Staco Energy UNISTAR VP Users Manual

Page 1
UNISTAR VP
120-240V 50/60Hz
6 and 10kVA
USER MANUAL
003-2520, REV L
Page 2
Page | i
Page 3
Staco Energy is highly specialized in the development and production of uninterruptible power
manufactured to ensure optimum performance.
systems (UPS). The UPS’s of this series are high quality products, carefully designed and

Safety Warnings

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for Models 6 and 10kVA UniStar VP series UPS that should be followed during installation and maintenance of the UPS. Please read all instructions before operating the UPS and save this manual for future reference.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
a. Do not use outdoors. b. Do not route wiring across or near hot surfaces. c. Do not install near gas or electric heaters. d. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is
spilled on skin or in eyes, flush acid with fresh water and contact a physician immediately.
e. Unit should be installed where it will not readily be subjected to tampering by unauthorized
personnel.
f. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
g. Do not use this UPS for other than intended use.
This UPS has been designed and manufactured in accordance with the standards for the product, for normal use and for all uses that may reasonably be expected. It may under no circumstances be used for any purposes other than those envisaged, or in any other ways than those described in this manual. Any interventions should be carried out in accordance with the criteria and the time-frames described in this manual.
Page | ii
Page 4
DANGER
WARNING
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Do not operate near water or excessive humidity (95% maximum).
WARNING
Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries.
There is a risk of explosion if batteries are replaced by an incorrect type. Replace with same type and rating only.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire

Emergency Interventions

The following information is of a general nature.

First aid interventions

Company regulations and traditional procedures should be followed for any first aid intervention that may be required.

Firefighting measures

1. Do not use water to put out a fire, but only fire extinguishers that are suitable for use with electrical and electronic equipment.
2. If exposed to heat or fire, some products may release toxic fumes into the atmosphere. Always use a respirator when extinguishing a fire.
Page | iii
Page 5

Symbols used in the Manual

Danger / Risk of Electric Shock
adequate precautions are taken.
Warning
taken
In this manual, some operations are shown by graphic symbols to alert the reader to the dangerous nature of the operations:
This symbol indicates possibility of serious injury or substantial damage to the unit, unless
This symbol indicates important information which must be understood and any stated precautions
Note
Protective Equipment
No maintenance operations shall be carried out on the unit without wearing the Personal Protective Equipment (PPE) described below. Personnel involved in the installation or maintenance of the unit must be properly clothed.
The following signs show the protective equipment that should be worn. The various items of PPE must be selected and sized according to the nature of the hazard (particularly electrical) posed by the unit.
Accident prevention footwear
Protective clothing
Work gloves
Protective eyewear
Helmet

GENERAL PRECAUTIONS

This manual contains detailed instructions for the use, installation and start-up of the UPS. Read the manual carefully before installation. For information on using the UPS, the manual should be kept close at hand and consulted before carrying out any operation on the UPS.
Page | iv
Page 6
Table of Contents
Safety Warnings ....................................................................................................................................... ii
Emergency Interventions ......................................................................................................................... iii
First aid interventions ........................................................................................................................... iii
Firefighting measures ........................................................................................................................... iii
Symbols used in the Manual .................................................................................................................... iv
Protective Equipment ............................................................................................................................... iv
GENERAL PRECAUTIONS ..................................................................................................................... iv
1. Safety Warnings and EMC instructions ................................................................................................ 1
1.1 UPS Location ................................................................................................................................. 1
1.2 Connections ................................................................................................................................... 1
1.3 Maintenance ................................................................................................................................... 1
1.4 Battery ............................................................................................................................................ 2
2. Installation ............................................................................................................................................ 3
2.1 Unpacking and Inspection .............................................................................................................. 3
2.2 UPS Rear Panel View ..................................................................................................................... 4
2.3 ISO Pack Cabinet Rear Panel View ................................................................................................ 5
2.4 System Single Line Diagram ........................................................................................................... 6
2.4.1 UPS Single Line Diagram ........................................................................................................ 6
2.4.2 ISO Pack Single Line diagram ................................................................................................. 6
2.5 Tower/Rack Installation .................................................................................................................. 7
2.5.1 Tower Installation ..................................................................................................................... 7
2.5.2 Rack type installation ............................................................................................................... 8
2.6 Single UPS Installation ................................................................................................................... 9
2.6.1 UPS Input/Output Wiring .......................................................................................................... 9
2.6.2 Battery Pack Installation ......................................................................................................... 10
2.7 ISO Pack Installation to Input of System ....................................................................................... 11
2.7.1 120V Input and 208V output .................................................................................................. 11
2.7.2 120V Input and 240V output .................................................................................................. 12
2.8 ISO Pack Installation to Output of System .................................................................................... 13
2.8.1 ISO Pack Input ................................
2.8.2 ISO Pack Output .................................................................................................................... 14
2.8.3 120V/120V Output ................................................................................................................. 14
2.8.4 208V Output ........................................................................................................................... 14
2.8.5 240V Output ........................................................................................................................... 15
2.8.6 Multiple Voltage Output .......................................................................................................... 16
2.8.7 120V and 208V Output........................................................................................................... 16
2.8.8 120V and 240V Output........................................................................................................... 16
2.9 EPO Connection ........................................................................................................................... 17
2.10 Parallel UPS Systems .................................................................... Error! Bookmark not defined.
2.10.1 Calibration ............................................................................................................................ 38
2.10.2 Parallel Operation. ............................................................................................................... 40
2.11 Frequency Converter Mode ........................................................................................................ 18
2.12 Permantly silence Audible Alarm ................................................................................................ 19
3. Operation ........................................................................................................................................... 20
3.1 Operating Mode/Status Description .............................................................................................. 20
3.2 Button Operation .......................................................................................................................... 20
3.3 LED Indicators .............................................................................................................................. 21
3.4 Audible alarm ............................................................................................................................... 21
3.5 Single UPS Operation................................................................................................................... 21
3.5.1 Turn on the UPS with utility power supply (to Line mode) ...................................................... 21
....................................................................................... 13
Page | v
Page 7
3.5.2 Turn on the UPS without utility power supply (to Battery mode) ............................................. 21
3.5.3 Connect devices to UPS ........................................................................................................ 22
3.5.4 Charge the batteries .............................................................................................................. 22
3.5.5 Battery Mode operation .......................................................................................................... 22
3.5.6 Test the batteries ................................................................................................................... 22
3.5.7 Turn off the UPS with utility power supply in Line mode ......................................................... 23
3.5.8 Turn off the UPS without utility power supply in Battery mode ................................................ 23
3.6 LCD Operation.............................................................................................................................. 24
3.6.1 Main interface (home page) ................................................................................................... 25
3.6.2 Operation menu ..................................................................................................................... 25
4. Trouble Shooting ................................................................................................................................ 32
4.1 Warning status.............................................................................................................................. 32
4.2 Fault mode ................................................................................................................................... 32
4.3 Trouble shooting table .................................................................................................................. 33
4.3.1 Warnings ............................................................................................................................... 33
4.3.2 Faults ..................................................................................................................................... 34
5. Specifications ..................................................................................................................................... 35
5.1 General Specification.................................................................................................................... 35
5.2 Nominal UPS Output Current ........................................................................................................ 36
5.3 Recommended Wiring .................................................................................................................. 36
5.4 Agency Listings ............................................................................................................................ 36
6. Storage .............................................................................................................................................. 36
7 Recommended Replacement Intervals ............................................................................................... 37
Figures
Figure 1: 6KVA/10KVA UPS Rear Panel ................................................................................................. 4
Figure 2: 6KVA/10KVA UPS Input/Output Terminal Connection .............................................................. 4
Figure 3: Battery Pack Rear Panel .......................................................................................................... 5
Figure 4: ISO Pack Rear Panel ............................................................................................................... 5
Figure 5: 3U Tower Installation ................................................................................................................ 7
gure 6: 6U Tower Installation ............................................................................................................... 7
Fi
Figure 7: Rack Mount Installation ............................................................................................................ 8
Figure 8: Terminal block wiring diagram of UPS...................................................................................... 9
Figure 9: Connection between Battery Pack and UPS .......................................................................... 10
Figure 10: ISO Pack 120V Input and 208V Output ................................................................................ 11
Figure 11: ISO Pack 120V Input and 208V Output ................................................................................ 12
Figure 12: ISO Pack Input 1-line ........................................................................................................... 13
Figure 13: Wiring UPS output to ISO Pack – 240V ................................................................................ 13
Figure 14: Wiring UPS output to ISO Pack – 208V ................................................................................ 13
Figure 15: Output wiring of ISO Pack – 120V ........................................................................................ 14
Figure 16: Output wiring of ISO Pack – 208V ........................................................................................ 14
Figure 17: Output wiring of ISO Pack – 240V ........................................................................................ 15
Figure 18: Output wiring of ISO Pack – 208V & 120V ........................................................................... 16
Figure 19: Output wiring of ISO Pack – 240V & 120V ........................................................................... 16
Figure 20: EPO connections on UPS .................................................................................................... 17
Figure 21: UPS Parallel Communication ports ...................................................................................... 38
Figure 22: Wiring of two UPS’s in parallel ............................................................................................. 40
Figure 23: Wiring of three UPS’s in parallel ........................................................................................... 40
Figure 24: Panel Layout ........................................................................................................................ 20
Page | vi
Page 8

1. Safety Warnings and EMC instructions

1.1 UPS Location

Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
Only operate your UPS at indoor temperatures between 32°F and 104°F (between 0°C and 40°C).
Leave adequate space around all sides of the UPS for proper ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit's internal cooling, eventually causing product damage not covered under warranty.

1.2 Connections

There is feedback protection inside.
This UPS should be connected with properly grounded utility system (TN grounding system).
The input source for this unit must be single-phase rated in accordance with the equipment nameplate and must be suitably grounded.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
An external branch circuit breaker at the UPS output side is strongly recommended to provide overcurrent protection or easy disconnection of load device.

1.3 Maintenance

Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed. Note that potentially lethal voltages exist within this unit as long as the battery supply is connected.
Your UPS power module and battery module(s) do not require routine maintenance. Do not open them for any reason. There are no user-serviceable parts inside.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists at the terminals of high capacity capacitor such as BUS-capacitors.
Fuses should be replaced only with fuses of the same number and type and should be replaced only by factory authorized personnel.
The battery circuit is not isolated from the input voltage. Verify that no voltage between the battery terminals and ground is present before maintenance or repair. Hazardous voltages may occur between the battery terminals and the ground.
Page | 1
Page 9

1.4 Battery

Do not operate your UPS without connecting it to an external battery module.
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions.
Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions.
o Remove watches, rings, or other metal objects. o Use tools with insulated handles. o Wear rubber gloves and boots. o Do not lay tools or metal parts on top of batteries. o Disconnect charging source prior to connecting or disconnecting battery terminals. o Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground.
Contact with any part of a grounded battery can result in electrical shock.
The batteries are recyclable. The batteries must be deposed of correctly according to local regulation.
Do not dispose of the batteries in a fire.
Do not short or bridge the battery terminals with any object.
Unplug and turn off the UPS before performing battery replacement.
Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). Use tools with insulated handles.
Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply.
Page | 2
Page 10

2. Installation

Model
Type
SCV-60022
6 kVA Single model
SCV-60022-P
6 kVA Parallel model
SCV-11022
10 kVA Single model
SCV-11022-P
10 kVA Parallel model
Model
Type
SCV-60021
6 kVA Single model
SCV-60021-P
6 kVA Parallel model
SCV-11021
10 kVA Single model
SCV-11021-P
10 kVA Parallel model
Systems with UPS and matching Battery Pack
Systems with UPS, matching Battery Pack and ISO Pack

2.1 Unpacking and Inspection

Unpack the package and check the package contents. The shipping package contains:
(1) UPS
(1) user manual
(1) monitoring software CD
(1) RS-232 cable (option)
(1) USB cable
(1) battery cable
Tower type installation supporters
Rack type installation ears
Battery cable connection ears
Depending on what UPS is ordered, the following optional parts may be in the package:
(1) Parallel cable
(1) Share current cable
(1) OP relay board
(1) parallel board
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged during transportation. If there is any damage or lack of parts, do not turn on the unit and notify the carrier and factory immediately. Please keep the original package in a safe place for future use.
Page | 3
Page 11
18

2.2 UPS Rear Panel View

Figure 1: 6KVA/10KVA UPS Rear Panel
Figure 2: 6KVA/10KVA UPS Input/Output Terminal Connection
(1) RS-232 communication port. Connect your UPS to a workstation or server. It uses RS-232
protocol to communicate. (2) USB communication port. Connect your UPS to a workstation or server. (3) EPO (Emergency Power Off) connector. Connect to a contact closure switch to enable
emergency power off. (4) Share current port. UPS balanced current control in parallel operation. (“-P” modules only) (5) Parallel port. UPS communication in parallel operation (“-P” modules only) (6) Intelligent slot. Optional accessories to remotely control and monitor your UPS system. (7) EMBS (External Maintain Bypass Switch) port. Interface between UPS and EMBS (8) Cooling fan. Ventilates the inside of the power module. (9) External battery connector. Use this to connect battery modules to the power module. (10) Input circuit breaker (11) Terminal cover (12) Convenience IEC outlets – 15A outlets for convenience (13) Breaker for IEC outlets (14) Input ground (15) Input terminals (16) Output terminals (17) Output ground (18) Equipment Ground Stud
Page | 4
Page 12
Figure 3: Battery Pack Rear Panel
(1) External Battery Connector (2) Battery pack output circuit breaker

2.3 ISO Pack Cabinet Rear Panel View

Figure 4: ISO Pack Rear Panel
Page | 5
Terminals: M6 bolts
Page 13

2.4 System Single Line Diagram

2.4.1 UPS Single Line Diagram

2.4.2 ISO Pack Single Line diagram

Note1: Field installed jumper required for 208V or 240V at T2 terminals.
Page | 6
Page 14

2.5 Tower/Rack Installation

2.5.1 Tower Installation

The UPS system is shipped with four plastic feet and plastic extensions. These can be used to tower mount the UPS power module (3U) or UPS power module and a Battery Pack (6U) or UPS power module, ISO Pack and a Battery Pack (9U). If an ISO Pack is ordered, the extra extension can be installed similar as in Figure 6 and the Battery Pack must be installed next to the UPS.
1. For the UPS module only
a. Assemble two feet and one short extension together to make one support with 5.12in
(13cm) width. The other support can be copied in same method.
2. For the UPS and matching Battery Pack
a. Assemble the two feet and two long extensions together to make one support with 10.25in
(26cm) width. The other support can be copied in same method.
3. For the UPS, ISO Pack and matching Battery Pack
a. Assemble the two feet and three long extensions together to make one support with
15.37in (39cm) width. The other support can be copied in same method.
4. Align the two supports in your installation area, approximately 13.75in (35cm) apart.
5. Place the units on their sides in the support. The LCD of UPS should be on upper half part of front
panel after completion.
6. For the UPS and battery pack only, install flat metal bracket across the rear of the UPS and battery
packs.
Page | 7
Figure 5: 3U Tower Installation
Figure 6: 6U Tower Installation
Page 15

2.5.2 Rack type installation

1. Attach mounting ears to the side mounting holes of UPS using the screws provided; the ears should face forward.
2. Lift the UPS module and slide it onto the mounting shelves.
3. Attach the UPS module to the rack by passing the screws, nuts and washers (user-provided) through mounting ears and into the rack rails.
4. Repeat steps 1-3 for the matching Battery Pack and ISO Pack.
Figure 7: Rack Mount Installation
Page | 8
Page 16

2.6 Single UPS Installation

Input Ground
Input Line 2 (N)
Input Line 1 (L)
Output Line 2 (N)
Output Line 1 (L)
Output Ground
Installation and wiring must be set in accordance with the national and local codes.

2.6.1 UPS Input/Output Wiring

1. Ensure the input feed wire and breakers are rated for the current capacity of the UPS to avoid the hazards of electric shock or fire. See 5.2 Nominal UPS Output Current for maximum current.
2. Remove t he t erminal bl ock c over on the rear panel of UPS. Then, c onnect the input and output wires according to Figure 8.
NOTE: Connect the earth ground wire first when making wire connection. Disconnect the earth
ground wire last when making wire disconnection.
NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: Install the output breaker between the output terminal and the load. The breaker should be qualified
with leakage current protection if necessary.
Figure 8: Terminal block wiring diagram of UPS
Page | 9
Page 17

2.6.2 Battery Pack Installation

Figure 9: Connection between Battery Pack and UPS
NOTE: Set the battery pack breaker in “OFF” position before installing the battery pack.
• Battery cable can connect to either battery connector in Battery Pack.
• If more than one (1) Battery Pack is used per UPS, subsequent Battery Packs are connected from previous Battery Pack to next Battery Pack. It does not matter which battery connector are used.
• For standard matching battery pack, there is one DC breaker to disconnect the battery pack and the UPS. But for other external battery packs, contact your Staco Representative.
• For the 10KVA model, it may be connected to a maximum of (11) extension battery packs with 9AH batteries.
• For the 6KVA model, it may be connected to a maximum of (14) extension battery packs with 9AH batteries.
• The battery cables are keyed to prevent accidental mis-wiring. However, verify the polarity marking on external battery connector and make sure the correct battery polarity is connected. Wrong connection may cause permanent damage to the UPS.
Page | 10
Page 18

2.7 ISO Pack Installation to Input of System

The ISO Pack can be used to obtain 120V inputs

2.7.1 120V Input and 208V output

Jumper must be added between N1 & N2 and X11 & X2 as shown in Figure 10 X11-N2
. Connect the input to
Page | 11
Figure 10: ISO Pack 120V Input and 208V Output
Page 19

2.7.2 120V Input and 240V output

Jumper must be added between N1 & N2 and X11 & X2 as shown in Figure 11 X11-N2
. Connect the input to
Figure 11: ISO Pack 120V Input and 240V Output
Page | 12
Page 20

2.8 ISO Pack Installation to Output of System

240V
X1
N
X3
N
L1
L2
X2
Inp ut
208V
N
The ISO Pack can be used to obtain 120V, 208V and/or 240V outputs.

2.8.1 ISO Pack Input

If an ISO Pack is being installed, the output of the UPS will be connected to the input terminals of the ISO Pack.
Figure 12: ISO Pack Input 1-line
240V System
208V System
Page | 13
Figure 13: Wiring UPS output to ISO Pack – 240V
Figure 14: Wiring UPS output to ISO Pack – 208V
Page 21

2.8.2 ISO Pack Output

The Transformer in the ISO Pack is an Isolation transformer. This is considered a separately derived source and any ground bonding needs to be done according to local and national regulations.

2.8.3 120V/120V Output

There are 2 sets of 120V. Each set can carry ½ of the total UPS capacity. Connect one load to X11-N1 and the other load to X2-N2.
Figure 15: Output wiring of ISO Pack – 120V

2.8.4 208V Output Jumper must be added between N1 and X2 as shown in Figure 16

Figure 16: Output wiring of ISO Pack – 208V
. Connect the load to X12-N2
Page | 14
Page 22

2.8.5 240V Output

Jumper must be added between N1 and X2 as shown in Figure 17
. Connect the load to X11-N2
Figure 17: Output wiring of ISO Pack – 240V
Page | 15
Page 23

2.8.6 Multiple Voltage Output

Due to limited terminal space, some connections for multiple output voltages need to be made external to the ISO Pack.

2.8.7 120V and 208V Output

120V load connects to X2-N2 208V load connects to X12-N2 (ref. Figure 18)
Figure 18: Output wiring of ISO Pack – 208V & 120V

2.8.8 120V and 240V Output

120V load connects to X2-N2 or X11-N1 240V load connects to X11-N2 (ref. Figure 19)
Page | 16
Figure 19: Output wiring of ISO Pack – 240V & 120V
Page 24
Terminals are shorted/NC for normal UPS

2.9 EPO Connection Note: Keep the EPO connector shorted for normal UPS operation. To activate EPO function, open the

terminals.
operation.
Figure 20: EPO connections on UPS
WARNING: The EPO, RS-232 and USB circuits are an IEC 60950 safety extra low voltage
(SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.
Page | 17
Page 25

2.10 Frequency Converter Mode

To set-up the unit to run as a Frequency Converter Mode follow the instructions below.
1. Install the UPS system per the instructions above.
2. Verify mains input is connected correctly, and the UPS input breaker is at “ON” position.
3. If battery pack is installed: Verify battery is connected correctly, and the battery pack breaker is at “ON” position.
4. Apply input power.
a. Fan will start running, LCD will initialize and UPS will start-up in Bypass mode and supply
power to load.
5. Press the “UP” or “DOWN” button at the home page, the screen will display the main menu. In the main menu, there are 5 items (Control / Measurement / Information / Setting / Alarm) for selection.
6. Press “UP” or “DOWN” button to select Setting Menu.
7. Press “ON/ENTER” button to confirm the selection.
8. Scroll to Freq. Press “ON/ENTER” button.
9. Using the Up/Down arrows, adjust to desired output frequency.
b. 50Hz: The output frequency is set for 50Hz. c. 60Hz: The output frequency is set for 60Hz. d. Auto: If selected, output frequency will be decided according to the latest normal utility
frequency.
i. 46Hz to 54Hz, the output frequency will be 50.0Hz.
ii. 56Hz to 64Hz, the output frequency will be 60.0Hz.
10. Press “ON/ENTER” button.
11. Scroll to CVCF. Press “ON/ENTER” button.
12. Using the Up/Down arrows, select “Enabled”.
Enable: The output frequency will be fixed at 50Hz or 60Hz according to setting of “Freq”. The input frequency could be from 46Hz to 64Hz.
Disable: The output frequency will synchronize with the input frequency within 46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz system.
13. Press “ESC” to return to Main Menu.
14. Turn On unit per the instructions in the User’s Manual and verify the output frequency is correct.
When the UPS is turned on for first time, the bypass will close for approximately 6 seconds until controls have fully initialized. It is recommended to have an interrupt device between Frequency Converter unit and critical load. The interrupt device should be open until Frequency Converter is fully initialized
.
If Frequency Converter is used without batteries, the user may have to reconfigure the system for Frequency Converter mode if the utility input to the unit is removed.
Page | 18
Page 26

2.11 Permantly silence Audible Alarm

WARNING: This procedure will not allow the audible alarm to activate for any alarm or fault.
1. On CD that came with unit, Install ViewPower software per software instructions.
2. Connect USB cord from computer to UPS unit (see Figure 1).
3. Open ViewPower software.
4. Click on connected unit.
5. Click on Login in upper right corner.
6. Enter password (default: administrator).
7. Click on UPS Settings.
8. Click on Parameter Settings.
9. Set parameter UPS Alarm to Disable.
10. Click Apply.
To turn on Audible Alarm, set UPS Alarm to Enable.
Page | 19
Page 27
Mode/Status
Description
When UPS is powered on, it will enter into this mode for a few seconds for initializing the CPU and system.
When the input voltage is within acceptable range, and the UPS is turned on (the
The UPS will also charge the battery in Line mode.
When the input voltage is within voltage regulation range and “ECO” is enabled,
will transfer to inverter supplying the power to load (similar to line mode).
When input frequency is within 46 to 64Hz, the UPS can be set with a constant
battery in this mode. There is no bypass in this mode.
When the input voltage is out of the acceptable range or power failure, and the
from the battery.
When input voltage is within acceptable range and bypass is enabled, and the
supply power to the load through bypass.
If some errors occur in the UPS (but it is still running normally), some alarms will
shooting.
When UPS has fatal error, it will beep continuously and go to fault mode and display fault messages on LCD.
Press this button to turn on the
selection in the menu.
Press this button to turn off the
menu.
Press this button to select the
setting.
Press this button to select the
*If pressing UP and DOWN buttons together, the LCD

3. Operation

3.1 Operating Mode/Status Description

UPS starting up
Line Mode
ECO Mode
Converter Mode
Battery Mode
Bypass Mode
Battery Test
Mode
Warning Status
Fault Mode
inverter is running), the UPS will output pure and stable sine wave AC voltage.
the UPS will bypass voltage to output for energy saving. If the input voltage is out of the regulation range but it is still within acceptable range of line mode, the UPS
output frequency (50 Hz or 60 Hz) through the inverter. The UPS will still charge
UPS is turned on (the inverter is running), the UPS will provide backup power
UPS (inverter) is not turned on or the inverter can’t take the load, the UPS will
This operation is used to check the battery status. When the UPS is in Line mode or Converter mode, and the battery test command is enabled through LCD or monitoring software, the UPS will start Battery Test.
appear on the LCD and buzzer; the warning information is useful for trouble

3.2 Button Operation

Button Function
ON/ENTER
OFF/ESC
UP*
DOWN*
display will rotate 90ºautomatically. This operation is used when configuring the UPS to Rack type or Tower type.
Figure 21: Panel Layout
UPS.
Or press it to confirm the
UPS.
Or press it to return to last
upper item in the menu.
Or previous page in the screen. Or increase the number in the
lower item in the menu
Or next page in the screen Or decrease the number in the
Page | 20
Page 28
LED
Bypass
Line
Battery
Fault
UPS starting up
  
Bypass mode
● ○ ○
Line mode / Converter mode
Battery mode
○ ○ ●
Fault mode
○ ○ ○
Battery test mode
○ ● ●
ECO mode
● ● ○
UPS status
Buzzer status
Muted
Bypass mode
Beeping once every 2 minutes
Yes
Battery / Battery-test mode (normal battery voltage)
Beeping once every 4 seconds
Yes
Battery / Battery-test mode (low battery voltage)
Beeping once every second
Yes
Fault
Beeping continuously
Yes
Warnings (except overload)
Beeping once every second
No
Overload
Beeping twice every second
No
Others
Mute
-

3.3 LED Indicators

There are 4 LEDs on the front panel to show the UPS working status:
Note: LED is lit; LED is off;  LED is flashing.

3.4 Audible alarm

3.5 Single UPS Operation

3.5.1 Turn on the UPS with utility power supply (to Line mode)

1. Verify mains input and battery are connected correctly, and the UPS input and battery pack breaker is at “ON” position;
2. Apply input power.
Fan will start running, LCD will initialize and UPS will start-up in Bypass mode and supply power to the load.
NOTE: When UPS is in Bypass mode, the load is not protected by UPS.
3. Press the “ON/ENTER” button while LCD is on default home screen,
LCD will show a prompt page of “Turn On”;
4. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”,
UPS will be starting up while beeping once.
You could also enter the “control menu” to select the instruction “Turn On” to startup the
UPS. See 3.6.2.2 Control items.
5. A few seconds later, the UPS will enter into Line mode; “Line mode” will be displayed on LCD.

3.5.2 Turn on the UPS without utility power supply (to Battery mode)

1. Verify mains input and battery are connected correctly, and the UPS input and battery pack breaker is at “ON” position;
2. Press the “ON/ENTER” button to start up the internal power,
UPS controls will turn on, but no power will be available to the load.
3. Within 15 seconds, press the “ON/ENTER” button while LCD is on default home screen,
LCD will show a prompt page of “Turn On”;
4. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”,
UPS will be starting up while beeping once.
You could also enter the “control menu” to select the instruction “Turn On” to startup the
UPS. See 3.6.2.2 Control items.
5. A few seconds later, the UPS will enter into Battery mode; “Battery mode” will be displayed on LCD.
Page | 21
Page 29

3.5.3 Connect devices to UPS

After the UPS is turned on, you can connect devices (load) to the UPS.
1. Turn on the UPS first and then switch on the devices one by one; the LCD panel will display total load level.
2. If inductive loads needed to be connected, such as a printer, the in-rush current should be calculated carefully to see if capacity of the UPS can handle the in-rush.
3. If the UPS is overloaded, the buzzer will beep twice every second.
4. When the UPS is overloaded, remove some loads immediately.
i. If the overload timer expires while in Line Mode, the UPS will automatically transfer to Bypass
mode. After the overload is removed, it will return to Line mode.
ii. If the overload timer expires while in Battery Mode, the UPS will enter fault status.
1. At this time, if bypass is enabled, the UPS will power the load via bypass.
2. If bypass function is disabled or the input power is not within bypass acceptable range, it will cut off output immediately.

3.5.4 Charge the batteries

1. After the UPS is connected to the utility power, the charger will charge the batteries automatically except in Battery mode or during battery test.
2. It is suggested to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter than expected.
3. Make sure the battery numbers setting on the control board (refer to the section of changing battery quantity) is consistent with actual connection.

3.5.5 Battery Mode operation

1. When the UPS is in Battery mode, the buzzer will beep according to different battery capacity.
i. Buzzer will beep once every 4 seconds in battery mode,
ii. When the battery voltage drops to the alarm level, the buzzer will beep once per second and
the UPS will shut down automatically soon.
1. Users could switch off some non-critical loads to disable the shutdown alarm and prolong the backup time.
2. If there is no more load to be taken off at that time, shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2. In Battery mode, you could enter “Control->Mute” on LCD to silence the buzzer. See 3.6.2.2 Control items.
3. The backup time depends on the external battery capacity.
4. The backup time may change under different environment temperature and load type.
5. The maximum backup time is limited by default 16.5 hours (After discharging 16.5 hours, UPS will shut down automatically to protect the battery). The time could be modified through LCD panel or communication port.

3.5.6 Test the batteries

1. If you need to check the battery status or performance when the UPS is running in Line / Converter / ECO mode, you could enter “Control->Batt Test” to instruct the UPS to do battery test. See 3.6.2.2 Control items.
2. Battery test can be set through monitoring software.
3. If the UPS is in battery testing, “Battery test mode” will be displayed on LCD, the buzzer indication will be the same as Battery mode, but both line LED and battery LED will be lit.
Page | 22
Page 30

3.5.7 Turn off the UPS with utility power supply in Line mode

1. When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
2. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”;
UPS will be turning off to bypass mode while beeping once. You could also enter the “control menu” to select the instruction “Turn Off” to turn off the UPS. See 3.6.2.2 Control items.
NOTE: “Turn Off” means that UPS is not working on line / converter / ECO / battery / battery test
mode. So even though the UPS is turned off, if input or bypass voltage is normal, the internal power supply will still be working; if bypass status has been set to “enable”, the output voltage of the UPS will still exist.
3. To fully cut off the output, please switch off the external input breaker. A few seconds later, there is no display shown on the panel and UPS is completely off.

3.5.8 Turn off the UPS without utility power supply in Battery mode

1. When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”;
2. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”;
UPS will be turning off to bypass mode while beeping once. You could also enter the “control menu” to select the instruction “Turn Off” to turn off the UPS. Please refer to the section of “LCD operation”.
3. If there is no bypass input voltage, the UPS will cut off all power supply and there is no display shown on the panel.
Page | 23
Page 31

3.6 LCD Operation

Page | 24
Page 32

3.6.1 Main interface (home page)

.
1. In the first line, it will display the operating mode.
2. When alarms happen, the warning or fault information will display below the “load” line.
3. When the front panel is not operated for a period of time, the screen will return to this home page.
4. Press the “UP” or “DOWN” button to enter the main operation menu.

3.6.2 Operation menu

3.6.2.1 Main menu
1. After pressing the “UP” or “DOWN” button at the home page, the screen will display the main menu. In the main menu, there are 5 items (Control / Measurement / Information / Setting / Alarm) for selection.
2. Press “UP” or “DOWN” button to select item.
3. Press “ON/ENTER” button to confirm the selection.
4. Press “OFF/ESC” button to exit to home page.
3.6.2.2 Control items
NOTE 1: “Turn On” will be displayed if UPS is off; “Turn Off” will be displayed if UPS is on.
NOTE 2: “Para Unlock” appears only during a parallel communication failure.
1) Turn On/Turn Off
This item is for turning on/off the UPS; a) In Bypass mode, it will display “Turn On”, if it is selected and confirmed, the UPS will transfer to
line mode/ converter mode/ ECO mode/ battery mode according to the setting and input status.
NOTE: The UPS can be turned on by pressing the “ON/ENTER” button in home page, it is not
necessary to enter into this control menu.
Page | 25
Page 33
b) For online mode, converter mode, ECO mode or battery mode, it will display “Turn Off”. If it is
selected and confirmed, the UPS will transfer to bypass mode or shutdown.
NOTE: The UPS can be turned off by pressing the “OFF/ESC” button in home page, it is not
necessary to enter into this control menu.
2) Battery Test
This item can be shown in all modes. However, battery test will not work in Battery/Fault/Eco mode.
3) Mute
This item is to mute the buzzer on battery/bypass/fault mode. Although this item could be seen under other modes, it will not work under other modes. After confirming, it will go to the home page and change the mute icon.
Page | 26
Page 34
4) Para Unlock
This is the instruction of “parallel (protection) unlock”. It only appears when the LCD shows the warning “3F: Para Protect” (that means the parallel system is in protection and could not startup). If it’s necessary to startup the UPS, this instruction must be executed.
NOTE: Before executing this instruction, you must check if the system cables and connections are in correct
and safe condition. Please read the related content in the section of trouble shooting.
3.6.2.3 Measurement pages
These pages display the measurement value of the parameters such as voltage / current / frequency / power / capacity / time etc. Press “UP” or “DOWN” to explore the pages.
Page | 27
Page 35
3.6.2.4 Information Pages
These pages display the information of parameters setting value or status. Press “UP” or “DOWN” to explore the pages.
3.6.2.5 Setting Menu
This menu is used to adjust the parameters or do calibration.
NOTE: Not all settings will be available in every operation mode. If the setting is not available in present
mode, the LCD will show prompt message of “Item cannot be set in this mode”. Press any button or just wait for several seconds then this message will disappear.
Page | 28
Page 36
Bypass setting
Interface
Description
Bypass:
Status: Open Enable HighLoss V: 264V LowLoss V: 110V HighLoss F: 64Hz LowLoss F: 56Hz
Bypass:
Status: Fo rbid
HighLoss V: 264V LowLoss V: 110V HighLoss F: 64Hz LowLoss F: 56Hz
1. Status (only available in bypass / line mode)
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
Interface
Description
1. Status (default: Disabled)
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
ECO setting (can only be changed while in bypass mode)
1.1 Open/Forbid: (default: Open) Open: Bypass allowed. When selected, UPS will run in Bypass mode depending on bypass enabled/disabled setting. Forbid: Bypass not allowed. When selected, running in Bypass
mode is not allowed under any situations.
1.2 Enable/Disable: (default: Enable)
This option appears only when “Open/Forbid” is set to “Open”.
Enable: Bypass enabled. When selected, Bypass mode is activated. Disable: Bypass disabled. When selected, automatic bypass is
acceptable, but “manual bypass” is not available. “Manual bypass” means users manually operate UPS in Bypass mode (for example, in Line mode turning off the UPS to Bypass mode). Here the UPS will go to bypass mode but without output if it is turned off in line mode.
NOTE: The following items are only available in bypass mode:
2. HighLoss V: (default: 264V)
Set the acceptable high voltage for bypass.
Setting range is from (Rated Output Volt +11V) to 276V.
3. LowLoss V: (default: 110V)
Set the acceptable low voltage for bypass.
Setting range is from 110V to (Rated Output Volt - 11V).
4. HighLoss F: (default: 64Hz) Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51Hz to 54 Hz. 60 Hz: Setting range is from 61Hz to 64Hz.
5. LowLoss F: (default: 56Hz) Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
2. HighLoss V: High voltage point in ECO mode.
3. LowLoss V: Low voltage point in ECO mode.
4. HighLoss F: (default: 58Hz)
5. LowLoss F: (default: 62Hz)
Page | 29
Enable: Enable ECO Function Disable: Disable ECO Function
The setting range is from +5% to +10% of the nominal voltage.
The setting range is from -5% to -10% of the nominal voltage.
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz. 60 Hz system: Setting range is from 56Hz to 58Hz.
Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
Page 37
Interface
Description
Output:
Vo lt: 208V Freq: Auto CVCF: Disable
1. Volt: (default: 208V*)
represents converter mode.
Interface
Description
Batter y:
DisChg Protect: Enable: 990 Minute Batt Test Type: Short Time: 10 Second
1. DisChg Protect: (default: Enable)
Output setting (can only be changed while in bypass mode)
200: Presenting the rated output voltage with 200Vac 208: Presenting the rated output voltage with 208Vac 220: Presenting the rated output voltage with 220Vac 230: Presenting the rated output voltage with 230Vac 240: Presenting the rated output voltage with 240Vac *NOTE: Units ending “-240” has defaut set to 240V
2. Freq: (default: Auto) 50Hz: The output frequency is set for 50Hz. 60Hz: The output frequency is set for 60Hz. Auto: If selected, output frequency will be decided according to the
latest normal utility frequency. 46Hz to 54Hz, the output frequency will be 50.0Hz. 56Hz to 64Hz, the output frequency will be 60.0Hz.
3. CVCF: (default: Disabled) To decide whether or not converter mode is activated. Enable: The output frequency will be fixed at 50Hz or 60Hz according to setting of “Freq”. The input frequency could be from 46Hz to 64Hz. Disable: The output frequency will synchronize with the input frequency within 46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz system. NOTE: CVCF means Constant Voltage and Constant Frequency, it
Battery setting (available in all operation modes)
Enable: Battery discharge protection function is enabled. When UPS has
been c ontinuously working in “ battery/battery t est m ode”, t he UPS wi ll automatically shut down after protection timer has expired
Disable: Battery discharge protection function is disabled.
000~999: (default: 990)The m aximum di scharge t ime ranging from 0 t o
999mins. UPS will shut down to protect b attery after backup time arrives when the “Dischg Protect” is enabled.
2. Batt Test Type: (default: Short Time)
2.1 Short Time: Battery test will last for constant 10 seconds;
2.2 Long Time: Battery test could last longer. This time duration is able to
adjust within 01~99 minutes.
2.3 Till Batt Low: Battery test will not stop until battery voltage is low.
Page | 30
Page 38
Interface
Description
Calibratio n:
Batt: 273.0 +0.0 Inv: 209.0 +0.0 Chg: 273.0 +0.0
1. Batt: Calibrate the battery voltage measurement; the calibration range
Interface
Description
Other Setting:
Hot Standby Backup Time
Hot Standby:
Status: Disable
Backup Time:
Batt Groups: 01 Batt Ca p: 9AH Factor: 0.9
Calibration
is from 0V to 5.7V, the default value is 0V. It is available in all operation modes.
2. Inv: Adjust the inverter output voltage; the adjustable range is from 0V to 6.4V, the default value is 0V.
It is only available in line/battery/converter mode;
3. Chg: Adjust the Charger output voltage; the adjustable value is from 0V to 6.9V, the default value is 0V.
It is only available in bypass/line/ECO /converter mode. (NOTE: Before making charger output voltage adjustment, be sure to disconnect all batteries first to get the accurate charger voltage. Be careful that the adjustment should be suitable to battery specifications.)
Other settings (available in all operation modes)
Hot standby: Enable: Hot standby function is enabled. It means that the current UPS is
set to be host of hot standby system, and it will automatically restart after AC recovery even without battery connected. Disable: Hot standby function is disabled. The UPS is running at normal mode and can’t restart without battery. Disable is default setting.
Backup Time: Batt Group: Number of Battery Strings connected to UPS. Can enter up
to 6 Batt Cap: Enter the size of the batteries used, Choose from 7/9/10/12/17/26/40/65/100 Ah. Factor: Set the factor to fine tune the battery runtime accuracy. Can be set from 0.0 to 9.9
3.6.2.6 Alarm page
This page records and displays the fault or warning events.
Page | 31
Page 39

4. Trouble Shooting

4.1 Warning status

When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems with the UPS. Users can see the warning code from LCD panel and refer to the trouble shooting table to check what problem has occurred.

4.2 Fault mode

1. When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error. Users can get t he fault code from the LCD panel. Please refer to the trouble shooting table to check what problems have occurred.
2. Don’t t ry t o turn on t he UPS ag ain be fore t he p roblem is c lear. If the p roblems c an’t b e fixed, please contact the distributor or service personnel immediately.
3. For e mergency c ase, pl ease c ut o ff the c onnection from u tility, ex ternal bat tery, and out put immediately to avoid further risk or danger.
Page | 32
Page 40

4.3 Trouble shooting table

LCD display
Possible cause
Remedy
01:
1) The battery is not connected
open.
07: Over Charge
1) Battery numbers and its setting is
charger failed.
08: Batt Low
1) Battery is discharged deeply to
3) Battery is at the end of life.
09: Over load
0A: Fan Error
1) Fan is blocked;
3) Fan detection circuit failed.
1) Unblock the fan;
3) Contact the factory for repair.
0B: EPO Enable
EPO plug (jumper) is removed or the external EPO switch is off.
Connect the EPO plug (jumper) properly or switch on the external EPO switch.
0D: Over Temp
The internal temperature is too high:
4) Load is too heavy.
0E: Charger Fail
10: IP Fuse Open
Input fuse on the power stage board is open.
33: Overload 3 Times
Locked in bypass after overload 3 times in 30 minutes.
Remove excess loads from UPS output first, then shut down the UPS and restart it.
3A: Maintain Open
EMBS port is open or the maintain
transferred to bypass).
3F: Para Protect
1) If the system is still needed to be operated in
the UPS may be destroyed.
If the UPS system does not operate correctly, please solve the problem by referring to the table below:

4.3.1 Warnings

Batt Open
properly;
2) The battery protection device is
The load is too heavy. Remove excess loads from UPS output.
Charger failed. Contact the factory for repair.
not matching;
2) Charger voltage is too high, the
low voltage;
2) Battery number is not correct;
2) Fan is at the end of life;
1) Environment is hot;
2) Fan is blocked or failed;
3) Ventilation is blocked by the wall or other goods;
1) Connect the battery properly;
2) Replace or restore the protection device.
1) Correct the battery number or its setting;
2) Disconnect the battery and check the charger output voltage, contact the factory for repair.
1) Recharge the battery;
2) Correct the battery number;
3) Replace the battery.
2) Contact the factory for replacing the fan;
1) Make sure the ambient temperature is not over 40ºC;
2) Make sure the fan is OK;
3) Make sure the ventilation is OK;
4) Remove some loads if possible.
switch sensor (connected to EMBS port) is triggered. (The UPS is
Parallel cable is still not connected properly when restart after the parallel system is faulted because of parallel communication failure. (When this warning appears, the UPS cannot start up; it is protection for parallel system)
Check and replace the input fuse.
If the EMBS port is short-circuited, the warning will disappear.
parallel mode, please connect the parallel cable properly, and choose “Para Unlock” in control menu to remove the warning, then the UPS can start up.
2) If the UPSs in the system are separated to single UPS, please disconnect the output to other UPSs and choose “Para Unlock” in control menu to remove the warning, then the UPS can start up.
NOTE: Be careful to check the UPS operation mode (parallel or single) and the connections. If the parallel cable is not connected in the parallel mode,
Page | 33
Page 41

4.3.2 Faults

01: Bus Start Fail 02: Bus Over
1) The mains input or load transient
2) The internal converter failed.
03: Bus Under
The internal converter failed, so the
DC bus voltage is too low.
04: Bus Unbalance
1) The load is special or abnormal, so
2) The internal converter failed.
11: Inv Start Fail
The internal inverter failed, so the
correctly.
12: Inv Volt High
The internal inverter failed, so the inverter voltage is too high.
13: Inv Volt Low
The internal inverter failed, so the inverter voltage is too low.
14: Output Short
Short circuit occurred on the UPS output.
1A: NegPower
UPS output power is negative. It
the parallel system.
21: Batt SCR Short
The internal battery SCR is failed and short.
24: Inv Rly Short
The internal inverter relay is stuck ON
Switch) is shorted.
35: Para Comm Fail
Parallel cable for communication is not
system.
36: OP.I Unbalance
The output current is extremely
parallel system.
41: Over Temp
The internal temperature is too high
4) Load is too heavy.
42: CPU Comm Fail
Internal communication between the CPUs failed
43: Over load
Overload time is out of the
automatically.
The internal converter failed, so the DC bus voltage could not be boosted correctly.
Contact the factory for repair
current cause the DC bus voltage to be too high;
the internal positive and negative DC bus voltages are unbalanced;
inverter voltage could not start up
means there is energy feedback into the internal of UPS from output. It may be caused by regenerative load; or caused by the current control failure in
1) Shutdown and restart the system to see if it happens again;
2) Contact the factory for repair.
Contact the factory for repair.
Contact the factory.
Contact the factory for repair.
Contact the factory for repair.
Contact the factory for repair.
Remove the short circuit.
Contact the factory.
or the SCR of STS (Static Transfer
connected properly in the parallel
unbalanced between the paralleled UPSs; there is some error in the
and reached the fault level (shutdown):
1) Environment is hot;
2) Fan is blocked or failed;
3) Ventilation is blocked by the wall
specification and the UPS shut down
or other goods;
Contact the factory for repair.
Contact the factory for repair.
Connect the parallel cable properly.
Contact the factory for repair.
1) Make sure the ambient temperature not over 40ºC;
2) Make sure the fan is OK;
3) Make sure the ventilation is OK;
4) Remove some loads if possible.
Contact the factory for repair.
Remove excess loads from UPS output and restart it.
Page | 34
Page 42

5. Specifications

MODEL
SCV-60022(P)
SCV-60021(P)
SCV-11022(P)
SCV-11021(P)
Phase
Single phase with ground
Capacity
6000 VA / 5400 W
10000 VA / 9000 W
INPUT
Nominal Voltage
200/208/220/230/240 VAC
Voltage Range
176 -300 VAC +/-3% @ 100% load
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
0.99 @ 100% load
Max Curr -208V/120V*
40A/58A
63A/96A
OUTPUT
Nominal Voltage, VAC
208/220/ 230/240
208/120 or 240/120
208/220/230/240
208/120 or 240/120
AC Voltage Regulation
± 1%
Frequency Sync Range
46~54 Hz or 56~64 Hz
Freq Range (Bat. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Overload (Line Mode)
100%~110%: 10min; 110%~130%: 1min; >130% : 1sec
Overload (Battery Mode)
Current Crest Ratio
3:1 (max.)
Harmonic Distortion (Load Type)
2% THD (Linear)
4% THD (Non-linear)
3% THD (Linear)
6% THD (Non-linear)
2% THD (Linear)
4% THD (Non-linear)
3% THD (Linear)
6% THD (Non-linear)
Transfer Time
0ms
Waveform (All Modes)
Pure Sinewave
EFFICIENCY
Line Mode
90%
84%
90%
84%
Battery Mode
88%
83%
88%
83%
ECO Mode
96%
87%
96%
87%
BATTERY
Nominal Voltage
240 VDC
Battery Type
VRLA, 12 V / 9 AH
VRLA, 12 V / 9 AH
Numbers
20
20
Typical Recharge Time
7 hours recover to 90% capacity
9 hours recover to 90% capacity
Float Charging Voltage
273 VDC
Charge Current (max.)
4 Amps
PHYSICAL
UPS Dimension, in**
17.24 x 5.15 x 23.85 (WxHxD)
17.24 x 5.15 x 27.00 (WxHxD)
Battery Dimension, in
17.24 x 5.15 x 24.631 (WxHxD)
ISO Pack, in (WxHxD)
N/A
17.24 x 5.15 x 24.81
N/A
17.24 x 5.15 x 27.96
UPS Weight, lbs.
37
44
Battery Weight, lbs.
138
Iso Pack Weight, lbs.
N/A
148
N/A
198
ENVIRONMENT
Operation Temperature
0 ~ 40°C (32°F ~ 104°F)(the battery life will decrease when > 25°C (77°F))
Operation Humidity
0-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 58dBA @ 1 Meter
Less than 60dBA @ 1 Meter
Operation Altitude***
<1000m
COMMUNICATIONS
Smart RS-232/USB Port
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, MAC
OPTIONS
SNMP Card
SNMP/ Web Browser capability
MODBUS Card
Provides communication with PCs through MODBUS protocol
CONTACT Card (AS/400)
*With ISO Pack 120V inputs paralleled for full capacity.

5.1 General Specification

100%~110%: 30sec; 110%~130%: 10sec; >130% : 1sec
Provides contact closures for remote monitoring of the UPS
**The depth dimension is from front of rear of UPS cabinet. The conduit landing area extends beyond the rear of the UPS
Cabinet 6KVA: 2.79” and 10kVA: 3.77”
*** If the UPS is installed or used in a place where the altitude is above 1000m(maximum 2000m), the output power must
be derated one percent per 100m.
*Product specifications are subject to change without further notice.
Page | 35
Page 43

5.2 Nominal UPS Output Current

Output Voltage
1201
208
220
230
240
6KVA
25
29
27
26
25
10KVA
42
48
45
43
42
Wiring spec (AWG)
1,2
Input
120V
Input
208/240V
Output
120V
208V
220V
230V
240V
6KVA 4 8
10
10
10
10
10
10KVA 1 6 8 8 8 8
8
Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (4th Edition)
Safety Markings : UL, CE
EMI
Conducted Emission.....................:IEC/EN 62040-2,FCC Part 15 Class A
Radiated Emission........................:IEC/EN 62040-2,FCC Part 15 Class A
EMS
ESD.............................................. :IEC/EN 61000-4-2, Level 4
RS.................................................:IEC/EN 61000-4-3, Level 3
EFT.............................................. :IEC/EN 61000-4-4, Level 4
SURGE........................................ :IEC/EN 61000-4-5, Level 4
CS................................................ :IEC/EN 61000-4-6, Level 3
Power-frequency Magnetic field...:IEC/EN 61000-4-8, Level 4
Low Frequency Signals................:IEC/EN 61000-2-2
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 30°C (-13°F - 86°F)
Every 8 months
5-8 hours
30°C - 40°C (86°F - 104°F)
Every 90 days
5-8 hours
40°C - 45°C (104°F - 113°F)
Every 30 days
5-8 hours
Model
NOTE 1: Current listed is for each 120V output

5.3 Recommended Wiring

Model
NOTE 1: It is recommended to use 75°C copper wire. NOTE 2: Recommended cable sized based on THW cables at 30°C ambient (NEC Table 310.16). If
different cables are used or installed at higher ambient, the cable size need to be reviewed. NOTE 3: 10 lb-in torque force when connecting to input/output terminal block for 6KVA models. NOTE 4: 18 lb-in torque force when connecting to input/output terminal block for 10KVA models. NOTE 5: External battery wires use reinforced insulation or double insulated wire.

5.4 Agency Listings

6. Storage

Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Page | 36
Page 44

7 Recommended Replacement Intervals

Component
Recommend Replace in:
Fans
4-5 years
Batteries
4-5 years
DC Filter Capacitor Board
5 years
The Staco UPS has a long design life. Due to the characteristics of the part, not the design of the UPS, certain components used in the design have a limited life, even with proper maintenance.
Service and maintenance work must be performed only by factory authorized personnel.
Staco recommends these limited-life components be periodically inspected and replaced before the expected expiration of their life cycle. The recommended replacement schedule is an estimate only. The life of these parts depends on site conditions such as ambient temperature, load profile, cleanliness of environment and other factors.
Staco Recommends a Factory Authorized Preventative Maintenance review is schedule at least once a year.
The functional lifetime of VRLA batteries is significantly affected by the temperature at which they are stored and operated. Ideally, VRLA batteries should be used in a 25º C (77º F) environment. For every
8.3º C (15º F) increase in temperature, the life expectancy of a battery will be halved.
Exposure to temperatures in excess of 32º C (90º F) should be limited to no more than 30 days per year. Under no circumstances should the VRLA battery be exposed to temperatures over 40º C (104º F) which can lead to thermal runaway, a condition that damages the battery. Thermal runaway can cause batteries to swell. If the battery cases burst, the hazardous contents may be exposed.
Maintaining proper ambient temperature usually requires installing the product in a temperature controlled space. Equipment rooms without cooling systems do not generally maintain the proper conditions for good battery life.
See Staco’s website for warranty details:
http://www.stacoenergy.com/support/literature-download-center.html
Page | 37
Page 45

Appendix – Optional Parallel UPS Systems

Requirements: Two parallel cables and two share current cables.
Parallel Operation requires a factory installed Paralleling Kit. (SCV-PAR-10)
At the rear of the unit; if plastic covers over (2) DB9 holes then the kit is NOT installed.
Figure 22: UPS Parallel Communication ports

A.1 Wiring Connection for Parallel Operation

Please follow below steps to connect cables for parallel models.
1. Please follow below figure to connect parallel cable and share current cable.
See Figure 21.
Page | 38
Page 46
2. Input and output grounding wires are directly connected to the case. Refer to below chart for the
Interface
Setting
-> - >
You c an c hoose Add or Sub to adjust i nverter v oltage. A nd the
input/output terminal wire connection.
3. If the UPS is connected to external battery pack, it’s required to install battery breaker (DC type) in each UPS.

A.2 Calibration

Verify items below before powering up the parallel system, in order to make sure UPS module parallel properly.
1. Make sure that the parallel board and OP relay board have been installed.
2. Make sure that each UPS has the same configuration (See 3.6.2.5 Setting Menu):
a) output voltage, b) output frequency, c) bypass voltage range, d) bypass frequency range, e) converter enable or disable, f) bypass enable or disable, g) bypass open or forbidden, h) frequency auto detect enable or disable, i) inverter short clear enable or disable
3. Turn on each UPS into the line mode or battery mode respectively (see 3.5.1 Turn on the UPS with utility power supply (to Line mode)). Measure and calibrate the output voltage with a multimeter.
Make sure the difference of the output voltage among the UPSs is less than 2.0V (typical 1V). If not, you can adjust the voltage via LCD as below (See 3.6.2.5 Setting Menu).
voltage range i s from 0V t o 9. 9V, the default value is 0V.
4. After ad justing the i nverter v oltage, c heck if the output v oltage de tection i s o k. If the di fference between the displayed value and t he voltage measured by a multimeter is more than 1V, please adjust it to make sure the difference is less than 1V. Then, shut down the UPS to save this setting into EEPROM.
Page | 39
Page 47

A.3 Parallel Operation.

1. Wire UPS parallel cables and Power cables as shown in below pictures:
Figure 23: Wiring of two UPS’s in parallel
Page | 40
Figure 24: Wiring of three UPS’s in parallel
Page 48
2. Turn on the parallel system
Master
Slave1
Slave2
With utility power supply (in AC mode)
a) Turn the breakers on for each battery pack and then turn on the input breaker and power on UPS
one by one.
NOTE: The parallel UPSs cannot use the same battery pack. Each UPS should be connected to its own battery pack.
At this moment, the fan is running and the UPS starts to initialize.
Several seconds later, UPSs operate in Bypass mode.
After a delay, UPS output relays close.
Then, parallel system supplies power to the loads via the bypass.
b) Check i f the pa rallel i nformation in LCD d isplay is s hown as in below p ictures. If p arallel UP S
systems are successfully set up, it will show “Parallel: Master”, “Parallel: Slave1” or “Parallel: Slave2”.
Note: If not , please do not go to nex t s tep and c heck i f t he par allel c ables hav e been c onnected properly.
c) Press and hold the “ON” button for 0.5s and turn on the UPSs one by one.
Without utility power supply (in Battery mode)
a) Turn on the battery breaker. b) Press the “ON” button of one UPS to turn on the power supply.
UPS will enter power on mode.
After initialization, UPS will enter No Output mode.
c) Within 15 seconds, press “ON” button again to turn on UPS d) A few seconds later, after UPS is on, the UPS will enter Battery mode. e) Then, repeat step b) and c) for remaining UPSs. f) The parallel system has been installed and starts to supply power to the load.
3. Turn off the parallel system
Press and hold the “OFF” button to turn off the UPS one by one. The buzzer will beep once. After a delay, the UPS will enter bypass mode or no output mode synchronously.
4. Add one new unit into the parallel system
a) You cannot add one new unit into the parallel system when whole system is running. You must
remove the load and shut down the system first. b) Make sure all of the UPSs are the parallel models and follow the connection diagram in step 1 c) Install the new parallel system.
5. Remove one unit from the parallel system
a) Press the “OFF” button twice. The U PS will enter into bypass mode or no output mode without
output. b) Turn off the output breaker of this unit. c) Turn off the input breaker of this unit. d) After it shuts down, move the parallel cable and share current cable. e) Remove the unit from the parallel system.
Page | 41
Page 49
Page | 42
Loading...