ST N30H User Manual

1
DIGITAL PANEL METER N30H TYPE
USER’S MANUAL
2
3
Contents
1. APPLICATION AND METER DESIGN ........................................5
2. METER SET ..................................................................................6
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY .................7
6. RS-485 INTERFACE ..................................................................27
7. SOFTWARE UPDATE ................................................................ 27
8. ERROR CODES .........................................................................41
9. TECHNICAL DATA ....................................................................42
10. ORDER CODES .........................................................................44
11. MAINTENANCE AND GUARANTEE .........................................46
4
5
1. APPLICATION AND METER DESIGN
The N30H meter is a programmable digital panel meter destined for the measurement of d.c. voltage or d.c. current. Additionally, the meter enables the indication of the current time. The readout field is a LED display, which allows the exposition of results in colours: red, green and orange. The measured input signal can be arbitrary converted by means of a 21-point individual characteristic.
Features of the N30H meter:
l display colour individually programmed in three intervals, l programmable thresholds of displayed overflows, l 2 NOC relay alarms operating in 6 modes, l 2 switched relay alarms with a switching contact operating
in 6 modes (option),
l signaling of the measuring range overflow, l automatic setting of the decimal point, l programming of alarm and analog outputs with the reaction
on the chosen input quantity (main or auxiliary input),
l real-time clock with the function of the clock supply support
in case of the meter supply decay,
l programmed averaging time – function of walking window with the
averaging time up to 1 hour,
l monitoring of set parameter values, l interlocking of introduced parameters by means of a password, l recount of the measured quantity on the base of a 21-point
individual characteristic,
l service of the interface with MODBUS protocol in the
RTU mode (option),
l conversion of the measured value into a standard – programmable
current or voltage signal (option),
l highlight of any measuring unit acc. to the order.
6
Fig. 1. View of the N30H meter
l signaling of alarm operation – switching the alarm on causes
the highlight of the output number,
l galvanic separation between connectors: alarm, supply, input,
analog output connections and RS-485 interface. Protection degree from frontal side: IP65
Meter overall dimensions: 96 x 48 x 93 mm (with terminals). The meter casing is made of plastics.
2. METER SET
The set is composed of:
- N30H meter .......................................................... 1 pc
- User’s manual ......................................................1 pc
- Guarantee card .................................................... 1 pc
- Clamps to fix in the panel ....................................4 pcs
- Seal ......................................................................1 pc
When unpacking the meter, please check whether the type and execu­tion code on the data plate correspond to the order.
7
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY
In the safety service scope, the N30H meter meets the requirements of the EN 61010-1 standard.
Observations concerning the operational safety
l All operations concerning transport, installation, and commissioning
as well as maintenance, must be carried out by qualified, skilled per­sonnel, and national regulations for the prevention of accidents must be observed.
l The programming of N30H meter parameters must be carried out
after disconnecting measuring circuits
l Before switching the meter on, one must check the correctness of
connections.
l Do not connect the meter to the network through an autotransformer. l Before removing the meter housing, one must switch the supply off
and disconnect measuring circuits.
l The meter is designed to be installed and exploited in electromag-
netic industrial environment conditions.
l Non-authorized removal of the housing, inappropriate use, incorrect
installation or operation, creates the risk of injury to personnel or meter damage.
For more detailed information, please study the User’s Manual.
l When connecting the supply, one must remember that a switch or
a circuit-breaker should be installed in the building. This switch should be located near the device, easy accessible by the operator, and suitably marked as an element switching the meter off.
8
Fig. 3. Overall dimensions
Fig. 2. Meter fixing
4. INSTALLATION
The meter has separable strips with screw terminals, which enable the connection of external wires of 2.5 mm2 cross-section. Strips of input signals are protected against any accidental disconnection by means of a screw joint.
One must prepare a hole of 92
+0,6
´ 45
+0,6
mm in the panel, which the
thickness should not exceed 6 mm. The meter is adapted to be mounted in a panel. The meter must be
introduced from the panel front with disconnected supply voltage. Be­fore the insertion into the panel, one must check the correct placement of the seal. After the insertion into the hole, fix the meter by means of clamps (fig.2).
9
4.1. Signals Leads
Signals led out on the meter connectors are presented on the fig. 4. All input signals are separated between them from remaining circuits. Analog outputs are not separated between them. One don’t have to
take simultaneously advantage of voltage and current measure­ments, since measuring circuits of voltage and current are not galva-
nically isolated.
Fig. 4. Description of signals on connection strips
· 1 A, 5 A – terminals for the current measurement on the 1 A or 5 A range.
· 100 V, 500 V – terminals for the voltage measurement on the 100 V or 500 V range.
· OC –output of open collector type with an npn output transistor. The output is turned on in case of a measuring range overflow.
10
4.2. Examples of Connections
An example of the N30H meter connection for current measurement is presented on the fig. 5.
However, an example of the meter connection in the configuration for voltage measurement is presented on the fig. 6.
Fig. 5. Meter connection in the configuration for current measurement
Fig. 6. Meter connection in the configuration for voltage measurement
11
5. SERVICE
5.1. Display Description
Fig. 7. Description of the meter frontal plate
5.2. Messages after Switching the Supply on
After switching the supply on, the meter displays the meter name N30H, and next the program version in the form „r x.xx” – where x.xx is the number of the current program version or the number of a custom-made execution. Next, the meter carries out measurements and displays the value of the input signal. The meter sets automa­tically the decimal point position, when displaying the value. The format (number of places after the decimal point) can be limited by the user.
12
5.3. Functions of Push-buttons
- Acceptation push-button:
Þ entry in programming mode (press and hold ca 3 seconds) Þ moving through the menu – level selection, Þ entry in the mode changing the parameter value, Þ acceptation of the changed parameter value. Þ stop the measurement – when holding down the push, the result
is not updated. The measurement is still carried out. Þ Turning on the power supply of the meter while holding the button – entering the software-update mode through RS485 interface
- Push-button increasing the value:
Þ display of maximal value, The pressure of the push-button causes the display of the maximal value during ca 3 seconds.
Þ entry in the level of the parameter group, Þ moving on the chosen level, Þ change of the chosen parameter value – increasing the value.
- Push-button to change the digit:
Þ display of minimal value, The pressure of the push-button causes the display of the maximal value during ca 3 seconds.
Þ entry in the level of parameter group, Þ moving through the chosen level, Þ change of chosen parameter value – shift on the next digit,
- Resignation push-button:
Þ entry in the menu monitoring the meter parameters (press and hold ca 3 seconds),
Þ exit from the menu monitoring meter parameters, Þ resignation of the parameter change, Þ strict exit from the programming mode (press and hold
ca 3 seconds).
13
The pressure of the push-button combination and hol­ding down them during ca 3 seconds causes the deletion of alarm signa­ling. This operation acts only when the support function is switched on.
The pressure of the push-button combination
causes
the erasing of the minimal value.
The pressure of the push-button combination
causes
the erasing of the maximal value.
The pressure and holding down the
push-button during ca 3 seconds causes the entry to the programming matrix. The program­ming matrix can be protected by a safety code.
The pressure and holding down the
push-button during ca 3 seconds causes the entry to the menu monitoring meter parameters.
One must move through the monitoring menu by means of
and
push-buttons. In this menu, all programmable meter parame­ters are available only for readout. In this mode, the menu Ser is not available. The exit from the monitoring menu is carried out by means of
the
push-button. In the monitoring menu, parameter symbols
are displayed alternately with their values. The service algorithm of the meter is presented on the fig. 8.
The appearance of the symbols mentioned below on the display means:
- Incorrectly introduced safety code.
- Overflow of the upper measuring range.
- Overflow of the lower measuring range.
14
Fig. 8. Service algorithm of the N30H meter
15
5.4. Programming
The pressure of the push-button and holding it down through ca 3 seconds causes the entry to the programming matrix. If the entry is protected by a password, then the safety code symbol SEC is display­ed alternately with the set value 0. The write of the correct code causes the entry to the matrix, the write of an incorrect code causes the display of the ErCod inscription. The matrix of transitions to the programming mode is presented on the fig. 9. The choice of the level is made by means of the
push-button, however the entry and moving through the parameters of the chosen level is carried out by means of the
and push-buttons. Parameter symbols are display­ed alternately with their current values. In order to change the value of the chosen parameter, one must use the
push-button. For
resignation from change, one must use the
push-button. In or­der to exit from the chosen level, one must chose the ----- symbol and press the
push-button. To exit from the programming matrix,
one must press during ca 1 second the
push-button. Then, the inscription End appears for ca 3 seconds and the meter transits to the display of the measured value. In case of leaving the meter in the para­meter programming mode, the automatic abandon of the programming mode (the parameter and next the menu) follows after 30 seconds and the meter transits to display the measured value.
5.4.1. Value Change Way of the Chosen Parameter
In order to increase the value of the chosen parameter, one must press the
push-button. A single pressure of the push, causes the increase of the value of 1. The increase of value when displaying the digit 9, causes the set of 0 on this digit (or the minus mark in case of the oldest display digit). The change of the cursor position after pres­sing the
push-button. In order to accept the set parameter,
16
Fig. 9. Programming matrix
17
InP 1
Parameter
symbol
Description Range of changes
tYP1
Kind of the connected input signal
500U – input 500 V. 100U – input 100 V 5A – input 5 A. 1A – input 1 A. HoUr – current time.
Cnt1
The measurement time is expressed in seconds. The result on the display pres­ents the mean value counted in the Cnt1 period. This parameter is not taken into consideration during the measurement in the HoUr modes.
1...3600
Table 1
one must hold down the
push-button. Then, the write of the parameter follows and the display of its symbol alternately with the new value. The pressure of the
push-button during the change of
the parameter value will cause the resignation of the write.
5.4.2. Changing Floating-point Values
The change is carried out in two stages ( the transition to the next stage follows after pressing the
push-button:
1) setting values from the range -19999M...99999, similarly as for
integral values;
2) setting decimal point positions (00000., 0000.0, 000.00, 00.000,
0.0000); the
push-button shifts the decimal point to the left,
however the
push shifts the decimal point to the right;
The pressure of the
push-button during the change of the pa-
rameter value will cause the resignation of the write.
5.4.3. Characteristic of Programmed Parameters
Programmed parameters and the range of their quantity changes are presented in the table below.
18
Table 2
dISP
Parameter
symbol
Description Range of changes
d_P
Minimal position of the decimal point when displaying the measured value
- display format. This parameter is not taken into consideration during the CoUntH and HoUr modes.
0.0000 – 0
00.000 – 1
000.00 – 2
0000.0 – 3 00000 – 4
CoLdo
Display colour, when the displayed value is less than CoLLo.
rEd – red grEEn – green orAnG -orange
CoLbE
Display colour, when the displayed value is higher than CoLLo and less than CoLHi.
CoLuP
Display colour when the displayed value is higher than CoLHi
CoLLo
Lower threshold of colour change
-19999..99999
CoLHi
Upper threshold of colour change
-19999..99999
ovrLo
Lower threshold of the display nar­rowing. Values below the declared threshold are signaled on the display by
the symbol.
-----
.
-19999..99999
ovrHi
Upper threshold of display narrowing. Values above the declared threshold are signaled on the display by the symbol.
-----
.
-19999..99999
Table 3
Ind
Parameter
symbol
Description Range of changes
IndCp
Number of points of the individual char­acteristic. For a value less than 2, the individual characteristic is switched off. The number of segments is the number of points decreased of one. The individual characteristic is not taken into consideration in the HoUr modes.
1...21
Xn
The point value for which we will expect Yn (n-point number)
-19999...99999
Yn
Expected value for Xn.
-19999...99999
19
Table 4
ALr1, ALr2, ALr3, ALr4
Parameter
symbol
Description Range of changes
P_A1 P_A2 P_A3 P_A4
Input quantity, steering the alarm.
InP1 – Main input (indicated value).
HoUr – real time clock
tYP1 tYP2 tYP3 tYP4
Alarm type. Fig. 12 presents the graphical imaging of alarm types.
n-on – normal (transition from 0 to 1),
n-oFF – normal (transition from 1 to 0),
on – switched on, oFF – switched off, H-on – manually switched
on; till the change time of the alarm type, the alarm output remains switched on for good,
H-oFF – manually switched off; till the change time of the alarm type the output alarm remains switched off
for good.
PrL1 PrL2 PrL3 PrL4
lower Alarm threshold.
-19999...99999
PrH1 PrH2 PrH3 PrH4
upper Alarm threshold.
-19999...99999
dLY1 dLY2 dLY3 dLY4
Delay of alarm switching.
0...900
20
LEd1 LEd2 LEd3 LEd4
Support of alarm signalling. In the situation when the support function is switched on , after the alarm state retreat, the signalling diode is not blanked . It signals the alarm state till its blanking moment by means of
the
push-but­ton combination. This function concerns only and exclusively the alarm signaling, thus relay contacts will operate without support according to the chosen type of alarm.
oFF – function switched off on – function switched on
out
Parameter
symbol
Description Range of changes
P_An
Input quantity, on which the analog output has to react..
InP – main input (indicated value).
HoUr – Real Time Clock
AnL
Lower threshold of the analog output. One must give the value, for which we want to obtain the minimal value of signal on the analog output.
-19999...99999
AnH
Upper threshold of the analog output. One must give the value on which we want to obtain the maximal value of signal on the analog output( 10 V or 20 mA).
-19999...99999
tYPA
Analog output type.
0_10U – napięciowe 0..10V 0_20A – prądowe 0..20mA 4_20A – prądowe 4..20mA
Table 5
21
bAud
Baud rate of the RS485 interface
4.8 – 4800 bit/s
9.6 – 9600 bit/s
19.2 – 19200 bit/s
38.4 – 38400 bit/s
57.6 – 57600 bit/s
115.2 – 115200 bit/s
prot
Type of transmission frame of the RS-485 interface.
r8n2 r8E1 r8o1 r8n1
Addr
Address in the MODBUS network. The write of the value 0 switches the interface off
.
0...247
Table 6
SEr
Parameter
symbol
Description Range of changes
SEt
Write of manufacturer’s settings. The setting of the value YES causes the write of standard parameters into the meter. The value of manufacturer’s parameters is presented in the
table 7.
no – do nothing. YeS – causes the write of
manufacturer’s settings.
SEC
Introduction of a new password. The introduction of the value 0 switched the password off.
0...60000
HOUR
Setting of the current time. The introduction of a wrong time can­cels the introduction of time. The introduced value will not be collected.
0.00...23.59
unIt
Backlighting of the unit.
On – unit highlight switched on.
Off – unit highlight switched off.
tESt
Display test. The test consists of a successive lighting up of digital display segments. Alarm diodes and unit highlighting diodes should be lighted .
YeS – causes the test start.
The pressure of the push-button ends the test.
no – do nothing.
22
5.4.4 Individual Characteristic
N30H meters can recalculated the measured value into any value thanks to the implemented individual characteristic function. The indivi­dual characteristic rescales the input signal measured according to the set characteristic. The way of the individual characteristic interaction on the meter operation has been presented on the fig.10.
Fig. 10. Action of the individual characteristic
The user can introduce maximally twenty linearizing functions by giving points defining intervals of the given function operation and expected values for successive points. On the base of given points and corre­sponding values to them, coefficients a and b of recalibrating straight lines are calculated. The programming of the individual characteristic consists on the definition of the number of points which the input fun­ction will be linearized by. On must remember that the number of linea­rizing functions is less of one than the number of points. Next, one must program successive points by giving the measured value (Hn) and the expected value corresponding to it, – value, which has to be displayed (Yn). The graphic interpretation of the individual characteristic is pre­sented on the fig. 11..
23
Fig. 11. Individual characteristic
During the function approximation, one must remember that for the ap­proximation of functions strongly differing from the linear characteristic , the higher the number of linearizing segments, the smallest the error related to the linearization.
If measured values are smallest from H1 then, recalculations will be made on the base of the first straight line calculated on the base of points (H1,Y1) an (H2,Y2). However, for values higher than Hn (where n – the last declared measured value) the value to display will be calcu­lated on the base of the last assigned linear function.
Note: All introduced points of the measured value (Hn) must be arran­ged in the increasing sequence, such to preserve the following depen­dence:
H1 < H2 < H3... < Hn
If the above is not fulfilled, the individual characteristic function will be automatically switched off (will not be realized) and a diagnostic flag will be set in the status register.
24
a) n-on b) n-off
c) on d) off
Fig. 12. Alarm types: a) n-on, b) n-off c) on d) off.
5.4.5 Alarm Types
The N30U meter is equipped with 2 alarm outputs with NOC contact (make contact) and two alarm outputs with NOC/NCC contact (make and break contact) (option). Each of alarms can work in one of the six modes . The work of alarms in modes is presented in the fig. 12. : n-on, n-off, on, off. Two remaining modes : h-on and h-off mean respectively, always switched on and always switched off. These modes are desti­ned for the manual simulation of alarm states.
25
Caution !
l In case of alarms of n-on, n-off, on, off types, the write of
PrL>PrH will cause the alarm switching off.
l In case of a measuring range overflow, the reaction of the relays
is compatible with written PrL, PrH, tYP parameters. In spite of the displayed overflow, the meter still carries out the measurement.
l The meter controls currently the value of the introduced parame-
ter at the moment. In case when the introduced value overflows the upper range given in the table 1, the meter will make automatically the change into the maximal value. Similarly, in case when the introduced value overflows the lower change range given in the table 1, the meter will make automatically the change into the minimal value.
5.4.6 Display Format
The N30H meter adapts automatically the display format (precision) to the value of measured quantity. So that the function could be fully used, one must choose the format 0.0000, then the meter will display the me­asured value with the possible highest accuracy. This function does not operate for the time display, where the format is set automatically. The current time (HOUr mode) is displayed in the 24 hours’ format, in the form hh.mm, where hh – current time, and mm – current minute..
26
Parameter symbol Level in the matrix
Standard value
tYP1 1
500U
Cnt1 1 1
indCP 2 no
H0 2 0
Y0 2 0
H1 2 100
Y1 2 100
... ... ...
Hn 2 (n-1)*100
Yn 2 (n-1)*100
d_P 3 0000.0
CoLdo 3 grEEn
CoLbE 3 orAng
CoLuP 3 rEd
CoLLo 3 50.00
CoLHi 3 80.00
ovrLo 3 -19999
ovrHi 3 99999
P_A1, P_A2,
P_A3, P_A4
4, 5, 6, 7 InP1
tYP1, tYP2,
tYP3, tYP4
4, 5, 6, 7 h-off
PrL1, PrL2,
PrL3, PrL4
4, 5, 6, 7 1000
PrH1, PrH2,
PrH3, PrH4
4, 5, 6, 7 2000
Table 7
5.5. Manufacturer’s Parameters
Standard settings of the N30U meter are presented in the table 8. The­se settings can be restored by means of the meter menu through the choice of the option Set from the menu Ser.
27
dLY1, dLY2, dLY3, dLY4,
4, 5, 6, 7 0
LEd1, LEd2,
LEd3, LEd4
4, 5, 6, 7 oFF
P_An 8 InP1
tYPA 8 0_10U
AnL 8 0
AnH 8 99999
bAud 8 9.6
prot 8 r8n2
Addr 8 1
SEt 9 no
SEC 9 0
HOUR 9 not defined
unit 9 off
tESt 9 off
6. RS-485 INTERFACE
N30H programmable digital meters have a serial link in RS-485 stan­dard for the communication in computer systems and with other de­vices fulfilling Master function. An asynchronous communication cha­racter protocol MODBUS has been implemented on the serial link. The transmission protocol describes ways of information exchange between devices through the serial link.
6.1. Connection Way of the Serial Interface
The RS-485 standard allows to a direct communication of 32 devices on a single serial link of 1200 m long (at baud rate 9600 b/s). For the connection of a higher quantity of devices, it is necessary to apply ad­ditional intermediate-separating systems ( e.g. PD51 converter).
28
Fig. 13. Connection way of the RS-485 interface
The lead wire of the interface line is presented on the fig. 4. To obtain a correct transmission, it is necessary to connect lines A and B in parallel with their equivalents in other devices. The connection must be made through a shielded wire. The wire shield must be connected to the pro­tection terminal in the nearest possible neighbourhood of the meter (connect the shield to a single point to the protection terminal).
The GND line serves to the additional protection of the interface line at long connections. Then, one must connect GND signals of all devices to the RS-485 bus.
To obtain the connection to the computer, a RS-485 interface card or an appropriate converter is indispensable, e.g. PD51 or PD10.
The connection way of devices is shown on the fig. 13
The designation of transmission lines for the card in the PC computer depends on the card producer.
29
6.2. Description of the MODBUS Protocol Implementation.
The implemented protocol is in accordance with the PI-MBUS-300 Rev G of Modicon Company specification.
Set of the serial link parameters of N30U meters in MODBUS protocol:
l meter address: 1...247,
l baud rate: 4800, 9600, 19200, 38400,
57600, 115200 bit/s,
l work mode: RTU with a frame in formats: 8N2,
8E1, 8O1, 8N1,
l maximal time to start
the response : 100 ms.
The parameter configuration of the serial link consists on the settlement of the baud rate (bAUd parameter), device address (Addr parameter), and the format of the information unit (Prot parameter).
Notice:
Each meter connected to the communication network must have:
l unique address, different from addresses of other devices connec-
ted to the network,
l identical baud rate and type of information unit.
6.3 Description of Applied Functions
Following functions of the MODBUS protocol have been implemented in the N30U meter:
l 03 – Readout of n-registers. l 04 – Readout of input n-registers. l 06 – Write of a single register. l 16 – Write of n-registers. l 17 – Identification of the slave device.
30
6.4 Register Map
The register map of the N30H meter is presented below.
Notice:
All given addresses are physical addresses. In some computer pro­grams logical addressing is applied, then addresses must be increa­sed of 1.
Table 8
Range of addreses
Value type Description
4000-4049 integer (16 bits) Value placed in a 16-bit register.
7000-7025 float (32 bits)
Value placed in two successive 16­bit registers. Registers include the same data as 32-bit register from the area 7500. Registers are only for readout.
7200-7363 float (32 bits)
Value placed in two successive 16­bit registers. Registers include the same data as 32-bit register from the area 7600. Registers can be read out and written.
7500-7512 float (32 bits)
Value placed in a 32-bit register. Registers are only for readout.
7600-7663 float (32 bits)
Value placed in a 32-bit register. Registers can be read out and written.
31
6.5. Registers for Write and Readout
Table 9
The value is placed in
16-bit registers
write (w)/ readout (r)
Input type4000
tYP1
w/r 0...4
Range DescriptionSymbol
Value
0 0.0000
1 00.000
0 500U - voltage measurement in the 500 V range
1 100U - voltage measurement in the 100 V range
2 5A - voltage measurement in the 5 A range
3 1A - voltage measurement in the1 A range
4 HoUr -current time
Value
Reserved4001 w/r
Reserved4002 w/r
4003
Cnt
w/r 1...3600
Measurement time expressed in seconds. This time defines the averaging time of the measured value. The displayed value is the mean value calculated from the Cnt1 period.
Reserved4004 w/r
Reserved4005 w/r
Reserved4006 w/r
Reserved4007 w/r
4008
IndCp
w/r 1...21
Number of points of the individual characteristic. For the value 1, the individual characteristic is swit­ched off. Segments of the individual characteristic are defined by parameters Xn and Yn, where n – point number..
Minimal position of the decimal point when display­ing the measured value.
4009
d_P
w/r 0...4
Description
32
Value
0 red
1 green
2 orange
2 000.00
3 0000.0
4 00000
Display colour when the displayed value is less than coLLo
Description
4010
CoLdo
w/r 0...2
Value
0 red
1 green
2 orange
Display colour when the displayed value is higher than coLLo and less than CoLHi
Description
4011
CoLbE
w/r 0...2
Value
0 red
1 green
2 orange
Display colour when the displayed value is higher than coLHi
Description
4012
CoLUp
w/r 0...2
DescriptionValue
0 Main input
1 Clock
Input quantity controlling the alarm
4013
P_a1
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 1 (description - fig. 6)
Description
4014
tyP1
w/r 0...5
Delay of alarm 1 (in seconds)
4015
dLY1
w/r 0...900
33
Support of alarm 1 signalling
4016
LEd1
w/r 0...1
Value
0 Support switched off
1 Support switched on
Descritpion
DescriptionValue
0 Main input
1 Clock
Input quantity controlling the alarm
4017
P_a2
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 2 (description - fig. 6)
Description
4018
tyP2
w/r 0...5
Delay of alarm 2 (in seconds)
4019
dLY2
w/r 0...900
Support of alarm 2 signalling
4020
LEd2
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
DescriptionValue
0 Main input
1 Clock
Input quantity controlling the alarm
4021
P_a3
w/r 0, 1
WartoϾ
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 3 (description - fig. 6)
Opis
4022
tyP3
w/r 0...5
Delay of alarm 3 (in seconds)
4023
dLY3
w/r 0...900
34
Support of alarm 3 signalling
4024
LEd3
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
DescriptionValue
0 Main input
1 Clock
Input quantity controlling the alarm
4025
P_a4
w/r 0, 1
Value
0 n-on
1 n-off
2 on
3 off
4 h-on
5 h-off
Type of alarm 4 (description - fig. 6)
Description
4026
tyP4
w/r 0...5
Delay of alarm 4 (in seconds)
4027
dLY4
w/r 0...900
Support of alarm 4 signalling
4028
LEd4
w/r 0...1
Value
0 Support switched off
1 Support switched on
Description
Input quantity, which the analog output has to react on.
4029
P_an
w/r 0, 1
Value
0 Main input
1 Clock
Description
Type of analog output
4030
tYPa
w/r 0...2
Value
0 Voltage input 0...10 V
1 Current input 0...20 mA
2 Current input 4...20 mA
Description
Baud rate
4031
bAud
w/r 0...5
Value
0 4800 bit/s
1 9600 bit/s
2 19200 bit/s
Description
35
Bit 15 Break of the supply
Bit 14 Re-set of the RTC clock.
3 38400 bit/s 4 57600 bit/s 5 115200 bit/s
Meter address. The write of the value 0 causes the inerface switching off.
4033
Addr
z/o 0...247
Transmission mode4032
prot
z/o 0...3
Update transmission parameters. Causes the appli­cation of introduced RS-485 interface settings.
4034
sAvE
z/o 0...1
Value
0 RTU 8N2 1 RTU 8E1 2 RTU 8O1
3 RTU 8N1
Description
Write of standard parameters4035
SEt
z/o 0...1
Value
0 without changes 1 set standard parameters
Description
Password for parameters4036
SEc
z/o 0...6000
Value
0 without password ... Entry in parameters preceded by a
request about the password
Description
Current time4037
hour
z/o 0...2359
This parameter occurs in the ggmm format,where: gg - means hours, mm – means minutes. The introduction of a wrong hour will cause the set­ting 23, however the introduction of wrong minutes will generate the setting of the value 59.
Switch on/off the unit backlight4038
unit
z/o 0, 1
Value
0 Highlighting switched off 1 Highlighting switched on
Description
Reserved
...
...
... ...
Meter status. Describes the current state of the meter. Successive bits present data of the event. The bit set on 1 means, that the event took place. Events can be only erased..
4048 Status1 z/o
0...65535
4039 z/o 0, 1
Extreme values’ deletion. Writing in “1” to the
register will cause the deletion of the minimum and
maximum values
36
Bit 13 Not used
Bit 12
Lack of communication with data memory
Bit 11 Wrong settings
Bit 10 Manufacturer’s setting restored
Bit 9
Lack of measured values in data memory
Bit 8 Not used
Bit 7 Output plate was detected
Bit 6 Output plate - error or lack of calibration
Bit 5 Not used
Bit 4 Not used
Bit 3
Wrong configuration of the individual character.
Bit 2 Not used
Bit 1 Not used
Bit 0 Not used
Bit 15 Not used
Bit 14 Not used
Meter status. Describes the current state of the meter. Successive bits present data of the event. The bit set on 1 means, that the event took place. Events can be only deleted.
Bit 13 Not used
Bit 12 Not used
Bit 11 Not used
Bit 10 Not used
Bit 9 Not used
Bit 8 Not used
Bit 7 LED4 - Signalling of alarm No.4
Bit 6 LED3 - Signalling of alarm No.3
Bit 5 LED2 - Signalling of alarm No.2
Bit 4 LED1 - Signalling of alarm No.1
Bit 3 Status of the alarm relay No.4
Bit 2 Status of the alarm relay No.3
Bit 1 Status of the alarm relay No.2
Bit 0 Status of the alarm relay No.1
4049 Status2 w/r
37
The value is placed in two successive
16-bit registers. These registers include
the same data as 32-bit registers from
the area 7600.
The value is placed in 32-bit registers
Sym-
bol
write
(w) /rea­dout
(r)
Range Description
7200 7600
coLLo
w/r -19999...99999
Lower threshold of the display colour change
7202 7601
coLHI
w/r -19999...99999
Upper threshold of the display colour change
7204 7602
ovrLo
w/r -19999...99999 Lower threshold of the display narrowing
7206 7603
ovrHI
w/r -19999...99999 Upper threshold of the display narrowing
7208 7604
PrL 1
w/r -19999...99999 Lower threshold of alarm 1
7210 7605
PrH 1
w/r -19999...99999 Upper threshold of alarm 1
7212 7606
PrL 2
w/r -19999...99999 Lower threshold of alarm 2
7214 7607
PrH 2
w/r -19999...99999 Upper threshold of alarm 2
7216 7608
PrL 3
w/r -19999...99999 Lower threshold of alarm 3
7218 7609
PrH 3
w/r -19999...99999 Upper threshold of alarm 3
7220 7610
PrL 4
w/r -19999...99999 Lower threshold of alarm 4
7222 7611
PrH 4
w/r -19999...99999 Upper threshold of alarm 4
7224 7612
AnL
w/r -19999...99999 Lower threshold of analog output
7226 7613
AnH
w/r -19999...99999 Upper threshold of analog output
7228 7614 w/r -19999...99999 Reserved
7230 7615 w/r -19999...99999 Reserved
7232 7616 w/r -19999...99999 Reserved
7234 7617 w/r -19999...99999 Reserved
7236 7618 w/r -19999...99999 Reserved
7238 7619 w/r -19999...99999 Reserved
Table 10
38
7240 7620 w/r -19999...99999 Reserved
7242 7621 w/r -19999...99999 Reserved
7244 7622
H1
w/r -19999...99999
Point of the individual charachteristic Point No.1.
7246 7623
Y1
w/r -19999...99999 Expected value for the point No. 1.
7248 7624
H2
w/r -19999...99999
Point of the individual charachteristic Point No. 2.
7250 7625
Y2
w/r -19999...99999 Expected value for the point No. 2.
7252 7626
H3
w/r -19999...99999
Point of the individual charachteristic Point No. 3.
7254 7627
Y3
w/r -19999...99999 Expected value for the point No. 3.
7256 7628
H4
w/r -19999...99999
Point of the individual charachteristic Point No.4.
7258 7629
Y4
w/r -19999...99999 Expected value for the point No. 4.
7260 7630
H5
w/r -19999...99999
Point of the individual charachteristic Point No. 5.
7262 7631
Y5
w/r -19999...99999 Expected value for the point No. 5.
7264 7632
H6
w/r -19999...99999
Point of the individual charachteristic Point No. 6.
7266 7633
Y6
w/r -19999...99999 Expected value for the point No. 6.
7268 7634
H7
w/r -19999...99999
Point of the individual charachteristic Point No. 7.
7270 7635
Y7
w/r -19999...99999 Expected value for the point No. 7.
7272 7636
H8
w/r -19999...99999
Point of the individual charachteristic Point No. 8.
7274 7637
Y8
w/r -19999...99999 Expected value for the point No. 8.
7276 7638
H9
w/r -19999...99999
Point of the individual charachteristic Point No. 9.
7278 7639
Y9
w/r -19999...99999 Expected value for the point No. 9.
7280 7640
H10
w/r -19999...99999
Point of the individual charachteristic Point No.10.
7282 7641
Y10
w/r -19999...99999 Expected value for the point No. 10.
7284 7642
H11
w/r -19999...99999
Point of the individual charachteristic Point No. 11.
7286 7643
Y11
w/r -19999...99999 Expected value for the point No. 11.
7288 7644
H12
w/r -19999...99999
Point of the individual charachteristic Point No. 12.
39
7290 7645
Y12
w/r -19999...99999 Expected value for the point No. 12.
7292 7646
H13
w/r -19999...99999
Point of the individual charachteristic Point No. 13.
7294 7647
Y13
w/r -19999...99999 Expected value for the point No. 13.
7296 7648
H14
w/r -19999...99999
Point of the individual charachteristic Point No. 14.
7298 7649
Y14
w/r -19999...99999 Expected value for the point No. 14.
7300 7650
H15
w/r -19999...99999
Point of the individual charachteristic Point No. 15.
7302 7651
Y15
w/r -19999...99999 Expected value for the point No. 15.
7304 7652
H16
w/r -19999...99999
Point of the individual charachteristic Point No. 16.
7306 7653
Y16
w/r -19999...99999 Expected value for the point No. 16.
7308 7654
H17
w/r -19999...99999
Point of the individual charachteristic Point No. 17.
7310 7655
Y17
w/r -19999...99999 Expected value for the point No. 17.
7312 7656
H18
w/r -19999...99999
Point of the individual charachteristic Point No. 18.
7314 7657
Y18
w/r -19999...99999 Expected value for the point No. 18.
7316 7658
H19
w/r -19999...99999
Point of the individual charachteristic Point No. 19.
7318 7659
Y19
w/r -19999...99999 Expected value for the point No. 19.
7320 7660
H20
w/r -19999...99999
Point of the individual charachteristic Point No. 20.
7322 7661
Y20
w/r -19999...99999 Expected value for the point No. 20.
7324 7662
H21
w/r -19999...99999
Point of the individual charachteristic Point No. 21.
7326 7663
Y21
w/r -19999...99999 Expected value for the point No. 21.
40
The value placed In two suc-
cessive 16-bit registers. These
registers include the same data as
32-bit registers from the area 7500
The value is placed in 32-bit
registers
Name
Write
(w)
/
rea-
dout
(r)
Unit Name of the quantity
7000 7500 Identifier O
Constant identifying the device. The value 187 means the N30H meter
7002 7501 Status O
Status is register describing the current state of the meter
7004 7502 Control O %
It is a register defining the control of the analog outpu
7006 7503 Minimum O
Minimal value of the currently displayed value
7008 7504 Maximum O
Maximal value of the currently dis­played value
7010 7505
Displayed
value
O Currently displayed value
7012 7506 O Current time
7014 7507 O Reserved
7016 7508 O
Password of analog-to-digital trans­ducer
7018 7509 O Reserved
7020 7510 O
Measured value – not recalculated In relation to the individual characteristic, a.s.l
.
7022 7511 O Reserved
7024 7512 O Reserved
6.6. Registers only for Readout
Table 11
41
7. SOFTWARE UPDATING
Note! After updating the software the manufacturer’s settings for the transducer ought to be set, therefore it is advisable to store the meters parameters before its updating using LPCon or eCon software.
After LPCon has been started, one ought to set serial port, baut rate, mode and the transducer address in Options. Then choose the N30H meter from the menu Devices and click the icon Read in order to read all set parameters (necessary for their later restoration). After selecting from the menu Updating the option Device software updating, the Lumel Updater (LU) window opens – Fig. 13 b. Press Connect. The information window Messages contains information on the updating process. At the correctly opened port, the message Port opened displays.
Fig. 13. The view of program window: a) LPCon, b) Lumel Updater (LU)
a)
b)
The N30H meters (from the version 1.09) in version with RS-485 interface come with the implemented function that allows for updating the software from a PC with LPCon or eCon software. In order to update software the RS-485 converter on USB, such as PD10 converter must be connected to the computer.
42
Entering the updating mode in the meter is carried out remotely by LU program (based on the settings in LPCon - adres, mode, baud rate, port Com) or by switching on the meter power supply with pressed key . Pulsating of the meter state diode AL1 in gre­en signals readiness for updating, whereas the LU program displays the message Device found and the name and version of the program of the conneted device. One should press the button ... and indicate the meter updating file. At the correctly opened file, the information File opened displays. One should press Send button. After upda­ting being successfully completed the meter switches to normal work, whereas the information window displays Done and the duration time of the updating. After the LU window closure, one should go to the parameters group Restoring manufacturer’s settings, mark the op­tion and press Apply button. Then press the icon Save in order to save readout initially set parameters. Current software version may also be checked by reading the meter welcome messages after switching on the power supply.
Note! Switching the supply off during the software updating process may result in permenent damage of the meter!
43
8. ERROR CODES
After switching the meter on to the network or during the work, messa­ges about errors can appear.
Messages about errors and their reasons are presented below. .
Table 12
Error message Description
Overflow of the upper value of the measuring range value or the programmed indication range.
Overflow of the lower value of the measuring range value or the programmed indication range.
ErFrt
Communication error with the data memory. One must contact the service workshop.
ErPar
Parameter error. Wrong configuration data. Manufactu­rer’s settings will be restored after pressing any push.
ErdEF
Default settings have been restored. One must press any push to transit to a normal work.
ErFPL
Error of measured values stored by the meter (measured value, maximal and minimal values). One must press any push to transit to a normal work. After pressing the push during 1 sec, the ErdEF message will be displayed.
ErCAo
Lack of calibration of analog outputs. One must press any push to transit to the normal work. Analog outputs will not be serviced. One must contact the service workshop.
ErCOd
Erroneous access code to meter parameters. The error appears in the moment of giving a wrong access code to meter parameters (only in case when meter parameters are protected by a password).
44
8. TECHNICAL DATA
Measuring ranges.
Table 13
Kind of input Indication of range class
500 V -600...600 V 0.1% of the range
100 V -130...130 V 0.1% of the range
5 A -6...6 A 0.1% of the range ± 5 mA
1 A -2...2 A 0.1% of the range ± 1 mA
Current time 00.00...23.59 0.5 seconds/24h
Relay outputs: - relays, NO voltageless contacts load capacity 250 V~/0.5A~
- relays, switched voltageless contacts load capacity 250 V~/0.5A~ (option)
Analog outputs (option): - programmable, current 0/4...20 mA load resistance £ 500 W
- programmable, current 0..10 V load resistance ³ 500 W
Alarm output OC (option): output of OC type, passive npn,
30 V d.c./30 mA.
Serial interface: RS-485 (option)
Transmission protocol: MODBUS RTU
Error of analog output: 0.2% of the set range.
Protection grade ensured by the casing:
frontal side IP65 terminal side IP10
45
Weight: < 0.2 kg
Dimensions: 96 ´ 48 ´ 93 mm
Reference Conditions and Rated Operating conditions:
- supply voltage 85..253 V d.c./a.c. 40..400Hz or 20..40 V a.c. (40...400 Hz),
20...60 V d.c.
40..400Hz
- ambient temperature -25..23..+55
o
C
- storage temperature -33..+70
o
C
- reltive air humidity 25..95% (inadmissible vapour condensation)
- work position any
Additional errors:
- from temperature changes: for analog inputs and outputs 50% of the class/10 K
Standards fulfilled by the meter:
Electromagnetic compatibility:
l Noise immunity acc. to EN 61000-6-2 l Noise emission acc. to EN 61000-6-4
Safety requirements:
Acc. to the EN61010-1 standard:
l isolation between circuits: basic,
l installation category: III,
l pollution level: 2,
l maximal phase-to-earth working voltage:
- 300 V for the supply circuit,
- for the measuring input 600 V for analog input signals – cat. II (300 V – cat. III),
- 50 V for remaining circuits.
l altitiude above sea level < 2000 m.
46
9. ORDER CODES
Table 14
*
- after agreeing with the Manufacturer
DIGITAL PANEL METER N30H - X X XX XX U X
Supply:
85... 253 V a.c. (40...400 Hz) or d.c. ........................ 1
20... 40 V a.c. (40...400 Hz), 20..60 V d.c. ............... 2
Additional outputs:
lack .................................................................................. 0
OC output, RS-485, analog outputs ................................ 1
OC output, RS-485, analog outputs,
switched-over relay outputs ............................................ 2
Unit:
unit code acc. to the table 15 ............................................... XX
Version:
standard ........................................................................................ 00
custom-made* .............................................................................. XX
Language:
English ................................................................................................... U
Acceptance tests:
without extra requirements ............................................................................ 0
with an extra quality inspection certificate .................................................... 1
Acc. to customer’s request* .......................................................................... X
Order example
The code N30H - 1 0 01 00 U 0 - means
N30H - programmable N30H panel digital meter
1 - supply: 85...253 V a.c./d.c 0 - lack of additional outputs 01 - unit „V” acc. to the table 2 00 - standard version U - English language 0 - without extra requirements
47
Code of the highlighted unit Table 15
Code Unit Code Unit
00 Lack of unit 29 % 01 V 30 %RH 02 A 31 pH 03 mV 32 kg 04 kV 33 bar 05 mA 34 m 06 kA 35 l 07 W 36 s 08 kW 37 h 09 MW 38 m
3
10 var 39 obr 11 kvar 40 szt 12 Mvar 41 imp 13 VA 42 rps 14 kVA 43 m/s 15 MVA 44 l/s 16 kWh 45 obr/min 17 MWh 46 rpm 18 kvarh 47 mm/min 19 Mvarh 48 m/min 20 kVAh 49 l/min 21 MVAh 50 m
3
/min 22 Hz 51 szt/h 23 kHz 52 m/h 24
W
53 km/h
25
kW
54 m
3
/h
26
o
C 55 kg/h
27
o
F 56 l/h
28 K XX On order
1)
1)
- after agreeing with the Manufacturer
48
10. MAINTENANCE AND GUARANTEE
The N30H digital panel meter does not require any periodical maintenance.
In case of some incorrect operations:
1. From the Shipping Date, During the Period Given in the
Annexed Guarantee Card:
One should take the meter down from the installation and return it to the Manufacturer’s Quality Control Dept. If the meter has been used in compliance with the instructions, the Manufacturer warrants to repair it free of charge.
2. After the Guarantee Period: One should turn over the meter to repair it in a certified
service workshop.The disassembling of the casing causes the cancellation of the granted guarantee. Spare parts are available for the period of five years from the date of purchase.
Our policy is one of continuous improvement and we reserve the right to make changes in design and speci­fications of any products as engineering advances or necessity requires and revise the above specifications without notice.
49
50
N30H-09A
Manufactured by:
Sifam Tinsley Instrumentation Inc 3105 Creekside Village Dr, Unit 801, Kennesaw GA 30144
Distributed by:
Veracious Canada Inc 1101 Britannia Rd E, Mississauga, ON L4W 3X1
E-mail: info@veraciousinc.ca
Contact: +1 416-640-5364 Fax:
+1 416-981-3933
www.veraciousinc.comWeb:
Loading...