Staco Energy FirstLine P, FirstLine P 924 User Manual

FirstLine P
FirstLine P 924
160-250kVA UPS
USER MANUAL
003-2460 Rev C
Staco Energy is highly specialized in the development and production of uninterruptible power
manufactured to ensure optimum performance.
No reproduction of any part of this manual, even partial, is permitted without the authorization of Staco Energy Products Company. The Staco Energy Products Company reserves the right to modify the product described herein, in order to improve it, at any time and without notice.
301 Gaddis Boulevard • Dayton, Ohio 45403
U.S. Toll Free 866-261-1191
(937) 253-1191 • Fax: (937) 253-1723
Web site: www.stacoenergy.com
Thank you for choosing our product.
systems (UPS). The UPS’s of this series are high quality products, carefully designed and
Page | ii
Applicability
WARNING
DANGER
This manual applies to the following models: FLU-160-xx
160 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta FLU-200-xx
200 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta FLU-250-xx
250 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta
The wye output configuration that provides an output neutral connection is only permitted when an input neutral is provided; delta-wye configuration is prohibited. The source must have a grounded neutral, even if the neutral is not connected to the UPS; a delta source may not be ungrounded or corner grounded. Please refer to Section C.3 Mains and Load Connections. for additional information.
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
This manual contains important instructions for Models 65, 80, 100 and 125kVA FIRSTLINE P series UPS that should be followed during installation and maintenance of the UPS. Please read all instructions before operating the UPS and save this manual for future reference.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
a. Do not use outdoors. b. Do not route wiring across or near hot surfaces. c. Do not install near gas or electric heaters. d. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is
spilled on skin or in eyes, flush acid with fresh water and contact a physician immediately.
e. Unit should be installed where it will not readily be subjected to tampering by unauthorized
personnel.
f. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
g. Do not use this UPS for other than intended use.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
Page | iii
WARNING
WARNING
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Do not operate near water or excessive humidity (95% maximum).
Input and output over-current protection and disconnect switches must be provided by others.
High ground leakage current may be present. Do not operate the unit without a proper protective ground.
WARNING
Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from b atterie s.
There i s a risk of explosion if batteries are replaced by an incorrect type. Replace with same type and rating only. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Never dispose of batteries in a fire
Emergency Interventions
The following information is of a general nature.
First aid interventions
Company regulations and traditional procedures should be followed for any first aid intervention that may be required.
Firefighting measures
1. Do not use water to put out a fire, but only fire extinguishers that are suitable for use with electrical and electronic equipment.
2. If exposed to heat or fire, some products may release toxic fumes into the atmosphere. Always use a respirator when extinguishing a fire.
Page | iv
Symbols used in the Manual
Danger / Risk of Electric Shock
adequate precautions are taken.
Warning
taken
In this manual, some operations are shown by graphic symbols to alert the reader to the dangerous nature of the operations:
This symbol indicates possibility of serious injury or substantial damage to the unit, unless
This symbol indicates important information which must be understood and any stated precautions
Note
Protective Equipment
No maintenance operations shall be carried out on the unit without wearing the Personal Protective Equipment (PPE) described below. Personnel involved in the installation or maintenance of the unit must be properly clothed.
The following signs show the protective equipment that should be worn. The various items of PPE must be selected and sized according to the nature of the hazard (particularly electrical) posed by the unit.
Accident prevention
Protective eyewear
footwear
Protective clothing
Helmet
Work gloves
General Precautions
This manual contains detailed instructions for the use, installation and start-up of the UPS. Read the manual carefully before installation. For information on using the UPS, the manual should be kept close at hand and consulted before carrying out any operation on the UPS.
This UPS has been designed and manufactured in accordance with the standards for the product, for normal use and for all uses that may reasonably be expected. It may under no circumstances be used for any purposes other than those envisaged, or in any other ways than those described in this manual. Any interventions should be carried out in accordance with the criteria and the time-frames described in this manual.
Page | v
Table of Contents
Applicability .............................................................................................................................................. iii
Safety Warnings ...................................................................................................................................... iii
Emergency Interventions ......................................................................................................................... iv
First aid interventions ........................................................................................................................... iv
Firefighting measures ........................................................................................................................... iv
Symbols used in the Manual ..................................................................................................................... v
Protective Equipment ................................................................................................................................ v
General Precautions ................................................................................................................................. v
1. Layout .................................................................................................................................................. 1
1.1 Views .............................................................................................................................................. 1
1.2 Preliminary Operations ................................................................................................................... 3
1.2.1 Removing the Packaging and Positioning the Device .............................................................. 3
1.2.2 Storage .................................................................................................................................... 3
1.2.3 Handling .................................................................................................................................. 3
1.2.4 Cooling of the Premises ........................................................................................................... 4
2. Installation ............................................................................................................................................ 5
2.1 Accessing the UPS terminals ......................................................................................................... 5
2.2 UPS - Single Module Configuration ................................................................................................ 6
2.3 Cable Entry ..................................................................................................................................... 7
2.4 Connect of Power Cables ............................................................................................................... 9
2.4.1 Input Line without Neutral ........................................................................................................ 9
2.4.2 Single Input ............................................................................................................................ 10
2.4.3 Connection of Power Cables for Dual input Unit ..................................................................... 12
2.5 Differential (GFI) ........................................................................................................................... 14
2.6 Emergency Power off Device (EPO) ............................................................................................. 14
2.7 Connection of Signals and Remote Commands ........................................................................... 15
2.7.1 Remote Commands, Alarms and EPO ................................................................................... 17
2.7.2 RS232-1 and RS232-2 ........................................................................................................... 18
2.7.3 SLOT 1 and SLOT 2 .............................................................................................................. 19
2.7.4 Optional Remote Alarm Cards ............................................................................................... 19
2.7.5 Optional MODEM ................................................................................................................... 20
2.7.6 Option a l MULTI I / O .............................................................................................................. 20
2.7.7 Optional Battery Temperature Sensor .................................................................................... 20
2.7.9 Multi Panel ............................................................................................................................. 20
2.7.10 SWOUT and SWMB aux. ..................................................................................................... 21
3. Operation ........................................................................................................................................... 23
3.1 Start up ......................................................................................................................................... 24
3.1.1 Before S tart Up ...................................................................................................................... 24
3.1.2 Start-Up Procedure Single Module ......................................................................................... 24
3.2 Single UPS and Load Shutdown ................................................................................................... 25
3.3 Transfer to Bypass/Inverter .......................................................................................................... 25
3.4 Operating Modes .......................................................................................................................... 25
3.4.1 On-line Factory Setting .......................................................................................................... 25
Page | vi
3.4.2 Standby-On / Smart Active ..................................................................................................... 25
3.4.3 Standby-Off (with Mains Present the Load is not Powered) ................................................... 26
3.4.4 Stabilizer (Operation In On-Line Mode Without Battery) ......................................................... 26
4. Control Panel and Display .................................................................................................................. 27
4.1 Signal panel functions .................................................................................................................. 27
4.2 Graphic Display ............................................................................................................................ 29
4.2.1 Diagram Items Shapes........................................................................................................... 30
4.2.2 Keys Numbers and Icons ....................................................................................................... 30
4.3 Basic menu (text lines area) ......................................................................................................... 31
4.3.1 The First Line of the Basic Menu ............................................................................................ 31
4.3.2 The Second Line of the Basic Menu....................................................................................... 32
4.4 Language setting menu (keys 1, 1) ............................................................................................... 33
4.5 Measurements menus (key 2) ...................................................................................................... 34
4.6 Full page Measurements and output waveforms (key 2, 7) ........................................................... 36
4.7 Controls Menu (key 3) .................................................................................................................. 37
4.7.1 Battery Test (Keys 3, 2) ......................................................................................................... 37
4.7.2 Customizing ........................................................................................................................... 38
4.7.3 "Recorder": Recorded Events (key 4) ..................................................................................... 48
4.7.4 Disabling the Audible Alarm (key 5) ....................................................................................... 50
4.7.5"Clock": Date/Time (key 6) ...................................................................................................... 51
4.7.6 "Arrow Down": Internal Codes, Firmware Ver.(key 7) ............................................................. 51
5. UL924 Emergency Lighting Systems ............................................................................................... 52
6. Maintenance ...................................................................................................................................... 53
6.1 Periodic Maintenance (to be carried out by trained personnel and with doors closed) .................. 53
6.2 Maintenance Inside the UPS (factory authorized personnel only) ................................................. 53
6.3 Ordinary Maintenance for Batteries (trained personnel only) ........................................................ 53
6.4 Recommended Replacement Intervals ......................................................................................... 54
7. Specifications ..................................................................................................................................... 55
7.1 Electrical Specifications ................................................................................................................ 55
7.2 Environmental Requirements ....................................................................................................... 56
7.3 Mechanical Specifications ............................................................................................................ 56
7.4 Rated Currents ............................................................................................................................. 57
7.4.1 Input (Single Input Module) .................................................................................................... 57
7.4.2 Rectifier Input (Dual Input Module) ......................................................................................... 57
7.4.3 Bypass Input (Dual Input Module) .......................................................................................... 57
7.4.4 Output .................................................................................................................................... 57
7.4.5 Battery ................................................................................................................................... 57
7.5 Torque specifications .................................................................................................................... 58
Appendix A – Alarms ............................................................................................................................. 59
Appendix B - Optional remote commands .............................................................................................. 62
Appendix C - Parallel Configuratio n ....................................................................................................... 63
C.1 Introduction .................................................................................................................................. 63
C.2 Electrical System Set-Up ............................................................................................................. 64
C.2.1 Input ...................................................................................................................................... 64
Page | vii
C.2.2 Ground Fault ......................................................................................................................... 64
C.2.3 Emergency Power Off Device (EPO) ..................................................................................... 64
C.2.4 External Maintenance Bypass. .............................................................................................. 65
C.3 Mains and Load Connections. ...................................................................................................... 65
C.4 Installing Parallel k it ..................................................................................................................... 66
C.4.1 Parallel Card Installation ........................................................................................................ 67
C.4.2 Parallel Card Connections ..................................................................................................... 68
C.4.3 Parallel Card RJ45 Installation .............................................................................................. 68
C.4.4 Parallel Card RJ45 Connections ............................................................................................ 69
C.5 Connection of Signals .................................................................................................................. 69
C.5.1 RJ45-flat-adapter signals parallel card. ................................................................................. 70
C.5.2 Single UPS Configured in Parallel ......................................................................................... 70
C.5.3 Two UPS’s in Parallel ............................................................................................................ 71
C.5.4 Three UPS’s in Parallel ......................................................................................................... 71
C.6 Parallel Start-up procedure .......................................................................................................... 72
C.7 Parallel Communication Troubleshooting ..................................................................................... 73
C.7.1 Normal Condition ................................................................................................................... 73
C.7.2 Single Opened Parallel Cable ................................................................................................ 73
C.7.3 Multiple Opened Parallel Cable ............................................................................................. 74
C.8 Mechanical Bypass ...................................................................................................................... 74
C.8.1 Mechanical bypass on a single unit ....................................................................................... 74
C.8.2 Mechanical bypass on the whole system ............................................................................... 75
C.9 Insertion and removal with UPS’s operating (hot swap) ............................................................... 76
C.9.1 Example of Hot Insertion ....................................................................................................... 76
C.9.2 Example of Hot Removal ....................................................................................................... 77
Page | viii
Figures
Figure 1 - FLU cabinet front view ............................................................................................................. 1
Figure 2 - FLU-T cabinet front view.......................................................................................................... 2
Figure 3 – Single Input 1-Line ................................................................................................................. 6
Figure 4 - Dual Input 1-Line ..................................................................................................................... 6
Figure 5 – FLU bottom Cable Entry Layout .............................................................................................. 7
Figure 6 – FLU-T bottom Cable Entry Layout .......................................................................................... 8
Figure 7 - Schematic diagram: Single In put without Source Neutral ......................................................... 9
Figure 8 - Schematic diagram: Dual Input without Source Neutral ............................................................ 9
Figure 9 – FLU UPS Single Input Power Connection Terminals ............................................................. 10
Figure 10 – FLU-T UPS Single Input Power Connection Terminals ....................................................... 11
Figure 11 – FLU UPS Dual Input Power Connection Terminals ............................................................. 12
Figure 12 – FLU-T UPS Dual Input Power Connection Terminals .......................................................... 13
Figure 13 – Emergency Power Off (EPO) ............................................................................................. 14
Figure 14 – FLU Signals and Remote Command Connections .............................................................. 15
Figure 15 – FLU-T Signals and Remote Command Connections ........................................................... 16
Figure 16 – Remote Alarm Contacts ......................................................................................................
Figure 17 – RS232-2 Female Connection ............................................................................................. 18
Figure 18 – RS232-1 Male Connection ................................................................................................. 19
Figure 19 – Single Module Wrap-around bypass ................................................................................... 21
Figure 20 – Parallel System Wrap-around bypass ................................................................................. 22
Figure 21 – Single Input 1-Line .............................................................................................................. 23
Figure 22 – Dual Input 1-Line ................................................................................................................ 23
Figure 23 – Signal Panel ....................................................................................................................... 27
Figure 24 – Graphic Display .................................................................................................................. 29
Figure 25 – Typical (3) Module Parallel System .................................................................................... 63
Figure 26 – Recommended Ground Fault Interrupter Layout ................................................................ 64
Figure 27 – Parallel System EPO .......................................................................................................... 64
Figure 28 - Three units connected in parallel (Typical) .......................................................................... 65
Figure 29 – Parallel Card Installation ..................................................................................................... 67
Figure 30 – Parallel Card connections ................................................................................................... 68
Figure 31 – Parallel Card RJ45 Installation ........................................................................................... 68
Figure 32 – Parallel Card Flat Cable Installation.................................................................................... 69
Figure 33 - Parallel Control Routing ...................................................................................................... 69
Figure 34 - RJ45-flat-adapter signals parallel card ................................................................................ 70
Figure 35 – Parallel Connection – Single Module .................................................................................. 70
Figure 36 – Parallel Connection – Two Modules ...................................................................................
Figure 37 – Parallel Connection – Three Modules ................................................................................. 72
18
71
Tables
Table 1 - Torque Specifications for Terminal Blocks on Customer Interface Board ................................. 16
Table 2 - Interface Remote Command Alarms and EPO ........................................................................ 17
Table 3 - Interface Terminal Connector ................................................................................................. 22
Table 4 - Led Status Indicators .............................................................................................................. 28
Table 5 - Diagram Items Shapes ........................................................................................................... 30
Table 6 - Keys Numbers and Icons ........................................................................................................ 30
Table 7 – Battery Models approved for UL924 ....................................................................................... 52
Table 8 – UL924 Approved Systems ...................................................................................................... 52
Table 9 - Recommended Replacement Intervals ................................................................................... 54
Table 10 – Parallel Kit Components ...................................................................................................... 66
Page | ix
Page | x
1. Layout
1.1 Views
Figure 1 - FLU cabinet front view
A - Control Panel with Graphic Display B - Door Handle C - Ventilation Grilles D - Communication Area E - Front Cover Panel with Ventilation Grilles F - Switch Cover Panel G - Door
1 - SWIN: Input Power Switch 2- SWBY: Static Switch Bypass Input 3 - SOUT: Static Switch Output
Page | 1
Figure 2 - FLU-T cabinet front view
A - Control Panel with Graphic Display B - Door Handle C - Ventilation Grilles D - Communication Area E - Front Cover Panel with Ventilation Grilles F - Switch Cover Panel G - Door
1 - SWIN: Input Power Switch 2 - SWBY: Static Switch Bypass Input 3 - SOUT: Static Switch Output 4 - SWMB: Mechanical Bypass Switch
Page | 2
1.2 Preliminary Operations
DANGER
1.2.1 Removing the Packaging and Positioning the Device
On delivery, the packaging must be inspected to ensure that it is whole and that it has not been crushed or dented. Check in particular that neither of the two impact resistant devices on the packaging is red; if one of them is red; follow the instructions on the packaging. The essential details of the device are provided on the shipping document. The marking, weight and dimensions of the various items making up the packing list are shown. Check the state of the device by means of a visual inspection of both the inside and the outside. Any dents seen mean that it has suffered shocks during shipping, which could compromise the normal operation of the device.
1.2.2 Storage
Place the device in covered premises that are protected from direct contact with atmospheric agents and dust. The following environmental values are those allowed in the storage area:
Temperature: -13°F to +167°F (-25 to + 75 °C) Relative humidity: 30-95 % max.
WARNING
For the installation of a battery cabinet, if provided with the uninterruptible power supply, follow the instructions given in the specific manual.
The list of material provided may vary depending on the order specifications. Most systems include the following: this manual, the installation drawing, the warranty and eventual accessories.
1.2.3 Handling
The equipment must only be handled by adequately trained personnel.
1 Insert the forks of the fork-lift truck in the lower part of the device, from the front or back, and
ensure that they stick out about 12 inches on the other side.
2 Secure the device to the fork-lift before moving it.
In order to avoid the risk of the device overturning, ensure that it is firmly secured to the fork-lift truck by means of appropriate ropes before moving it.
When being moved the cabinet should be handled with care; shocks or drops can damage it. Once in position, remove the packaging carefully in order not to scratch the device.
The packaging should be removed as follows:
1. Cut the bands
2. Slide away the carton from above.
Page | 3
3. Remove the screws securing the cabinet to the wooden base.
1.2.4 Cooling of the Premises
The recommended operating temperature for the lifetime of the UPS and of the batteries is between 20 and 25°C. The lifespan of the battery depends on the operating temperature; with an operating temperature increase from 20°C to 30°C, the lifespan of the batteries is halved.
The airflow inside UPS is by the fans located inside the UPS (forced convection) and by the air around the side panels (natural convection).
In order to ensure proper air circulation measures must be taken during installation to avoid any obstructions to the free circulation of air. These include the following:
Ensure a distance of at least 24 inches from the ceiling, so as not to hinder air extraction,
Leave a free space of at least 36 inches at the front of the equipment to ensure both the circulation of the air and installation and maintenance operations;
With natural convection the thermal load is dissipated to the outside through the walls; thus a cabinet placed against a wall or in a hollow dissipates less heat than one located in a free environment. The following rule must be observed:
Leave at least one of the three side walls free: right, left or back.
The bottom side kick panels must not be mounted for installations where cabinets are placed side by side.
Page | 4
2. Installat ion
DANGER
Check the Safety Instructions.
Any incorrect connection or handling may cause damage to the UPS and/or the loads
connected to it. Read these instructions carefully and follow the steps indicated.
This UPS must be installed by qualified electrician.
It is advisable to provide a maintenance bypass switch or an electrical panel with individual
protection for input, output, and static bypass, as well as a manual bypass. This allows isolation of unit during preventive maintenance or repair.
2.1 Accessing the UPS terminals
The following operations must be performed while the UPS is disconnected from the utility mains power, switched off and all the input and output power switches on the equipment are open. Before performing connection, open all the input and output power switches and check that the UPS is completely isolated from all power sources: battery and AC power line. In particular, check that:
- UPS input line is completely isolated;
- Batt er y circuit breaker/disconnect is open;
- All UPS power and load connection switches (SW IN, SWBY, SWOUT and SWMB) are in the open position;
- No dangerous voltages are present (use a multimeter).
The first connection to be performed is the protective wire (earth ground cable) which has to be inserted into the terminal labeled PE. The UPS must operate with the grounding system connected.
WARNING
Do not connect the output neutral to the input neutral.
If the input connection is Delta the UPS can supply only Delta load.
The output neutral must not be connected unless the UPS is the Wye version supplied
with an input neutral.
TRANSFORMER BOXES (optional) are available for converting the distribution systems from 3 to 4 wires.
If a three-phase non-linear load is connected to the output, the current on the neutral conductor can reach a value equal to 1.5 times the value of the phase current. Dimension the input/output neutral cable appropriately taking this fact into account.
The UPS cannot feed from a corner ground or mid-point grounded delta supply source.
Use only lugs or cables with tin-plated eyes for the connections.
Ensure correct phase rotation at the input and output terminals
Ensure correct polarity battery connections
The DC input requires a disconnect means which is provided in most Staco supplied battery cabinets. AC and DC cables and cable lugs are to be provided by others as part of the UPS installation
Page | 5
Each model can be configured for a delta input source with a delta connected load or for a wye input with a wye connected load. If the load requires a neutral connection (i.e. wye), then an input neutral must be provided. Refer to the Power Connection terminals diagrams later in this section for details concerning configuration of the neutral to ground bond.
2.2 UPS - Single Module Configuration
The UPS is designed to work as Single input Unit or as Dual input Unit.
Figure 3 – Single Input 1-Line
Figure 4 - Dual Input 1-Line
Page | 6
2.3 Cable Entry
The cables can enter in the UPS from the bottom or from the top with the optional (Top Entry Cabinet) Proceed as follows in order to open the UPS
1. Open the door
2. Remove the switch cover panel
3. Remove the bottom cable entry cover plates
4. Drill or punch conduit holes in the cover plates
5. Route the power cable through the bottom to the UPS terminals in base to your configuration (see Figure 5 and Figure 6)
Page | 7
Figure 5 – FLU bottom Cable Entry Layout
Figure 6 – FLU-T bottom Cable Entry Layout
Page | 8
2.4 Connect of Power Cables
2.4.1 Input Line without Neutral
If utility is a 3-wire source and the load requires a neutral, a transformer must be inserted either on the mains supply line or on the bypass line.
Figure 7 - Schematic diagram: Single Input without Source Neutral
Figure 8 - Schematic diagram: Dual Input without Source Neutral
Page | 9
2.4.2 Single Input
Connect the input, output and battery cables to the terminals as shown in Figure 9 and Figure 10:
Figure 9 – FLU UPS Single Input Power Connection Terminals
For the Input, Output and Battery connections, follow the order from the top to bottom, or right to left, as described in the boxes. The label marked “N” present on the terminal identifies the neutral terminal.
The single input is a factory default configuration. Do not remove the bypass jumper. The input phase connections are made using bolts to one of the three holes in the busbar. Do not loosen the bolts that attach the busbar.
The UPS is provided with a separate busbar that connects the Neutral Output to the frame Ground for delta input connection. This is required to meet NEC grounding code for separately derived neutrals. When a Neutral is provided in a Wye configured input connection the busbar must be removed.
Once installation has been completed inside the equipment, put the switch cover panel back and close the door.
Page | 10
Figure 10 – FLU-T UPS Single Input Power Connection Terminals
For the Input, Output and Battery connections, follow the order from the top to bottom, or right to left, as described in the boxes. The label marked “N” present on the terminal identifies the neutral terminal.
The single input is a factory default configuration. Do not remove the bypass jumper. The input phase connections are made using bolts to one of the three holes in the busbar. Do not loosen the bolts that attach the busbar.
The UPS is provided with a separate busbar that connects the Neutral Output to the frame Ground for delta input connection. This is required to meet NEC grounding code for separately derived neutrals. When a Neutral is provided in a Wye configured input connection the busbar must be removed.
Once installation has been completed inside the equipment, put the switch cover panel back and close the door.
Page | 11
2.4.3 Connection of Power Cables for Dual input Unit
Connect the input, bypass, out put and battery cables to the terminals as shown in Figure 11 and Figure 12
Figure 11 – FLU UPS Dual Input Power Connection Terminals
The single input is a factory default configuration. Remove the jumpers present between the SWIN and SWBY. The input phase connections attach using bolts through the holes that were previously used to attach the busbars. The main (rectifier) input is located on the left and the bypass input is on the right. The neutral input comes from the bypass source; no neutral is to run to the rectifier input source, although the rectifier source must be a grounded wye.
For the Input, Bypass, Output and Battery connections, follow the order from the top to bottom, or right to left, as described in the boxes. The label marked “N” present on the terminal identifies the neutral terminal.
The UPS is provided with a separate busbar that connects the Neutral Output to the frame Ground for delta input connection. This is required to meet NEC grounding code for separately derived neutrals. When a Neutral is provided in a Wye configured input connection the busbar must be removed.
Once installation has been completed inside the equipment, put the switch cover panel back and close the door.
Page | 12
Figure 12 – FLU-T UPS Dual Input Power Connection Terminals
The single input is a factory default configuration. Remove the jumpers present between the SWIN and SWBY. The input phase connections attach using bolts through the holes that were previously used to attach the busbars. The main (rectifier) input is located on the left and the bypass input is on the right. The neutral input comes from the bypass source; no neutral is to run to the rectifier input source, although the rectifier source must be a grounded wye.
For the Input, Bypass, Output and Battery connections, follow the order from the top to bottom, or right to left, as described in the boxes. The label marked “N” present on the terminal identifies the neutral terminal.
The UPS is provided with a separate busbar that connects the Neutral Output to the frame Ground for delta input connection. This is required to meet NEC grounding code for separately derived neutrals. When a Neutral is provided in a Wye configured input connection the busbar must be removed.
Once installation has been completed inside the equipment, put the switch cover panel back and close the door.
Page | 13
2.5 Differential (GFI)
UPS
a
b
a - EPO terminal board located on the UPS b - EPO switch (not provided).
If the UPS protection against electric shock uses a differential current device (Ground Fault Interrupter), it will have to have the following characteristics:
Sensitivity 300mA
Sensitive direct current and unidirectional components (class A or class B)
Insensitive to transient cur r ent pulses
Delay greater than or equal to 0.1 s.
In the standard version without an isolation transformer on the bypass line, the neutral from the mains power supply is connected to the output neutral of the UPS.
THE ELECTRICAL SYSTEMS UPSTREAM AND DO WNSTREAM OF THE UPS MUST BE EXACTLY THE SAME (DELTA-DELTA or WYE-WYE)
When operating in the presence of mains supply, a differential breaker (GFI) insta l led on the input will intervene as the output circuit is not isolated from the input cir cuit. When operating without mains supply (from battery) the input differenti al breaker will intervene only if it is able to switch as a result of leakage current without any voltage at its poles (for example a differential breaker with an auxiliary relay is not suitable). However it is possible to install additional differential breakers on the output of the UPS possibly coordinated with those on the input.
2.6 Emergency Power off Device (EPO)
The UPS has an EPO (Emergency Power Off) function. In the event of an em er gency, using this function will cause the UPS to shut down the rectifier, inverter, and static switch and completely disconnect the power to the load. The Output circuit of the UPS should not be considered safe, unless the UPS is Off and the input power source to the UPS has been removed by opening the input disconnect devices which are external to the UPS, including the battery.
This function can be activated from the button (under a hinged clear plastic cover) on the control panel or by a remote contact. This button must be depressed and held down until the UPS shuts down. On the UPS, the jumper on the EPO terminals must be removed, and the wires from the auxiliary contact of the button must be connected in place of the jumper. The contact must be closed with the button in the rest position and must open when the button is pressed.
Figure 13 – Emergency Power Off (EPO)
Page | 14
2.7 Connection of Signals and Remote Commands
A-
Parallel
N-
Terminal Block
In order to access the interface cards, open the door and remove the protection panel secured with screws (K) as shown in the drawing:
B-
EPO (Emergency Power Off control)
C-
Remote Commands and Alarms
D-
RS232-2
E-
RS232-1
F-
Slot 2 (Main)
G-
Slot 1 (Main)
H-
Remote Alarms (Optional)
M-
Aux Signals Isolation Board
Figure 14 – FLU Signals and Remote Command Connections
Page | 15
AWG Wire size range
Torque Load
A-
Parallel
B-
EPO (Emergency Power Off control)
C-
Remote Commands and Alarms
D-
RS232-2
E-
RS232-1
F-
Slot 2 (Main)
G-
Slot 1 (Main)
H-
Remote Alarms (Optional)
I-
Remote Alarms (Optional)
M-
Aux Signals Isolation Board
N-
Terminal Block
Figure 15 – FLU-T Signals and Remote Command Connections
Table 1 - Torque Specifications for Terminal Blocks on Customer Interface Board
Page | 16
#22 -12AWG 4.4 lbf-ft
6 Nm
PIN
NAME
TYPE
FUNCTION
Bypass / fault, the contact changes position when the UPS switches the load a result of a fault in the inverter stage. See Note 1
Battery discharging, the contact changes position when the load is powered from the battery due to a mains power failure
End of battery discharge, the contact changes position when, during a mains
factory-set end of discharge pre-alarm value is 5 minutes)
10
+12V
POWER
Power supply +12Vdc 80mA (max.) [pins 10 and 11]
11
GND
POWER
Inverter OFF. Connect pin 11 to pin 12 (for at least 2 seconds).
not powered). See Note 1
If the jumper on the connector is opened, the voltage on the UPS output will be
2.7.1 Remote Commands, Alarms and EPO
The card is equipped with a terminal board with 14 positions.
Power Supply - 1 power supply 12Vdc 80mA (max.) [Pins 10 and 11]; Alarms - 3 potential-free change-over contacts for alarms (they are capable of switching up to 30 V
AC or DC at UP to 1 A);
Command - 1 command programmable from the panel [Pins 11 and 12]
Table 2 - Interface Remote Command Alarms and EPO
1,2,3
4,5,6
7,8,9
12
13,14
Note 1: If the UPS installation includes a Staco Maintenance Bypass Switch (MBS) Cabinet, this connection is
RL 1 OUTPUT 1
RL 2 OUTPUT 2
RL 3 OUTPUT 3
IN 1 INPUT 1
EPO
required to be connected to the MBS and is not available for other use. An Optional Remote Alarm interface can be installed if a second function is required in this case.
INPUT
EPO
onto the bypass line either during normal operation (e.g. due to overload) or as
outage, the remaining time for battery discharge has reached the minimum value defined. Once this time has passed, the load will remain unpowered (the
-
In “NORMAL OPERATION”, If the INVERTER OFF command is received, the UPS switches the power supply of the load onto the bypass line (load is not protected should there be a mains outage).
-
In “EMERGENCY OPERATION”,
If the STOP INVERTER command is received, the UPS shuts down (load is
cut. The UPS is factory-fitted with the EPO terminals short circuited. If this input is used, the UPS can be shut down in a hazardous situation from a remote position simply by pressing a button.
WARNING
If only the mains power supply is removed, for example by opening the switch of the power supply panel, as a means to shut down the UPS in an emergency the UPS will keep the load powered using the energy in the batteries.
The functions of the three contacts and the command may be reprogrammed via the display panel. The ALARMS and the COMMAND are factory-set. The position of the contacts as shown is without the alarm present. The contacts can take a maximum cur rent of 1A with 24Vac.
Page | 17
Loading...
+ 60 hidden pages