Stahl-electronics HS-1000 Data Sheet & User Manual

HS-1000
Fast Low Noise High Voltage Switch
HS-1000_User_Manual_1_24 .doc
16 - march - 2017
Data Sheet & User Manual
Rev. 1.24
Applications:
● Piezo-Driver
Features:
● fast and low noise switch (SPDT, push-pull)
● max. 1000V switching voltage
● TTL/CMOS level control
● floating up to 800V vs. GND
www.stahl-electronics.com
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
2
TABLE OF CONTENTS
1. Safety Hints ………………………………….…………………………………… 3
2. General Information and Overview………………….………………………….. 4
2.1 Purpose and Description of the Device…………………………….. 4
2.2 Functional Principle and Block Diagram…………………………. 4
2.3 Device Variety……………………………………………………… 5
3. Installation ……………………………………………………………………..… 6
3.1 Mechanical and Electrical Installation……………………………… 6
4. Operation and Control Elements ……………………………………………….. 7
4.1 Elements on the front plate………………………………………… 7
4.2 Elements on the rear side..………………………………………… 7
4.3 Output Characteristics……………………………………………… 8
5. Maintenance………………………………………….…………………………. 10
6. Specifications……………………………………………………………………. 11
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
3
1. Safety Hints
Read all installation, operation, and safety instructions
Prior to operation, thoroughly review all safety, installation, and operating instructions accompanying
this equipment. Rear side switch turns device completely off
If the device is not in use for a longer time, it is
recommended to turn the mains switch at rear side off. This equipment must be connected to an earth safety ground
This product is grounded through the grounding
conductor of the power cord. To avoid electrical
hazard, the grounding conductor must be connected to
protective earth ground. Do not modify the unit Do not make electrical or mechanical modifications to
this unit. Change cabling only when device is off Changing the cabling, when voltages are present at the
outputs can lead to formation of harmful sparks. Do not operate in wet/damp conditions To avoid electric shock hazard, do not operate this
product in wet or damp conditions. Protect the device
from humidity and direct water contact. Beware of external magnetic fields External magnetic fields can impair, damage or even
destroy this device. A maximum external field strength
of no more than B = 5mT is admissible. Having placed
the device at any time into an external magnetic of
bigger B = 5mT (regardless if power was turned on or
off) can lead to severe overheating of the device and
severely increased hazard of fire. Service is to be performed by qualified service persons only
All servicing on this equipment must be carried out by
factory-qualified service personnel only. Do not block chassis ventilation openings Slots and openings in the chassis are provided for
ventilation purposes to prevent overheating of the
equipment and must not be restricted.
All case vents should continuously be cleared (fan inlet
at rear side, air outlet at rear side), in order to prevent
overheating. Operate carefully with respect to risk of electrical shock
This device can produce high voltages at its output
lines, which are harmful in case of direct touch with the
human body or other external circuitry. Care must be
taken to avoid unintentional touching of any output line
to the human body or any devices which might be
endangered by high voltages. Routinely cleaning from dust After long operation, or operation in a dusty
environment it is strongly recommended to have the
internal parts of the device cleaned by the
manufacturer, or an appropriately qualified workshop
in order to reduce the hazard of overheating. No outdoor operation Outdoor operation of the device is not admissible.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
4
2. General Information and Overview
2.1 Purpose and Description of the Device
Purpose of the HS series devices is the fast switching of electrodes, electrostatic lenses, beam deflectors or ion traps. Unlike DC power switches, the outputs expect capacitive loads. The outputs are optimized for high stability and very low noise. The HS series switches are housed in standard 19-inch rack-mount cases. They are available in single-channel or dual-channels versions. In the dual channel version two completely identical switched are housed inside the same housing. These two switches are completely independent.
fig 2.1: front view (DUAL version)
2.2 Functional Principle and Block Diagram
The following scheme displays a block diagram of the internal structure and illustrates the functional principle. The control input (BNC socket on front plate) defines the position of the internal high voltage switch, which connects either input A or input B to the output. A digital signal (TTL/CMOS level 0V/5V) may be applied to this control input at a rate between 0Hz (static operation) to 2kHz. A three-position manual switch on the front side allows to override the digital control signal. The high voltage switching elements inside the device are implemented as MOSFET-transistors, allowing fast switching transitions in the order of 100ns and less.
fig 2.2: Block diagram of a HS-1000 device. Inside the DUAL version, the scheme exists twice, i.e. there are two independent switches.
Unlike high voltage pulse-generators the internal switch circuitry is implemented as fast static switch, which means that the applied control input level defines the (static) switch position as illustrated in the scheme above. The output is connected to the selected input by a (transistor based) resistor. The non­selected input is isolated from the output by a high isolation resistance.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
5
Note that the applied supply voltages at inputs A and B must obey a certain order: voltage at input A always needs to be more positive than voltage at input B. In general both input voltages may float up to +/-800V versus the case ground. However, for normal operation the voltage difference (A-B) should not exceed 1000V.
Application example: Generation of 10µs-duration positive 200Volt-pulse
The subsequent oscilloscope screen shot shows a typical application example. A control pulse of logic levels (high = 5V, low = 0V) is applied to the control input. High voltage inputs A and B were provided with an external voltage of 200V and 0V respectively. At the edges of the control signal the switch is triggered, and switches from 0V to 200V (trace 1: 50V/div.) and after 10µs back to 0 Volt. Trace 2 shows the control signal, being used to trigger the switch (trace 2: 5V/div.). A rectangular pulse results with steep slopes and constant-voltage static levels.
fig 2.3: Oscilloscope screen shot of a positive 200V pulse, t = 10s duration. The lower trace (trace 2) shows the digital control signal, trace 1 (upper trace) the output signal.
2.3. Device Variety
The following devices are currently members of the HS/HVS series device family:
HS-200 single or dual version Output voltages of maximum 200V span
1)
HS-500 single or dual version Output voltages of maximum 500V span
1)
HS-1000 single or dual version Output voltages of max. 1000V span
1)
The devices with outputs up to 500V (vs. GND) are provided by default with BNC outputs at their rear side, the other variants with higher voltages have SHV connectors. Voltages are referenced to case ground.
Note
1)
: span is the maximum voltage difference between positive and negative inputs A and B.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
6
3. Installation
3.1. Mechanical and Electrical Installation
Positioning: Provide sufficient air cooling of the device and locate in normal horizontal position to allow for defined air convection. Rack mounting into a standard 19” rack is as well possible as resting the device on a table. If mounted in a rack, please make sure that all case vents are permanently cleared (fan inlet at rear side, air outlets at rear side), in order to prevent overheating.
fig. 3.1: Keep air vents always cleared to ensure sufficient ventilation
Beware of external magnetic fields: Strong external magnetic fields can impair, damage or even destroy this device (e.g. proximity to a superconducting magnet). A maximum external field strength of no more than B = 5mT is admissible. Not observing this important condition can lead to severe overheating of the device and increases the hazard of fire.
Connecting to mains power: Connect the device to the mains power supply (220 to 240V ac) by using an appropriate power cord, being properly wired and providing a grounded outlet. The power cord must be suited with respect to possible load currents and should be rated to 2A current.
Cabling of voltage outputs: Always provide appropriate and safe cabling when connecting the device to other devices or vacuum/experimental setups. Cabling is preferred using high voltage cable with proper shielding. BNC or SHV connector cables are a suitable choice in order to ensure proper shielding against external noise pickup and in order to provide protective ground for safety reasons. Always be aware about the potential hazard of high electrical voltages to human beings and sensitive objects of all kind (see also safety hints in section 1).
Please note that wiring may only be done when the device is turned off. Connecting a powered­up output to external circuitry can easily cause sparks and electrical discharges. The resulting overvoltages can severely and permanently damage the device itself and also external circuitry.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
7
4. Operation and Control Elements
4.1 Elements on the front plate
mains supply Switch 1 Switch 2
switch BNC ext. / manual BNC ext. / manual
fig. 4.1: front plate elements (2-channel version shown)
The front plate contains the control elements of the device. It is powered up after turning on the rear­side mains supply switch and also the power button on the front plate. The Power-on-LED (green) indicates proper operation of the internal circuitry.
fig. 4.2: manual switch, BNC input and LED indicators.
Each channel features a three-position manual switch (fig. 4.2). Lifted upwards, the output (rear side) is connected to the high voltage input A, moved into lower position it connects the output to input B. In the center position of this switch the control voltage, being applied to the BNC input, defines the high voltage switch position. A high level connects the output with A, low level to B. Common 5V / 0V signal may be applied to this BNC control input. In practical cases a PC controlled Delay-Gate generator or function generator is often connected to this BNC input. Switching rates up to 2kHz are supported. The LED indicators on the right hand side show the switch status, indicating which input (A or B) is connected to the output.
4.2 Elements on the rear side
fig. 4.3: rear side elements (a dual channel version is shown)
The rear side of the device contains the ventilation elements, 230V supply connector, power on/off switch (with fuses) and the high voltage inputs and outputs.
fig. 4.4: BNC sockets for at inputs and output
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
8
Fig. 4.4 shows the BNC sockets for the two DC high voltage supply voltages A, and B and the switch output OUT. Please note that the voltage on input A needs to be more positive compared to the voltage on input B. This is indicated by the plus and minus sign “+” and “-“. In general, both input voltages may reside in the range between -800V and +800V versus GND, but their difference should not exceed 1000V. The fuse sockets shown in fig. 4.4 contain safety fuses for the two high voltage inputs. In case extensive currents flow, they may blow. Nominal rating is 0.5 Ampere, fast blow.
The inputs A and B can be connected to an appropriate high voltage supply, e.g. a device from the stahl-electronics HV-series. The output is supposed to be connected to a switched electrode element or ion trap. Please note that the capacitive load on this output may impair the switching speed performance. Nominal loads from 0pF to 300pF may be connected. See also next section for waveforms.
4.3 Output Characteristics
Dynamic Response
As soon as the internal switch connects either input A or B to the output, the latter assumes the voltage on the respective input. There is a time constant related to each voltage transition, essentially given by the internal switch resistance (approx. 250 ), the internal output current limit (approx. ±490mA) and the capacitive load on the output, including all cables to an experimental setup. In case of BNC cable type one may count about 100pF each meter cable length, therefore extensively long cables should be avoided.
The following oscilloscope screen shots show voltage step transitions observed at the output with small (17pF) and medium capacitive loads (300pF) for further illustration.
fig. 4.5 (left frame) positive voltage step of 100V with small capacitive load (C = 17pF) at the output; (right frame) voltage step of 200V with small capacitive load (C=17pF); transient rise time (10% to 90% of voltage step size) is in the order of 25ns in each case. Both graphs have an oscilloscope time grid of 25ns per division.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
9
fig. 4.6 (left frame) positive voltage step of 200V with medium capacitive load (C = 300pF); (right frame) negative voltage step of 200V with medium capacitive load (C = 300pF); transient rise (10% to 90%) time is in the order of 148ns each. Both graphs feature a time grid of 100ns per division.
fig 4.7: Oscilloscope screen shot of a positive 200V pulse, t = 10s duration, C = 100pF load at the output. The lower trace (trace 2) shows the digital control signal, trace 1 (upper trace) the output signal.
Fast Pulses
Upon request the device can be equipped with the capability to create pulses shorter than 10µs. The subsequent oscilloscope trace shows the output signal of a modified device with 1µs minimum pulse duration. The output is switched from +500V to -500V and back, resting for 1µs at the negative voltage level. Capacitive load was 180pF for this measurement.
fig 4.8: Oscilloscope trace of a negative 1kV pulse, t = 1s duration, C = 180pF load at the output.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
10
Noise and Ripple
In contrast to other devices, based on switched circuit / power switching technology, the HS series devices feature a very low noise level. This makes them specially suited for ion traps, ion sources and low energy beam line applications. Each output exhibits a very low broadband noise (DC to 20MHz) of smaller than 350µV
rms
and a low ripple level (50Hz) smaller 50µV
rms
. The outputs are free of
parasitic switching spikes in the RF region.
Floating Voltage
As mentioned above may the two input voltages float versus the case ground. The maximum admissible voltage is limited by the occurrence of excessive leakage currents and sparking. The HS­1000 device is rated for a permanent voltage of 800V (positive or negative) versus the case gound. During factory commissioning a test voltage of 1200V is applied for a duration of 15min. and the leakage current observed. Typically a leakage current of 5nA is measured. At a voltage of 1000V versus case ground the leakage drops to about 3nA, it may therefore be assumed to be safe to run the device for short times (max. hours) at a maximum voltage of 1000V referenced to case ground.
5. Maintenance
The HS series high voltage switches are designed for years of reliable operation. Under normal operating conditions, they should not require electrical maintenance, except routine cleaning of dust. Exchange of ventilation fan is strongly recommended every 50’000 operation hours (see below). If any question should arise, please contact the manufacturer.
Routine cleaning
All ventilation openings should be checked periodically and kept free of dust and other obstructions. A vacuum cleaner may be used to clean these vents when the unit is powered off. The front panel may be cleaned periodically with a clean cloth and mild alcohol solution, when the unit is powered off. It is recommended to send the device to the manufacturer routinely in 4-year intervals for internal cleaning from dust.
Fan life time and temperature monitoring
The air ventilation fan is a part which shows unavoidable deterioration in time. Exchange of this part is strongly recommended after 50´000 hours of operation. Please contact manufacturer for replacement. Complete failure can lead to overheating of the device. Several temperature fuses and other protection measures provide a certain degree of safety against fire hazard in this case.
Fire hazard
Please note, that excessive accumulation of dust inside the case of the device can lead to overheating. This, together with possible discharges increases the risk of fire, caused by electrical sparks. Routinely cleaning the device from dust minimizes this risk. It is therefore recommended to send the device to the manufacturer routinely in 4-year intervals for internal cleaning from dust, or to have it cleaned by an accordingly qualified electronical workshop. Also air conditions containing oil mists (e.g. in proximity to a vacuum pump or mechanical machines) place a severe danger, since inflammable substances could enter the device through the ventilation holes. If in doubt, cleaning by an accordingly qualified electronical workshop or the manufacturer is strongly recommended. An increased hazard of fire may also occur if the device has been (permanently or temporarily) located in proximity to a strong (e.g. superconducting) magnet. A maximum external field of B = 5mT is admissible.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
11
6. Specifications
Control Input
typ. max. Conditions and remarks
required drive level 0V and 5V -2V to +6V
vs. GND threshold 2.4V input impedance
1k// 6pF
drive rate / switching rate 1.2kHz output pulse length greater or equal
10µs; for shorter pulses apply rate max. 500Hz
Output Switch, static
static resistance from A or B to OUT “on”-state
250 330
I
OUT
< 200mA
isolation resistance from A or B to OUT
>10M
voltage differences from A or B to OUT smaller or equal 1000V
leakage currents from A or B to OUT 40nA* 200nA*
voltage differences from A or B to
OUT smaller or equal 1000V intrinsic switch capacitance on OUT terminal
25pF to 35pF
Noise 350µV
rms
Transfer characteristics
delay from control input change to output reaction 200ns
200V output step size
(positive or negative going) delay jitter 1 ns rms T = 25°C +/-1°C max. pulse duration infinite min. pulse duration
6.6µs
1.0µs on request
50ns capacitive load of 17pF (probehead)Output rise or fall time, 10% to 90% step size, at max. 500V voltage step
190ns capacitive load of 300pF
Input Voltage Rating
Input A or B vs. GND +/-800V both polarities may be applied vs.
GND Voltage difference from A to B 1000V
input A always needs to be on more
positive level with respect to B Fuse rating 500mA, fast fuse replaceable on rear side
Environmental Conditions
Magnetic Field max. 5 mT Storage Temperature -55 C° to +85
C° Operating Humidity & Temperature
noncondensing relative humidity up to 95% between temperatures of +10°C and +35°C.
Power Supply
AC input voltage 230VACat 50Hz.
The power entry module is EMI/RFI-filtered.
Fuse: medium fast blow 1.0A
Power Consumption typ. 3.9W
Case dimensions
19.00” wide x 10” deep x 1 height unit. Front-panel mounting holes are configured for M6 rack configurations
weight approximately 1.2kg
Note *): Inputs A and B feature 1Gresistors to ground for protection aginst parasitic charge up.
HS/HVS-Series Installation and User Manual, Rev 1.22
www.stahl-electronics.com phone: +49 6242-504882, fax: +49 6242 504884
12
Currents through these protection resistors add to the numbers mentioned above.
DECLARATION OF CONFORMITY
Manufacturer's Name: Dr. Stefan Stahl
- Electronics for Science and Research -
Manufacturer's Address: Dr. Stefan Stahl
Kellerweg 23 67582 Mettenheim Germany.
Declares, that the product
Product Name: HS series high voltage switches Model Number: HS-200, HS-500, HS-1000
Product Options: This declaration covers all options of the above product(s)
Conforms with the following European Directives:
The product herewith complies with the requirements of the:
1. Low Voltage Directive 73/73EEC;
2. EMC Directive 89/336/EEC (including 93/68/EEC) and carries the CE Marking accordingly
Date Of Issue __________________
8. April 2014 General Director
Loading...