Staco Energy SC60021T, SC60022T, SC80021T, SC80022T, SC11021T User Manual

...
003-2282 Rev G 12/11/2009
301 Gaddis Boulevard • Dayton, Ohio 45403 U.S. Toll Free 866-261-1191
(937) 253-1191 • Fax: (937) 253-1723 Web site: www.stacoenergy.com
6kVA, 8kVA & 10kVA
Parallel Redundancy/Capacity
On-Line UPS
User’s Manual
Tower Models SC60021T, SC60022T SC80021T, SC80022T SC11021T, SC11022T
Form No. 003-2282 Rev G
1
Table of Contents
1. Important Safety Instruction ............................................................................. 2
1.1. An Important Notice ......................................................................................... 2
1.2. Storage Instruction ............................................................................................ 4
2. Product Introduction ......................................................................................... 5
2.1. General Characteristics ..................................................................................... 5
2.2. Symbols on the LCD Display Panel ................................................................. 7
2.3. Panel explanation ............................................................................................ 10
2.4. Communication Port Explanation ................................................................... 13
3. Installation and Operation ............................................................................... 14
3.1. Unpacking ....................................................................................................... 14
3.2. Selecting Installation Location........................................................................ 15
3.3. Installation of Casters Cover ........................................................................... 15
3.4. Terminal Block Explanation ........................................................................... 16
3.5. Operation Test and Installation Instruction ..................................................... 19
4. Troubleshooting Guide ................................................................................... 32
4.1. Trouble Shooting ............................................................................................ 32
5. Bundled Software Installation Guide .............................................................. 34
5.1. Hardware Installation ...................................................................................... 34
5.2. Software Installation ....................................................................................... 34
6. Customer Options Slots .................................................................................. 35
6.1. All the below interface cards are with built-in EPO function ......................... 35
6.2. R2E(2nd RS-232 ) card ................................................................................... 35
6.3. RSE(RS-485) card .......................................................................................... 35
6.4. USE(USB) card ............................................................................................... 36
6.5. DCE(Dry Contact)-B card .............................................................................. 36
6.6. SNMP Cards ................................................................................................... 37
6.7. The Installation of Interface Cards .................................................................. 38
7. Hot Swappable Battery Replacement ............................................................. 39
8. Specifications .................................................................................................. 41
Form No. 003-2282 Rev G
2
1. Important Safety Instruction
1.1. An Important Notice
1.1.1 For Parallel System installation, please refer to Parallel System Installation Guide Part number 003-2302
1.1.2 Because of small leakage currents” generated by the EMI filter of the UPS, it is necessary to insure that the UPS is properly grounded before connecting AC power to the input.
1.1.3 To ensure safety in all applications where a UPS is hard wired to the Electrical Supply, ensure that the system is installed by a Qualified Electrical Contractor.
1.1.4 The UPS has its own internal energy source (battery). When the UPS is operating from battery power when no AC input is available, there will be voltage at the output terminals.
1.1.5 Make sure that the AC Utility power source is correctly grounded.
1.1.6 Do not open the case, as there are no serviceable parts inside. Your Warranty will be void.
1.1.7 Do not try to repair the unit yourself; contact your local supplier or your warranty will be void.
1.1.8 Make sure that the rated input voltage of the UPS matches the available AC mains voltage.
1.1.9 Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system.
1.1.10 To eliminate any overheating of the UPS, keep all ventilation openings free from obstruction, and do not store anything on top of the UPS. Keep the UPS 12 inches away from the wall.
1.1.11 Make sure the UPS is installed within the proper environment as specified. (0-40 and 30-90% non-condensing humidity)
Form No. 003-2282 Rev G
3
1.1.12 Do not install the UPS in direct sunlight. Your warranty may be void if the batteries fail.
1.1.13 Install the UPS indoors as it is not designed for installation outdoors.
1.1.14 Dusty, corrosive and salty environments can do damage to any UPS.
1.1.15 Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
1.1.16 If liquids are spilled onto the UPS, or foreign objects dropped into the unit, the warranty will be null and void.
1.1.17 The battery will discharge naturally if the system is unused for any length of time.
1.1.18 Recharge the batteries every 2-3 months if unused. If this is not done the warranty will be null and void. When installed and being used, the batteries will be automatically recharged and kept in top condition.
1.1.19 This UPS supports electronic equipment in offices, telecommunications, process control, medical and security applications. This UPS is NOT intended for use in the following application:
a. Medical equipment directly related to human life b. Elevator, Metro (Subway) system or any other equipment related to
human safety.
c. Public system or critical computer systems.
1.1.20 Do not install the UPS in an environment with sparks, smoke or gas.
1.1.21 Make sure the UPS is completely turned off when moving the UPS from one place to another. It might cause electrical shock if the output is not turned off.
1.1.22 The UPS is equipped with a Maintenance Bypass Switch. Please follow the procedures strictly to switch on/off the Maintenance Bypass Switch.
Form No. 003-2282 Rev G
4
1.1.23 The UPS offers CVCF (Constant Voltage Constant Frequency) setting function.
a. For correct setting and wiring, please contact your local agent. b. Do not attempt to configure the UPS for CVCF by yourself; otherwise your warranty will be void.
1.1.24 This UPS has been designed and constructed to protect your assets from the wide range of power aberrations experienced on Utility power lines today. It is your insurance for reliable, clean and stable voltage supply. It is worth taking care to install the system correctly and to have it maintained correctly by your local dealer.
1.1.25 SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions that should be Followed during Installation and Maintenance of the UPS and Batteries.
1.1.26 Intended for Installation in a Controlled Environment.
1.1.27 CAUTION – 6Kva - A load disconnect switch shall be provided by others for the AC output circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit over-current protection for 30 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
1.1.28 CAUTION – 8/10Kva - To reduce the risk of fire, connect only to a circuit provided with branch circuit over-current protection for 40 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
1.1.29 Use No. 10 AWG, 60C copper wire and 22.1 lb-in Torque force when connecting to terminal block.
1.2. Storage Instruction
For extended storage through moderate climate, the batteries should be charged for 12 hours every 3 months by connecting the UPS input to an appropriate power source and start the UPS according to the instructions in this manual. Repeat this procedure every 2 months under high temperature environment.
Form No. 003-2282 Rev G
5
2. Product Introduction
2.1. General Characteristics
2.1.1 True online architecture continuously supplies in your critical device with a stable, regulated, transient-free pure sine wave AC Power.
2.1.2 20KHz PWM sine-wave topology yields an excellent overall performance. High crest factor capability of the inverter handles all high­inrush current loads without a need to upgrade the power rating.
2.1.3 Multi-functional LCD/LED panel displays various conditions of the UPS. The LED display shows the UPS working status, Utility Status and UPS Abnormal status. The LCD display shows Input and Output Voltage, Frequency, Load Status, Inner cabinet temperature, and Abnormal conditions.
2.1.4 To protect the unit from overload, it automatically switches to bypass mode in 160 seconds~ 40ms if loading is between 105%~ 150% of rating. At 150% of rating, it switches to bypass mode immediately. The UPS will automatically switch the load back to inverter mode once the overload condition ceases.
2.1.5 If a short circuit is connected to the output the UPS will shut off the output voltage instantly. The output voltage will remain off until the short circuit is removed from the output.
2.1.6 Should the unit become overheated, the internal thermal Switch will detect the heat and switch to bypass mode. When the unit is cooled it will switch the load back to inverter automatically.
2.1.7 Fully digitalized control circuits built into the UPS enhance functionality while providing a high-level of protection of the UPS. Powerful Communication capability enhances its capability for remote control and monitoring.
2.1.8 Maintenance-free sealed-type battery minimizes after-sales service.
2.1.9 Built in maintenance bypass switch provides an easy and safe troubleshooting or maintenance function when the Utility is normal.
Form No. 003-2282 Rev G
6
2.1.10 Providing four different working modes, such as Normal, ECO, CF50 and CF60, it may widely be used in a variety of applications.
2.1.11 DC-start function allows the UPS to be started during power outages.
2.1.12 Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut-off point and extend the life of batteries.
2.1.13 Intelligent temperature-controlled fan extends the life of the fan and reduces noise.
2.1.14 Built in diagnostics use fault codes, displayed on the LCD, to assist in finding the cause of a problem with the unit.
2.1.15 In case the UPS is out of order, Fault status will be shown on the LCD screen.
2.1.16 When the UPS is operated as a frequency converter under CF50 or CF60 mode, the recommended load connected shall be 75% of rated capacity if the input voltage is between 176~280Vac and 50% of the rated capacity if the input voltage is 160~280Vac.
Form No. 003-2282 Rev G
7
2.2. Symbols on the LCD Display Panel
Item
Symbol
Description
1
LINE
Utility or Bypass Source
2
Battery Low
3
Battery Abnormal
4
UPS Overloading
5
UPS Working in specified mode*
6
A Blackout Transfer occurred in UPS Output
7
Bypass Input Abnormal, UPS fails to transfer
to bypass, Bypass Abnormal at ECO mode
8
Utility Input Abnormal
9
OFF
UPS Shutoff
10
LINE OFF
UPS Abnormal Lock
11
UPS Flow Chart
12
4 Digits Measurement Display
13
Indicate the item desired to be measured
14
UPS ON Switch or Alarm Silence
15
UPS OFF Switch
Form No. 003-2282 Rev G
8
16
Previous Page or Setting Change
17
Next Page
18
Special Function Log in /out
19
Enter or Reconfirmed
20
Utility Input Normal LED
21
Bypass Input Normal LED
22
UPS under Redundancy Mode
23
UPS under ECO Mode
24
UPS Fault or Abnormal Warning LED
25
EPO
Emergency Power Off
26
Er05
Battery Weak or Dead
27
Er06
Output Short Circuit
28
Er10
Inverter Over-current
29
Er11
UPS Overheat
30
Er12
UPS Output Overloading
31
Er14
Fan error
32
Er15
Wrong Procedure to enter Maintenance Mode
Form No. 003-2282 Rev G
9
33
Er16
Output Parameters Set Error in Parallel
System
34
Er17
ID Numbers are in conflict in Parallel System
or ID number Error in single unit
35
Er21
Parallel communication error ( communication
wire disconnected or failure to find ID1 UPS )
in parallel system
36
Er24
CVCF mode with Bypass input
37
Er27
The UPS must be operated in normal mode in
parallel system
38
Er28
Bypass Overload Time out and cut off output.
39
Er31
The settings of both control board and driver
board are not matched each other.
40
Er33
Isolated transformer overheat
41
Er**
Other Error code
The specified modes include Normal mode, ECO mode, CVCF mode, etc..
Form No. 003-2282 Rev G
10
2.3. Panel explanation
2.3.1 Front Panel Function Explanations
LCD Display Green LED lights up to indicate the UPS has the capability to run under
redundancy mode.
Green LED steadily lights up to indicate that the Utility input voltage is within
the nominal range. Green LED lights up to indicate Bypass Input is normal. UPS ON/Alarm Silence. Go to previous page or change the setting of the UPS. To re-confirm the change of UPS Setting. Go to next page. UPS OFF Switch. Special functions log in/out . UPS is working under ECO(Economic) mode. UPS Fault or Abnormal .
Form No. 003-2282 Rev G
11
2.3.2 Rear Panel Explanation M E D C B A
A RS232 Port B Terminal Resistor for Parallel function C CAN Bus Connection Port for Parallel System D Customer Options Slot 1 E Customer Options Slot 2 F Cooling Fan G External Battery Connector H External Charger Connector I Utility Input Breaker CB1 J CAM Switch(Maintenance Bypass Switch) K Input/Output Terminal Block
N
K J I F G H L
Form No. 003-2282 Rev G
12
L Fixing Holes for External Charger Cabinet M EPO (Emergency Power Off) : Short to enable the function N Thermal breaker for protection of load in abnormal conditions: CB3 (8 and 10kVA models only)
OUTPUT
INPUT
G2
N22
L22
N21
L23
L21
G1
N1
L12
L11
N22, L22, N21, L23, L21 : UPS OUTPUT L11 : (not connected, used for Dual Input Only)
G2 : OUTPUT EARTH GROUND L12-N1 : UTILITY INPUT
G1 : INPUT EARTH GROUND
Form No. 003-2282 Rev G
13
5 4 3 2 1
9 8 7 6
2.4. Communication Port Explanation
The Communication port on the UPS provides RS232 protocol to communicate with UPS software for remote monitoring.
Available optional interfaces cards, which contains R2E (2nd RS232, SC-RS232), RSE (RS485, SC-RS485), USE (USB, SC-USB), DCE (Dry Contact, SC­Contact/EPO), as well as SNMP card (SC-SNMP1), can be added according to need. However, the R2E card, RSE card and USE card cannot be used simultaneously.
The bundled software of the UPS is compatible with many operating systems such as Windows 98, & 2000, ME, NT and XP. For other applications like Novell, NetWare, Unix, Linux, please contact your local distributor.
When the optional interface cards are used together with the onboard RS232 port, during communication the EPO signals (SC-Contact/EPO) will get the highest priority in control command, then the SNMP/WEB card (SC-SNMP-1), then the shutdown command at the DCE card, R2E, RSE and USE. Finally the onboard RS232 port will get the lowest priority.
2.4.1 RS232
2.4.1.1.1. The RS232 interface settings The RS232 interface shall be set as follows:
Baud Rate
9600 bps
Data Length
8 bits
Stop Bit
1 bit
Parity
None
2.4.1.1.2. The Pin Assignments of true RS232 type
The Pin Assignments of true RS232 type are illustrated as follows:
Pin 3: RS232 Rx Pin 2: RS232 Tx Pin 5: Ground