Staco Energy FLU-160-00, FLU-200-00, FLU-250-00 User Manual

FIRSTLINE P
Maintenance Bypass
Switch Cabinet
160kVA-250kVA, 480V Input/O utput
With SKRU
003-2621
Table of Contents
SECTION 1 .......................................................................................................................... 1
Introduction ....................................................................................................................... 1
Overview ........................................................................................................................... 1
Applicability ....................................................................................................................... 2
Part Numbers ................................................................................................................... 2
Section 2 .............................................................................................................................. 3
SAFETY WARNINGS ....................................................................................................... 3
DANGER .......................................................................................................................... 3
WARNING ........................................................................................................................ 3
CAUTION ......................................................................................................................... 4
Section 3 .............................................................................................................................. 5
Cabinet Setup ................................................................................................................... 5
Inspecting the Equipment ................................................................................................. 5
Floor Loading .................................................................................................................... 5
CLEARANCES ................................................................................................................. 5
Unloading the Cabinet(s) .................................................................................................. 6
Attaching the Cabinet to the UPS ..................................................................................... 7
Section 4 .............................................................................................................................. 8
Electrical Installation ......................................................................................................... 8
Wiring Preparation ............................................................................................................ 8
Control Connections ....................................................................................................... 12
Terminal Strip Torque Requirements .............................................................................. 12
Section 5 ............................................................................................................................ 13
Operation ........................................................................................................................ 13
Maintenance Bypass Switch (MBS) ................................................................................ 13
Section 6 ............................................................................................................................ 18
Maintenance ................................................................................................................... 18
Section 7 ............................................................................................................................ 18
FirstLine P Maintenance Bypass Switch Technical Specifications ................................. 18
Table 1 - Symbols ................................................................................................................ 4
Table 2 - Model Floor Loadings ............................................................................................ 5
Table 3 - Wire Size Requirements. .................................................................................... 10
Table 4 - Recommended Crimp Lugs ................................................................................. 10
Table 5 - Maximum Current Ratings................................................................................... 10
Table 6 - Terminal Tightening Torques .............................................................................. 10
Table 7 - Maintenance Bypass Switch States .................................................................... 16
Table 8 - Maintenance Bypass Switch State Change Procedures ..................................... 17
Table 9 - Technical Specifications ...................................................................................... 18
Figure 1 - The FirstLine P Maintenance Bypass Switch Cabinet .......................................... 1
Figure 2 - Pallet Mounting Hardware .................................................................................... 6
Figure 3 - Cabinet to Cabinet Mounting Hole Locations ....................................................... 7
Figure 4 - Inside View of Maintenance Bypass Switch Cabinet ............................................ 9
Figure 5 - Terminal Pa d ........................................................................................................ 9
Figure 7 - Customer Low Voltage Connection Terminal Block ........................................... 12
Figure 8 - Circuit Breaker Sequence Label ........................................................................ 16
Page | ii
SECTION 1
FRONT VIEW
11.85 [301.0]
11.85 [301.0]
20.00 [507.9]
(6) Ø.41 [Ø10.3]
MOUNTING HOLES
ON BOTTOM FEET
4.46 [113.2]
TOP VIEW
.11 [2.8] THICK
DOOR LATCH REQUIRES PHILLIPS
SCREWDRIVER TO OPEN
75.00 [1905.0]
33.35 [847.0]
20.75 [527.0]
LEFT SIDE VIEW
REMOVABLE TOP COVERS .08 [2.0] THICK
HINGED FRONT DOOR
Introduction Overview
The FirstLine P Mai n te nance Bypass Switch C abi net for 160 kVA, 200 kVA, 250 kVA with 480 V Input and Output is a steel cabinet that attaches to the side of the UPS cabinet, thereby extending the cabinet, and providing the maintenance bypass function. The cabinet has conduit attachment points at the top and the botto m for max i mu m flexibility in wiring the source and load power connections. Please refer to Figure 1 for the outline drawing of the cabinet.
Figure 1 - The FirstLine P Maintenance Bypass Switch Cabinet
All dimensions in Inches (millimeters)
Page | 1
Applicability
This equipment can be applied to UPS models FLU-160-00, FLU-200-00, and FLU-250-00. These UPS models operate at 480 V, 60 Hz and can be wired as delta in and delta out (3 wire plus ground) or wye in and wye out (4 wire plus ground). For installations requiring other voltages or other wiring configurations, the equipment covered by this manual is not appropriate. Please contact Staco Energy Products Company for recommendations regarding the proper equipment. It is permissible to use a larger Maintenance Bypass Switch Cabinet (MBS) than is required for the UPS, but special installation requirements must be met: the power source connected to the MBS must include circuit protection as specified for the input in the UPS manual and an output breaker must be provided per the UPS manual. For example, if a 250 kVA MBS is applied to a 160 kVA UPS, a 300 A breaker must be provided at the power source and a 300 A breaker must be provided between the MBS and the load. If the MBS rating matches the UPS rating, then the breakers that form the MBS switch arrangement satisfy the input and output breaker requirement for the UPS.
Part Numbers
FLU-P-160-MBPS*SK for use with 160 kVA UPS FLU-P-200-MBPS*SK for use with 200 kVA UPS FLU-P-250-MBPS*SK for use with 250 kVA UPS
Page | 2
SECTION 2
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Do not use outdoors.
Do not route wiring across or near hot surfaces.
Do not install near gas or electric heaters.
Equipment should be installed where it will not readily be subjected to tampering by
unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
This equipment connects to the output of an uninterruptible power supply.
Hazardous voltages may be present even when the electrical supply to this equipment is turned off.
If equipped with a maintenance bypass switch, control connections between this equipment and the ups must be present to prevent the possibility of backfeed.
Read and follow the instructions that came with the associated UPS or emergency lighting system before operating this equipment.
DANGER
This equipment contains lethal voltages. All repairs and service should only be performed by authorized service personnel. There are no user serviceable parts inside this equipment. Operation of switches and breakers require access to the cabinet interior and should only be performed by qualified personnel exercising appropriate caution.
WARNING
This equipment connects to the output of a UPS which contains its own energy source (batteries). The UPS output may carry live voltage even when the UPS is not connected to an AC supply.
To reduce the risk of fire and electric shock, install this equipment in a humidity controlled, indoor environment, free of conductive contaminants. Do not operate near water or excessive humidity (95% maximum). If condensation is present, the equipment must be allowed to completely dry before operation.
Page | 3
CAUTION
The UPS associated with this equipment contains batteries. Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should only be performed by qualified service personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batt eri es . Read, understand, and follow all instructions in the ups manual before attempting any operations involving the battery.
Table 1 - Symbols
Danger / Risk of Electric Shock
Caution
Risk of Explosion
Note
Ground Connection
Electrostatic Sensitive Device
Page | 4
Loading...
+ 14 hidden pages