ST N30U User Manual

Page 1
1
DIGITAL PANEL METER N30U TYPE
USER’S MANUAL
Page 2
2
Page 3
3
Contents
1. APPLICATION AND METER DESIGN ........................................5
2. METER SET ..................................................................................6
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY .................7
6. RS-485 INTERFACE ..................................................................28
7. UPDATING OF SOFTWARE ...................................................... 42
8. ERROR CODES .........................................................................44
9. TECHNICAL DATA ....................................................................45
10. ORDER CODES .........................................................................48
11. MAINTENANCE AND GUARANTEE .........................................50
User’s manual for meters with firmware version 2.00
Page 4
4
Page 5
5
1. APPLICATION AND METER DESIGN
The N30U meter is a programmable digital panel meter destined for measurements of signals originating from standard sensors destined for temperature measurements and for the measurement of analog standard signals applied in automation. Additionally, the meter enables the indication of the current time. The readout field is a LED display, which allows the exposition of results in colours: red, green and orange. The measured input signal can be arbitrary converted by means of a 21-point individual characteristic.
Features of the N30U meter:
l display colour individually programmed in three intervals, l programmable thresholds of displayed overflows, l 2 NOC relay alarms operating in 6 modes, l 2 switched relay alarms with a switching contact operating
in 6 modes (option),
l signaling of measuring range overflow, l automatic setting of the decimal point, l programming of alarm and analog outputs with the reaction on the
selected input quantity (main or auxiliary input),
l real-time clock with the function of the clock supply support in case
of the meter supply decay,
l programmed averaging time – function of walking window with the
averaging time up to 1 hour,
l monitoring of set parameter values, l locking of introduced parameters by means of a password, l recount of the measured quantity on the base of the 21-point
individual characteristic,
l service of the interface with MODBUS protocol in the
RTU mode (option),
l conversion of the measured value into a standard – programmable
current or voltage signal (option),
l highlight of any measuring unit acc. to the order,
Page 6
6
2. METER SET
The set is composed of:
- N30U meter ........................................................................1 pc
- User’s manual ....................................................................1 pc
- Guarantee card ..................................................................1 pc
- Set of clamps to fix the meter in the panel .........................4 pcs
- Set of labels with units .......................................................2 pcs
- Seal ....................................................................................1 pc
When unpacking the meter, please check whether the type and execu­tion code on the data plate correspond to the order.
l signaling of alarm operation – switching the alarm on causes the
highlight of the output number,
l galvanic separation between connections: alarm, supply, input,
analog output, output of the auxiliary supply, RS-485 interface.
Protection grade from frontal side: IP65 Meter overall dimensions: 96 x 48 x 93 mm (with terminals). The meter casing is made of plastic.
Fig. 1 View of the N30U Digital Meter
Page 7
7
3. BASIC REQUIREMENTS, OPTIONAL SAFETY
In the safety service scope, the N30U meter meets the requirements of the EN 61010-1 standard.
Mentioned below applied symbols mean:
- especially important , one must acquaint with this information before connecting the meter. The non­ observance of notices marked by this symbol can occasion injures of the personnel and a damage of the instrument.
- One must take note of this when the instrument is working inconsistently to the expectations. Possible consequences if disregarded.
Observations concerning the operational safety
· All operations concerning transport, installation, and commissioning as well as maintenance, must be carried out by qualified, skilled personnel, and national regulations for the prevention of accidents must be observed.
· Before switching the meter on, one must check the correctness of connections.
· Do not connect the meter to the network through an autotransformer.
· Before removing the meter housing, one must switch the supply off and disconnect measuring circuits.
· The meter is designed to be installed and exploited in electromagnetic industrial environment conditions.
· When connecting the supply, one must remember that a switch or a circuit-breaker should be installed in the building. This switch should be located near the device, easy accessible by the opera­ tor, and suitably marked as an element switching the meter off.
· Non-authorized removal of the housing, inappropriate use, incorrect installation or operation, creates the risk of injury to personnel or meter damage. For more detailed information, please study the User’s Manual.
Page 8
8
Fig. 3. Overall Dimensions
Fig. 2. Meter Fixing
4. INSTALLATION
The meter has separable strips with screw terminals, which enable the connection of external wires of 1.5 mm2 cross-section for input signals and 2.5 mm2 for other signals.
One must prepare a hole of 92
+0,6
´ 45
+0,6
mm in the panel, which the
thickness should not exceed 6 mm. The meter is adapted to be mounted in a panel. The meter must be
introduced from the panel front with disconnected supply voltage. Be­fore the insertion into the panel, one must check the correct placement of the seal. After the insertion into the hole, fix the meter by means of clamps (fig.2).
Page 9
9
4.1. Lead-out of Signals
Signals led out on the meter connectors are presented on the fig. 4. Circuits of successive groups of signals are separated between them.
Fig. 4. Description of Signals on Connection Strips
· 0...10 V – input for the measurement ±10 V voltage,
· GND – mass for the 0...10 V input and 0...20 mA input,
· 0...20 mA – input for the measurement of ±20 mA current,
· 60 mV TC – input for the measurement of 60 mV voltage, or for the connection of RTD sensors,
· R, PT – input for the resistance measurement or for the connection of RTD sensors. The compensation wire has been marked by a broken line,
· OC – open collector output of npn type– signaling of the measuring range overflow.
Page 10
10
4.2. Examples of Connections
An example of the N30U meter connection to different signals is pre­sented on the fig. 5.
Fig. 5. Ways of the meter Connection
For the connection of input signals in environments with a high noise level, one must apply shielded wires.
Page 11
11
5. SERVICE
5.1. Display Description
Fig. 6. Description of the Meter Frontal Plate
5.2. Messages after Switching the Supply on
After switching the supply on, the meter displays the meter name N30U and next the program version in the „r x.xx” shape – where x.xx is the number of the current program version or the number of a custom-made execution. Next, the meter carries out measurements and displays the value of the input signal. The meter sets up automatically the decimal point position when displaying the value. The format (number of places after the decimal point) can be limited by the user.
Page 12
12
5.3. Functions of Buttons
- Acceptation button:
Þ entry in programming mode (hold down ca 3 seconds) Þ moving through the menu – choice of level, Þ entry in the mode changing the parameter value, Þ acceptation of the changed parameter value, Þ stop the measurement – when holding down the button, the result
is not updated. The measurement is still carried out.
- button increasing the value:
Þ display of maximal value, The pressure of the button causes the display of the maximal value during ca 3 seconds.
Þ entry in the level of the parameter group, Þ moving through the chosen level, Þ change of the chosen parameter value – increasing the value.
- Button to change the digit:
Þ display of minimal value, The pressure of the button causes the display of the maximal value during ca 3 seconds.
Þ entry in the level of parameter group, Þ moving through the chosen level, Þ change of chosen parameter value – shift on the next digit,
- resignation button:
Þ entry in the menu monitoring the meter parameters (by holding down ca 3 seconds),
Þ exit from the menu monitoring meter parameters, Þ resignation of the parameter change, Þ absolute exit from the programming mode (by holding down
ca 3 seconds).
Page 13
13
The pressure of the button combination and holding them down ca 3 seconds, causes the reset of alarm signaling. This
operation acts only when the support function is switched on.
The pressure of the
button combination causes the era-
sing of the minimal value.
The pressure of the
button combination causes the era-
sing of the maximal value.
The pressure and holding down the
button ca 3 seconds cau-
ses the entry in the programming matrix. The programming matrix can
be protected by the safety code.
The pressure and holding down the
button during 3 seconds
causes the entry in the menu monitoring meter parameters. One must
move through the monitoring menu by means of and
buttons. In this menu, all programmable meter parameters are only ava- ilable for readout. In this mode, the menu Ser is not available. The exit
from the monitoring menu is carried out by means of the button. In the monitoring menu, parameter symbols are displayed alternately with their values.
The service algorithm of the meter is presented on the fig. 7.
Page 14
14
Fig. 7. Service Algorithm of the N30U Meter
Page 15
15
5.4. Programming
The pressure of the button and holding it down through ca 3 seconds causes the entry to the programming matrix. If the entry is pro­tected by a password, then the safety code symbol SEC is displayed alternately with the set value 0. The write of the correct code causes the entry in the matrix, the write of an incorrect code causes the display of the ErCod symbol. The matrix of transitions to the programming mode is presented on the fig. 8. The choice of the level is made by means of the
button, however the entry and moving through the para-
meters of the chosen level is carried out by means of the
and
buttons. Parameter symbols are displayed alternately with their current values. In order to change the value of the chosen parameter, one must use the
button. For resignation from change, one must
use the
button. In order to exit from the chosen level, one must
chose the ----- symbol and press the
button. To exit from the
programming matrix, one must press the
button during ca 1 second. Then, the symbol End appears for ca 3 seconds and the meter transits to the display of the measured value. In case of leaving the meter in the parameter programming mode, the automatic abandon of the programming mode follows (parameter, and next the menu) after 30 seconds and the meter transits to display the measured value.
5.4.1. Value Change Way of the Selected Parameter
In order to increase the value of the selected parameter, one must press the
button. A single pressure of the button, causes the increase of the value of 1. The increase of value when displaying the digit 9 causes the set of 0 on this digit. The change of the digit follows after pressing the button. In order to accept the set parameter, one must hold down the button. Then, the write of the parameter follows and the display of its symbol, alternately with the new value. The pressure of the button during the change of the parameter value will cause the resignation of the write.
Page 16
16
Fig. 8. Programming Matrix.
Page 17
17
Table 1
5.4.2. Changing Floating-Point Values
The change is carried out in two stages (the transition to the next stage follows after pressing the
button):
1) setting the value from the range -19999M...99999, similarly as for
integral values;
2) setting of the decimal point position (00000., 0000.0, 000.00,
00.000, 0.0000); the
button shifts the decimal point to the
left, however the button shifts the decimal point to the right;
The pressure of the
button during the change of the parameter
value will cause the resignation of the write.
5.4.3. Characteristic of Programmed Parameters
Programmed parameters and the range of their quantity changes are presented in the table below.
InP 1
Parameter
symbol
Description Range of changes
tYP1
Kind of the connected input signal
Pt1 – Pt100 Pt5 – Pt500 Pt10 – Pt1000 rEZL – measurement of resistance up to 400 W rEZH – measurement of resistance up to 4000 W tE-J – J (Fe-CuNi) tE-h – K (NiCr-NiAl) tE-n – N (NiCrSi-NiSi) tE-E – E (NiCr-CuNi) tE-r – R (PtRh13-Pt) tE-S – S (PtRh10-Pt) 0_10U – voltage measurement, range 10 V. 0_20A – current measurement, range 20mA 0_60n – voltage measurement, range 60mV. HOUr – current time.
Page 18
18
Table 2
Ind
Parameter
symbol
Description Range of changes
IndCp
Number of points of the individual characteristic. For a value lower than 2, the individual characteristic is switched off. The number of segments is the number of points decreased of one. The individual characteristic is not taken into consideration in the CountH and HoUr modes.
1...21
Hn
The point value for which we will expect Yn (n-point number)
-19999...99999
Yn
Expected value for Xn.
-19999...99999
cd. Table 1
Con
Choice of the measured value compensation. Concerns only the work in the mode of temperature or resistance measurement. The wire linking the meter with the sensor defines the resistance for RTD sensors, however for thermocouples, the compensa­tion is defined by the cold junc­tion temperature. The choice of a value beyond the range causes the switching of the automatic compensation on.
-19999...99999
Introduction of values:
0..20 W - causes the switching of the manual compensation on for the resistance or tempera­ture measurement by means of RTD (resistance thermometers).
0...60
o
C – causes the switching
of the manual compensation on for thermocouples.
Cnt1
The measurement time is expressed in seconds. The result on the display presents the mean value counted in the Cnt1 period. This parameter is not taken into consideration during the measurement in counter modes.
1...3600
Page 19
19
dISP
Parameter
symbol
Description Range of changes
d_P
Minimal position of the decimal point When displaying the measured value
- display format. This parameter is not taken into consideration during tCountH and HoUr modes.
0.0000 – 0
00.000 – 1
000.00 – 2
0000.0 – 3 00000 – 4
CoLdo
Display colour, when the displayed value is ower than CoLLo
rEd – red grEEn – green orAnG - orange
CoLbE
Display colour, when the displayed value is higher than CoLLo and lower than CoLHi
CoLuP
Display colour when the displayed value is higher than CoLHi
CoLLo
Lower threshold of colour change
-19999..99999
CoLHi
Upper threshold of colour change
-19999..99999
ovrLo
Lower threshold of display narrowing Values below the declared threshold are signaled on the display by the
-----
symbol.
-19999..99999
ovrHi
Upper threshold of display narrowing Values above the declared threshold are signaled on the display by the
-----
symbol.
-19999..99999
Table 3
Table 4
ALr1, ALr2, ALr3, ALr4
Parameter
symbol
Description Range of changes
P_A1 P_A2 P_A3 P_A4
Input quantity, steering the alarm.
InP1 – Main input (indicated value).
HoUr – Real-time clock.
Page 20
20
tYP1 tYP2 tYP3 tYP4
Alarm type. Fig. 11 presents the graphical imaging of alarm types
n-on – normal (transition from 0 na 1),
n-oFF – normal (transition from 1 na 0),
on - switched on,
oFF – switched off,
H-on – manually switched
on; till the change time of the alarm type, the alarm output remains switched on
H-oFF – manually switched off; till the change time of the alarm type the output alarm remains switched off for good.
PrL1 PrL2 PrL3 PrL4
Lower alarm threshold.
-19999...99999
PrH1 PrH2 PrH3 PrH4
Upper alarm threshold.
-19999...99999
dLY1 dLY2 dLY3 dLY4
Delay of alarm switching.
0...32400
cd. Table 4
Page 21
21
LEd1 LEd2 LEd3 LEd4
Support of alarm signaling. In the situation when the support function is switched on, After the alarm state retrea, the signaling diode is not blanked. It signals the alarm state till its blank­ing moment by means of the
button com­bination. This function concerns only and exclusively the alarm signaling thus relay contacts will operate without support accord­ing to the chosen type of alarm.
oFF – function switched off on – function switched on
out
Parameter
symbol
Description Range of changes
P_An
Input quantity, which the analog output has to react on.
InP1 – main input (indicated value).
Hour – real-time clock.
tyPA
Type of analog output
0_10U – voltage 0...10 V 0_20A – current 0...20 mA 4_20A – current 4...20 mA
AnL
Lower threshold of the analog output. give the value, on which we want to obtain the minimal value of signal on the analog output.
-19999...99999
AnH
Upper threshold of the analog output. give the value on which we want to obtain the maximal value of signal on the analog output(10 V or 20 mA).
-19999...99999
Table 5
cd. Table 4
Page 22
22
bAud
Baud rate of the RS485 interface
4.8 – 4800 bit/s
9.6 – 9600 bit/s
19.2 – 19200 bit/s
38.4 – 38400 bit/s
57.6 – 57600 bit/s
115.2 – 115200 bit/s
prot
Type of transmission frame of the RS-485 interface.
r8n2 r8E1 r8o1 r8n1
Addr
Address in the MODBUS net­work. The write of the value 0 switches the interface off.
0...247
Table 6
SEr
Parameter
symbol
Description Range of changes
SEt
Write of manufacturer’s settings. The setting of the value YES causes the write of standard parameters into the meter. The value of manufacturer’s parameters is presented in the table 7.
no – do nothing. YeS – causes the write of
manufacturer’s settings.
SEC
Introduction of a new password. The introduction of the value 0 switches the password off.
0...60000
HOUR
Setting of the current time. The introduction of a wrong time cancels the introduction of time. The introduced value is not taken.
0,00...23,59
unIt
Highlight of the unit.
On – unit highlight switched on.
Off – unit highlight switched off.
cd. Table 5
Page 23
23
tESt
Display test. The test consists in a successive lighting up of digital display segments. Alarm diodes and unit highlighting diodes should be lighted.
YeS – causes the test start
The pressure of the button ends the test.
no – do nothing.
5.4.4 Individual Characteristic
N30U meters can recalculated the measured value into any value thanks to the implemented individual characteristic function. The indivi­dual characteristic rescales the input signal measured according to the set characteristic. The way of the individual characteristic interaction on the meter operation has been presented on the fig. 9.
Fig. 9. Action of the Individual Characteristic.
The user can introduce maximally twenty functions through giving inter­vals and expected values for successive points.
The programming of the individual characteristic consists on the defi­nition of the number of points which the input function will be linearized by. On must remember that the number of linearizing functions is of one
Page 24
24
Rys. 10. Individual Characteristic.
During the function approximation, one must remember that for the ap­proximation of functions strongly differing from the linear characteristic, higher the number of linearizing segments, smaller the error related to the linearization.
If measured values are smaller than H1, recalculations will be made on the base of the first straight line calculated on the base of points (H1,Y1) an (H2,Y2). However, for values higher than Hn (where n – the last declared measured value) the value to display will be calculated on the base of the last assigned linear function.
Note: All introduced points of the measured value (Hn) must be arran-
smaller than the number of points. Next, one must program successive points by giving the measured value (Hn) and the expected value cor­responding to it, – value which has to be displayed (Yn). The graphic in­terpretation of the individual characteristic is presented on the fig. 10.
Page 25
25
ged in the increasing sequence, such to preserve the following depen­dence:
H1<H2<H3...<Hn
If the above is not fulfilled, the individual characteristic function will be automatically switched off (will not be realized) and a diagnostic flag will be set in the status register.
a) n-on b) n-off
c) on d) off
Fig. 11. Alarm Types: a) n-on, b) n-off c) on d) off.
5.4.5 Alarm types
The N30U meter is equipped with 2 alarm outputs with NOC contact (make contact) and two alarm outputs with NOC/NCC contact (make and break contact) (option). Each of alarms can work in one of the six modes. The work of alarms in modes is presented in the fig. 12: n-on, n­off, on, off. Two remaining modes: h-on and h-off mean suitably, always switched on and always switched off. These modes are destined for the manual simulation of alarm states.
Page 26
26
Caution !
l In case of alarms of n-on, n-off, on, off types the write of PrL>PrH will
cause the alarm switching off.
l In case of a measuring range overflow, the reaction of the relays is
compatible with written PrL, PrH, tYP parameters. In spite of the dis­played overflow, the meter still carries out the measurement.
l The meter controls currently the value of the introduced parameter
at the moment. In case when the introduced value overflows the upper range given in the table 1, the meter will make automatically the change into the maximal value. Similarly, in case when the introduced value overflows the lower change range given in the table 1, the meter will make automatically the change into the minimal value.
5.4.6 Display Format
The N30U meter adapts automatically the display format (precision) to the value of measured quantity. So that the function could be fully used, one must choose the format 0.0000, then the meter will display the me­asured value with the possible highest accuracy. This function does not operate for the time display, where the format is set automatically. The current time (mode HOUr) is displayed in the 24 hours’ format, in the shape hh.mm, where hh – current hour, and mm – current minute.
Caution: Remember that the display with a higher resolution is not al­ways desired, it can conduct to a deterioration of the indication stabi­lity.
Page 27
27
Parametru symbol Level in the matrix
Standard value
tYP1 1
Pt1
Con 1 0
Cnt1 1 1
indCP 2 no
H0 2 0
Y0 2 0
H1 2 100
Y1 2 100
... ... ...
Hn 2 (n-1)*100
Yn 2 (n-1)*100
d_P 3 00000
CoLdo 3 grEEn
CoLbE 3 orAng
CoLuP 3 rEd
CoLLo 3 5000
CoLHi 3 8000
ovrLo 3 -19999
ovrHi 3 99999
P_A1, P_A2,
P_A3, P_A4
4, 5, 6, 7 InP1
tYP1, tYP2,
tYP3, tYP4
4, 5, 6, 7 h-off
PrL1, PrL2,
PrL3, PrL4
4, 5, 6, 7 1000
Table 7
5.5. Manufacturer’s Parameters
Standard settings of the N30U meter are presented in the table 7. These settings can be restored by means of the meter menu through
the choice of the option Set from the menu Ser.
Page 28
28
PrH1, PrH2,
PrH3, PrH4
4, 5, 6, 7 2000
dLY1, dLY2, dLY3, dLY4,
4, 5, 6, 7 0
LEd1, LEd2,
LEd3, LEd4
4, 5, 6, 7 oFF
P_An 8 InP1
tYPA 8 0_10U
AnL 8 0
AnH 8 99999
bAud 8 9.6
prot 8 r8n2
Addr 8 1
SEt 9 no
SEC 9 0
HOUR 9 Not defined
unit 9 off
tESt 9 off
6. INTERFACE RS-485
N30U programmable digital meters have serial links in RS-485 stan­dards for the communication in computer systems and with other de­vices fulfilling Master function. An asynchronous communication cha­racter protocol MODBUS has been implemented on the serial link. The transmission protocol describes ways of information between devices through the serial link.
6.1. Connection Way of the Serial Interface
The RS-485 standard allows to a direct communication of 32 devices on a single serial link of 1200 m long (at baud rate 9600 b/s). For the
Page 29
29
Fig. 12. Connection Way of the RS-485 interface
connection of a higher quantity of devices, it is necessary to apply ad­ditional intermediate-separating systems (e.g. PD51 converter).
The lead out interface line is presented on the fig. 4. To obtain a cor­rect transmission, it is necessary to connect lines A and B in parallel with their equivalents in other devices. The connection must be made through a shielded wire. The wire shield must be connected to the pro­tection terminal in the nearest possible neighbourhood of the meter (connect the shield only in a single point to the protection terminal).
The GND line serves to the additional protection of the interface line at long connections. Then, one must connect GND signals of all devices on the RS-485 bus.
To obtain the connection to the computer, a RS-485 interface card or a suitable converter is indispensable, e.g. PD51 or PD10.
The connection way of devices is shown on the fig. 12
The designation of transmission lines for the card in the PC computer depends on the card producer.
Page 30
30
6.2. Description of the MODBUS Protocol Implementation
The implemented protocol is in accordance with the PI-MBUS-300 Rev G of Modicon Company specification.
Set of the serial link parameters of N30U meters in MODBUS protocol:
l meter address: 1...247,
l baud rate: 4800, 9600, 19200, 38400,
57600, 115200 bit/s,
l work mode: RTU with frame format 8n2, 8e1,
8o1, 8n1,
l maximal response time: 100 ms.
The parameter configuration of the serial link consists in the settlement of the baud rate (bAUd parameter), device address (Addr parameter), and the format of the information unit (prot parameter)
Notice: Each meter connected to the communication network must have:
l unique address, different from addresses of other devices connec-
ted to the network,
l identical baud rate and type of information unit.
6.3 Description of Applied Functions
Following MODBUS functions have been implemented in the N30U meter:
l 03 – readout of the register group l 04 – readout of input registers l 06 – write a signle register l 16 – write of the register group l 17 – identification of the slave device.
Page 31
31
6.4 Register map
The register map of the N30U meter is presented below
Notice:
All given addresses are physical addresses. In some computer pro­grams logic addressing is applied, then addresses must be increased of 1.
Table 8
Range
of address
Value type Description
4000-4049 integer (16 bits) Value placed in a 16-bit register.
7000-7039 float (32 bits)
Value placed in two successive 16­bit registers. Registers include the same data as 32-bit register from the area 7500. Registers are only for readout.
7200-7326 float (32 bits)
Value placed in two successive 16­bit registers. Registers include the same data as 32-bit register from the area 7600. Registers can be read out and written.
7500-7519 float (32 bits)
Value placed in a 32-bit register. Registers are only for readout.
7600-7663 float (32 bits)
Value placed in a 32-bit register. Registers can be read out and written.
Page 32
32
6.5. Registers for Write and Readout
Table 9
The value is placed in
16-bit registers
write (w)/readout (r)
Input type4000
tYP1
w/r 0...14
Range DescriptionSymbol
0 Pt1 – Pt100
1 Pt5 – Pt500
2 Pt10 – Pt1000
3 rEZL – Resistance, range 400 W
4 rEZL – Resistance, range 4000 W
5 tE-J – J – thermocouple of J type
6 tE-h – K – thermocouple of K type
7 tE-n – N – thermocouple of N type
8 tE-E – E – thermocouple of E type
9 tE-r – R – thermocouple of R type
10 tE-S – S – thermocouple of S type
11 0_10U –
voltage measurement, range
10 V
12 0_20A –
current measurement, range
20 mA
13 0_60n –
voltage measurement, range
60 mV
14 HoUr – current time
Value
Reserved4001 w/r
Reserved4002 w/r
4003
Cnt
w/r 1...3600
Measurement time expressed in seconds. This time defines the averaging time of the measured value. The displayed value is the mean value calculated from the Cnt1 period.
Reserved4004 w/r
Reserved4005 w/r
Reserved4006 w/r
Reserved4007 w/r
Page 33
33
Value
0 0.0000
1 00.000
2 000.00
3 0000.0
4 00000
4008
IndCp
w/r 1...21
Number of points of the individual characteristic. For the value 1, the individual characteristic is switched off. Segments of the individual characteristic are defined by parameters Xn and Yn, where n – point number.
Minimal position of the decimal point when displaying the measured value.
4009
d_P
w/r 0...4
Value
0 red
1 green
2 orange
Display colour when the displayed value is smaller than coLLo
Description
4010
CoLdo
w/r 0...2
Value
0 red
1 green
2 orange
Display colour when the displayed value is higher
than coLLo and smaller than coLHi
Description
4011
CoLbE
w/r 0...2
Value
Display colour when the displayed value is higher than coLHi
Description
4012
CoLUp
w/r 0...2
0 red
1 green
2 orange
DescriptionValue
0 Main input
1 clock
Input quantity controlling the alarm
4013
P_a1
w/r 0, 1
Description
Page 34
34
Support of alarm 1 signaling
4016
LEd1
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
DescriptionValue
0 Main input
1 clock
Input quantity controlling the alarm
4017
P_a2
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 2 (description – fig. 6)
Description
4018
tyP2
w/r 0...5
Delay of alarm 2 (in seconds)
4019
dLY2
w/r 0...32400
Support of alarm 2 signaling
4020
LEd2
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
DescriptionValue
0 Main input
1 clock
Input quantity controlling the alarm
4021
P_a3
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 1 (description – fig. 6)
Description
4014
tyP1
w/r 0...5
Delay of alarm 1 (in seconds)
4015
dLY1
w/r 0...32400
Page 35
35
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 3 (description – fig. 6)
Description
4022
tyP3
w/r 0...5
Delay of alarm 3 (in seconds)
4023
dLY3
w/r 0...32400
Support of alarm 3 signaling
4024
LEd3
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
DescriptionValue
0 Main input
1 clock
Input quantity controlling the alarm
4025
P_a4
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 4 (description – fig. 6)
Description
4026
tyP4
w/r 0...5
Delay of alarm 4 (in seconds)
4027
dLY4
w/r 0...32400
Support of alarm 4 signaling
4028
LEd4
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
Input quantity, which the analog output
has to react on.
4029
P_an
w/r 0, 1
Value
0 Main input
1 clock
Description
Page 36
36
Type of analog output
4030
tYPa
w/r 0...2
Value
0 voltage input 0...10 V
1 current input 0...20 mA
2 current input 4...20 mA
Description
Baud rate
4031
bAud
w/r 0...5
Value
0 4800 bit/s
1 9600 bit/s
2 19200 bit/s
Description
3 38400 bit/s 4 57600 bit/s 5 115200 bit/s
Meter address. The write of the value 0 causes the
interface switching off
4033
Addr
w/r 0...247
Transmission mode4032
prot
w/r 0...3
Update transmission parameters. Causes the
application of introduced RS-485 interface settings.
4034
sAvE
w/r 0...1
value
0 RTU 8N2 1 RTU 8E1 2 RTU 8O1 3 RTU 8N1
Description
Write of standard parameters4035
SEt
w/r 0...1
Value
0 without changes 1 set standard parameters
Description
Password for parameters4036
SEc
w/r 0...6000
Value
0 without password ... Entry in parameters preceded by a
request about the password
Description
Current time4037
hour
w/r 0...2359
This parameter occurs in the ggmm format, where: gg - means hours, mm – means minutes. The introduction of a wrong hour will cause the setting of 23, however the introduction of wrong minutes will generate the setting of the value 59.
Page 37
37
Bit 15 Break of the supply
Bit 14 Re-set of the RTC clock
Switch on/off the unit highlight4038
unit
w/r 0, 1
Value
0 highlight swiched off 1 highlight swiched on
Description
Reserved
...
...
... ...
Meter status. Describes the current state of the meter. Successive bits represent the given event. The bit set on 1 means, that the event took place. Events can be only erased.
Bit 13 Not used
Bit 12 Lack of communication with data memory
Bit 11 Wrong settings
Bit 10 Manufacturer’ s setting restored
Bit 9 Lack of measured values in data memory
Bit 8 Not used
Bit 7 Output plate is detected
Bit 6 Output plate – error or lack of calibration
Bit 5 Not used
Bit 4 Not used
Bit 3 Wrong configuration of the individual characteristic
Bit 2 Not used
Bit 1 Not used
Bit 0 Averaging period is not elapsed
Bit 15 Not used
Bit 14 Not used
Meter status. Describes the current state of the meter. Successive bits represent the given event. The bit set on 1 means, that the event took place. Events can be only cancelled.
Bit 13 Not used
Bit 12 Not used
Bit 11 Not used
Bit 10 Not used
Bit 9 Not used
Bit 8 Not used
4049 Status2 w/r
4048 Status1 w/r 0...65535
Reset of extrem values
4039 w/r 0, 1
Value
0 no change 1 Reset of min. and max. values
Description
Page 38
38
Table 10
Bit 7 LED4 – Signaling of alarm nr 4.
Bit 6 LED3 – Signaling of alarm nr 3.
Bit 5 LED2 – Signaling of alarm nr 2.
Bit 4 LED1 – Signaling of alarm nr 1.
Bit 3 Status of the alarm relay nr 4.
Bit 2 Status of the alarm relay nr 3.
Bit 1 Status of the alarm relay nr 2.
Bit 0 Status of the alarm relay nr 1.
4049 Status2 z/o
The value is placed in two suc-
cessive 16-bit registers. These
registers include the same data as
32-bit registers from the area 7600
The value is placed in 32-bit
registers
Symbol
write
(w)
/
rea-
dout
(r)
Range Description
7200 7600
CoLLo
w/r -19999...99999
Lower threshold of the display colour
change
7202 7601
CoLHI
w/r -19999...99999
Upper threshold of the display colour
change
7204 7602
ovrLo
w/r -19999...99999
Lower threshold of the display
narrowing
7206 7603
ovrHI
w/r -19999...99999
Upper threshold of the display
narrowing
7208 7604
PRL 1
w/r -19999...99999 Lower threshold of alarm 1
7210 7605
PrH 1
w/r -19999...99999 Upper threshold of alarm 1
7212 7606
PRL 2
w/r -19999...99999 Lower threshold of alarm 2
7214 7607
PrH 2
w/r -19999...99999 Upper threshold of alarm 2
7216 7608
PRL 3
w/r -19999...99999 Lower threshold of alarm 3
7218 7609
PrH 3
w/r -19999...99999 Upper threshold of alarm 3
7220 7610
PRL 4
w/r -19999...99999 Lower threshold of alarm 4
Page 39
39
7222 7611
PrH 4
w/r -19999...99999 Upper threshold of alarm 4
7224 7612
AnL
w/r -19999...99999 Lower threshold of analog output
7226 7613
AnH
w/r -19999...99999 Upper threshold of analog output
7228 7614
Con
w/r -19999...99999 Reserved
7230 7615 w/r 0...60000 Reserved
7232 7616 w/r 0...60000 Reserved
7234 7617 w/r -19999...99999 Reserved
7236 7618 w/r -19999...99999 Reserved
7238 7619 w/r 0...60000 Reserved
7240 7620 w/r 0...60000 Reserved
7242 7621 w/r -19999...99999 Reserved
7244 7622
H1
w/r -19999...99999
Point of the individual characteristic.
Point nr 1
7246 7623
Y1
w/r -19999...99999 Expected value for the point nr 1
7248 7624
H2
w/r -19999...99999
Point of the individual characteristic.
Point nr 2
7250 7625
Y2
w/r -19999...99999 Expected value for the point nr 2
7252 7626
H3
w/r -19999...99999
Point of the individual characteristic.
Point nr 3
7254 7627
Y3
w/r -19999...99999 Expected value for the point nr 3
7256 7628
H4
w/r -19999...99999
Point of the individual characteristic.
Point nr 4
7258 7629
Y4
w/r -19999...99999 Expected value for the point nr 4
7260 7630
H5
w/r -19999...99999
Point of the individual characteristic.
Point nr 5
7262 7631
Y5
w/r -19999...99999 Expected value for the point nr 5
7264 7632
H6
w/r -19999...99999
Point of the individual characteristic.
Point nr 6
7266 7633
Y6
w/r -19999...99999 Expected value for the point nr 6
7268 7634
H7
w/r -19999...99999
Point of the individual characteristic.
Point nr 7
7270 7635
Y7
w/r -19999...99999 Expected value for the point nr 7
7272 7636
H8
w/r -19999...99999
Point of the individual characteristic.
Point nr 8
7274 7637
Y8
w/r -19999...99999 Expected value for the point nr 8
7276 7638
H9
w/r -19999...99999
Point of the individual characteristic.
Point nr 9
Page 40
40
7278 7639
Y9
w/r -19999...99999 Expected value for the point nr 9
7280 7640
H10
w/r -19999...99999
Point of the individual characteristic.
Point nr 10
7282 7641
Y10
w/r -19999...99999 Expected value for the point nr 10
7284 7642
H11
w/r -19999...99999
Point of the individual characteristic.
Point nr 11
7286 7643
Y11
w/r -19999...99999 Expected value for the point nr 11
7288 7644
H12
w/r -19999...99999
Point of the individual characteristic.
Point nr 12
7290 7645
Y12
w/r -19999...99999 Expected value for the point nr 12
7292 7646
H13
w/r -19999...99999
Point of the individual characteristic.
Point nr 13
7294 7647
Y13
w/r -19999...99999 Expected value for the point nr 13
7296 7648
H14
w/r -19999...99999
Point of the individual characteristic.
Point nr 14
7298 7649
Y14
w/r -19999...99999 Expected value for the point nr 14
7300 7650
H15
w/r -19999...99999
Point of the individual characteristic.
Point nr 15
7302 7651
Y15
w/r -19999...99999 Expected value for the point nr 15
7304 7652
H16
w/r -19999...99999
Point of the individual characteristic.
Point nr 16
7306 7653
Y16
w/r -19999...99999 Expected value for the point nr 16
7308 7654
H17
w/r -19999...99999
Point of the individual characteristic.
Point nr 17
7310 7655
Y17
w/r -19999...99999 Expected value for the point nr 17
7312 7656
H18
w/r -19999...99999
Point of the individual characteristic.
Point nr 18
7314 7657
Y18
w/r -19999...99999 Expected value for the point nr 18
7316 7658
H19
w/r -19999...99999
Point of the individual characteristic.
Point nr 19
7318 7659
Y19
w/r -19999...99999 Expected value for the point nr 19
7320 7660
H20
w/r -19999...99999
Point of the individual characteristic.
Point nr 20
7322 7661
Y20
w/r -19999...99999 Expected value for the point nr 20
7324 7662
H21
w/r -19999...99999
Point of the individual characteristic.
Point nr 21
7326 7663
Y21
w/r -19999...99999 Expected value for the point nr 21
Page 41
41
The value placed In two successive
16-bit registers. These registers include
the same data as 32-bit registers from
the area 7500
The value is placed in 32-bit registers
Name
Write
(w)
/readout
(r)
Unit Name of the quantity
7000 7500 Identifier O
Constant identifying the device. The value 183 means the N30U meter
7002 7501 Status O
Status is register describing the current state of the meter
7004 7502 Control O %
It is a register defining the control of the analog output
7006 7503 Minimum O
Minimal value of the currently displayed value
7008 7504 Maximum O
Maximal value of the currently displayed value
7010 7505
Displayed
value
O Currently displayed value
7012 7506 Current time O Current time
7014 7507
Wire
resistance
O
W
Wire resistance - for resistance measurement - measured value
7016 7508 ADC O ADC (analog-to- digtal converter) value
7018 7509
Terminal
temperature
O
°C
Temperature of terminals – the mea­surement is only carried out during the temperature measurement by means of thermoelectric sensors or during time measurements
6.6. Registers Only for Readout
Table 11
Page 42
42
7020 7510
Measured
value
O
Measured value - not recalculated in relation to the individual character­istic, a.s.l.
7022 7511 EMF O
mV
EMF measured on meter terminals, when measuring temperature by means of thermocouples.
7024 7512 Resistance O Ohm
Resistance measured on the mean line – only for the resistance measure­ment or when measuring temperature by means of resistance thermometers (RTD)
Table 11
7. UPDATING OF SOFTWARE
Function enabling updating of software from the computer of the PC with software LPCon was implementation in meter N30U (from ver­sion of software 1.10) in the realization with the interface RS485. Free software LPCon and update files are accessible on the manufacturer’s website. The connected to the computer convertor RS485 is required on USB to the updating, e.g.: the convertor PD10.
a) b)
Pic. 13. Program view: a) LPCon, b) updating of software
Page 43
43
Warning! Before doing update, currently settings of meter should be saved by program LPCon, because when software is updated default settings of meter are restored.
After starting LPCon’s software COM port, baudrate, transmission mode and adress should be set. It can be done in Options. Then, N30U meter should be selected from Device. Push icon Load to read and save current settings. Open window Lumel Updater (LU) – figure 13b from Updating->Updating of devices firmware. Push Connect. Update progress is shown in Messages section. Text Port opened appear after correctly opened port. Putting meter in update’s mode can be done in two ways: remote from LU (with settings from LPCon – port, baudrate, transmission mode and adress) or by turning power on while button
pressed (updating by standard communication parameters ­baudrate 9600 kb/s, mode 8N2). AL1 led signals that device is ready for update. LU will show message „Device found” with name and cur­rent version of firmware. Using button ... a valid file should be selected. If the file is correct, message File opened will show. Send button should be pressed. During firmware update AL1-AL4 leds indicate process progress. If firmware update is successful device starts normal opera­tion and message Done and update duration will show. Close LU and go to Restoration of manufacturer’s parameters. Select checkbox and press Apply button. Next press Send button to restore previously read parameters. Current firmware version can be checked when meter is power on.
Warning! Power loss during firmware update could result permanent meter damage!
Page 44
44
8. ERROR CODES
After switching the meter to the network or during the work, messages about errors can appear.
Messages about errors and their reasons are presented below.
Error message Description
Overflow of upper value of the measuring range value or the programmed indication range. The message can also mean a break in the sensor circuit (thermocouples or resistance thermometers). Overflow of lower value of the measuring range value or the programmed indication range. The message can also mean a shorting in the sensor circuit (thermocouples or resistance thermometers).
ErFrt
Communication error with the data memory. Contact the service workshop.
ErPar
Parameter error. Wrong configuration data. Manufacturer’s settings will be restored after pressing any button.
ErdEF
Default settings have been restored. Press any button to transit to a normal work.
ErFPL
Error of measured values stored by the meter (measured, maximal and minimal values). Press any button to transit to a normal work. After pressing the button during 1 sec, the ErdEF message will be displayed.
Table 12
ErCAo
Lack of calibration of analog outputs. Press any button to transit to the normal work. Analog outputs will not be serviced. Contact the service workshop.
ErCAL
Error of calibration. The work is stopped – The meter is not in the state to carry out measurements in a correct way. Incorrect checksum of calibration coefficients or lack of calibration.
Page 45
45
9. TECHNICAL DATA
Measuring ranges
Table 13
Kind of input Indication range Class
Pt100
-205...855°C (-200...850°C)
0.1
Pt500
Pt1000
400 W 0...410 W (0...400 W)
4000 W 0...4010 W (0...4000 W) Thermocouple of J type -200...1200 °C (-100...1200 °C)
Thermocouple of K type -200...1370 °C (-100...1370 °C)
Thermocouple of N type -200...1300 °C (-100...1300 °C)
Thermocouple of E type -200...1000 °C (-100...1000 °C)
Thermocouple of R type -50...1768 °C (-50...1760 °C)
Thermocouple of S type -50...1768 °C (-50...1760 °C)
Voltage input 0...10 V -13...13 V (-10...10 V)
Current imput -24...24 mA (- 20...20 mA)
Voltage input 60 mV -10...63 mV (0...60 mV)
Current time 00.00...23.59 0.5 sec/24 h
Additional error:
- of automatic thermocouple cold junction temperature compensation: 1 °C
- of automatic wire resistance compensation for thermoresistors:  0,5 °C
- of automatic wire resistance compensation for resistance measurement:  0,2 W
- of temperature changes: for analog outputs 50 % of the class / 10 K for analog inputs 100 % of the class / 10 K Inputs parameters:
- resistance of the supply input [V]: > 1 M W
- resistance of the current input [mA]: 12 ±1 W%
- current flowing through the resistance thermometer 270 ± 10 uA
- resistance of wires connecting the resistance thermometer with transmitter: <10 W
Page 46
46
Relay outputs - relays, NOC voltageless contacts load capacity 250 V~/0.5A~
- relays, switched voltageless contacts load capacity 250 V~/0.5A~ (option)
Analog outputs (option) - rogrammable, current 0/4..20mA load resistance 500 W
- programmable, voltage 0..10V load resistance 500 W
Output of auxiliary supply 24 V d.c./30 mA
Alarm output OC (option) output of OC type, passive npn,
30 V d.c./30 mA.
Serial interface RS-485 (option)
Transmission protocol MODBUS RTU
Error of analog output 0.2% of the set range
Protection level ensured by the casing:
- frontal side IP65
- terminal side IP10
Weight < 0.2 kg
Overall dimensions 96 ´ 48 ´ 93 mm (with terminals)
Reference conditions and rated operating conditions:
- supply voltage 85...253 V d.c./a.c. 40...400 Hz or
20...40 V a.c. (40...400 Hz), 20...60 V d.c.
- ambient temperature - 25...23...+55
o
C
- storage temperature -30...+70
o
C
- relative air humidity 25...95% (inadmissible condensa­ tion of water vapour)
- work position any
- power consumption < 6 VA
Page 47
47
Standards fulfilled by the meter:
Electromagnetic compatibility:
l noise immunity acc. to EN 61000-6-2 l noise emissions acc. to EN 61000-6-4
Safety requirements:
acc. to EN61010-1 standard:
l isolation between circuits: basic,
l installation category: III,
l pollution level: 2,
l maximal phase-to-earth work voltage:
- 300 V for the supply circuit and,
- 50 V for remaining circuits.
l altitude above sea level: < 2000 m.
Page 48
48
10. ORDER CODES
Table 14
*
- after agreeing with the manufacturer.
DIGITAL PANEL METER N30U - X X XX XX U X
Supply:
85... 253 V a.c. (45...65 Hz) or d.c. .......................... 1
20...40V a.c. (40...400 Hz ) , 20...60 V d.c. ............... 2
Additional outputs:
lack .................................................................................. 0
OC output, RS485, analog outputs ................................. 1
OCoutput, RS485, analog outputs,
switched relay outputs .................................................... 2
Unit:
unit code number acc. tab. 15 .............................................. XX
Version:
standard ........................................................................................ 00
custom-made* .............................................................................. XX
Language:
English ................................................................................................... U
Acceptance tests:
without extra quality requirements ............................................................... 0
with an extra quality inspection certificate ................................................... 1
acc. to customer’s request* ......................................................................... X
ORDER EXAMPLE:
the code: N30U - 1 0 26 00 U 0 means: N30U – programmable digital meter type,
1 – supply: 85...253 V a.c/d.c.(45...65 Hz), 0 – lack of additional outputs, 26 – unit „°C” acc. to the table 3, 00 – standard version, U – English language, 0 – without extra quality requirements.
Page 49
49
Code of the highlighted unit Table 15
Code Unit Code Unit
00 Lack of unit 29 % 01 V 30 %RH 02 A 31 pH 03 mV 32 kg 04 kV 33 bar 05 mA 34 m 06 kA 35 l 07 W 36 s 08 kW 37 h 09 MW 38 m
3
10 var 39 obr 11 kvar 40 szt 12 Mvar 41 imp 13 VA 42 rps 14 kVA 43 m/s 15 MVA 44 l/s 16 kWh 45 rev/min 17 MWh 46 r.p.m. 18 kvarh 47 mm/min 19 Mvarh 48 m/min 20 kVAh 49 l/min 21 MVAh 50 m
3
/min 22 Hz 51 szt/h 23 kHz 52 m/h 24
W
53 km/h
25
kW
54 m
3
/h
26
o
C 55 kg/h
27
o
F 56 l/h
28 K XX on order
1)
1)
- after agreeing with the manufacturer.
Page 50
50
11. MAINTENANCE AND GUARANTEE
The N30U digital panel meter does not require any periodical mainte­nance.
In case of some incorrect operations:
1. From the Shipping Date, During the Period Given in the Annexed Guarantee Card
One should take the meter down from the installation and return it to the Manufacturer’s
Quality Control Dept. If the meter has been used in compliance with the instructions, the
Manufacturer warrants to repair it free of charge.
2. After the Guarantee Period: One should turn over the meter to repair it in a certified service
workshop. The disassembling of the casing causes the cancellation of the
granted guarantee.
Our policy is one of continuous improvement and we reserve the right to make changes in design and speci­fications of any products as engineering advances or necessity requires and revise the above specifications without notice.
Page 51
51
Page 52
52
N30U-09A
Sifam Tinsley Instrumentation Inc
3105, Creekside Village Drive, Suite 801
Kennesaw GA 30144
email – psk@sifamtinsley.com
Phone - +1 404 736 4903
Loading...