5300, Dura-Guard™, Dura-Storm™,
All rights reserved. Reproduction
Dura-Max™ 5400-Series*, ProCare™ 8300A*, and DuraCare™ 7500A TL-FBO Automac Slide door systems.
On Dura-Glide sliding doors, the iQ Controller replaces the MC521 and MC521Pro, or both the
microprocessor control box and the interface board on older models. The door acvaon devices (SU-100
moon sensors, carpets, control mats, push plates, etc.), lock, funcon switch, doorway holding beams, and
door posion switches previously connected to the interface board must be connected to the iQ Controller.
Aachment 1 illustrates the iQ Controller controls and indicators. Aachment 2 illustrates system wiring for
Dura-Glide series sliders.
This manual supports the hardware and rmware at the me of this released revision.
Applicability
Copyright 2019 Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
This manual is applicable to the Dura-Glide series sliding doors used on Dura-Glide™ 2000/3000, 5200/5300,
Dura-Guard™, Dura-Storm™, Dura-Max™ 5400-Series, ProCare™ 8300A, and DuraCare™ 7500A TL-FBO
Automac Slide door systems.
Instrucons for connecng oponal accessories are not provided in this manual.
01.25.2019
2 Document # 204144 REV B • www.stanleyaccess • 1.800.7.ACCESS
iQ Control Box
Prerequisites
Special Items Required:
• Stanley Access Technologies document No. 203957, “SU-100 Moon Sensor Installaon and Operaon” (if
installed).
• SU-100 tune-in remote control (if SU-100 Moon Sensor is installed).
• Stanley Access Technologies document No. 203768, “StanguardTM Threshold Sensor Installaon and Operaon”
(if installed).
• Optex X Zone T or X Zone ST manufacturer’s installaon and tune-in instrucons (if installed).
• Hotron HR100 ST manufacturer’s installaon and tune-in instrucons (if installed).
• Bluetooth adapter or cable to connect compable handheld device to iQ Controller.
• Degreaser.
• Instrucons for any other device to be wired into the iQ Controller.
Precautions
All ANSI/BHMA and UL Requirements in Attachment 4 must be met before the door is put into operation.
2
INSTALLATION INSTRUCTIONS
Installing the iQ Controller
NOTE: This manual covers new door installaons in which the iQ is factory-installed and wired.
3
WIRING INSTRUCTIONS
Evaluating Power Requirements
• ENSURE power source is a dedicated 115 VAC, 50/60 Hz source with 20A circuit rang. If four operators are
used, the source should have a 30A rang.
• ENSURE no more than four operators will be connected to one circuit.
• ENSURE power source is not shared with other equipment, i.e., cash registers, EAS systems, or other
electromagnec interference generators.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 3
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Connecting Main Power Wiring
Warning: To prevent injury to personnel, incoming electrical power to the header must be de-energized
before connecng electrical service to the control box.
Warning: All electrical wiring must conform to Naonal Electrical Code Requirements.
1. DE-ENERGIZE incoming electrical power to header.
2. Refer to Aachment 2, and, using wire nuts, CONNECT incoming line, neutral, and ground wires
to the controller power harness.
3. IF adhesive wire clamps will be used, DE-GREASE metal surfaces on inside of header cover
where clamps will mount.
4. SECURE wiring to top of the header track tube, and ENSURE the following:
• All wires are clear of belts and belt brackets.
• Header cover opens and closes without interference.
Connecting Accessories (As Applicable)
Refer to Aachments 2 and 3, and CONNECT any of the following subsystems to the iQ Controller:
• Funcon switch (rotary, rocker and “POWER” switch wiring).
• StanguardTM threshold sensor.
• Doorway holding beam(s).
• Breakout switch.
• Solenoid lock.
• SU-100 moon sensor(s) wiring (refer to Stanley Document #203957).
• Optex X Zone T and X Zone ST Sensor(s) wiring.
• Push plate wiring.
• Door posion switch closed contact (with door closed).
• Hotron HR100 ST Sensor(s) wiring.
All rights reserved. Reproduction
4
TUNE-IN INSTRUCTIONS
Warning: The door path must be free of objects and remain clear unl the First Install Sequence (FIS)
is complete. During this sequence the sensors are inacve and the door has no SAFETY. To stop the door,
turn power off or put the doors into breakout.
NOTES:
1. Tune-In: The iQ Controller can be tuned-in using a handheld device or using the pushbuon switches
located on the controller. Tune-in using a handheld device is the preferred method.
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
4 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
2. Status Codes: During normal operaon, the digital display indicates status codes. The “UP” and “DOWN”
pushbuon switches can be used to enter and display data values. The user interface values are shown
in Tables 2 through 4.
iQ Control Box
PULLEY ROTATES CCW
WHILE OPENING
USE RIGHT HAND IN FIS
PULLEY ROTATES CW
WHILE OPENING
USE LEFT HAND IN FIS
RIGHT HAND
LEFT HAND
HANDING
3. Solenoid Lock: If a solenoid lock is installed with no lock circuit board (new style), set Lock Logic to the
actual lock type (Fail Safe or Fail Secure). If a Fail Safe or Fail Secure Lock is being installed with a lock circuit
board (old style), the Lock Logic must be set to Fail Secure.
4. Handing (For purpose of FIS only): Manually open door nong rotaon of belt pulleys. If counter clockwise (CCW)
use right hand during FIS. If clockwise (CW) use le hand during FIS. See gure below.
5. FIS: The rst installaon sequence (FIS) is used to perform the inial conguraon. Upon compleon of FIS, all
setup parameters are stored in non-volale memory. Subsequent power cycles will reload the
conguraon parameters that were congured during FIS.
6. Decimal points on digital display are encoder 1 signals. Rotang motor will cause decimal points to blink
and appear to dim.
7. Aer changing values, the values must be saved in non-volale memory by cycling the door to full open.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 5
01.25.2019
iQ Control Box
Tuning In the iQ Controller Using the Controller Pushbuttons
1. To change the INDEX and VALUE:
To show the INDEX press and hold ENTER, the current INDEX will display. Once ENTER is released, the display
will show the VALUE of that INDEX. Aer 2.5 seconds, the display will return to the current status code.
2. To change the INDEX:
Hold ENTER switch while pressing UP or DOWN to get desired INDEX.
3. To change a VALUE:
a. Unlock the keypad by seng index 99 to value 00.
b. Aer the desired INDEX is selected, release ENTER and within 2.5 seconds press UP or DOWN to get the
desired VALUE. (If the UP or DOWN buons are not pressed within 2.5 seconds of releasing the ENTER
buon, the display will change from the VALUE back to the STATUS.)
4. To display STATUS CODE:
A few seconds aer the VALUE is selected, the display indicates the STATUS CODE.
5. Refer to Tables 2 and 3 for a list of index seng descripons and values. Read the descripons enrely
before performing each step. Check the INDEX and VALUE aer each step.
6. To STORE CHANGES in permanent memory:
Cycling door open one me will store changes.
7. To LOCK keypad:
Lock keypad by seng index 99 to value 01 or by turning power OFF and then ON.
8. To ACCESS the door cycle counter funcon:
a. Ensure that the keypad is locked by seng index 99 to 01.
b. Ensure that the index is set to any index but 99.
c. Press the up or down key to access the door cycle counter.
The display will show “dc” followed by four pairs of digits, followed by “dc”.
Example: If the Door Count was 12345678 cycles the controller will display “dc” “12” “34” “56” “78” “dc”.
All rights reserved. Reproduction
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
6 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 1. FIS Procedure using Pushbuttons
StepDescriptionDisplay
IndexValueStatus Code
1Set Funcon Switch to Closed.
2Turn power on.
3Unlock keypad.990000
4Restart FIS.9601A0
5Select door type: Slide, 01 single motor or 02 dual motor.0001 (Single)
02 (Dual)
6Select Handing: 00 Right or 01 Le.
Manually open door and note rotation of belt pulleys.
If counterclockwise (CCW) use right hand during FIS.
If clockwise (CW) use left hand during FIS.
01
7Accept FIS. Display will go to A1. 0301A1
8Make changes: Funcon Switch
1101 (Rocker)
01 Rocker or 00 Rotary. The INDEX will start at 00.
NOTE: For locks with circuit board, set to 01 Fail Secure.
For locks with no circuit board, set to Fail Safe
or Fail Secure.
10
Warning: During this sequence the sensors are inactive and the door
has NO SAFETY. To stop the door, TURN POWER OFF or PUT THE DOOR
INTO BREAKOUT.
Function Switch: Switch to OPEN, momentarily, then CLOSED/
LOCKED. The door opens fully, delays and then closes fully.
The iQ displays A2 when FIS is completed.
11Aer FIS is complete it might be necessary to change index
11 (safety logic) and Index 20 (Safety Beam Type) to match
the systems installed.
Adjust any other index sengs as needed (refer to Table 3
for opons).
12Lock keypad.990100
13Final Tune-In.
Walk test doors to conrm compliance with applicable ANSI
Standards and local codes.
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 7
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
iQ Control Box
Table 2. Index List
IndexDescription
0 - 99Sengs Values, see Table 3.
90 - 95Reserved.
96Command – Restart FIS. Entering “01” will cause FIS to restart.
97Firmware – Entering “01” will display “FE” followed by two pairs of digits followed by “FE”. For example,
if the rmware was 0609 the controller will display “FE” “06” “09” “FE”.
98Command – Restart auto conguraon. Entering “01” sets the Control Box to “A1” keeping all previous
values and then re-learns the encoder count.
99*Command – Lock. Entering “01” will lock all value inputs except this index. This prevents inadvertent
changes to input values. Values may be unlocked by entering “00” in this index.
Table 3. Settings
IndexMin.
Value
0199*Open
1199*Close
All rights reserved. Reproduction
2199*Open
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Max
Value
Speed
Speed
Check
Speed
Open Speed is the speed used during normal operaon
in the opening state (02).
This speed is set to change how long it takes the door
to open.
This parameter sets the target speed seng. Other
parameters like open torque, open startup torque, open
startup length, and open acceleraon as well as door
properes like fricon, door length, and door weight
aect door speed.
Close Speed is the speed used during normal operaon in the
closing state (07).
This speed is set to change how long it takes the door
to close.
This parameter sets the target speed seng. Other
parameters like Close Torque, Close Startup Torque, Close
Startup Length, and Close Acceleraon as well as door
properes like fricon, door length, and door weight aect
door speed.
Open Check Speed is the speed used during normal
operaon in the open check state (04) prior to arriving at
full open.
This speed is set to determine how fast the door arrives at
full open aer open speed.
This parameter sets the target speed seng. Other
parameters like open check torque, open acceleraon,
and open braking as well as door properes like fricon,
door length, and door weight aect door speed.
Defaults
SingleDual
9999
3525
1010
NOTE: With the iQ Toolbox, the Max Values are 125.
Table 3 Settings continued next page.
01.25.2019
8 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
iQ Control Box
Table 3. Settings (continued)
IndexMin
Value
Max
Value
DescriptionDefaults
3599Open Check Length Open Check Length is the percent of door
length in which the door starts to slow down to
open check speed.
This parameter typically is adjusted based on
door weight and open speed seng.
4599Close Check Length Close Check Length is the percent of door length
in which the door starts to slow down to Close
Check Speed.
This parameter typically is adjusted based on
door weight and Close Speed seng.
5199Reduced Open
Length
Reduced Open Length is the percent of door length
from the full open posion the door will stop at if in
reduced open mode.
6199Hold Open DelayDelay that the door stays open aer all sensors
have cleared (0 to 25 seconds).
703Lock Logic Select to choose desired Lock Logic.
NOTE: Dura-Max 5400 logic is dierent and has
its own two opons:
00 = Fail Safe (unlocked when power
is removed),
01 = Fail Secure (locked when power
is removed),
02 = Dura-Max Fail Safe (unlocked when power
is removed),
03 = Dura-Max Fail Secure (locked when power
is removed).
8199*Open TorqueOpen Torque is the torque used during normal
operaon following the end of open startup
length.
SingleDual
4025
1515
11
1515
11
4045
This torque must be set to comply with BHMA/
ANSI door force requirements.
This parameter sets the maximum current
available to the motor which is directly
proporonal to the door force. This torque
seng is used in conjuncon with open speed.
Table 3 Settings continued next page.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 9
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
01.25.2019
Table 3. Settings (continued)
iQ Control Box
IndexMin
Value
Max
Value
DescriptionDefaults
9199Close Torque Close Torque is the torque used during normal
operaon following the end of Close Startup Length.
This torque must be set to comply with BHMA/ANSI
door force equirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force. This torque seng is used in
conjuncon with Close Speed.
10199Close Check
Torque
Close Check Torque is the torque used during normal
operaon in close check state.
This torque must be set to comply with BHMA/ANSI
door force requirements.
This parameter sets the maximum current available
to the motor which is directly proporonal to the
door force. This torque seng is used in conjuncon with close check speed.
1102Funcon
Switch Type
00 = Double pole rotary
01 = Rocker
02 = ICU
12012S Operaon; 00 = 2S mode disabled / normal
01 = Push switch to open, push switch to close;
SingleDual
3025
3525
11
00
13160Close
Obstrucon
Time
Close Obstrucon Time is the amount of me in
increments of 0.025s the door applies force when
almost stopped or stopped when the controller
indicates a state of “07”.
All rights reserved. Reproduction
Before increasing this parameter, check mechanical
issues, and speed and torque parameter sengs.
14040Open
Acceleraon
Open Acceleraon aects the rate at which the door
gets to its target speed.
This parameter is used when the door is lagging
open speed; open startup torque and open startup
length should be invesgated prior to increasing.
This parameter aects all open moon speeds: open
speed, open check speed, open learn speed, as well
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Table 3 Settings continued next page.
01.25.2019
10 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
as open braking.
5050
3030
iQ Control Box
Table 3. Settings (continued)
IndexMin
Value
Max ValueDescriptionDefaults
15110Open
Braking
16040Close
Acceleraon
17110Close
Braking
The Open Braking parameter adjusts
how quickly the door slows down prior
to check speed.
Increasing this parameter increases
braking power.
Close Acceleraon aects the rate at
which the door gets to its target speed.
This parameter is used when the door is
lagging close speed, close startup torque
and close startup length should be
invesgated prior to increasing.
This parameter aects all close moon
speeds: close speed, close check speed,
close learn speed, as well as close
braking.
The Close Braking parameter adjusts
how quickly the door slows down prior
to check speed.
SingleDual
88
2020
42
Increasing this parameter increases
braking power.
1806Delayed EgressSpecial Locking Applicaon. See the
Delay Egress Instrucon Manual for use.
00 = O
01 = 15 sec delay 1 second nuisance
02 = 30 sec delay 1 second nuisance
03 = 15 sec delay 2 second nuisance
04 = 30 sec delay 2 second nuisance
05 = 15 sec delay 3 second nuisance
06 = 30 sec delay 3 second nuisance
zone control (the threshold zone
is enabled and disabled by the iQ).
1 - Monitored 4 Sensors: Threshold
zone control (the threshold zone is
enabled and disabled by the iQ).
2 - Monitored StanGuard™: (not
recommended for Telescopic doors).
3 - Monitored 2 sensors.
4 - Non-monitored sensors.
5 - Monitored 4 sensors.
00
22
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Table 3 Settings continued next page.
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204144 REV B 11
01.25.2019
Table 3. Settings (continued)
iQ Control Box
IndexMin
Value
Max
Value
DescriptionDefaults
2001Hold Beam Type00 - Non-monitored Hold Beam
01 - Monitored Hold Beam
Selects the hold beam type to be used for
monitored or non-monitored applicaons.
For Monitored Hold Beams: Photobeam Pro or
Optex OSC12CT refer to wiring diagrams
per applicaon.
21150Lock Delay This allows the lock to mechanically unlock
before door moon. Lock Delay in 0.1 second
increments.
22099Open Stop DistanceDistance from full open that the door will stop.
This will be in 0.25” increments.
23199Close Check SpeedClose Check Speed is the speed used during
normal operaon in the close check state (09)
prior to arriving at full closed.
This speed is set to determine how fast the
door arrives at full closed aer close speed.
This parameter sets the target speed seng.
Other parameters like close check torque, close
acceleraon, and close braking as well as door
properes like fricon, door length, and door
weight aect door speed.
2401Access Control Pro
Enabled
Inside sensor lockout funcon.
00= OFF
01= ON
When set to 01-On, the interior acvaon input is inhibited if the exterior acvaon input
is acve. Acvaon override can be
accomplished through TB2 pin 9 and 10.
2505Close PressClose Press aects how the doors press
All rights reserved. Reproduction
together at full closed. If the value selected is
0, the door does not press at the closed
posion. A value of 1 will have a soer release
of motor energy and a value of 5 will be a
quicker release.
27199Lock Release TorqueLock Release Torque is the torque used on
lock release state. A closed posion switch is
required, connected to TB-5.
This parameter sets the maximum current
available to the motor which is directly
proporonal to the door force.
28160Close Check
Copyright 2019, Stanley Access Technologies, LLC.
in whole or in part without the express written permission of Stanley is prohibited.
Obstrucon Time
Close Check Obstrucon Time is the amount of
me in increments of 0.025s the door
applies force when almost stopped or stopped
when the controller indicates a state of “09”.
Before increasing this parameter, check
01.25.2019
mechanical issues, and speed and torque
parameter sengs.
SingleDual
11
11
44
88
00
22
2020
5050
12 Document # 204144 REV B • www.stanleyaccess.com • 1.800.7.ACCESS
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.