Operation principle UM0575
4/20
1 Operation principle
1.1 Compressor starter application
Single-phase induction motors, used for compressor control, use an auxiliary winding. This
winding permits a higher torque to be applied at startup. The most popular method to control
the start winding is to add a positive temperature coefficient (PTC) resistor in series with this
winding and the thermostat (Figure 2). Then, each time the thermostat is closed, the current
flows through the start winding and begins to heat the PTC. After a few hundreds of
milliseconds, the PTC value rapidly increases from a few W to several tens of kW. This
results in reducing the start winding current to a few tens of mA. This winding can then be
considered as open. The PTC then behaves like a switch in OFF state, but with a high
leakage current, resulting in high power losses (approx. 2.5 W).
Figure 2 gives the typical schematics of this application where a run or a start capacitor can
be connected in parallel (point 1) or in series (point 2) respectively with the PTC.
1.2 Standard PTC behavior
The transition between PTC ON and OFF states brings a voltage increase across this
variable resistor. Figure 3 and Figure 4 show two oscillograms of the same PTC in two
different operating conditions, for a 230 V compressor which can use both a start and run
capacitor. We see that, at the end of the PTC conduction, the voltage across it reaches
approximately 250 V (refer to "VPTC_OFF" indication). This voltage level is similar whatever
the operating conditions are (min or max RMS line voltage, run capacitor or not, etc.). The
PTC could be turned off as soon as this level has been reached. Section 1.3 explains how to
implement an electronic solution to achieve this function.
Figure 2. Compressor starter application