Stanley BRANDON 80K, BRANDON 100K Installation And Commissioning Instructions

Page 1
BRANDON
80K/100K GAS FIRED COOKER
TO BE INSTALLED BY A TRAINED COMPETENT PERSON
Installation and Commissioning Instructions
THIS MANUAL IS TO BE LEFT WITH END USER
Page 2
TABLE OF CONTENTS
PAGE NO.
2. Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5. Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6. Hearth Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8. Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
9. Flue Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
10. Pre-Installation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
11. Chimney’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
12. Sealing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
13. Flue Height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
14. Flue Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
15. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
16. Suitable Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
17. Flue Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
18. Use of Existing Chimneys and Flues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
19. Draught Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
20. Flue Liners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
21. Factory Made Insulated chimneys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
22. Ventilation and Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
23. Outside Air Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
24. Down Draughts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
25. Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
26. Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
27. Gas Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
28. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
29. Gas Pipes & Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
30. Water Pipe Fittings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
31. Water Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
32. Draining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
33. Internal Pump Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
34. Water Circuit Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
35. Care of your Central Heating System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
36. Indirect Domestic Cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
37. General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
38. Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
39. Safety Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
40. By-Pass Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
41. Heating Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
42. Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
43. Y Plan Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
44. Wiring Diagram S Plan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
45. 4 Zone Heating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
46. S Plan Wiring Using Same Timer For All Central Heating . . . . . . . . . . . . . . . . . . . . . . 20
47. S Plan Wiring Diagram Showing Zone Controlled by Underfloor Heating Zone . . . . . . 21
48. Commissioning Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
49. Commissioning of Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
50. Removal of Transport Screw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
51. Burner Fault Finding Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
52. 100K Boiler Burner Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
53. 80K Boiler Burner Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
54. 100K/80K Cooker Burner Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
55. Burner Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
56. Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
57. Door Handle Replacement Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1
Page 3
2
IMPORTANT NOTICE: Any alteration to this appliance that is not approved in writing by Waterford Stanley, will render the guarantee void.
The Installation must comply with the following:
The Building Regulations: Part J England & Wales, Part F Section 5 Scotland, Part LNorthern Ireland and Part J Ireland. B.S. 5449:Forced circulation hot water central heating system for domestic installation. B.S. 7671: Requirements for Electrical Regulations. Safety Document 635:The Electricity at Work Regulations. B.S. 7074: Part 1 &2: Hot Water Supply. B.S. 4814:Sealed Systems B.S. 7593: Treatment of Water in Domestic Hot Water Systems. B.S. 5440: Part 1 & 2: Installations & Maintenance of Flues and Ventilation. B.S. 6762: Services for Leisure Accommodation, Vehicles and Transportable Accommodation Units B.S. 6891: Pipe Sizing. I.S. 813: Domestic Gas Installation. PAS33: 1999: Product Assessment Specification for Design, Installation & Commissioning of Gas Fired Central Heating Systems in domestic premises.
IMPORTANT — Control of Substances Harmful to Health:
It is the Users/Installers responsibility to ensure that the necessary personal protective clothing is worn when handling materials that could be interpreted as being injurious to health and safety.
When handling Firebricks, Fire Cement, Fuels, use disposable gloves. Exercise caution and use disposable masks and gloves when handling glues and sealants. When working with fibre glass, mineral wool, insulation materials, ceramic blanket/board, avoid inhalation as it may be harmful. Avoid contact with skin, eyes, nose and throat, use disposable protection. Installation should be carried out in a well ventilated area.
Congratulations on purchasing this fine Irish made Gas-Fired Central Heating Appliance. It is built to exacting standards and it will give you every satisfaction in use. We invite you to read carefully the operating and installation instructions provided. This will enable you to familiarise yourself with this appliance.
In your own interest and that of safety, it is the law that all gas appliances are installed by competent persons in accordance with the Gas Safety Installation and Use Regulations.
Cookers can become very hot with use and retain their heat for a long period of time after use. Children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot surfaces or be in the vicinity when in use or until the appliance has thoroughly cooled down after use.
The complete installation must be done in accordance with current Standards and Local Codes. It should be noted that the requirements and these publications may be superseded during the life of this manual.
INTRODUCTION
As manufacturers and suppliers of cooking and heating appliances, we take every possible care to ensure, as reasonably practicable, that these appliances are so designed and constructed as to meet the general safety requirements when properly used and installed.
U.K.
Section 10 of the Consumer Protection Act. Gas Safety (Installation and Use) Regulations 1998 (as amended). Gas Appliance Safety Regulations (as amended). Health & Safety at Work Act
Ireland
Safety Health and Welfare at Work Act 1989. S.I. 101 of 1992 (as amended). S.I. 150 of 1995 (as amended).
Page 4
3
SPECIFICATION
FEATURE METRIC (mm)
Hot Plate 550W x 323L
Roasting Oven 390W x 310H x 406D
Simmering Oven: 390W x 220H x 406D
The manufacturers reserve the right to make alterations to design, materials or construction for manufacturing or other reasons subsequent to publication.
U.K.: ALL GAS APPLIANCES MUST BY LAW BE INSTALLED BY A COMPETENT PERSON, ONLY USE A C.O.R.G.I REGISTERED ENGINEER.
IRELAND: ALL GAS APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON AS OUTLINED IN I.S. 813.
THE APPLIANCE MUST BE CONNECTED TO A FULLY PUMPED SYSTEM.
Note: Dimensions stated in Fig.1 are in millimetres unless
otherwise stated and may be subject to a slight +/- variation.
Page 5
4
TECHNICAL DATA
FUELS: 2nd Family, Natural Gas PRODUCT IDENTIFICATION: 63AR5080 COUNTRY OF DESIGNATION: IE, GB GAS TYPES: N.G.: I2H, G20, 20 mbar (IE, GB) MAINS CURRENT: 230V - 240V, 50 Hz, A.C. SUPPLY FUSE RATING: 5 Amp. IONISATION CURRENT: Minimum of 7µa I.P. PROTECTION DEGREE: IP 20 ELECTRICAL INPUT: 90 watts. MAINS GAS PRESSURE: 20 mbar 8” wg
100K 80K
BOILER BURNER ­GAS RATE : 3 m3/ hr (106 ft3/ hr) 2.6m3/hr (91.8 ft3/hr) (Continuous running) COOKER BURNER:
GAS RATE: 1.65 m
3
/ hr (58 ft3 / hr) 1.65m3/hr (58 ft3/hr) (Continuous running) BOILER NOMINAL HEAT INPUT: 34.0 kW /116,008 Btu/hr 28 kW/95,536 Btu/hr OVEN NOMINAL HEAT INPUT: 17.60 kW/60,051 Btu/hr 17.6 kW/60,051 Btu/hr NOMINAL HEAT OUTPUT TO WATER Boiler Mode 28.7 kW/98,000 Btu/hr 23.8 kW/81,206 Btu/hr
Oven Mode 2.05 kW/7,000 Btu/hr 2.05 kW/7,000 Btu/hr
SPACE HEATING -Boiler Mode 0.70 kW/2,500 Btu/hr 0.7 kW/2,500 Btu/hr
Oven Mode 2.91 kW/10,000 Btu/hr 2.91 kW/10,000 Btu/hr
BOILER CAPACITY: 17 Litres (3.74 Gallons)
FLUE GAS TEMPERATURE: Boiler: 180°C (356°F) Cooker: 250°C. (482°F) BOILERCONSTRUCTION: 4mm &6mm mild steel plate BOILER TYPE: B23 MAX. BOILER WORKING PRESSURE: 1.9 Bar 27.3 P.S.I. TEST PRESSURE OF BOILER: 2.7 Bar 40 P.S.I. OPERATING TEMP. LIMIT IN BOILER: 96°C (205oF) COOKER WEIGHT: 380Kgs (838 lbs) FLUE CONNECTION: 6” (150mm) Diameter or FT 20 Fan Assisted Flue
Whilst the primary air is fixed and the gas rate has been set on this appliance, combustion tests and gas rating must be carried during commissioning and adjusted properly.
NOTE: This appliance shall be installed in accordance with the regulations in force and only used in a well ventilated location. Read the technical instructions before installing this appliance. Read the user’s instructions before lighting this appliance.
Differential Pressure Across the Boiler
Design flow rate through the boiler 38.2 L/min / 8.4 Gpm
Static differential across the boiler 52.4 mbar / 21” wg
Dynamic pressure differential across the boiler 33 mbar / 13.23” wg
Note: Design temperature differential across the boiler = 11°C (20°F)
Page 6
5
SCHEMATIC
1. Platerack (to order)
2. Splashback (to order)
3. Hotplate Covers
4. 150mm (6”) 90° Bend
5. Bend Cleaning Plate
6. Hob
7. Towel Rail
8. Firedoor
9. Burner Door
10. Main Oven Door
11. Simmer Oven Door
12. Boiler Tappings
13. Base Frame
14. Hotplate
15. Simmer and Cleaning Plate
16. Control Box Cover
17. Simmer Plate Cover
NOTE: These instructions are only valid if the country symbol appears on the appliance. If the symbol does not appear on the appliance it is necessary to refer to the technical instructions covering modifications of the appliance to the conditions of use of the country.
0558
Fig 1.
This appliance has been tested and approved in accordance with Gas Appliance Directive (90/396/EEC), the Low Voltage Directive (72/23/EEC) and the Electromagnetic Compatibility Directive (89/336/EEC) as amended.
Page 7
6
LOCATION
Prior to installation, ensure that the local distribution conditions (nature of the gas and gas pressure) and adjustment conditions are compatible. The adjustment conditions for this appliance are stated on the data badge which is fitted inside the bottom burner door.
When choosing a location for this appliance you must have:
(a) Sufficient room for the installation (see
clearances), a satisfactory flue (see flue system), and an adequate air supply for correct combustion and operation (see Ventilation & Combustion Air Requirements).
(b) Adequate space for maintenance and air
circulation.
(c) Solid floor or base of non-combustible material
which is capable of supporting the total weight. (see Technical Data).
HEARTH CONSTRUCTION
When a non-combustible floor surface is not available then we recommend that the cooker be placed on a slab of pre-cast concrete 40mm (11/2”) deep or a slab of other insulating material. This hearth must extend 150mm (6”) to either side of the appliance and 225mm (9”) to the front.
ELECTRICAL SUPPLY
All wiring external to the appliance must conform to the current BS 7671 (U.K.), B.S. 7462, &Safety Document 635, ETC: Part 1 section 5.6.4 & The Electricity at Work Regulations. The cooker requires a 230V - 240V, 50Hz supply. Connection of the appliance and any system controls to the mains supply must be through a moulded on plug top, (with a 5 Amp fuse fitted) which is fitted to the appliance in accordance with EN 60335, Consumer Protection, SI 1994 No. 1768, plug and sockets etc. (safety) Regulations 1994.
Always install in accordance with current local wiring regulations.
WARNING: THIS SUPPLY MUST BE EARTHED (Refer to B.S. 7430 : Code for
Practice of Earthing).
Where a risk of low voltage can occur, a voltage sensitive device should be fitted to prevent start up of the burner so as not to endanger the installation. Primary fuse is located in the control box tray.
To isolate the appliance completely unplug from the mains socket. Always ensure that this socket is easily accessible and close to the appliance.
Persons in charge of this appliance should be aware of this socket outlet position.
CLEARANCES TO COMBUSTIBLES
When bringing your kitchen units up to the sides of the cooker, leave a 10mm gap between the Stanley and adjacent units, this gap can be reduced by fitting an optional hob side filler strip to the Stanley leaving a 5mm gap (see fig. 2 & 3). Likewise the base of your units can be brought up flush to the Stanley’s built-in plinth.
When bringing the work top up to the side of the hob leave a 10mm gap to combustible material (see fig.2).
Fig 2
Fig 3
Fig.4
Where the flue passes through a combustible material a twin wall solid packed insulated chimney connector must be used and must come flush with the outer surface of the material and run all the way to the masonry chimney or to the point of termination of the factory made chimney. (See Fig.
4)
When installing a non combustible worktop, it is necessary to allow adequate clearance for the removal of the hob.
FLUE SYSTEMS
PRE-INSTALLATION CHECK
Before installing your appliance, check that the chimney is clean and clear of obstructions. Cracked brickwork and leaking joints should be made good. Where flue piping passes through a closure plate with a sliding door, ensure that the pipe continues up and is ultimately connected to the flue liner and well sealed with fire cement.
Page 8
Do not connect to a flue serving another appliance. Always ensure that the connection is to a chimney of the same size - never connect to one of smaller dimensions. Flues wholly constructed of single skin pipe are not recommended under any circumstances. Due to their inability to retain heat such flues will inevitably give rise to the formation of condensation.
Fig. 5
CHIMNEY’S
Generally the most effective chimney for gas is one that is straight, avoid offsets and terminate with a straight sided pot.
IT IS NOT RECOMMENDED TO CONNECT TO A FLUE SMALLER THAN 150MM (6”) OR IN EXCESS OF 175MM (7”) DIAMETER.
7
150mm (6”) Diameter Flue Liner
Note:
Fill voids and area around liner with vermiculite or a comparable approved material. (See Fig. 6 & 7)
Fig.6
Hotplate
Simmer Plate
Vermiculite or a Comparable Material
Pipe Bend Cleaning Plate
Seal Bend to Connecting Collar
Flex Pipe Adaptor
150mm (6”) Flexible Flue Liner
Fire Sealing Cement
Closure Plate
Cleaning Plate
Flue Diameter of 150mm (6”)
Page 9
8
SEALING
This cooker and flue system operate under a positive pressure, it is essential that all flue joints are tightly sealed against flue gas leakage and tested accordingly (see Fig. 8).
There is a flue pipe collar available which surrounds the flue pipe where it meets the wall, giving a tidier finish to a tiled background (see fig. 9). The hob back filler piece and flue pipe collar rosette is available as an optional extra. (see fig. 9).
Flue greater than 150mm
(6”) Diameter
Fig. 7
NOTE: Never connect to a chimney or flue system serving another appliance.
Fig.8
Fig.8a
FLUE HEIGHT
The flue must be high enough 4.5 mts. (15ft) minimum measured vertically from the appliance outlet to the top of the flue terminal, to allow the flue gases to vent into the clear air, away from the turbulence that may be caused by roof structures, other chimney stacks, etc. The terminal position should be in accordance with B.S. 5440 Part 1 and the Building Regulations:
FLUE SYSTEM
Where the standard masonry chimney is not available, a proprietary type of non-combustible or non-corrosive material 150mm (6”) twin wall fully insulated pipe may be used. The pipe must terminate at a point not lower than the main ridge or adjacent outside obstructions. With such installations, access to the chimney must be provided for cleaning purposes.
Fig.9
Refer to Flue Assembly Instruction sheets.
Approved Flue Terminal
Vermiculite Filler or comparable material
Flexible Flue Liner 150mm (6”)
Clay Liner
Sealing & Clamping Plate
Seal Flue Connector
Page 10
9
Horizontal runs more than 450mm (18”) and 90° bends numbering more than 2 per installation should be avoided. If it is necessary to offset the chimney the recommended angle is 60° to the horizontal and the statutory minimum is 45° (see fig. 10).
CONNECTIONS
A cast iron 90° bend with cleaning door is available with the cooker. A vertical cast iron outlet pipe with cleaning door is also available. A flexible flue adaptor is supplied, this is to connect the cooker 150mm (6”) bend or straight pipe to the 150mm (6”) chimney liner.
ALL FLUE CONNECTIONS MUST BE THOROUGHLY SEALED. Blocked chimneys are
dangerous, keep chimneys and flueways clean, read the operating instructions.
STANLEY CAST IRON PIPES AND BENDS ARE HIGHLY RECOMMENDED FOR INTERIOR USE.
WHERE THE APPLIANCE SPIGOT OR FLUE PIPE PROTRUDES INTO THE CHIMNEY, CARE SHOULD BE TAKEN TO ENSURE THAT IT DOES NOT BLOCK THE CHIMNEY.
SUITABLE MATERIALS
* Mineral Fibre cement pipes conforming to B.S.
7435.
* Sheet metal conforming to B.S. 715. & B.S.
4076.
* Insulated metal chimneys conforming to B.S.
4543 and B.S. 5440 (a galvanised finish is not
suitable). * Clay flue linings conforming to B.S. EN 1457. * Pre-cast concrete chimney blocks,
incorporated into the building structure. It is
particularly important that the correct
connection block be provided at the base of the
flue, B.S. 3572. * Cast Iron or acid resistant vitreous enamel lined
mild steel to B.S. 41.
FLUE CLEANING
The flue pipe must be fitted with a cleaning plate. The flue must be inspected annually and cleaned when necessary.
Fig. 10
USE OF EXISTING FLUES AND CHIMNEYS
When connecting to an existing chimney it is necessary to line the flue using approved 150mm (6”) rigid or flexible stainless steel flue liner.
An existing flue pipe or chimney that has proved to be satisfactory when used for solid fuel can normally be used for this appliance provided that its construction, condition and dimensions are acceptable. Flues that have proved to be unsatisfactory, particularly with regard to down draught, must not be considered for this appliance until they have been examined and any faults corrected. If there is any doubt about an existing chimney a smoke test to B.S. 5440: Part 1 should be carried out.
Before connecting this appliance to a chimney or flue pipe which has previously been used with another fuel, the chimney or flue pipe should be thoroughly swept and lined accordingly.
All register plates, restrictor plates, damper etc. which could obstruct the flue at a future date should be removed before connecting this appliance.
Where a chimney is not to be lined a suitable void should be provided at the base to contain any debris which might fall from the inside wall, so as to prevent debris from obstructing the appliance flue outlet. (Removal of debris should be facilitated by the provision of an access door). The void should have a depth of not less than 250mm (10”) below the appliance connection.
The combustion products from this appliance will have a descaling effect on hardened soot deposits left from burning solid fuels.
ALTHOUGH THE CHIMNEY MAY HAVE BEEN CLEANED OF LOOSE SOOT PRIOR TO INSTALLATION, IT IS IMPERATIVE THAT THE CHIMNEY IS INSPECTED FOR SCALED SOOT PARTICLES AFTER THE FIRST MONTH OF OPERATION AND ANY LOOSE MATERIALS REMOVED TO AVOID BLOCKAGE.
DRAUGHT REQUIREMENTS
While inadequate draught can seriously effect the efficient operation of the appliance, chimneys over (5.4m) 18ft or houses built on high ground can experience excessive draught, a steady draught of between 1mm (0.04”) and 1.5mm (0.06”) W.G. is required for satisfactory operation.
FLUE LINERS
Chimney’s lined with salt glazed earthenware pipes are acceptable if the pipes comply with BS EN 1457 and must be 150mm (6”). When lining an existing chimney, a liner approved to BS 715 and BS 4543,
Page 11
10
VENTILATION AND COMBUSTION AIR REQUIREMENTS
It is imperative that there is sufficient air supply to the burners of the cooker in order to support combustion.
Detailed recommendations for air supply are given in BS 5440 Part 2. The minimum effective air requirement for this appliance is 215 cm2(100K) or 185cm2(80K). When calculating combustion air requirements for this appliance use the following equation: 5cm2per each kW of rated input above 7 kW.
If there is another combustion appliance fitted in the same or adjacent room, it will be necessary to refer to B.S. 5440: Part 2 to calculate the additional air supply.
All materials used in the manufacture of air vents should be such that the vent is dimensionally stable and corrosion resistant.
The effective free area of any vent should be ascertained before installation. The effect of any screen or grills should be allowed for when determining the effective free area of any vent.
Air vents direct to the outside of the building should be located so that any air current produced will not pass through normally occupied areas of the room.
An air vent outside the building should not be located less than the dimensions specified within the Building Regulations (see Technical Data) from any
FACTORY MADE INSULATED CHIMNEYS
Factory-made insulated chimneys should be constructed and tested to meet the relevant standards and recommendations given in:
* B.S. 7566 - Installation of factory-made
chimneys conforming to B.S. 4543 for
domestic appliances.
Part 1: Method of specifying installations
design information.
Part 2: Specification for installation design.
Part 3: Specification for site installation.
Part 4: Recommendation for installation
design and installation.
Parts 1, 2 &3 should be used. The liner should be secured at the top and bottom by using closure/ clamping plate firmly sealed and secured and an approved low resistance terminal used at the top.
It is essential that every flue system be inspected and tested by a competent person for its correct effectiveness, to ensure that the combustion products are completely discharged to the outside atmosphere.
part of any flue terminal. These air vents must also be satisfactorily fire proofed as per Building Regulations.
Air vents in internal walls should not communicate with bedrooms, bedsits, toilets, bathrooms or rooms containing a shower.
Air vents traversing cavity walls should include a continuous duct across the cavity. The duct should be installed in such a manner as not to impair the weather resistance of the cavity.
Joints between air vents and outside walls should be sealed to prevent the ingress of moisture. Existing air vents should be of the correct size and unobstructed for the appliance in use.
If there is an air extraction fan fitted in the room or adjacent rooms where this appliance is fitted, additional air vents will be required to alleviate the possibility of spillage of products of combustion from the appliance/flue while the fan is in operation. Refer B.S. 5440 Part 2, I.S. 813 and the Gas Safety (Installation & Use) Regulations as amended.
Where such an installation exists, a test for spillage should be made with the fan or fans and other gas burning appliances in operation at full rate. (i.e. extraction fans, tumble dryers) with all external doors and windows closed.
If spillage occurs following the above operation, an additional air vent of sufficient size to prevent this occurrence should be installed.
OUTSIDE AIR CONNECTION
If this option is used additional air as indicated in BS 5440, Part 2 is not required.
1. This appliance may be connected direct to the outside of the house for its combustion air supply.
2. Remove the blanking plate located at the back right hand corner and remove the primary air grill located at the front and right hand corner. Fix blanking plates over the front primary air inlet. (See fig. 12 & 13) and the right hand side primary air inlet.
3. Connect the optional 125mm (5”) spigot to the base, see fig. 13.
4. To connect this appliance to an outside air supply use either 125mm (5”) rigid or flexible stainless steel pipes or non-combustible corrosion-resistant materials not more than 965mm (38”) in length and having no sharp bends or corners other than the down turn at the terminus.
Page 12
11
DOWN DRAUGHTS
However well designed, constructed and positioned, the satisfactory performance of the flue can be adversely affected by down draught caused by nearby hills, adjacent tall buildings or trees. These can deflect wind to blow directly down the flue to create a zone of high pressure over the terminal.
A suitable anti-down draught terminal or cowl will usually effectively combat direct down blow but no cowl is likely to prevent down draught due to a high pressure zone. Ensure that any cowl used will not restrict the flue exit or cause excessive back pressure. (See fig. 14)
Fig.12
Fig. 13
5. Air inlets traversing cavity walls should include a continuous duct across the cavity. The duct should be installed in such a manner as not to impair the weather resistance of the cavity.
6. Joints between air vents and outside walls should be sealed to prevent ingress of moisture.
Fig. 14
HEATING
METERS
A suitable gas meter must be connected to the service pipe either by a representative of the gas supplier or by an appointed contractor. If using an
Fig.11
Outside Air Spigot ­(Not Supplied)
Air Inlet Blanking Plate
Page 13
12
GAS CONNECTION
A combined elbow and shut off valve fitting is packed in the oven. This should be fitted to the appliance as in Fig.15. which shows the valve in the ‘on’ position. To close the valve use a large flat screw-driver on the screw and turn through 90 degrees in a clockwise direction.
GAS PIPES AND FITTINGS
Materials used for installation work should be fire resistant and gas tight and should conform to the following or their equivalent.
Fig.15
* B.S. 2871: Part 1 and EN 1057 - Copper
Tubes * B.S. 219, EN 29453 & ISO 9453 - soft solders. * B.S. 669 - flexible hoses, fittings & sockets. * B.S. 759 - Valves, gauges and other safety
equipment. * B.S. 1387 - Steel tubes. * B.S. 6362 & B.S. 4127 - Stainless steel tubes. * B.S. 1740 - Wrought steel pipes. * B.S. 4089 - LPG hoses and assemblies. * B.S. 5295 & B.S. 6956 Jointing materials. * B.S. 1552 Manual shut off valves.
WATER PIPE FITTINGS
Materials used for installation work should be fire resistant, sound and should conform to the current editions of the following or equivalent.
EXCESS PIPE COMPOUNDS
Fig 16
NOTE: Clean off any excess pipe compounds from connections.
WATER PIPE SIZE
The flow and return pipe must be 28mm diameter. Care should be taken to ensure that the heating system is correctly installed and that it complies with all relevant codes of practice. If this appliance is being connected to an existing system, it is strongly recommended to check the following:
(a) That the system is sound.
(b) That pipework is adequately insulated (where
applicable).
(c) Check all controls, i.e. pump, motorised valves,
time control etc. are operating satisfactorily and are compatible with the requirements of the cooker.
(d) Are any modifications necessary to make the
heating system more efficient?
(e) Cleanse the system and add suitable inhibitor.
1.1 Ferrous Materials
BS 1387 Steel tubes.
BS 1740 Steel pipe fittings.
BS 6956 Jointing materials.
1.2 Non-Ferrous Materials
EN 29453 Soft Solder Alloys.
BS 864 Compression Tube Fittings.
BS 2871 & BS EN 1057 Copper and Copper
Alloys
WARNING: To avoid pipe sealing compounds from entering into the gas train, do not apply sealing compound to the first two threads at the tip of the gas connection.
existing meter have it checked to ensure that the meter is capable of dealing with the total rate of gas supply needed (see Technical Data).
GAS PIPE SIZE
It is important that the correct service pipe size be used in order to ensure an adequate gas supply (200 Cubic ft./hr. (5.66 m3/hr) Natural Gas). This depends on the distance between the supply meter, the pressure drops caused by bends and the expected pressure drop in the gas mains at peak demand times.
A Flexible hose must not be used to connect the gas supply to the cooker.
Check all joints for gas tightness and ensure that any excess jointing compounds are cleared from the connection
Page 14
13
DRAINING
Key-operated drain taps to BS 2879 should be provided in accessible positions in all low parts of the system. However, it should be noted that there may be short sections of pipework, e.g. when passing under doorways, that may not be possible to drain.
INTERNAL PUMP THERMOSTAT
This appliance has the capability for switching the circulating pump ‘on’ and ‘off’ automatically. To wire in the pump, connect the phase to terminal marked CIRC Pump (L) and connect the Neutral to terminal marked CIRC Pump (N). The earth wire is to be connected into the earth block.
The connection circuit board/control panel is located within the appliance beneath the warming oven. (See Fig.18)
Fig. 17
The use of motorised valves, room thermostats, radiator thermostatic valves, domestic hot water controllers, etc, can greatly enhance a heating system and we recommend their use.
Only approved competent personnel should be employed to carry out the heating installation.
It is important that no external control devices e.g. economiser be directly fitted to this appliance unless covered by these installation instructions or agreed with the manufacturer in writing. Any direct connection of a control device not approved by the manufacturer could make the guarantee void.
The flow and return can be taken either side of the cooker. (See Fig. 17)
1. To take off from the left simply connect direct onto the exposed boiler connection.
2. To take off from the right side:
a. Remove the two blanking plates at the back of
the cooker. Then punch out the two blanking plates on the right hand side.
b. Using some copper pipe, punch out a passage
way through the insulation material to the boiler connections.
c. Clear insulation away from the boiler
connections.
d. To avoid insulation from going into the flow
and return pipe, blank off ends using insulating tape before passing through cooker.
e. Remove insulating tape and connect to boiler.
f. Replace blanking plates.
g. Test for leaks.
WATER CIRCUIT TEMPERATURE
The return water temperature must be maintained at not less than 50oC (122oF) so as to avoid condensation forming within the boiler.
CARE FOR YOUR CENTRAL HEATING SYSTEM
We strongly recommend the use of suitable corrosion inhibitors and anti-freeze solution in your heating system, in an effort to minimise black oxide, sludge and scale build-up, which effects efficiency.
In hard water areas the use of a suitable limescale preventer / remover is advised.
Use only quantities specified by the water treatment product manufacturer. Only add to the heating system after flushing and finally refilling. Refer to BS 7953.
INDIRECT DOMESTIC CYLINDER
The cooker must only be connected to an indirect cylinder of no less than 180 litres using 28mm diameter flow and return piping. It is recommended that the cylinder is lagged together with pipework with runs in excess of 4 meters (12’).
Fig. 18
Blanking Plates
50mm Knockouts RH Boiler Connections
Page 15
14
BY-PASS LOOP
A 15mm system by-pass must be fitted not less than 1.5mts (4.9ft) from the cooker to allow correct water circulation for the pump and to prevent condensation forming in the boiler. This should be balanced. A heat leak radiator / towel rail may be installed if desired. (See Fig. 19 & 20) in addition to the by-pass.
Fig.19
The following diagrams illustrate the different types of central heating systems to which this appliance can be connected, but are not to be used as working drawings.
Fig. 20
GENERAL MAINTENANCE
It is important that the user is familiar with their heating system and that they ensure regular checks and maintenance which can limit unnecessary break-downs.
We recommend that you evaluate the overall insulation in your house, i.e. attic, external walls, windows and external doors. Insulation and draught-proofing can greatly reduce running costs while equally enhancing living conditions.
NOTE: We strongly advise the use of pipe lagging and also the use of a frost thermostat if the installation is likely to be exposed to situations where the temperature will dip to a level consistent with frost.
SERVICING
To ensure continued efficient and safe operation of the appliance, it is recommended that it is checked and serviced by an Authorised Stanley Service Engineer at least once a year.
NOTE: As the valve and the venturi come preset, if either need to be replaced then it will be necessary to purchase a valve and venturi combined preset from the manufacturer.
SAFETY VALVE
A non-adjustable 3 bar safety valve must be fitted to the primary flow pipe adjacent to boiler connection ensuring that any discharge will not create a hazard to occupants or cause damage to electrical components or property.
OPEN SYSTEM (WITH PUMP ON RETURN)
Safety Valve 28mm Flow Pipe
By-pass Lock Shield Valve
Pump
28mm Return
1.5m
By-pass not less than 1.5
meters from the cooker
Page 16
15
Fig. 21
SEALED SYSTEM (WITH PUMP ON FLOW)
Fig.22
OPEN SYSTEM (WITH PUMP ON FLOW)
Page 17
16
Fig.23
PROVISION FOR FILLING SEALED SYSTEM
Fig.24
TEMPORARY HOSE (Must be disconnected after filling)
INTERLINK SYSTEM
S PLAN SYSTEM
Fig.25
Page 18
17
WIRING DIAGRAM GAS 100K / 80K Fig. 26
Page 19
18
EARTH
MAINS
EARTH POST
NEUTRAL
LIVE
FLUE FAN
INTERSTAT
PUMP L
PUMP N
NEUTRAL
GREEN/YELL
WHITE
BLUE
GREY
HON EY WEL L
V4073A
L641A
Cyl.Stat
T6360B
Room Stat
ORANGE
HEATING Timer
DHW Timer
NO DHW Timer
Boiler Run
Brandon
TERMINALS
WIRING
CENTRE
PERMANENT
(FUSED) LIVE
PUMP
C
2
3
1
2
Y - PLAN WIRING DIAGRAM Fig.27
Note:
It is essential that the interstat can bring on the
motorised valves directly as shown, failure to observe
this will result in nuisance lockout.
Please Note:
EARTHS NOT SHOWN FOR CLARITY
CONNECT EARTHS IN ACCORDANCE
WITH REGULATIONS!
If wires are a different colour
code, please refer to the
manufacturers instructions.
1
2
4
5
6
7
8
9
10
11
12
13
3
Page 20
19
S PLAN WIRING DIAGRAM USING MULTI TIMER FOR ALL CENTRAL HEATING ZONES Fig. 28
EARTH
MAINS
EARTH POST
NEUTRAL
LIVE
FLUE FAN
INTERSTAT
PUMP L
PUMP N
NEUTRAL
HEATING Timer
DHW Timer
NO DHW Timer
Boiler Run
Brandon
TERMINALS
WIRING
CENTRE
PERMANENT
(FUSED) LIVE
BROWN
BROWN
GREY
GREY
GREY
GREY
BLUE
BLUE
GREY
BLUE
BROWN
BROWN
ORANGE
Note:
It is essential that the interstat can bring on one of the motorised valves
directly as shown, failure to observe this will result in nuisance lockout.
Please Note:
EARTHS NOT SHOWN FOR CLARITY
CONNECT EARTHS IN ACCORDANCE
WITH REGULATIONS!
BROWN
T6360B
Room Stat
T6360B
Room Stat
T6360B
Room Stat
L641A
Cyl. Stat
Motorised Valve
Domestic Hot Water
Motorised Valve
Wet Heating ZONE 1
Motorised Valve
Wet Heating ZONE 2
Motorised Valve
Wet Heating ZONE 3
If wires are a different colour
code, please refer to the
manufacturers instructions.
1
2
4
5
6
7
8
9
10
11
12
13
3
Page 21
20
4 ZONE HEATING SYSTEM
When connecting the a Brandon cooker to a 4 ­zoned heating system (i.e. separate time switches and thermostats for domestic hot water and four central heating zones), the domestic hot water and one zone must be controlled directly from the cooker enabling the inter thermostat to operate if necessary. All other zones can be controlled from the cooker where a constant live supply must be connected to the time clocks only (see figure 27).
Under no circumstances can other supply sources be connected directly to the cooker.
4 ZONE HEATING SYSTEM
EARTH
EARTH POST
MAINS
NEUTRAL
LIVE
FLUE FAN
INTERSTAT
PUMP L
PUMP N
NEUTRAL
HEATING Timer
DHW Timer
NO DHW Timer
Boiler Run
Brandon
TERMINALS
WIRING
CENTRE
PERMANENT
(FUSED) LIVE
PUMP
If wires are a different colour
code, please refer to the
manufacturers instructions.
L641A
Cyl.Stat
T6360B
Room Stat
T6360B
Room Stat
T6360B
Room Stat
Motorised Valve
Domestic Hot Water
Motorised Valve
WET HEATING ZONE 1
Motorised Valve
WET HEATING ZONE 2
Motorised Valve
WET HEATING ZONE 3
c
1
2
3
2
3
2
2
3
M
M
M
M
Blue
Blue
Blue
Brown
Brown
Brown
Orange
Grey
Grey
Grey
Grey
Brown
S PLAN WIRING DIAGRAM USING SAME TIMER FOR ALL CENTRAL HEATING
ZONES Fig. 29
1
2
4
5
6
7
8
9
10
11
12
13
3
Page 22
21
S PLAN WIRING DIAGRAM SHOWING ZONE CONTROLLED BY UNDERFLOOR HEATING ZONE Fig.30
EARTH
PUMP
M
L641A
Cyl.Stat
T6360B
Room Stat
Motorised Valve WET
HEATING ZONE 1
ZONE 2 UNDERFLOOR
HEATING SYSTEM &
CONTROL
Motorised Valve
Domestic Hot Water
EARTH POST
MAINS
Brandon
TERMINALS
WIRING
CENTRE
NEUTRAL
LIVE
FLUE FAN
INTERSTAT
PUMP L
PUMP N
NEUTRAL
HEATING Timer
DHW Timer
NO DHW Timer
Boiler Run
PERMANENT
(FUSED) LIVE
M
Orange
Grey
Grey
Brown
Brown
Brown
Blue
Blue
Grey
Orange
Orange
1
2
4
5
6
7
8
9
10
11
12
13
3
Page 23
22
COMMISSIONING CHECKS
1. Check all items of packaging are removed from ovens and the shelves are properly fitted.
2. Check that electrical wiring is correct.
3. Check that boiler and heating system is full of water and purged of air.
4. Check that boiler plate transport screw has been removed and that the plates are in their correct positions. (See section Removal of Transport Screw and Fig.32)
5. Time switches and room thermostats must be on.
6. Check that the boiler thermistor and oven thermocouple are functional.
7. Connect burners to gas lines making sure that the connection is straight and properly connected.
8. Check that the mains Natural Gas supply line is capable of supplying sufficient amounts for running both of the burners simultaneously.
9. Turn on the mains Natural Gas supply ensuring that the cooker is switched off. Test the whole gas installation including the meter for soundness and purge in accordance with B.S. 6891 (U.K.) and I.S. 813 (I.E.), purge not to exceed 50 mbar.
10. Check the gas supply and burners for escapes using an approved leak detector spray and tighten if necessary.
13. With the mains Natural Gas supply off switch on the burners.
14. Complete the start sequence to lock out observing the correct operating functions.
15. Pre-purge time to run for up to 30 seconds.
16. Reinstate the gas supply and switch on the burners to ensure that they fire correctly.
17. With the cooker operating on full flame check for adequate gas supply by connecting a water manometer to the gas point on the gas train.
18. When commissioning ensure that all doors of the appliance are closed while in operation.
19. Check that the interstat connection has been wired directly to a motorised valve. This is done by turning off room thermostats, time switches and temporarily linking terminals 6 & 9. This should bring on a motorised valve which will then call the boiler.
Note: When the interstat calls; normally the motorised valve will open, but the burner will not operate as the supply to No.6 will be disabled.
20. After a minimum of 15 minutes of continuous operation with each burner still running, check flue gas analysis.
21. Check temperature differential between flow and return 11°C (20°F) and adjust pump or by­pass accordingly.
22. Check heating circuit and balance if necessary.
23. Make sure specified clearances are adhered to.
24. A spillage test should be then carried out with all external doors and windows closed and all extract fans and any other appliances requiring air in full operation.
25. Check flue joints are sealed correctly and that no escapes are occurring.
26. Check flue joints are sealed correctly and no escapes are occurring.
27. Check that the ignition electrodes and ionisation probes on each burner are set correctly.
28. Check the ionisation current on both burners.
29. If the cooker is not operating correctly, refer to the trouble shooting guide and/or the Manufacturers Technical Section.
30. IMPORTANT Check that the mains cable anti-lug gland located at the left side of the cooker at base level in service and tightened if required.
31. Refer to the Operation Instructions Manual for correct operation of the appliance and familiarise the occupants on the correct method of operating the appliance.
Page 24
23
COMMISSIONING OF BURNERS
Both burners used in the Brandon Cooker are fully pre-mixed burners, thus allowing very silent operation and excellent combustion. The burner controls are fully independent for each burner.
The following checks must be carried out when commissioning the burners.
1. Gas Pressures & Rates
The inlet pressure at the pressure test point on the gas train must be measured when the cooker is off and when both burners are running. This pressure should be approximately 20 mbar when both burners are running.
Measure the gas rate on each burner while it is operating alone. The gas rate is dependent on the volume of air being pulled through the venturi, therefore it is essential to have the flue fully connected when rating each burner. If the cooker is fitted with a fan flue ensure the draught is between 1-1.5 mm W.G. when rating the burners. If necessary it is possible to adjust the gas rate using the rate adjustment screw on the venturi (see fig.31). Tighten the screw to reduce the rate and loosen the screw to increase the rate, the adjustment of the rate will also create a change in CO2. As there is no air adjuster on the burner it is essential to monitor the CO2 when adjusting the rate.
Boiler Cooker
Inlet Pressure 20mbar 20mbar
CO2 Range 8.6 - 9.2 9.0 - 9.6
Ionisation Current 7µ Amps min 7µ Amps min
Co. Max 50ppm 50ppm
REMOVAL OF TRANSPORT SCREWS
Remove the hotplate and boiler top plate. Remove retaining screws from boiler plates. Check that all plates have remained in their correct positions and that no debris has accumulated on them during transport. Replace boiler top plate and hotplate ensuring that all seals are intact. See fig. 32.
Fig.32
Commissioning Table
2. Ionisation Current
The ionisation current for each burner must be measured. This is done by removing the ionisation lead from the control box and connecting an ammeter in series.
Fig 31
Page 25
24
Call for heat from timer or thermostat.
Allow 10 seconds to pass and then press either reset buttons. The lockout lights will go out and the ignition sequence will start. The control system waits 30 seconds before attempting to relight.
During the 5 second ignition period, pins 4 & 6 on the S4565AD control box will become live and a spark from the electrode can be heard.
Replace the S4565AD Control Box.
Burner Fault Finding Sequence
Starting point, call for heat but no main burner ignition
Ignition board S4565AD
Is the fan running?
Are the lockout lights on?
Does the burner light?
Are live and neutral
correctly connected?
Is the appliance earthed
correctly?
Is the valve energised?
Is there 230V ac
between pins 10 & 11
of the S4565AD
Control Box?
The ignition control is either running normally or is in an ignition attempt.
Measure between Live and Neutral (230V ac) Pin 10 to pin 11 on the S4565AD control box.
Measure between Live and Earth (230Vac) Pin 10 to Pin 12 on the S4565AD control box.
Measure between Neutral and Earth (0 to 15Vac) Pin 11 to pin 12 on the S4565AD control box.
Correct wiring if necessary.
Measure resistance between pin 12 on the S4565AD control box and a known Earth point (not on the appliance) Resistance must be less than 10 Ohms.
Correct wiring if necessary.
Check Wiring
Check for 230V ac to the fan motor.
NOTE
When working correctly the gas valve will not pass gas unless the fan is running.
WARNING
The gas controls fitted are unique to advanced premix burner systems, they are pre-set in the factory and to not require adjustment. They MUSTNOT be adjusted unless suitable test equipment is available.
Is there a spark between the b ent ignition electrode and the shorter straight earth electrode?
Check for continuity between pins 4 & 6 on the control box.
Check insulation of lead and electrode position
Check flue for adequate draught . Check temperature switch and wiring.
Check the val ve ports, if necessary replace the ignition board.
Check for gas at the inlet test point and purge air from gas line. If necessar y rep lace the gas valve.
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Page 26
25
100K BOILER BURNER EXPLODED VIEW
Page 27
80K BOILER BURNER EXPLODED VIEW
26
Page 28
100K/80K COOKER BURNER EXPLODED VIEW
27
Page 29
BURNER tech Burner Parts List 100K 80K
Boiler
Burner - DESCRIPTION PART NO. BOM CODE PART NO. BOM CODE QTY
Burner Head 51005 D00134AXX 51005 D00134AXX 1
Boiler Mounting Plate Gasket 88014 D00135AXX 88014 D00135AXX 1
Burner Head Gasket 88018 D00136AXX 88018 D00136AXX 1
Boiler Mounting Plate 71007 D00137AXX 71007 D00137AXX 1
Boiler Adaptor Manifold Gasket 88015 D00138AXX 88015 D00138AXX 1
Boiler Adaptor Manifold 77004 D00139AXX 77004 D00139AXX 1
Electrode Assembly Gasket 88023 D00140AXX 88023 D00140AXX 1
Electrode Assembly 41005 D00161AXX 41005 D00161AXX 1
RG 148 Fan Assembly 20004 D00142AXX 20004 D00142AXX 1
Fan Gasket 88040 D00143AXX 88040 D00143AXX 1
Restrictor Plate 71022 D00144AXX 71023 D00154AXX 1
Ignition Cable 31001 D00145AXX 31001 D00145AXX 1
Ionisation Cable 32002 D00146AXX 32002 D00146AXX 1
Earth Cable 31003 D00147AXX 31003 D00147AXX 1
Gas Valve Assembly 03001 D00148AXX 03001 D00148AXX 1
Control Box 06004 D00149AXX 06004 D00149AXX 1
Venturi Gasket 88009 D00150AXX 88009 D00150AXX 1
Venturi Manifold Assembly 60001 D00151AXX 60002 D00155AXX 1
Filter Assembly 92012 D00152AXX 92012 D00152AXX 1
Venturi Side Mounting Gasket 88005 D00153AXX 88005 D00153AXX 1
BURNER tech Burner Parts List - Oven Burner 100K 80K
DESCRIPTION
PART NO. BOM CODE QTY
End Firing Burner Head 51006 D00156AXX 1
Cooker Mounting Plate Gasket 88012 D00157AXX 1
Burner Head Gasket 88018 D00136AXX 1
Cooker Mounting Plate 71006 D00158AXX 1
Cooker Adaptor Manifold Gasket 88013 D00159AXX 1
Cooker Adaptor Manifold 77003 D00160AXX 1
Fan Gasket 88040 D00143AXX 1
Electrode Assembly Gasket 88023 D00140AXX 1
Electrode Assembly 41004 D00161AXX 1
RG 130 Fan Assembly 20005 D00162AXX 1
Ignition Cable 31001 D00145AXX 1
Ionisation Cable 32002 D00146AXX 1
Earth Cable 31003 D00147AXX 1
Gas Valve Assembly 03001 D00148AXX 1
Control Box 06004 D00149AXX 1
Venturi Gasket 88009 D00150AXX 1
Venturi Manifold Assembly 60007 D00163AXX 1
Filter Assembly 92010 D00164AXX 1
Venturi Side Mounting Gasket 88005 D00153AXX 1
28
Page 30
INSTALLATION CHECK LIST
Flue System
The relevant guidelines must be adhered to for the relevant flue system A, B & C:
A. Use of an Existing Chimney
1. If connecting to an existing chimney, the appliance should be connected to a 150mm (6”) diameter continuous, rigid or flexible flue pipe suitable for gas-fired appliances that terminates in excess of 0.6 metres from the nearest point on the roof measured vertically, and in excess of 2.3 metres measured horizontally.
2. Minimum Flue Height of 4.6 metres (15 feet).
3. Any horizontal flue sections should not exceed 450mm (18”).
4. The chimney serving this appliance should not serve any other appliance.
5. A suitable flue terminal should be fitted at the flue termination point.
6. Closure-clamping plates should be used to seal the top & bottom of the chimney.
7. If the flue passes through a combustible wall, a twin wall insulated connector must be used and come flush to the external surface of the wall.
8. The flue should be capable of producing a continuous draught of between 0.04” to 0.06” w.g.
B. Use of an External Flue
1. If using an external flue, the appliance should be connected to a 150mm (6”) diameter rigid insulated flue pipe suitable for gas-fired appliances that terminates in excess of 0.6 metres from the nearest point on the roof measured vertically and in excess of 2.3 metres measured horizontally.
2. Minimum Flue Height of 4.6 metres (15 feet).
3. Any horizontal flue sections should not exceed 450mm (18”).
4. The chimney serving this appliance should not serve any other appliance.
5. A suitable flue terminal should be fitted at the flue termination point.
6. The flue should be capable of producing a continuous draught of between 0.04” to 0.06” w.g.
C. Use of a Stanley Fan Flue
1. The flue terminal should be positioned to adhere to the minimum clearances to external obstructions as described in the Position of Fan Flue Terminals for Oil Fired Cookers on the Brandon Fan Flue manual.
2. The exhaust point of the flue should be orientated to avoid any potential recirculation of flue gases through the air vents.
Location
1. The cooker should be installed on a non-combustible material capable of supporting the weight of the unit.
2. The cooker should be positioned so as to maintain a 10mm gap between the cooker and the adjacent kitchen units.
Plumbing
1. A three bar safety valve must be fitted to the primary flow pipe adjacent to the boiler connection on the stove.
2. The cooker must be connected to a fully pumped system using 28mm flow & return supply pipes.
3. A 15mm system by-pass must be fitted not less than 1.5 metres from the cooker.
4. Hot supply to the central heating system should be controlled using a motorised valve with live supply to valve provided by the relevant connection on the cooker control board.
Ventilation & Combustion Air Requirements
1. The room in which the appliance is located should have an air vent of adequate size to support correct combustion when all air-using appliances are working at full capacity (See Ventilation & Combustion Air Requirement Section for specific details).
Gas Supply
1. A 1” rigid gas supply pipe must be used to connect directly from the gas meter to the cooker. In the event of a number of appliances using the same supply pipe, the pipe size may need to be increased.
2. The elbow & shut off valve, supplied, must be used to connect the gas supply to the cooker.
3. A soundness test must be conducted to check all joints for gas tightness.
Tick
29
Page 31
Remove the 2 round head screws and the retaining clip on the back of the door while ensuring the spring behind does not spring out. See Fig. A & B.
Retaining Clip
Round Head Screws
DOOR HANDLE REPLACEMENT INSTRUCTIONS
Fig.A
Fig.C
Fig.B
Compression Spring
Tools required
* Small Philips head screw driver * 2 mm allen key * Flat head screwdriver.
Remove the compression spring and screw. See Fig. C.
Round Head Screws
Retaining Clip
Step 1
Step 2
30
Step 3
From the front face loosen the grub screw on the underside of the latch using the 2mm allen key. See Fig.D.
Grub Screw
Fig.D
Page 32
Rev 004 DP130913N00351AXX
Replace the Nylon handle with the chromed handle and reverse the above procedure - Step 5 - 1. See Fig. I
Using a small flat head screwdriver remove the circlip from the end of the door handle axle. See Fig.E & F.
Circlip Removed
Fig.I
While holding the handle pull out the door handle axle. See Fig.G & H.
Circlip
Fig.G
Step 4
Step 5
Step 6
Fig.E
Fig.F
Fig.H
31
Manufactured by
Waterford Stanley Ltd.,
Unit 401-403, IDA Industrial Estate, Cork Road,
Waterford, Ireland.
Tel: (051) 302300 Fax (051) 302315
Loading...