Stamford AC generators, UCI 224, UCI 274, UCM 224, UCM 274 Installation & Maintenance Manual

...
Installation, Service & Maintenance
Manual
AC generators with the following for prefixes:
SAFETY PRECAUTIONS
Before operating the generating set, read the generating set operation manual and this generator manual and become familiar with it and the equipment.
SAFE AND EFFICIENT OPERATION CAN ONLY BE ACHIEVED IF THE EQUIPMENT IS CORRECTLY OPERATED AND MAINTAINED.
Many accidents occur because of failure to follow fundamental rules and precautions.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
Observe all WARNING/CAUTION notices.
Ensure installation meets all applicable safety and local electrical codes. Have all installations performed by a qualified electrician.
Do not operate the generator with protective covers, access covers or terminal box covers removed.
Disable engine starting circuits before carrying out maintenance.
Disable closing circuits and/or place warning notices on any circuit breakers normally used for connection to the mains or other generators, to avoid accidental closure.
Observe all IMPORTANT, CAUTION, WARNING, and DANGER notices, defined as:
Important ! Important refers to hazard or unsafe
method or practice which can result in product damage or related equipment damage.
Caution refers to hazard or unsafe
method or pr actice w hic h can r esult in product damage or personal injury.
Warning refers to a hazard or unsafe method or practice which CAN result in severe personal injury or possible death.
Danger refers to immediate hazards which WILL result in severe personal injury or death.
Due to our policy of continuous improvement, details in this manual which were correct at time of printing, may now be due for amendment. Information included must therefore not be regarded as binding.
Front Cover Photograph
This photograph is representative only. Several variations are available within the range of generators covered by this manual.
Warnin
g
!
Danger !
Caution !
FOREWORD
The function of this book is to provide the user of the Stamford generator with an understanding of the principles of operation, the criteria for which the generator has been designed, and the installation and maintenance procedures. Specific areas where the lack of care or use of incorrect procedures could lead to equipment damage and/or personal injury are highlighted, with WARNING and/or CAUTION notes, and it is important that the contents of this book are read and understood before proceeding to fit or use the generator.
STAMFORD Service, Sales and Technical staff of are always ready to assist and reference to the company for advice is welcomed.
Incorrect installation, operation, servicing or replacement of parts can result in severe personal injury or death, and/or equipment damage. Service personnel must be qualified to perform electrical and mechanical service.
EC DECLARATION OF INCORPORATION
All Stamford generators are supplied with a declaration of incorporation for the relevant EC legislation, typically in the form of a label as below.
Under the EC Machinery Directive section 1.7.4. It is the responsibility of the generator set builder to ensure the generator identity is clearly displayed on the front cover of this book.
ELECTROMAGNETIC COMPATIBILITY
Additional Information European Union
Council Directive 89/336/EEC
For installations within the European Union, electrical products must meet the requirements of the above directive, and STAMFORD ac generators are supplied on the basis that:
They are to be used for power-generation or related function.
They are to be applied in one of the following environments:
Portable (open construction - temporary site supply) Portable (enclosed - temporary site supply) Containerised (temporary or permanent site supply) Ship-borne below decks (marine auxiliary power) Commercial vehicle (road transport / refrigeration etc) Rail transport (auxiliary power) Industrial vehicle (earthmoving, cranes etc) Fixed installation (industrial - factory / process plant) Fixed installation (residential, commercial and light industrial - home / office / health) Energy management (Combined heat and power and/or peak lopping) Alternative energy schemes
.
The standard generators are designed to meet the ‘industrial’ emissions and immunity standards. Where the generator is required to meet the residential, commercial and light industrial emissions and immunity standards reference should be made to document reference N4/X/011, as additional equipment may be required.
The installation earthing scheme involves co nnection of the generator frame to the site protective earth conductor using a minimum practical lead length.
Maintenance and servicing with anything other than factory supplied genuine STAMFORD parts will invalidate warranty and our liability for EMC compliance.
Installation, maintenance and servicing is carried out by adequately trained personnel fully aware of the requirements of the relevant EC directives
Warnin
g
!
CONTENTS
SAFETY PRECAUTIONS FOREWORD 1 CONTENTS 2&3 SECTION 1 INTRODUCTION 4
1.1 INTRODUCTION 4
1.2 DESIGNATION 4
1.3 SERIAL NUMBER LOCATION AND IDENTITY NUMBER LOCATION 4
1.4 RATING PLATE AND CE MARKING 4
SECTION 2 PRINCIPLE OF OPERATION 5
2.1 SELF-EXCITED AVR CONTROLLED GENERATORS 5
2.2 PERMANENT MAGNET GENERATOR (PMG) EXCITED ­ AVR CONTROLLED GENERATORS 5
2.3 AVR ACCESSORIES 5
2.4 TRANSFORMER CONTROLLED GENERATORS 5
SECTION 3 APPLICATION OF THE GENERATOR 6 SECTION 4 INSTALLATION - PART 1 8
4.1 LIFTING 8
4.2 ASSEMBLY 8
4.2.1 NO FOOT OPTION 8
4.2.2 TWO BEARING GENERATORS 9
4.2.3 SINGLE BEARING GENERATORS 9
4.3 EARTHING 9
4.4 PRE-RUNNING CHECKS 9
4.4.1 INSULATION CHECK 9
4.4.2 DIRECTION OF ROTATION 10
4.4.3 VOLTAGE AND FREQUENCY 10
4.4.4 AVR SETTINGS 10
4.4.4.1 TYPE SX460 AVR 10
4.4.4.2 TYPE SX440 AVR 10
4.4.4.3 TYPE SX421 AVR 11
4.4.4.4 TYPE MX341 AVR 11
4.4.4.5 TYPE MX321 AVR 11
4.4.5 TRANSFORMER CONTROLLED EXCITATION SYSTEM (Series 5) 12
4.5 GENERATOR SET TESTING 12
4.5.1 TEST METERING/CABLING 12
4.6 INITIAL START-UP 12
4.7 LOAD TESTING 13
4.7.1 AVR CONTROLLED GENERATORS - AVR ADJUSTMENTS 13
4.7.1.1 UFRO (Under Frequency Roll Off) (AVR Types SX460, SX440, SX421, MX341 and MX321) 13
4.7.1.2 EXC TRIP (Excitation Trip) 14
4.7.1.3 OVER/V (Over Voltage) 14
4.7.1.4 TRANSIENT LOAD SWITCHING ADJUSTMENTS 14
4.7.1.5 RAMP BUILD UP TIME 15
4.7.2 TRANSFORMER CONTROLLED GENERATORS ­ TRANSFORMER ADJUSTMENT 15
4.8 ACCESSORIES 15
SECTION 5 INSTALLATION - PART 2 16
5.1 GENERAL 16
5.2 GLANDING 16
5.3 EARTHING 16
5.4 PROTECTION 16
5.5 COMMISSIONING 16
CONTENTS
SECTION 6 ACCESSORIES 17
6.1 REMOTE VOLTAGE ADJUST (ALL AVR TYPES) 17
6.2 PARALLEL OPERATION 17
6.2.1 DROOP 17
6.2.1.1 SETTING PROCEDURE 18
6.2.2 ASTATIC CONTROL 18
6.3 MANUAL VOLTAGE REGULATOR (MVR) ­ MX341 and MX321 AVR 18
6.4 OVERVOLTAGE DE-EXCITATION BREAKER SX421 and MX321 AVR 18
6.4.1 RESETTING THE BREAKER 19
6.5 CURRENT LIMIT - MX321 AVR 19
6.5.1 SETTING PROCEDURE 19
6.6 POWER FACTOR CONTROLLER (PFC3) 20
SECTION 7 SERVICE AND MAINTENANCE 21
7.1 WINDING CONDITION 21
7.1.1 WINDING CONDITION ASSESSMENT 21
7.1.2 METHODS OF DRYING OUT GENERATORS 21
7.2 BEARINGS 23
7.3 AIR FILTERS 23
7.3.1 CLEANING PROCEDURE 23
7.4 FAULT FINDING 23
7.4.1 SX460 AVR - FAULT FINDING 23
7.4.2 SX440 AVR - FAULT FINDING 24
7.4.3 SX421 AVR - FAULT FINDING 24
7.4.4 TRANSFORMER CONTROL - FAULT FINDING 24
7.4.5 MX341 AVR - FAULT FINDING 25
7.4.6 MX321 AVR - FAULT FINDING 25
7.4.7 RESIDUAL VOLTAGE CHECK 26
7.5 SEPARATE EXCITATION TEST PROCEDURE 26
7.5.1 GENERATOR WINDINGS, ROTATING DIODES and PERMANENT MAGNET GENERATOR (PMG) 26
7.5.1.1 BALANCED MAIN TERMINAL VOLTAGES 26
7.5.1.2 UNBALANCED MAIN TERMINAL VOLTAGES 27
7.5.2 EXCITATION CONTROL TEST 27
7.5.2.1 AVR FUNCTION TEST 27
7.5.2.2 RANSFORMER CONTROL 28
7.5.3 REMOVAL AND REPLACEMENT OF COMPONENT ASSEMBLIES 28
7.5.3.1 REMOVAL OF PERMANENT MAGNET GENERATOR (PMG) 28
7.5.3.2 REMOVAL OF BEARINGS 28
7.5.3.3 REMOVAL OF ENDBRACKET AND EXCITER STATOR 28
7.5.3.4 REMOVAL OF THE ROTOR ASSEMBLY 29
7.6 RETURNING TO SERVICE 29
SECTION 8 SPARES AND AFTER SALES SERVICE 30
8.1 RECOMMENDED SPARES 30
8.2 AFTER SALES SERVICE 30
SECTION 9 PARTS IDENTIFICATION 32
TYPICAL SINGLE BEARING GENERATOR (Fig. 11) 33 TYPICAL TWO BEARING GENERATOR (Fig. 12) 35 TYPICAL TWO BEARING (SERIES 5) GENERATOR (Fig. 13) 37 ROTATING RECTIFIER ASSEMBLY (Fig. 14) 38
SECTION 1
INTRODUCTION
1.1 INTRODUCTION
The UC22/27 range of generators is of brushless rotating field design, available up to 660V/50Hz (1500 rpm) or 60Hz (1800 rpm), and built to meet BS5000 Part 3 and international standards. All the UC22/27 range are self-excited with excitation power derived from the main output windings, using either the SX460/SX440/SX421 AVR. The UC22 is also available with specific windings and a transformer controlled excitation system.
A permanent magnet generator (PMG) powered excitation system is available as an option using either the MX341 or MX321 AVR.
Detailed specification sheets are available on request.
1.2 DESIGNATION
1.3 SERIAL NUMBER LOCATION AND IDENTITY NUMBER LOCATION
Each generator is metal stamped with it’s own unique serial number, the location of this number is described below.
UCI and UCM generators have their serial number stamped into the upper section of the drive end frame to end bracket adaptor ring, shown as item 31 in the parts lists at the back of this book.
UCD generators have their serial number stamped into the top of the drive end adaptor /fan shroud casting. If for any reason this casting is removed, it is imperative that care is taken to refit it to the correct generator to ensure correct identification is retained.
Inside the terminal box two adhesive rectangular labels have been fixed, each carrying the generators unique identity number. One label has been fixed to the inside of the terminal box sheet metal work, and the second label fixed to the main frame of the generator.
1.4 RATING PLATE
The generator has been supplied with a self adhesive rating plate label to enable fitting after final assembly and painting.
It is intended that this label will be stuck to the outside of the terminal box on the left hand side when viewed from the N.D.E. To assist with squarely positioning the label, location protrusions have been made in the sheet metalwork.
A CE Mark label is also supplied loose for fitment after f inal assembly and painting. This should be attached to an external surface of the Generator at a suitable location where it will not be obscured by the customer's wiring or other fittings.
The surface in the area where a label is to be stuck must be flat, clean, and any paint finish be fully dry before attempting to attach label. Recommended method for attaching label is peel and fold back sufficient of the backing paper to expose some 20 mm of label adhesive along the edge which is to be located against the sheet metal protrusions. Once this first section of label has been carefully located and stuck into position the backing paper can be progressively removed, as the label is pressed down into position. The adhesive will achieve a permanent bond in 24 hours. .
SECTION 2
PRINCIPLE OF OPERATION
2.1 SELF-EXCITED AVR CONTROLLED
The main stator provides power for excitation of the exciter field via the SX460 (SX440 or SX421) AVR which is the controlling device governing the level of excitation provided to the exciter field. The AVR responds to a voltage sensing signal derived from the main stator winding. By controlling the low power of the exciter field, control of the high power requirement of the main field is achieved through the rectified output of the exciter armature.
The SX460 or SX440 AVR senses average voltage on two phases ensuring close regulation. In addition it detects engine speed and provides voltage fall off with speed, below a pre­selected speed (Hz) setting, preventing over-excitation at low engine speeds and softening the effect of load switching to relieve the burden on the engine.
The SX421 AVR in addition to the SX440 features has three phase rms sensing and also provides for over voltage protection when used in conjunction with an external circuit breaker (switchboard mounted).
2.2 PERMANENT MAGNET GENERATOR (PMG) EXCITED - AVR CONTROLLED GENERATORS
The permanent magnet generator (PMG) provides power for excitation of the exciter field via the AVR (MX341 or MX321) which is the controlling device governing the level of excitation provided to the exciter field. The AVR responds to a voltage sensing signal derived, via an isolating transformer in the case of MX321 AVR, from the main stator winding. By controlling the low power of the exciter field, control of the high power requirement of the main field is achieved through the rectified output of the exciter armature.
The PMG system provides a constant source of excitation power irrespective of main stator loading and provides high motor starting capability as well as immunity to waveform distortion on the main stator output created by non linear loads, e.g. thyristor controlled dc motor.
The MX341 AVR senses average voltage on two phases ensuring close regulation. In addition it detects engine speed and provides an adjustable voltage fall off with speed, below a pre-selected speed (Hz) setting, preventing over-excitation at low engine speeds and softening the effect of load switching to relieve the burden on the engine. It also provides over­excitation protection which acts following a time delay, to de­excite the generator in the event of excessive exciter field voltage.
The MX321 provides the protection and engine relief features of the MX341 and additionally incorporates 3 phase rms sensing and over-voltage protection. The detailed function of all the AVR circuits is covered in the load testing (subsection 4.7).
2.3 AVR ACCESSORIES
The SX440, SX421, MX341 and MX321 AVRs incorporate circuits which, when used in conjunction with accessories, can provide for parallel operation either with 'droop' or 'astatic' control, VAR/PF control and in the case of the MX321 AVR, short circuit current limiting.
Function and adjustment of the accessories which can be fitted inside the generator terminal box are covered in the accessories section of this book.
Separate instructions are provided with other accessories available for control panel mounting.
2.4 TRANSFORMER CONTROLLED GENERATORS
The main stator provides power for excitation of the exciter field via a transformer rectifier unit. The transfor mer com bines voltage and current elements derived from the main stator output to form the basis of an open-loop control system, which is self regulating in nature. The system inherently compensates for load current magnitude and power factor and provides short circuit maintenance in addition to a good motor starting performance.
Three phase generators normally have a three phase transformer control for improved performance with unbalanced loads but a single phase transformer option is available.
No accessories can be provided with this control system.
SECTION 3
APPLICATION OF THE GENERATOR
The generator is supplied as a component part for installation in a generating set. It is not, therefore, practicable to fit all the necessary warning/hazard labels during generator manufacture. The additional labels required are packaged with this Manual, together with a drawing identifying their locations. (See below).
It is the responsibility of the generating set manufacturer to ensure that the correct labels are fitted, and are clearly visible.
The generators have been designed for use in a maximum ambient temperature of 40°C and altitude less than 1000m above sea level in accordance with BS5000.
Ambients in excess of 40°C and altitudes above 1000m can be tolerated with reduced ratings - refer to the generator nameplate for rating and ambient. In the event that the generator is required to operate in an ambient in excess of the nameplate value or at altitudes in excess of 1000 metres above sea level, refer to the factory.
The generators are of air-ventilated screen protected drip­proof design and are not suitable for mounting outdoors unless adequately protected by the use of canopies. Anti­condensation heaters are recommended during storage and for standby duty to ensure winding insulation is maintained in good condition.
When installed in a clos ed cano py it must be ens ured t hat the ambient temperature of the cooling air to the generator does not exceed that for which the generator has been rated.
The canopy should be designed such that the engine air intake to the canopy is separated from the generator intake, particularly where the radiator cooling fan is required to draw air into the canopy. In addition the generator air intake to the canopy should be designed such that the ingress of moisture is prohibited, preferably by use of a 2 stage filter.
The air intake/outlet must be suitable for the air flow given in the following table with additional pressure drops less than or equal to those given below :
Air Flow
Frame
50Hz 60Hz
Additional (intake/outlet) Pressure Drop
0.216m³/sec 0.281m³/sec 6mm water gauge
UC22
458cfm 595cfm (0.25”)
0.25m³/sec 0.31m³/sec 6mm water gauge
UCD22
530cfm 657cfm (0.25”)
0.514m³/sec 0.617m³/sec 6mm water gauge
UC27
1090cfm 1308cfm (0.25”)
0.58m³/sec 0.69m³/sec 6mm water gauge
UCD27
1230cfm 1463cfm (0.25”)
Important ! Reduction in cooling air flow or inadequate
protection to the generator can result in damage and/or failure of windings.
Dynamic balancing of the generator rotor assembly has been carried out during manufacture in accordance with BS 6861 Part 1 Grade 2.5 to ensure vibration limits of the generator are in accordance with BS 4999 Part 142.
The main vibration frequencies produced by the component generator are as follows:- :
4 pole 1500 rpm 25 Hz 1800 rpm 30 Hz
However, vibrations induced by the engine are complex and contain frequencies of 1.5, 3, 5 or more times the fundamental frequency of vibration. These induced vibrations can result in generator vibration levels higher than those derived from the generator itself. It is the responsibility of the generating set designer to ensure that the alignment and stiffness of the bedplate and mountings are such that the vibration limits of BS5000 Part 3 are not exceeded.
In standby applications where the running time is limited and reduced life expectancy is accepted, higher levels than specified in BS5000 can be tolerated, up to a maximum of 18mm/sec.
Two bearing generators open coupled require a substantial bedplate with engine/generator mounting pads to ensure a good base for accurate alignment. Close coupling of engine to generator can increase the overall rigidity of the set. For the purposes of establishing set design the bending moment at the engine flywheel housing to generator adaptor interface should not exceed 1000ft.lb. (140 kgm). A flexible coupling, designed to suit the specific engine/generator combination, is recommended to minimise torsional effects.
Belt driven applications of t wo bearing gener ators require t he pulley diameter and design to be such that the side load or force applied to the shaft is central to the extension and does not exceed the values given in the table below : -
Side Load
Frame
kgf N
Shaft
Extension
mm UC22 408 4000 110 UC27 510 5000 140
In instances where shaft extensions greater than specified in the table have been supplied reference must be made to the factory for appropriate loadings.
Alignment of single bearing generators is critical and vibration can occur due to the flexing of the flanges between the engine and generator. As far as the generator is concerned the maximum bending moment at this point must not exceed 1000ft.lb. (140kgm). A substanial bedplate with engine/generator mounting pads is required.
It is expected that the generator will be incorporated into a generating set operating in an environment, where the maximum shock load experienced by the generator will not exceed 3g. in any plane. If shock loads in excess of 3g are to be encountered, anti-vibration mountings must be incorporated into the generating set to ensure they absorb the excess.
The maximum bending moment of the engine flange must be checked with the engine manufacturer.
Generators can be supplied without a foot, providing the option for customers own arrangement. See SECTION 4.2.1 for assembly procedure.
Torsional vibrations occur in all engine-driven shaft systems and may be of a magnitude to cause damage at certain critical speeds.
It is therefore necessary to consider the torsional vibration effect on the generator shaft and couplings. It is the responsibility of the generator set manufacturer to ensure compatibility, and for this purpose drawings showing the shaft dimensions and rotor inertias are available for customers to forward to the engine supplier. In the case of single bearing generators coupling details are included.
Important ! Torsional incompatibility and/or excessive
vibration levels can cause damage or failure of generator and/or engine components.
The terminal box is constructed with removable panels for easy adaptation to suit specific glanding requirements. Within the terminal box there are insulated terminals for line and neutral connections and provision for earthing. Additional earthing points are provided on the generator feet.
The neutral is NOT connected to the frame. The main stator winding has leads brought out to the
terminals in the terminal box.
No earth connections are made on the generator and reference to site regulations for earthing must be made. Incorrect earthing or protection arrangements can result in personal injury or death.
Fault current curves (decrement curves), together with generator reactance data, are available on request to assist the system designer to select circuit breakers, calculate fault currents and ensure discrimination within the load network.
Incorrect installation, service or replacement of parts can result in severe personal injury or death, and/or equipment damage. Service personnel must be qualified to perform electrical and mechanical service.
Warnin
g
!
Warnin
g
!
SECTION 4
INSTALLATION - PART 1
4.1 LIFTING
Incorrect lifting or inadequate lifting capacity can result in severe personal injury or equipment damage. MINIMUM LIFTING CAPACITY REQUIRED IS 750Kg. Generator lifting lugs should NOT be used for lifting the complete generator set.
Two lifting lugs are provided for use with a shackle and pin type lifting aid. Chains of suitable length and lifting capacity must be used. Lifting points are designed to be as close to the centre of gravity of the generator as possible, but due to design restrictions it is not possible to guarantee that the generator frame will remain horizontal while lifting. Care is therefore needed to avoid personal injury or equipment damage. The correct lifting arrangement is shown on the label attached to the lifting lug. (See sample below).
Single bearing generators are supplied fitted with a rotor retaining bar at the non-drive end of the shaft.
To remove retaining bar :
1. Remove the four screws holding the sheet metal cover at the non drive end and remove cover
2. Remove central bolt holding the retaining bar to the shaft
3. Refit sheet metal cover.
Once the bar is removed, to couple the rotor to engine, the rotor is free to move in the frame, and care is needed during coupling and alignment to ensure the frame is kept in the horizontal plane.
Generators fitted with a PMG excitation system are not fitted with retaining bar. Refer to frame designation to verify generator type (subsection 1.2)
4.2 ASSEMBLY
During the assembly of the generator to the engine it will be necessary firstly to carefully align, then rotate, the combined generator rotor - engine crankshaft assembly, as part of the construction process, to allow location, insertion and tightening of the coupling bolts. This requirement to rotate the combined assemblies exists for both single and two bearing units.
During the assembly of single bearing units it is necessary to align the generator's coupling holes with the engine flywheel holes; it is suggested that two diametrically opposite location dowel pins are fitted to the engine flywheel, over which the generator coupling can slide into final location into the engine flywheel spigot recess. The dowels must be removed and replaced by coupling bolts before the final bolt tightening sequence.
While fitting and tightening the coupling bolts it will be necessary to rotate the engine crankshaft - generator rotor assembly. Care should be taken to ensure that rotation is carried out in an approved manner that ensures safe working practice when reaching inside the machine to insert or tighten coupling bolts, and that no component of the assembly is damaged by nonapproved methods of assembly rotation.
Engine manufacturers have available a proprietary tool or acility designed to enable manual rotation of the crankshaft assembly. This must always be used, having been engineered as an approved method of assembly rotation, engaging the manually driven pinion with the engine flywheel starter ring-gear.
Before working inside the generator, during the aligning and fitting of coupling bolts, care should be taken to lock the assembly to ensure there is no possibility of rotational movement.
4.2.1 NO FOOT OPTION
Generators can be supplied without a foot providing the option for customers own arrangement. For details of mounting this arrangement, see the general arrangement drawing supplied with the generator. Alternatively refer to the STAMFORD factory for a copy of the latest general arrangement drawing showing the 'NO FOOT OPTION' appropriate to your generator.
Warnin
g
!
Caution !
4.2.2 TWO BEARING GENERATORS
A flexible coupling should be fitted and aligned in accordance with the coupling manufacturer's instruction. If a close coupling adaptor is used the alignment of machined faces must be checked by offering the generator up to the engine. Shim the generator feet if necessary. Ensure adaptor guards are fitted after generator/engine assembly is complete. Open coupled sets require a suitable guard, to be provided by the set builder. In the case of belt driven generators, ensure alignment of drive and driven pulleys to avoid axial load on the bearings. Screw type tensioning devices are recommended to allow accurate adjustment of belt tension whilst maintaining pully alignment. Side loads should not exceed values given in SECTION 3. Belt and pulley guards must be provided by the set builder.
Important ! Incorrect belt tensioning will result in
excessive bearing wear. Incorrect guarding and/or generator
alignment can result in personal injury and/or equipment damage.
4.2.3 SINGLE BEARING GENERATORS
Alignment of single bearing generators is critical. If necessary shim the generator feet to ensure alignment of the machined surfaces.
For transit and storage purposes the generator frame spigot and rotor coupling plates have been coated with a rust preventative. This MUST BE
removed before assembly to engine.
A practical method for removal of this coating is to clean the mating surface areas with a de-greasing agent based on a petroleum solvent.
Care should be taken not to allow any cleaning agent to come into prolonged contact with skin.
The sequence of assembly to the engine should generally be as follows:
1. On the engine check the distance from the coupling mating face on the flywheel to the flywheel housing mating face. This should be within +/-0.5mm of nominal dimension. This is n e cessary to ensure that a thrust is not applied to the a.c. generator bearing or engine bearing.
1. Check that the bolts securing the flexible plates to the coupling hub are tight and locked into position. Torque tightening is 24.9kgfm (244Nm; 180 lb ft).
2a. UCD224 Only
Torque tightening is 15.29 kgfm (150Nm; 110 lb ft).
1. Remove covers from the drive end of the generator to gain access to coupling and adaptor bolts.
1. Check that coupling discs are concentric with adaptor spigot. This can be adjusted by the use of tapered wooden wedges between the fan and adaptor. Alternatively the rotor can be suspended by means of a rope sling through the adaptor opening.
1. Offer the a.c. generator to engine and engage both coupling discs and housing spigots at the same time, finally pulling home by using the housing and coupling bolts. Use heavy gauge washers between bolt head and discs on disc to flywheel bolts.
1. Tighten coupling disc to flywheel. Refer to engine manual for torque setting of disc to flywheel bolts.
1. Remove wooden wedges.
Incorrect guarding and/or generator alignment can result in personal injury and/or equipment damage.
4.3 EARTHING
The generator frame should be solidly bonded to the generating set bedplate. If antivibration mounts are fitted between the generator frame and its bedplate a suitably rated earth conductor (normally one half of the cross sectional area of the main line cables) should bridge across the antivibration mount.
Refer to local regulations to ensure that the correct earthing procedure has been followed.
4.4 PRE-RUNNING CHECKS
4.4.1 INSULATION CHECK
Before starting the generating set, both after completing assembly and after installation of the set, test the insulation resistance of windings. The AVR should be disconnected during this test. A 500V Megger or similar instrument should be used. Disconnect any earthing conductor connected between neutral and earth and megger an output lead terminal U, V or W to earth. The insulation resistance reading should be in excess of 5MΩ to earth. Should the insulation resistance be less than 5MΩ the winding must be dried out as detailed in the Service and Maintenance section of this Manual.
Important ! The windings have been H.V. tested during
manufacture and further H.V. testing may degrade the insulation with consequent reduction in operating life. Should it be necessary to demonstrate H.V. testing, for customer acceptance, the tests must be carried out at reduced voltage levels i.e. Test Voltage= 0.8 (2 X Rated Voltage + 1000)
Caution !
Caution !
Caution !
Warnin
g
!
4.4.2 DIRECTION OF ROTATION
The generator is supplied to give a phase sequence of U V W with the generator running clockwise looking at the drive end (unless otherwise specified at the time of ordering). If the generator phase rotation has to be reversed after the generator has been despatched apply to factory for appropriate w iring diagram s.
UCI224, UCI274, UCM224, UCM274
Machines are fitted with bi-directional fans and are suitable for running in either direction of rotation.
UCD224, UCD274
Machines are fitted with uni-directional fans and are suitable for running in one direction only.
4.4.3 VOLTAGE AND FREQUENCY
Check that the voltage and frequency levels required for the generating set application are as indicated on the generator nameplate.
Three phase generators normally have a 12 ends out reconnectable winding. If it is necessary to reconnect the stator for the voltage required, refer to diagrams in the back of this manual.
4.4.4 AVR SETTINGS
To make AVR selections and adjustments remove the AVR cover and refer to 4.4.4.1, 4.4.4.2, 4.4.4.3, 4.4.4.4 or 4.4.4.5 depending upon type of AVR fitted. Reference to the generator nameplate will indicate AVR type (SX460, SX440, SX421, MX341 or MX321).
Most of the AVR adjustments are factory set in positions which will give satisfactory performance during initial running tests. Subsequent adjustment may be required to achieve optimum performance of the set under operating conditions. Refer to 'Load Testing' section for details.
4.4.4.1 TYPE SX460 AVR
The following 'jumper' connections on the AVR should be checked to ensure they are correctly set for the generating set application. Refer to Fig. 1 for location of selection links.
1. Frequency selection
50Hz operation LINK C-50 60Hz operation LINK C-60
2. External hand trimmer selection
No external hand trimmer LINK 1-2 External hand trimmer required - REMOVE LINK 1-2 and
connect trimmer across terminals 1 and 2.
3. AVR Input Selection
High voltage (220/240V) Input NO LINK Low voltage (110/120V) Input LINK 3-4
Refer to diagram in the back of this manual to determine wiring.
4.4.4.2 TYPE AS440 AVR
The following 'jumper' connections on the AVR should be checked to ensure they are correctly set for the generating set application.
Refer to Fig. 2 for location of selection links.
1. Frequency selection terminals
50Hz operation LINK C-50 60Hz operation LINK C-60
2. Stability selection terminals
Frame UC22 LINK A-C Frame UC27 LINK B-C
3. Sensing selection terminals
LINK 2-3 LINK 4-5 LINK 6-7
4. Excitation Interruption Link
LINK K1-K2
4.4.4.4 TYPE MX341 AVR
The following 'jumper' connections on the AVR should be checked to ensure they are correctly set for the generating set application.
Refer to Fig. 4 for location of setting links.
1. Frequency selection terminals
50Hz operation LINK 2-3 60Hz operation LINK 1-3
2. Stability selection terminals
Frame UC22 LINK A-C Frame UC27 LINK B-C
3. Sensing selection terminals *
LINK 2-3 LINK 4-5 LINK 6-7
4. Excitation Interruption Link
LINK K1-K2
Fig. 4
4.4.4.5 TYPE MX321 AV R
The following 'jumper' connections on the AVR should be checked to ensure they are correctly set for the generating set application.
Refer to Fig. 5 for location of setting links.
Fig. 5
1. Frequency selection terminals
50Hz operation LINK 2-3 60Hz operation LINK 1-3
2. Stability selection terminals
Frame UC22 LINK A-C Frame UC27 LINK B-C
3. Terminals K1 - K2
Excitation circuit breaker closed. If this option not fitted, K1 - K2 linked at auxiliary terminal block.
Loading...
+ 30 hidden pages