64 Kbit EEPROM tag IC at 13.56 MHz with 64-bit UID and
password based on ISO/IEC 15693 and ISO/IEC 18000-3 Mode 1
Features
■ Based on ISO/IEC 15693 and
ISO/IEC 18000-3 mode 1 standards
■ 13.56 MHz ±7 kHz carrier frequency
■ To tag: 10% or 100% ASK modulation using
1/4 (26 Kbit/s) or 1/256 (1.6 Kbit/s) pulse
position coding
■ From tag: load modulation using Manchester
coding with 423 kHz and 484 kHz subcarriers
in low (6.6 Kbit/s) or high (26 Kbit/s) data rate
mode. Supports the 53 Kbit/s data rate with
Fast commands
■ Internal tuning capacitor (27.5 pF)
■ More than 1 million write cycles
■ More than 40-year data retention
■ 64 Kbit EEPROM organized into 2048 blocks of
32 bits
■ 64-bit unique identifier (UID)
■ Multipassword protection
■ Read Block & Write (32-bit blocks)
■ Write time: 5.75 ms including the internal verify
The LRIS64K is a contactless memory powered by the received carrier electromagnetic
wave, which follows the ISO/IEC 15693 and ISO/IEC 18000-3 mode 1 recommendation for
radio-frequency power and signal interface. It is a 64 Kbit electrically erasable
programmable memory (EEPROM). The memory is organized as 64 sectors divided into 32
blocks of 32 bits.
The LRIS64K is accessed via the 13.56 MHz carrier electromagnetic wave, on which
incoming data are demodulated from the received signal amplitude modulation (ASK:
amplitude shift keying). The received ASK wave is 10% or 100% modulated with a data rate
of 1.6 Kbit/s using the 1/256 pulse coding mode, or a data rate of 26 Kbit/s using the 1/4
pulse coding mode. Outgoing data are generated by the LRIS64K load variation using
Manchester coding with one or two subcarrier frequencies at 423 kHz and 484 kHz. Data
are transferred from the LRIS64K at 6.6 Kbit/s in low data rate mode and 26 Kbit/s in high
data rate mode. The LRIS64K supports the 53 Kbit/s data rate in high data rate mode with a
single subcarrier frequency of 423 kHz.
The LRIS64K also features a unique 32-bit multi-password protection scheme.
The LRIS64K is divided into 64 sectors of 32 blocks of 32 bits as shown in Tab l e 2 . Figure 2
shows the memory sector organization. Each sector can be individually read- and/or writeprotected using a specific password command. Read and write operations are possible if
the addressed data are not in a protected sector.
The LRIS64K also has a 64-bit block that is used to store the 64-bit unique identifier (UID).
The UID is compliant with the ISO/IEC 15963 description, and its value is used during the
anticollision sequence (Inventory). This block is not accessible by the user and its value is
written by ST on the production line.
The LRIS64K includes an AFI register that stores the application family identifier, and a
DSFID register that stores the data storage family identifier used in the anticollision
algorithm.
The LRIS64K has three additional 32-bit blocks that store the RF password codes.
Figure 2.Memory sector organization
Sector details
The LRIS64K user memory is divided into 64 sectors. Each sector contains 1024 bits. The
protection scheme is described in Section 3: System memory area.
A sector provides 32 blocks of 32 bits. Each read and write access are done by block. Read
and write block accesses are controlled by a Sector Security Status byte that defines the
access rights to all the 32 blocks contained in the sector. If the sector is not protected, a
Write command updates the complete 32 bits of the selected block.
Doc ID 15336 Rev 1111/100
User memory organizationLRIS64K
Table 2.Sector details
Sector
number
0
RF block
address
Bits [31:24]Bits [23:16]Bits [15:8]Bits [7:0]
0useruseruseruser
1useruseruseruser
2useruseruseruser
3useruseruseruser
4useruseruseruser
5useruseruseruser
6useruseruseruser
7useruseruseruser
8useruseruseruser
9useruseruseruser
10useruseruseruser
11useruseruseruser
12useruseruseruser
13useruseruseruser
14useruseruseruser
15useruseruseruser
16useruseruseruser
17useruseruseruser
18useruseruseruser
19useruseruseruser
20useruseruseruser
21useruseruseruser
22useruseruseruser
23useruseruseruser
24useruseruseruser
25useruseruseruser
26useruseruseruser
27useruseruseruser
28useruseruseruser
29useruseruseruser
30useruseruseruser
31useruseruseruser
12/100Doc ID 15336 Rev 11
LRIS64KUser memory organization
Table 2.Sector details (continued)
Sector
number
1
..................
RF block
address
32useruseruseruser
33useruseruseruser
34useruseruseruser
35useruseruseruser
36useruseruseruser
37useruseruseruser
38useruseruseruser
39useruseruseruser
...............
2016useruseruseruser
2017useruseruseruser
2018useruseruseruser
2019useruseruseruser
2020useruseruseruser
2021useruseruseruser
2022useruseruseruser
Bits [31:24]Bits [23:16]Bits [15:8]Bits [7:0]
63
2023useruseruseruser
2024useruseruseruser
2025useruseruseruser
2026useruseruseruser
2027useruseruseruser
2028useruseruseruser
2029useruseruseruser
2030useruseruseruser
2031useruseruseruser
2032useruseruseruser
2033useruseruseruser
2034useruseruseruser
2035useruseruseruser
2036useruseruseruser
2037useruseruseruser
2038useruseruseruser
2039useruseruseruser
Doc ID 15336 Rev 1113/100
User memory organizationLRIS64K
Table 2.Sector details (continued)
Sector
number
63 continued
RF block
address
2040useruseruseruser
2041useruseruseruser
2042useruseruseruser
2043useruseruseruser
2044useruseruseruser
2045useruseruseruser
2046useruseruseruser
2047useruseruseruser
Bits [31:24]Bits [23:16]Bits [15:8]Bits [7:0]
14/100Doc ID 15336 Rev 11
LRIS64KSystem memory area
3 System memory area
3.1 LRIS64K RF block security
The LRIS64K provides a special protection mechanism based on passwords. Each memory
sector of the LRIS64K can be individually protected by one out of three available passwords,
and each sector can also have Read/Write access conditions set.
Each memory sector of the LRIS64K is assigned with a Sector security status byte including
a Sector Lock bit, two Password Control bits and two Read/Write protection bits as shown in
Ta bl e 4 . Ta b le 3 describes the organization of the Sector security status byte which can be
read using the Read Single Block and Read Multiple Block commands with the Option_flag
set to ‘1’.
On delivery, the default value of the SSS bytes is reset to 00h.
When the Sector Lock bit is set to ‘1’, for instance by issuing a Lock-sector Password
command, the 2 Read/Write protection bits (b
, b2) are used to set the Read/Write access of
1
the sector as described in Ta b l e 5 .
Table 5.Read / Write protection bit setting
Sector
Lock
, b
b
2
Sector access when password
1
presented
Sector access when password not
presented
0xxReadWriteReadWrite
100ReadWriteReadNo Write
101ReadWriteReadWrite
110ReadWriteNo ReadNo Write
111ReadNo WriteNo ReadNo Write
The next 2 bits of the Sector security status byte (b3, b4) are the Password Control bits. The
value these two bits is used to link a password to the sector as defined in Ta b le 6 .
Table 6.Password Control bits
b4, b
3
Password
00The sector is not protected by a Password
01The sector is protected by the Password 1
10The sector is protected by the Password 2
11The sector is protected by the Password 3
The LRIS64K password protection is organized around a dedicated set of commands plus a
system area of three password blocks where the password values are stored. This system
area is described in Ta b le 7 .
Table 7.Password system area
Add07 815 16232431
1Password 1
2Password 2
3Password 3
The dedicated password commands are:
●Write-sector Password
The Write-sector Password command is used to write a 32-bit block into the password
system area. This command must be used to update password values. After the write
cycle, the new password value is automatically activated. It is possible to modify a
password value after issuing a valid Present-sector Password command.
On delivery, the three default password values are set to 0000 0000h and are activated.
●Lock-sector Password
The Lock-sector Password command is used to set the Sector security status byte of
the selected sector. Bits b
16/100Doc ID 15336 Rev 11
to b1 of the Sector security status byte are affected by the
4
LRIS64KSystem memory area
Lock-sector Password command. The Sector Lock bit, b0, is set to ‘1’ automatically.
After issuing a Lock-sector Password command, the protection settings of the selected
sector are activated. The protection of a locked block cannot be changed. A Locksector Password command sent to a locked sector returns an error code.
●Present-sector Password
The Present-sector Password command is used to present one of the three passwords
to the LRIS64K in order to modify the access rights of all the memory sectors linked to
that password (Tab l e 5 ) including the password itself. If the presented password is
correct, the access rights remain activated until the tag is powered off or until a new
Present-sector Password command is issued. If the presented password value is not
correct, all the access rights of all the memory sectors are deactivated.
3.2 Example of the LRIS64K security protection
Ta bl e 8 and Ta ble 9 show the sector security protections before and after a valid Present-
sector Password command. Ta bl e 8 shows the sector access rights of an LRIS64K after
power-up. After a valid Present-sector Password command with password 1, the memory
sector access is changed as shown in Ta b le 9 .
Table 8.Sector security protection after power-up
Sector
address
0 Protection: Standard ReadNo Writexxx 00001
1 Protection: Pswd 1ReadNo Writexxx 01001
2 Protection: Pswd 1ReadWritexxx 01011
3 Protection: Pswd 1No ReadNo Writexxx 01101
4 Protection: Pswd 1No ReadNo Writexxx 01111
Table 9.Sector security protection after a valid presentation of password 1
Sector
address
0Protection: StandardReadNo Writexxx00001
1Protection: Pswd 1ReadWritexxx01001
2Protection: Pswd 1ReadWritexxx01011
3Protection: Pswd 1ReadWritexxx01101
4Protection: Pswd 1ReadNo Writexxx01111
Sector security status byte
b
7b6b5b4b3b2b1b0
Sector security status byte
b
7b6b5b4b3b2b1b0
Doc ID 15336 Rev 1117/100
Initial delivery stateLRIS64K
4 Initial delivery state
The device is delivered with the following factory settings:
●All bits in the memory array are set to 1 (each byte contains FFh).
●The default value of the SSS bytes is reset to 00h.
●The three default password values are set to 0000 0000h and are activated.
System parameters are set to:
●(E0 02 xx xx xx xx xx xx )h for UID
●(03 07 FF)h for Memory Size
●00h for AFI
●00h for DSFID
18/100Doc ID 15336 Rev 11
LRIS64KCommands
5 Commands
The LRIS64K supports the following commands:
●Inventory, used to perform the anticollision sequence.
●Stay Quiet, used to put the LRIS64K in quiet mode, where it does not respond to any
inventory command.
●Select, used to select the LRIS64K. After this command, the LRIS64K processes all
Read/Write commands with Select_flag set.
●Reset To Ready, used to put the LRIS64K in the ready state.
●Read Block, used to output the 32 bits of the selected block and its locking status.
●Write Block, used to write the 32-bit value in the selected block, provided that it is not
locked.
●Read Multiple Blocks, used to read the selected blocks and send back their value.
●Write AFI, used to write the 8-bit value in the AFI register.
●Lock AFI, used to lock the AFI register.
●Write DSFID, used to write the 8-bit value in the DSFID register.
●Lock DSFID, used to lock the DSFID register.
●Get System Info, used to provide the system information value
●Get Multiple Block Security Status, used to send the security status of the selected
block.
●Initiate, used to trigger the tag response to the Inventory Initiated sequence.
●Inventory Initiated, used to perform the anticollision sequence triggered by the Initiate
command.
●Write-sector Password, used to write the 32 bits of the selected password.
●Lock-sector Password, used to write the Sector security status bits of the selected
sector.
●Present-sector Password, enables the user to present a password to unprotect the
user blocks linked to this password.
●Fast Initiate, used to trigger the tag response to the Inventory Initiated sequence.
●Fast Inventory Initiated, used to perform the anticollision sequence triggered by the
Initiate command.
●Fast Read Single Block, used to output the 32 bits of the selected block and its
locking status.
●Fast Read Multiple Blocks, used to read the selected blocks and send back their
value.
Doc ID 15336 Rev 1119/100
CommandsLRIS64K
5.1 Initial dialogue for vicinity cards
The dialog between the vicinity coupling device (VCD) and the vicinity integrated circuit
Card or VICC (LRIS64K) takes place as follows:
●activation of the LRIS64K by the RF operating field of the VCD.
●transmission of a command by the VCD.
●transmission of a response by the LRIS64K.
These operations use the RF power transfer and communication signal interface described
below (see Power transfer, Frequency and Operating field). This technique is called RTF
(Reader Talk First).
5.1.1 Power transfer
Power is transferred to the LRIS64K by radio frequency at 13.56 MHz via coupling antennas
in the LRIS64K and the VCD. The RF operating field of the VCD is transformed on the
LRIS64K antenna to an AC Voltage which is rectified, filtered and internally regulated. The
amplitude modulation (ASK) on this received signal is demodulated by the ASK
demodulator.
5.1.2 Frequency
The ISO/IEC 15693 standard defines the carrier frequency (fC) of the operating field as
13.56 MHz ±7 kHz.
5.1.3 Operating field
The LRIS64K operates continuously between H
●The minimum operating field is H
●The maximum operating field is H
A VCD shall generate a field of at least H
volume.
and H
min
and has a value of 150 mA/m rms.
min
and has a value of 5 A/m rms.
max
and not exceeding H
min
max
.
max
in the operating
20/100Doc ID 15336 Rev 11
LRIS64KCommunication signal from VCD to LRIS64K
105%
a
95%
5%
60%
Carrier
Amplitude
t
t
2
t
1
t
3
t
4
Min (µs)
t1
6,0
t22,1
t3
0
Max (µs)
9,44
t1
4,5
t4
00,8
b
The clock recovery shall be operational after t
4
max.
ai15793
6 Communication signal from VCD to LRIS64K
Communications between the VCD and the LRIS64K takes place using the modulation
principle of ASK (Amplitude Shift Keying). Two modulation indexes are used, 10% and
100%. The LRIS64K decodes both. The VCD determines which index is used.
The modulation index is defined as [a – b]/[a + b] where a is the peak signal amplitude and
b, the minimum signal amplitude of the carrier frequency.
Depending on the choice made by the VCD, a “pause” will be created as described in
Figure 3 and Figure 4.
The LRIS64K is operational for any degree of modulation index from between 10% and
30%.
Figure 3.100% modulation waveform
Table 10.10% modulation parameters
SymbolParameter definitionValue
hr0.1 x (a – b)Max
hf0.1 x (a – b)Max
Doc ID 15336 Rev 1121/100
Communication signal from VCD to LRIS64KLRIS64K
Figure 4.10% modulation waveform
Carrier
Carrier
Amplitude
Amplitude
a
a
b
b
t1
t1
t1
t23,0 µs
t23,0 µs
t23,0 µst30
t30
t30
Modulation
Modulation
Modulation
Index
Index
Index
The VICC shall be operational for any value of modulation index between 10 % and 30 %.
The data coding implemented in the LRIS64K uses pulse position modulation. Both data
coding modes that are described in the ISO/IEC15693 are supported by the LRIS64K. The
selection is made by the VCD and indicated to the LRIS64K within the start of frame (SOF).
7.1 Data coding mode: 1 out of 256
The value of one single byte is represented by the position of one pause. The position of the
pause on 1 of 256 successive time periods of 18.88 µs (256/f
byte. In this case the transmission of one byte takes 4.833 ms and the resulting data rate is
1.65 kbits/s (f
/8192).
C
Figure 5 illustrates this pulse position modulation technique. In this figure, data E1h (225
decimal) is sent by the VCD to the LRIS64K.
The pause occurs during the second half of the position of the time period that determines
the value, as shown in Figure 6.
A pause during the first period transmits the data value 00h. A pause during the last period
transmit the data value FFh (255 decimal).
), determines the value of the
C
Figure 5.1 out of 256 coding mode
Doc ID 15336 Rev 1123/100
Data rate and data codingLRIS64K
AI06657
2
2
5
18.88 µs
9.44 µs
Pulse
Modulated
Carrier
2
2
6
2
2
4
. . . . . . .. . . . . . .
Time Period
one of 256
Figure 6.Detail of a time period
7.2 Data coding mode: 1 out of 4
The value of 2 bits is represented by the position of one pause. The position of the pause on
1 of 4 successive time periods of 18.88 µs (256/f
successive pairs of bits form a byte, where the least significant pair of bits is transmitted first.
In this case the transmission of one byte takes 302.08 µs and the resulting data rate is 26.48
Kbits/s (f
Figure 8 shows the transmission of E1h (225d - 1110 0001b) by the VCD.
/512). Figure 7 illustrates the 1 out of 4 pulse position technique and coding.
C
), determines the value of the 2 bits. Four
C
24/100Doc ID 15336 Rev 11
LRIS64KData rate and data coding
AI06658
9.44 µs9.44 µs
75.52 µs
28.32 µs9.44 µs
75.52 µs
47.20µs9.44 µs
75.52 µs
66.08 µs9.44 µs
75.52 µs
Pulse position for "00"
Pulse position for "11"
Pulse position for "10" (0=LSB)
Pulse position for "01" (1=LSB)
AI06659
75.52µs75.52µs75.52µs75.52µs
00
10
0111
Figure 7.1 out of 4 coding mode
Figure 8.1 out of 4 coding example
Doc ID 15336 Rev 1125/100
Data rate and data codingLRIS64K
AI06661
37.76µs
9.44µs
9.44µs
37.76µs
AI06660
37.76µs
9.44µs
9.44µs
37.76µs
9.44µs
AI06662
9.44µs
37.76µs
9.44µs
7.3 VCD to LRIS64K frames
Frames are delimited by a start of frame (SOF) and an end of frame (EOF). They are
implemented using code violation. Unused options are reserved for future use.
The LRIS64K is ready to receive a new command frame from the VCD 311.5 µs (t
sending a response frame to the VCD.
The LRIS64K takes a power-up time of 0.1 ms after being activated by the powering field.
After this delay, the LRIS64K is ready to receive a command frame from the VCD.
7.4 Start of frame (SOF)
The SOF defines the data coding mode the VCD is to use for the following command frame.
The SOF sequence described in Figure 9 selects the 1 out of 256 data coding mode. The
SOF sequence described in Figure 10 selects the 1 out of 4 data coding mode. The EOF
sequence for either coding mode is described in Figure 11.
Figure 9.SOF to select 1 out of 256 data coding mode
) after
2
Figure 10. SOF to select 1 out of 4 data coding mode
Figure 11. EOF for either data coding mode
26/100Doc ID 15336 Rev 11
LRIS64KCommunications signal from LRIS64K to VCD
8 Communications signal from LRIS64K to VCD
The LRIS64K has several modes defined for some parameters, owing to which it can
operate in different noise environments and meet different application requirements.
8.1 Load modulation
The LRIS64K is capable of communication to the VCD via an inductive coupling area
whereby the carrier is loaded to generate a subcarrier with frequency f
generated by switching a load in the LRIS64K.
The load-modulated amplitude received on the VCD antenna must be of at least 10mV
when measured as described in the test methods defined in International Standard
ISO/IEC10373-7.
8.2 Subcarrier
The LRIS64K supports the one-subcarrier and two-subcarrier response formats. These
formats are selected by the VCD using the first bit in the protocol header. When one
subcarrier is used, the frequency f
When two subcarriers are used, the frequency f
is 484.28 kHz (f
continuous phase relationship between f
of the subcarrier load modulation is 423.75 kHz (fC/32).
S1
/28). When using the two-subcarrier mode, the LRIS64K generates a
C
and fS2.
S1
is 423.75 kHz (fC/32), and frequency fS2
S1
. The subcarrier is
S
8.3 Data rates
The LRIS64K can respond using the low or the high data rate format. The selection of the
data rate is made by the VCD using the second bit in the protocol header. It also supports
the x2 mode available on all the Fast commands. Ta bl e 1 1 shows the different data rates
produced by the LRIS64K using the different response format combinations.
Table 11.Response data rates
Data rateOne subcarrierTwo subcarriers
Standard commands6.62 Kbit/s (f
Low
Fast commands13.24 Kbit/s (f
Standard commands26.48 Kbit/s (f
High
Fast commands52.97 Kbit/s (f
/2048)6.67 Kbit/s (fc/2032)
c
/1024)not applicable
c
/512)26.69 Kbit/s (fc/508)
c
/256)not applicable
c
Doc ID 15336 Rev 1127/100
Bit representation and codingLRIS64K
37.76µs
ai12076
18.88µs
ai12066
37.76µs
ai12077
18.88µs
ai12067
9 Bit representation and coding
Data bits are encoded using Manchester coding, according to the following schemes. For
the low data rate, same subcarrier frequency or frequencies is/are used, in this case the
number of pulses is multiplied by 4 and all times will increase by this factor. For the Fast
commands using one subcarrier, all pulse numbers and times are divided by 2.
9.1 Bit coding using one subcarrier
9.1.1 High data rate
A logic 0 starts with 8 pulses at 423.75 kHz (fC/32) followed by an unmodulated time of
18.88 µs as shown in Figure 12.
Figure 12. Logic 0, high data rate, one subcarriers
For the fast commands, a logic 0 starts with 4 pulses at 423.75 kHz (f
/32) followed by an
C
unmodulated time of 9.44 µs as shown in Figure 13.
Figure 13. Logic 0, high data rate, one subcarriers x2
A logic 1 starts with an unmodulated time of 18.88 µs followed by 8 pulses at 423.75 kHz
(f
/32) as shown in Figure 14.
C
Figure 14. Logic 1, high data rate, one subcarriers
For the Fast commands, a logic 1 starts with an unmodulated time of 9.44 µs followed by 4
pulses of 423.75 kHz (f
/32) as shown in Figure 15.
C
Figure 15. Logic 1, high data rate, one subcarriers x2
28/100Doc ID 15336 Rev 11
LRIS64KBit representation and coding
151.04µs
ai12068
75.52µs
ai12069
151.04µs
ai12070
75.52µs
ai12071
9.1.2 Low data rate
A logic 0 starts with 32 pulses at 423.75 kHz (fC/32) followed by an unmodulated time of
75.52 µs as shown in Figure 16.
Figure 16. Logic 0, low data rate, one subcarriers
For the Fast commands, a logic 0 starts with 16 pulses at 423.75 kHz (f
/32) followed by an
C
unmodulated time of 37.76 µs as shown in Figure 17.
Figure 17. Logic 0, low data rate, one subcarriers x2
A logic 1 starts with an unmodulated time of 75.52 µs followed by 32 pulses at 423.75 kHz
(f
/32) as shown in Figure 18.
C
Figure 18. Logic 1, low data rate, one subcarriers
For the Fast commands, a logic 1 starts with an unmodulated time of 37.76 µs followed by
16 pulses at 423.75 kHz (f
/32) as shown in Figure 18.
C
Figure 19. Logic 1, low data rate, one subcarriers x2
Doc ID 15336 Rev 1129/100
Bit representation and codingLRIS64K
37.46µs
ai12074
37.46µs
ai12073
149.84µs
ai12072
149.84µs
ai12075
9.2 Bit coding using two subcarriers
9.3 High data rate
A logic 0 starts with 8 pulses at 423.75 kHz (fC/32) followed by 9 pulses at 484.28 kHz
(f
/28) as shown in Figure 20. For the Fast commands, the x2 mode is not available.
C
Figure 20. Logic 0, high data rate, two subcarriers
A logic 1 starts with 9 pulses at 484.28 kHz (f
(f
/32) as shown in Figure 21. For the Fast commands, the x2 mode is not available.
C
Figure 21. Logic 1, high data rate, two subcarriers
9.4 Low data rate
A logic 0 starts with 32 pulses at 423.75 kHz (fC/32) followed by 36 pulses at 484.28 kHz
(f
/28) as shown in Figure 22. For the Fast commands, the x2 mode is not available.
C
Figure 22. Logic 0, low data rate, two subcarriers
A logic 1 starts with 36 pulses at 484.28 kHz (f
(f
/32) as shown in Figure 23. For the Fast commands, the x2 mode is not available.
C
/28) followed by 8 pulses at 423.75 kHz
C
/28) followed by 32 pulses at 423.75 kHz
C
Figure 23. Logic 1, low data rate, two subcarriers
30/100Doc ID 15336 Rev 11
LRIS64KLRIS64K to VCD frames
113.28µs
ai12078
37.76µs
56.64µs
ai12079
18.88µs
453.12µs
ai12080
151.04µs
10 LRIS64K to VCD frames
Frames are delimited by an SOF and an EOF. They are implemented using code violation.
Unused options are reserved for future use. For the low data rate, the same subcarrier
frequency or frequencies is/are used. In this case the number of pulses is multiplied by 4.
For the Fast commands using one subcarrier, all pulse numbers and times are divided by 2.
10.1 SOF when using one subcarrier
10.2 High data rate
The SOF includes an unmodulated time of 56.64 µs, followed by 24 pulses at 423.75 kHz
(f
/32), and a logic 1 that consists of an unmodulated time of 18.88 µs followed by 8 pulses
C
at 423.75 kHz as shown in Figure 24.
Figure 24. Start of frame, high data rate, one subcarrier
For the Fast commands, the SOF comprises an unmodulated time of 28.32 µs, followed by
12 pulses at 423.75 kHz (f
9.44µs followed by 4 pulses at 423.75 kHz as shown in Figure 25.
Figure 25. Start of frame, high data rate, one subcarrier x2
10.3 Low data rate
The SOF comprises an unmodulated time of 226.56 µs, followed by 96 pulses at 423.75 kHz
(f
/32), and a logic 1 that consists of an unmodulated time of 75.52 µs followed by 32 pulses
C
at 423.75 kHz as shown in Figure 26.
Figure 26. Start of frame, low data rate, one subcarrier
/32), and a logic 1 that consists of an unmodulated time of
C
Doc ID 15336 Rev 1131/100
LRIS64K to VCD framesLRIS64K
226.56µs
ai12081
75.52µs
112.39µs
ai12082
37.46µs
449.56µs
ai12083
149.84µs
For the Fast commands, the SOF comprises an unmodulated time of 113.28 µs, followed by
48 pulses at 423.75 kHz (f
/32), and a logic 1 that includes an unmodulated time of 37.76 µs
C
followed by 16 pulses at 423.75 kHz as shown in Figure 27.
Figure 27. Start of frame, low data rate, one subcarrier x2
10.4 SOF when using two subcarriers
10.5 High data rate
The SOF comprises 27 pulses at 484.28 kHz (fC/28), followed by 24 pulses at 423.75 kHz
(f
/32), and a logic 1 that includes 9 pulses at 484.28 kHz followed by 8 pulses at
C
423.75 kHz as shown in Figure 28.
For the Fast commands, the x2 mode is not available.
Figure 28. Start of frame, high data rate, two subcarriers
10.6 Low data rate
The SOF comprises 108 pulses at 484.28 kHz (fC/28), followed by 96 pulses at 423.75 kHz
(f
/32), and a logic 1 that includes 36 pulses at 484.28 kHz followed by 32 pulses at
C
423.75 kHz as shown in Figure 29.
For the Fast commands, the x2 mode is not available.
Figure 29. Start of frame, low data rate, two subcarriers
32/100Doc ID 15336 Rev 11
LRIS64KLRIS64K to VCD frames
113.28µs
ai12084
37.76µs
56.64µs
ai12085
18.88µs
453.12µs
ai12086
151.04µs
226.56µs
ai12087
75.52µs
10.7 EOF when using one subcarrier
10.8 High data rate
The EOF comprises a logic 0 that includes 8 pulses at 423.75 kHz and an unmodulated time
of 18.88 µs, followed by 24 pulses at 423.75 kHz (f
56.64 µs as shown in Figure 30.
Figure 30. End of frame, high data rate, one subcarriers
For the Fast commands, the EOF comprises a logic 0 that includes 4 pulses at 423.75 kHz
and an unmodulated time of 9.44 µs, followed by 12 pulses at 423.75 kHz (f
unmodulated time of 37.76 µs as shown in Figure 31.
Figure 31. End of frame, high data rate, one subcarriers x2
/32), and by an unmodulated time of
C
/32) and an
C
10.9 Low data rate
The EOF comprises a logic 0 that includes 32 pulses at 423.75 kHz and an unmodulated
time of 75.52 µs, followed by 96 pulses at 423.75 kHz (f
226.56 µs as shown in Figure 32.
Figure 32. End of frame, low data rate, one subcarriers
For the Fast commands, the EOF comprises a logic 0 that includes 16 pulses at 423.75 kHz
and an unmodulated time of 37.76 µs, followed by 48 pulses at 423.75 kHz (f
unmodulated time of 113.28 µs as shown in Figure 33.
Figure 33. End of frame, low data rate, one subcarriers x2
/32) and an unmodulated time of
C
/32) and an
C
Doc ID 15336 Rev 1133/100
LRIS64K to VCD framesLRIS64K
112.39µs
ai12088
37.46µs
449.56µs
ai12089
149.84µs
10.10 EOF when using two subcarriers
10.11 High data rate
The EOF comprises a logic 0 that includes 8 pulses at 423.75 kHz and 9 pulses at
484.28 kHz, followed by 24 pulses at 423.75 kHz (f
(f
/28) as shown in Figure 34.
C
/32) and 27 pulses at 484.28 kHz
C
For the Fast commands, the x2 mode is not available.
Figure 34. End of frame, high data rate, two subcarriers
10.12 Low data rate
The EOF comprises a logic 0 that includes 32 pulses at 423.75 kHz and 36 pulses at
484.28 kHz, followed by 96 pulses at 423.75 kHz (f
(f
/28) as shown in Figure 35.
C
For the Fast commands, the x2 mode is not available.
/32) and 108 pulses at 484.28 kHz
C
Figure 35. End of frame, low data rate, two subcarriers
34/100Doc ID 15336 Rev 11
LRIS64KUnique identifier (UID)
11 Unique identifier (UID)
The LRIS64K is uniquely identified by a 64-bit Unique Identifier (UID). This UID complies
with ISO/IEC 15963 and ISO/IEC 7816-6. The UID is a read-only code and comprises:
●8 MSBs with a value of E0h
●The IC Manufacturer code of ST 02h, on 8 bits (ISO/IEC 7816-6/AM1)
●a Unique Serial Number on 48 bits
Table 12.UID format
MSBLSB
6356 5548 470
0xE00x02Unique serial number
With the UID each LRIS64K can be addressed uniquely and individually during the
anticollision loop and for one-to-one exchanges between a VCD and an LRIS64K.
Doc ID 15336 Rev 1135/100
Application family identifier (AFI)LRIS64K
!)
)NVENTORYREQUEST
RECEIVED
.O
.OANSWER
9E S
.O
!&)VALUE
9E S
.O
!&)FLAG
SET
9E S
!NSWERGIVENBYTHE,2)3+
TOTHE)NVENTORYREQUEST
!&)VALUE
)NTERNAL
VALUE
12 Application family identifier (AFI)
The AFI (application family identifier) represents the type of application targeted by the VCD
and is used to identify, among all the LRIS64Ks present, only the LRIS64Ks that meet the
required application criteria.
Figure 36. LRIS64K decision tree for AFI
The AFI is programmed by the LRIS64K issuer (or purchaser) in the AFI register. Once
programmed and Locked, it can no longer be modified.
The most significant nibble of the AFI is used to code one specific or all application families.
The least significant nibble of the AFI is used to code one specific or all application
subfamilies. Subfamily codes different from 0 are proprietary.
(See ISO/IEC 15693-3 documentation)
36/100Doc ID 15336 Rev 11
LRIS64KData storage format identifier (DSFID)
13 Data storage format identifier (DSFID)
The data storage format identifier indicates how the data is structured in the LRIS64K
memory. The logical organization of data can be known instantly using the DSFID. It can be
programmed and locked using the Write DSFID and Lock DSFID commands.
13.1 CRC
The CRC used in the LRIS64K is calculated as per the definition in ISO/IEC 13239. The
initial register contents are all ones: “FFFF”.
The two-byte CRC are appended to each request and response, within each frame, before
the EOF. The CRC is calculated on all the bytes after the SOF up to the CRC field.
Upon reception of a request from the VCD, the LRIS64K verifies that the CRC value is valid.
If it is invalid, the LRIS64K discards the frame and does not answer to the VCD.
Upon reception of a Response from the LRIS64K, it is recommended that the VCD verifies
whether the CRC value is valid. If it is invalid, actions to be performed are left to the
discretion of the VCD designer.
The CRC is transmitted least significant byte first. Each byte is transmitted least significant
bit first.
Table 13.CRC transmission rules
LSByte
LSBit MSBit
LSBit MSBit
MSByte
CRC 16 (8 bits)CRC 16 (8 bits)
Doc ID 15336 Rev 1137/100
LRIS64K protocol descriptionLRIS64K
14 LRIS64K protocol description
The transmission protocol (or simply protocol) defines the mechanism used to exchange
instructions and data between the VCD and the LRIS64K, in both directions. It is based on
the concept of “VCD talks first”.
This means that an LRIS64K will not start transmitting unless it has received and properly
decoded an instruction sent by the VCD. The protocol is based on an exchange of:
●a request from the VCD to the LRIS64K
●a response from the LRIS64K to the VCD
Each request and each response are contained in a frame. The frame delimiters (SOF,
EOF) are described in Section 10: LRIS64K to VCD frames.
Each request consists of:
●a request SOF (see Figure 9 and Figure 10)
●flags
●a command code
●parameters, depending on the command
●application data
●a 2-byte CRC
●a request EOF (see Figure 11)
Each response consists of:
●an answer SOF (see Figure 24 to Figure 29)
●flags
●parameters, depending on the command
●application data
●a 2-byte CRC
●an answer EOF (see Figure 30 to Figure 35)
The protocol is bit-oriented. The number of bits transmitted in a frame is a multiple of eight
(8), that is an integer number of bytes.
A single-byte field is transmitted least significant bit (LSBit) first. A multiple-byte field is
transmitted least significant byte (LSByte) first, each byte is transmitted least significant bit
(LSBit) first.
The setting of the flags indicates the presence of the optional fields. When the flag is set (to
one), the field is present. When the flag is reset (to zero), the field is absent.
Table 14.VCD request frame format
Request SOF Request_flags
Table 15.LRIS64KResponse frame format
Response
SOF
Response_flags ParametersData2-byte CRC
Command
code
ParametersData2-byte CRC
Request
EOF
Response
EOF
38/100Doc ID 15336 Rev 11
LRIS64KLRIS64K protocol description
Figure 37. LRIS64K protocol timing
Request
VCD
frame
(Ta ble 1 4 )
LRIS64K
Timing<-t
Request
frame
(Ta ble 1 4 )
Response
frame
(Ta ble 1 5 )
-><-t2-><-t1-><-t2->
1
Response
frame
(Ta ble 1 5 )
Doc ID 15336 Rev 1139/100
LRIS64K statesLRIS64K
15 LRIS64K states
An LRIS64K can be in one of 4 states:
●Power-off
●Ready
●Quiet
●Selected
Transitions between these states are specified in Figure 38: LRIS64K state transition
diagram and Table 16: LRIS64K response depending on Request_flags.
15.1 Power-off state
The LRIS64K is in the Power-off state when it does not receive enough energy from the
VCD.
15.2 Ready state
The LRIS64K is in the Ready state when it receives enough energy from the VCD. When in
the Ready state, the LRIS64K answers any request where the Select_flag is not set.
15.3 Quiet state
When in the Quiet state, the LRIS64K answers any request except for Inventory requests
with the Address_flag set.
15.4 Selected state
In the Selected state, the LRIS64K answers any request in all modes (see Section 16:
Modes):
●Request in Select mode with the Select_flag set
●Request in Addressed mode if the UID matches
●Request in Non-Addressed mode as it is the mode for general requests
40/100Doc ID 15336 Rev 11
LRIS64KLRIS64K states
AI06681
Power Off
In field
Out of field
Ready
Quiet
Selected
Any other Command
where Select_Flag
is not set
Out of field
Out of field
Stay quiet(UID)
Select (UID)
Any other command
Any other command where the
Address_Flag is set AND
where Inventory_Flag is not set
Stay quiet(UID)
Select (UID)
Reset to ready where
Select_Flag is set or
Select(different UID)
Reset to ready
Table 16.LRIS64K response depending on Request_flags
Address_flagSelect_flag
Flags
1
Addressed0Non addressed
1
Selected0Non selected
LRIS64K in Ready or Selected
state (Devices in Quiet state do not
XX
answer)
LRIS64K in Selected stateXX
LRIS64K in Ready, Quiet or
Selected state (the device which
XX
matches the UID)
Error (03h)XX
Figure 38. LRIS64K state transition diagram
1. The intention of the state transition method is that only one LRIS64K should be in the selected state at a
time.
Doc ID 15336 Rev 1141/100
ModesLRIS64K
16 Modes
The term “mode” refers to the mechanism used in a request to specify the set of LRIS64Ks
that will answer the request.
16.1 Addressed mode
When the Address_flag is set to 1 (Addressed mode), the request contains the Unique ID
(UID) of the addressed LRIS64K.
Any LRIS64K that receives a request with the Address_flag set to 1 compares the received
Unique ID to its own. If it matches, then the LRIS64K executes the request (if possible) and
returns a response to the VCD as specified in the command description.
If the UID does not match, then it remains silent.
16.2 Non-addressed mode (general request)
When the Address_flag is cleared to 0 (Non-Addressed mode), the request does not contain
a Unique ID. Any LRIS64K receiving a request with the Address_flag cleared to 0 executes
it and returns a response to the VCD as specified in the command description.
16.3 Select mode
When the Select_flag is set to 1 (Select mode), the request does not contain an LRIS64K
Unique ID. The LRIS64K in the Selected state that receives a request with the Select_flag
set to 1 executes it and returns a response to the VCD as specified in the command
description.
Only LRIS64Ks in the Selected state answer a request where the Select_flag set to 1.
The system design ensures in theory that only one LRIS64K can be in the Select state at a
time.
42/100Doc ID 15336 Rev 11
LRIS64KRequest format
17 Request format
The request consists of:
●an SOF
●flags
●a command code
●parameters and data
●a CRC
●an EOF
Table 17.General request format
S
OFRequest_flagsCommand codeParametersDataCRCEO
F
17.1 Request flags
In a request, the “flags” field specifies the actions to be performed by the LRIS64K and
whether corresponding fields are present or not.
The flags field consists of eight bits. The bit 3 (Inventory_flag) of the request flag defines the
contents of the 4 MSBs (bits 5 to 8). When bit 3 is reset (0), bits 5 to 8 define the LRIS64K
selection criteria. When bit 3 is set (1), bits 5 to 8 define the LRIS64K Inventory parameters.
Table 18.Definition of request flags 1 to 4
Bit NoFlagLevelDescription
Bit 1Subcarrier_flag
Bit 2Data_rate_flag
(1)
(2)
Bit 3Inventory_flag
Bit 4Protocol_extension_flag
1. Subcarrier_flag refers to the LRIS64K-to-VCD communication.
2. Data_rate_flag refers to the LRIS64K-to-VCD communication
0A single subcarrier frequency is used by the LRIS64K
1Two subcarrier are used by the LRIS64K
0Low data rate is used
1High data rate is used
0The meaning of flags 5 to 8 is described in Ta ble 1 9
1The meaning of flags 5 to 8 is described in Ta ble 2 0
0No Protocol format extension
1Protocol format extension
Doc ID 15336 Rev 1143/100
Request formatLRIS64K
.
Table 19.Request flags 5 to 8 when Bit 3 = 0
Bit NoFlagLevelDescription
Request is executed by any LRIS64K according to the setting of
0
flag
(1)
(1)
Bit 5Select flag
Bit 6
Address
Bit 7Option flag
Bit 8RFU0
1. If the Select_flag is set to 1, the Address_flag is set to 0 and the UID field is not present in the request.
Table 20.Request flags 5 to 8 when Bit 3 = 1
Bit NoFlagLevelDescription
Address_flag
1Request is executed only by the LRIS64K in Selected state
Request is not addressed. UID field is not present. The request is
0
executed by all LRIS64Ks.
Request is addressed. UID field is present. The request is executed
1
only by the LRIS64K whose UID matches the UID specified in the
request.
0Option not activated.
1Option activated.
Bit 5AFI flag
Bit 6Nb_slots flag
Bit 7Option flag0
Bit 8RFU0
0AFI field is not present
1AFI field is present
016 slots
11 slot
44/100Doc ID 15336 Rev 11
LRIS64KResponse format
18 Response format
The response consists of:
●an SOF
●flags
●parameters and data
●a CRC
●an EOF
Table 21.General response format
S
O
F
18.1 Response flags
In a response, the flags indicate how actions have been performed by the LRIS64K and
whether corresponding fields are present or not. The response flags consist of eight bits.
Table 22.Definitions of response flags 1 to 8
Response_flags ParametersDataCRCEO
F
Bit NoFlagLevelDescription
0No error
Bit 1Error_flag
1Error detected. Error code is in the "Error" field.
Bit 2RFU0
Bit 3RFU0
Bit 4Extension flag0No extension
Bit 5RFU0
Bit 6RFU0
Bit 7RFU0
Bit 8RFU0
Doc ID 15336 Rev 1145/100
Response formatLRIS64K
18.2 Response error code
If the Error_flag is set by the LRIS64K in the response, the Error code field is present and
provides information about the error that occurred.
Error codes not specified in Ta ble 2 3 are reserved for future use.
Table 23.Response error code definition
Error codeMeaning
02hThe command is not recognized, for example a format error occurred
03hThe option is not supported
0FhError with no information given
10hThe specified block is not available
11hThe specified block is already locked and thus cannot be locked again
12hThe specified block is locked and its contents cannot be changed.
13hThe specified block was not successfully programmed
14hThe specified block was not successfully locked
15hThe specified block is read-protected
46/100Doc ID 15336 Rev 11
LRIS64KAnticollision
19 Anticollision
The purpose of the anticollision sequence is to inventory the LRIS64Ks present in the VCD
field using their unique ID (UID).
The VCD is the master of communications with one or several LRIS64Ks. It initiates
LRIS64K communication by issuing the Inventory request.
The LRIS64K sends its response in the determined slot or does not respond.
19.1 Request parameters
When issuing the Inventory Command, the VCD:
●sets the Nb_slots_flag as desired
●adds the mask length and the mask value after the command field
●The mask length is the number of significant bits of the mask value.
●The mask value is contained in an integer number of bytes. The mask length indicates
the number of significant bits. LSB is transmitted first
●If the mask length is not a multiple of 8 (bits), as many 0-bits as required will be added
to the mask value MSB so that the mask value is contained in an integer number of
bytes
●The next field starts at the next byte boundary.
Table 24.Inventory request format
MSB
1. Gray means that the field is optional.
SOF
Request
_flags
8 bits8 bits
Command
Optional
(1)
AFI
8 bits8 bits0 to 8 bytes16 bits
Mask
length
Mask valueCRC
LSB
EOF
In the example of the Ta ble 2 5 and Figure 39, the mask length is 11 bits. Five 0-bits are
added to the mask value MSB. The 11-bit Mask and the current slot number are compared
to the UID.
Table 25.Example of the addition of 0-bits to an 11-bit mask value
(b15) MSBLSB (b0)
0000 0100 1100 1111
0-bits added11-bit mask value
Doc ID 15336 Rev 1147/100
AnticollisionLRIS64K
AI06682
Mask value received in the Inventory command0000 0100 1100 1111b16 bits
The Mask value less the padding 0s is loaded
into the Tag comparator
100 1100 1111b11 bits
The Slot counter is calculated
xxxxNb_slots_flags = 0 (16 slots), Slot Counter is 4 bits
The Slot counter is concatened to the Mask value
xxxx 100 1100 1111
b
Nb_slots_flags = 015 bits
The concatenated result is compared with
the least significant bits of the Tag UID.
Figure 39. Principle of comparison between the mask, the slot number and the UID
The AFI field is present if the AFI_flag is set.
The pulse is generated according to the definition of the EOF in ISO/IEC 15693-2.
The first slot starts immediately after the reception of the request EOF. To switch to the next
slot, the VCD sends an EOF.
The following rules and restrictions apply:
●if no LRIS64K answer is detected, the VCD may switch to the next slot by sending an
EOF,
●if one or more LRIS64K answers are detected, the VCD waits until the complete frame
has been received before sending an EOF for switching to the next slot.
48/100Doc ID 15336 Rev 11
LRIS64KRequest processing by the LRIS64K
20 Request processing by the LRIS64K
Upon reception of a valid request, the LRIS64K performs the following algorithm:
●NbS is the total number of slots (1 or 16)
●SN is the current slot number (0 to 15)
●LSB (value, n) function returns the n Less Significant Bits of value
●MSB (value, n) function returns the n Most Significant Bits of value
●“&” is the concatenation operator
●Slot_Frame is either an SOF or an EOF
SN = 0
if (Nb_slots_flag)
then NbS = 1
SN_length = 0
endif
else NbS = 16
SN_length = 4
endif
label1:
if LSB(UID, SN_length + Mask_length) =
LSB(SN,SN_length)&LSB(Mask,Mask_length)
then answer to inventory request
endif
wait (Slot_Frame)
if Slot_Frame = SOF
then Stop Anticollision
decode/process request
exit
endif
if Slot_Frame = EOF
if SN < NbS-1
then SN = SN + 1
goto label1
exit
endif
endif
Doc ID 15336 Rev 1149/100
Explanation of the possible casesLRIS64K
21 Explanation of the possible cases
Figure 40 summarizes the main possible cases that can occur during an anticollision
sequence when the slot number is 16.
The different steps are:
●The VCD sends an Inventory request, in a frame terminated by an EOF. The number of
slots is 16.
●LRIS64K_1 transmits its response in Slot 0. It is the only one to do so, therefore no
collision occurs and its UID is received and registered by the VCD;
●The VCD sends an EOF in order to switch to the next slot.
●In slot 1, two LRIS64Ks, LRIS64K_2 and LRIS64K_3 transmit a response, thus
generating a collision. The VCD records the event and remembers that a collision was
detected in Slot 1.
●The VCD sends an EOF in order to switch to the next slot.
●In Slot 2, no LRIS64K transmits a response. Therefore the VCD does not detect any
LRIS64K SOF and decides to switch to the next slot by sending an EOF.
●In slot 3, there is another collision caused by responses from LRIS64K_4 and
LRIS64K_5
●The VCD then decides to send a request (for instance a Read Block) to LRIS64K_1
whose UID has already been correctly received.
●All LRIS64Ks detect an SOF and exit the anticollision sequence. They process this
request and since the request is addressed to LRIS64K_1, only LRIS64K_1 transmits a
response.
●All LRIS64Ks are ready to receive another request. If it is an Inventory command, the
slot numbering sequence restarts from 0.
Note:The decision to interrupt the anticollision sequence is made by the VCD. It could have
continued to send EOFs until Slot 16 and only then sent the request to LRIS64K_1.
50/100Doc ID 15336 Rev 11
LRIS64KExplanation of the possible cases
!)
3LOT3LOT3LOT3LOT
6#$3/&
)NVENTORY
2EQUEST
%/&%/&%/&%/&3/&
2EQUESTTO
,2)3+?
%/&
2ESPONSE
2ESPONSE
,2)3+S
2ESPONSE
FROM
,2)3+?
2ESPONSE
2ESPONSE
2ESPONSE
4IMINGTTTTTTTT
#OMMENT
.O
COLLISION
#OLLISION
.O
2ESPONSE
#OLLISION
4IME
Figure 40. Description of a possible anticollision sequence
Doc ID 15336 Rev 1151/100
Inventory Initiated commandLRIS64K
22 Inventory Initiated command
The LRIS64K provides a special feature to improve the inventory time response of moving
tags using the Initiate_flag value. This flag, controlled by the Initiate command, allows tags
to answer to Inventory Initiated commands.
For applications in which multiple tags are moving in front of a reader, it is possible to miss
tags using the standard inventory command. The reason is that the inventory sequence has
to be performed on a global tree search. For example, a tag with a particular UID value may
have to wait the run of a long tree search before being inventoried. If the delay is too long,
the tag may be out of the field before it has been detected.
Using the Initiate command, the inventory sequence is optimized. When multiple tags are
moving in front of a reader, the ones which are within the reader field will be initiated by the
Initiate command. In this case, a small batch of tags will answer to the Inventory Initiated
command which will optimize the time necessary to identify all the tags. When finished, the
reader has to issue a new Initiate command in order to initiate a new small batch of tags
which are new inside the reader field.
It is also possible to reduce the inventory sequence time using the Fast Initiate and Fast
Inventory Initiated commands. These commands allow the LRIS64Ks to increase their
response data rate by a factor of 2, up to 53 Kbit/s.
52/100Doc ID 15336 Rev 11
LRIS64KTiming definition
23 Timing definition
23.1 t1: LRIS64K response delay
Upon detection of the rising edge of the EOF received from the VCD, the LRIS64K waits for
a time t
next slot during an inventory process. Values of t
in Figure 11 on page 26.
23.2 t2: VCD new request delay
t2 is the time after which the VCD may send an EOF to switch to the next slot when one or
more LRIS64K responses have been received during an Inventory command. It starts from
the reception of the EOF from the LRIS64Ks.
The EOF sent by the VCD may be either 10% or 100% modulated regardless of the
modulation index used for transmitting the VCD request to the LRIS64K.
t
is also the time after which the VCD may send a new request to the LRIS64K as
2
described in Table 37: LRIS64K protocol timing.
before transmitting its response to a VCD request or before switching to the
1nom
are given in Tab l e 2 6. The EOF is defined
1
Values of t
are given in Ta bl e 2 6 .
2
23.3 t3: VCD new request delay in the absence of a response from
the LRIS64K
t3 is the time after which the VCD may send an EOF to switch to the next slot when no
LRIS64K response has been received.
The EOF sent by the VCD may be either 10% or 100% modulated regardless of the
modulation index used for transmitting the VCD request to the LRIS64K.
From the time the VCD has generated the rising edge of an EOF:
●If this EOF is 100% modulated, the VCD waits a time at least equal to t
sending a new EOF.
●If this EOF is 10% modulated, the VCD waits a time at least equal to the sum of t
the LRIS64K nominal response time (which depends on the LRIS64K data rate and
subcarrier modulation mode) before sending a new EOF.
does not apply for write alike requests. Timing conditions for write alike requests are defined in the
1max
command description.
is the time taken by the LRIS64K to transmit an SOF to the VCD. t
3. t
SOF
rate: High data rate or Low data rate.
318.6 µs320.9 µs323.3 µs
309.2 µsNo t
(2)
t
1max
+ t
SOF
(1)
(3)
nom
No t
nom
.
C
depends on the current data
SOF
3min
No t
No t
before
max
max
3min
+
Doc ID 15336 Rev 1153/100
Commands codesLRIS64K
24 Commands codes
The LRIS64K supports the commands described in this section. Their codes are given in
Ta bl e 2 7 .
Table 27.Command codes
Command code
standard
01hInventory2ChGet Multiple Block Security Status
02hStay QuietB1hWrite-sector Password
20hRead Single BlockB2hLock-sector Password
21hWrite Single Block B3hPresent-sector Password
23hRead Multiple BlockC0hFast Read Single Block
25hSelectC1hFast Inventory Initiated
26hReset to ReadyC2hFast Initiate
27hWrite AFIC3hFast Read Multiple Block
28hLock AFID1hInventory Initiated
29hWrite DSFIDD2hInitiate
2AhLock DSFID
2BhGet System Info
Function
Command code
custom
Function
54/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.1 Inventory
When receiving the Inventory request, the LRIS64K runs the anticollision sequence. The
Inventory_flag is set to 1. The meaning of flags 5 to 8 is shown in Table 20: Request flags 5
to 8 when Bit 3 = 1.
The request contains:
●the flags,
●the Inventory command code (see Table 27: Command codes)
●the AFI if the AFI flag is set
●the mask length
●the mask value
●the CRC
The LRIS64K does not generate any answer in case of error.
Table 28.Inventory request format
Request
SOF
Request_flags Inventory
8 bits01h
1. Gray means that the field is optional.
Optional
(1)
AFI
Mask
length
Mask
value
CRC16
8 bits8 bits0 - 64 bits16 bits
Request
EOF
The response contains:
●the flags
●the Unique ID
Table 29.Inventory response format
Response
SOF
Response_
flags
DSFIDUIDCRC16
Response
EOF
8 bits8 bits64 bits16 bits
During an Inventory process, if the VCD does not receive an RF LRIS64K response, it waits
a time t
before sending an EOF to switch to the next slot. t3 starts from the rising edge of
3
the request EOF sent by the VCD.
●If the VCD sends a 100% modulated EOF, the minimum value of t
t
min = 4384/fC (323.3µs) + t
3
●
If the VCD sends a 10% modulated EOF, the minimum value of t3 is:
t
min = 4384/fC (323.3µs) + t
3
SOF
NRT
is:
3
where:
●t
●t
t
NRT
is the time required by the LRIS64K to transmit an SOF to the VCD
SOF
is the nominal response time of the LRIS64K
NRT
and t
are dependent on the LRIS64K-to-VCD data rate and subcarrier modulation
SOF
mode.
Doc ID 15336 Rev 1155/100
Commands codesLRIS64K
24.2 Stay Quiet
Command code = 0x02
On receiving the Stay Quiet command, the LRIS64K enters the Quiet State if no error
occurs, and does NOT send back a response. There is NO response to the Stay Quiet
command even if an error occurs.
When in the Quiet state:
●the LRIS64K does not process any request if the Inventory_flag is set,
●the LRIS64K processes any Addressed request
The LRIS64K exits the Quiet State when:
●it is reset (power off),
●receiving a Select request. It then goes to the Selected state,
●receiving a Reset to Ready request. It then goes to the Ready state.
Table 30.Stay Quiet request format
Request
SOF
Request flagsStay QuietUIDCRC16
Request
EOF
8 bits02h64 bits16 bits
The Stay Quiet command must always be executed in Addressed mode (Select_flag is reset
to 0 and Address_flag is set to 1).
Figure 41. Stay Quiet frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K
Timing
Stay Quiet
request
EOF
56/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.3 Read Single Block
On receiving the Read Single Block command, the LRIS64K reads the requested block and
sends back its 32-bit value in the response. The Protocol_extention_flag should be set to 1
for the LRIS64K to operate correctly. If the Protocol_extention_flag is at 0, the LRIS64K
answers with an error code. The Option_flag is supported.
Table 31.Read Single Block request format
Request
SOF
1. Gray means that the field is optional.
Request_
Read Single
flags
8 bits20h
Block
UID
(1)
Block
number
CRC16
64 bits16 bits16 bits
Request parameters:
●Option_flag
●UID (optional)
●Block number
Table 32.Read Single Block response format when Error_flag is NOT set
Response
SOF
Response_
flags
8 bits
1. Gray means that the field is optional.
Sector
security
status
8 bits32 bits16 bits
(1)
DataCRC16
Response
Response parameters:
●Sector security status if Option_flag is set (see Table 33: Sector security status)
●4 bytes of block data
Table 33.Sector security status
b
Reserved for future
b
7
use. All at 0
b
6
5
b
b
4
password
control bits
3
b
2
Read / Write
protection bits
b
1
b
0
0: Current sector not locked
1: Current sector locked
Request
EOF
EOF
Table 34.Read Single Block response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Doc ID 15336 Rev 1157/100
Response
EOF
Commands codesLRIS64K
Response parameter:
●Error code as Error_flag is set
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
–15h: the specified block is read-protected
Figure 42. Read Single Block frame exchange between VCD and LRIS64K
VCDSOF
Read Single Block
request
EOF
LRIS64K<-t
-> SOF
1
Read Single Block
response
EOF
58/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.4 Write Single Block
On receiving the Write Single Block command, the LRIS64K writes the data contained in the
request to the requested block and reports whether the write operation was successful in
the response. The Protocol_extention_flag should be set to 1 for the LRIS64K to operate
correctly. If the Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
The Option_flag is supported.
During write cycle W
the LRIS64K may not program correctly the data into the memory. The W
t
+ 18 × 302 µs.
1nom
Table 35.Write Single Block request format
Request
SOF
Request_
flags
, there should be no modulation (neither 100% nor 10%). Otherwise,
t
Write
Single
Block
UID
(1)
Block
number
DataCRC16
time is equal to
t
Request
8 bits21h64 bits16 bits32 bits16 bits
1. Gray means that the field is optional.
Request parameters:
●UID (optional)
●Block number
●Data
Table 36.Write Single Block response format when Error_flag is NOT set
Response SOFResponse_flagsCRC16Response EOF
8 bits16 bits
Response parameter:
●No parameter. The response is send back after the writing cycle.
Table 37.Write Single Block response format when Error_flag is set
EOF
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
–12h: the specified block is locked and its contents cannot be changed.
–13h: the specified block was not successfully programmed
Doc ID 15336 Rev 1159/100
Response
EOF
Commands codesLRIS64K
Figure 43. Write Single Block frame exchange between VCD and LRIS64K
When receiving the Read Multiple Block command, the LRIS64K reads the selected blocks
and sends back their value in multiples of 32 bits in the response. The blocks are numbered
from '00h to '7FFh' in the request and the value is minus one (–1) in the field. For example, if
the “number of blocks” field contains the value 06h, 7 blocks are read. The maximum
number of blocks is fixed at 32 assuming that they are all located in the same sector. If the
number of blocks overlaps sectors, the LRIS64K returns an error code.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
The Option_flag is supported.
Table 38.Read Multiple Block request format
Request
SOF
Request_
flags
Read
Multiple
Block
8 bits23h
1. Gray means that the field is optional.
(1)
UID
64 bits16 bits8 bits16 bits
First
block
number
Number
of blocks
CRC16
Request parameters:
●Option_flag
●UID (optional)
●First block number
●Number of blocks
Table 39.Read Multiple Block response format when Error_flag is NOT set
Response
SOF
Response_
flags
8 bits
1. Gray means that the field is optional.
2. Repeated as needed.
Sector
security
(1)
status
(2)
8 bits
DataCRC16
(2)
32 bits
16 bits
Response
Response parameters:
●Sector security status if Option_flag is set (see Table 40: Sector security status)
●N blocks of data
Table 40.Sector security status
b
Reserved for future
b
7
use. All at 0
b
6
5
b
b
4
password
control bits
3
b
2
Read / Write
protection bits
b
1
b
0
0: Current sector not locked
1: Current sector locked
Request
EOF
EOF
Doc ID 15336 Rev 1161/100
Commands codesLRIS64K
Table 41.Read Multiple Block response format when Error_flag is set
Figure 44. Read Multiple Block frame exchange between VCD and LRIS64K
VCDSOF
Read Multiple
Block request
EOF
LRIS64K<-t
-> SOF
1
Read Multiple
Block response
EOF
62/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.6 Select
When receiving the Select command:
●if the UID is equal to its own UID, the LRIS64K enters or stays in the Selected state and
sends a response.
●if the UID does not match its own, the selected LRIS64K returns to the Ready state and
does not send a response.
The LRIS64K answers an error code only if the UID is equal to its own UID. If not, no
response is generated. If an error occurs, the LRIS64K remains in its current state.
Table 42.Select request format
Request
SOF
Request_
flags
SelectUIDCRC16
8 bits25h64 bits16 bits
Request parameter:
●UID
Table 43.Select Block response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter.
Table 44.Select response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Request
EOF
Response
EOF
Response
EOF
Response parameter:
●Error code as Error_flag is set:
–03h: the option is not supported
–0Fh: error with no information given
Figure 45. Select frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Select
request
EOF
-> SOF
1
Select
response
Doc ID 15336 Rev 1163/100
EOF
Commands codesLRIS64K
24.7 Reset to Ready
On receiving a Reset to Ready command, the LRIS64K returns to the Ready state if no
error occurs. In the Addressed mode, the LRIS64K answers an error code only if the UID is
equal to its own UID. If not, no response is generated.
Table 45.Reset to Ready request format
Request
SOF
Request_
flags
Reset to
Ready
UID
(1)
CRC16
8 bits26h64 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
Table 46.Reset to Ready response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter
Table 47.Reset to ready response format when Error_flag is set
Response
SOF
Response_flagsError codeCRC16
8 bits8 bits16 bits
Request
EOF
Response
EOF
Response
EOF
Response parameter:
●Error code as Error_flag is set:
–03h: the option is not supported
–0Fh: error with no information given
Figure 46. Reset to Ready frame exchange between VCD and LRIS64K
Reset to
VCDSOF
LRIS64K<-t
64/100Doc ID 15336 Rev 11
Ready
request
EOF
-> SOF
1
Reset to
Ready
response
EOF
LRIS64KCommands codes
24.8 Write AFI
On receiving the Write AFI request, the LRIS64K programs the 8-bit AFI value to its
memory. The Option_flag is supported.
During write cycle W
, there should be no modulation (neither 100% nor 10%). Otherwise,
t
the LRIS64K may not write correctly the AFI value into the memory. The W
t
+ 18 × 302 µs.
1nom
Table 48.Write AFI request format
Request
SOF
Request
_flags
Write
AFI
UID
(1)
AFICRC16
8 bits27h64 bits8 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
●AFI
Table 49.Write AFI response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter.
Table 50.Write AFI response format when Error_flag is set
time is equal to
t
Request
EOF
Response
EOF
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set
–03h: the option is not supported
–0Fh: error with no information given
–12h: the specified block is locked and its contents cannot be changed.
–13h: the specified block was not successfully programmed
Doc ID 15336 Rev 1165/100
Response
EOF
Commands codesLRIS64K
Figure 47. Write AFI frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Write AFI
request
EOF
-> SOF
1
LRIS64K<---------------- W
Write AFI
response
----------------> SOF
t
EOF
Write sequence
when error
Write AFI
response
EOF
66/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.9 Lock AFI
On receiving the Lock AFI request, the LRIS64K locks the AFI value permanently. The
Option_flag is supported.
During write cycle W
, there should be no modulation (neither 100% nor 10%). Otherwise,
t
the LRIS64K may not Lock correctly the AFI value in memory. The W
+ 18 × 302 µs.
Table 51.Lock AFI request format
Request
SOF
Request_
flags
Lock
AFI
UID
(1)
8 bits28h64 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
Table 52.Lock AFI response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter
Table 53.Lock AFI response format when Error_flag is set
time is equal to t
t
CRC16
Request
Response
EOF
1nom
EOF
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set
–03h: the option is not supported
–0Fh: error with no information given
–11h: the specified block is already locked and thus cannot be locked again
–14h: the specified block was not successfully locked
Doc ID 15336 Rev 1167/100
Response
EOF
Commands codesLRIS64K
Figure 48. Lock AFI frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Lock AFI
request
EOF
-> SOF
1
Lock AFI
response
EOF
LRIS64K<--------------- Wt ---------------> SOF
Lock sequence when
error
Lock AFI
response
EOF
68/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.10 Write DSFID
On receiving the Write DSFID request, the LRIS64K programs the 8-bit DSFID value to its
memory. The Option_flag is supported.
During write cycle W
, there should be no modulation (neither 100% nor 10%). Otherwise,
t
the LRIS64K may not write correctly the DSFID value in memory. The W
t
+ 18 × 302 µs.
1nom
Table 54.Write DSFID request format
Request
SOF
Request_
flags
Write
DSFID
UID
(1)
DSFIDCRC16
8 bits29h64 bits8 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
●DSFID
Table 55.Write DSFID response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter
Table 56.Write DSFID response format when Error_flag is set
time is equal to
t
Request
EOF
Response
EOF
Response
SOF
Response_flagsError codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set
–03h: the option is not supported
–0Fh: error with no information given
–12h: the specified block is locked and its contents cannot be changed.
–13h: the specified block was not successfully programmed
Doc ID 15336 Rev 1169/100
Response
EOF
Commands codesLRIS64K
Figure 49. Write DSFID frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Write DSFID
request
EOF
-> SOF
1
LRIS64K<--------------- W
Write DSFID
response
---------------> SOF
t
EOF
Write sequence when
error
Write DSFID
response
EOF
70/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.11 Lock DSFID
On receiving the Lock DSFID request, the LRIS64K locks the DSFID value permanently.
The Option_flag is supported.
During write cycle W
the LRIS64K may not lock correctly the DSFID value in memory. The W
t
+ 18 × 302 µs.
1nom
Table 57.Lock DSFID request format
Request
SOF
Request_
flags
, there should be no modulation (neither 100% nor 10%). Otherwise,
t
t
Lock
DSFID
UID
(1)
CRC16
8 bits2Ah64 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
Table 58.Lock DSFID response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter.
Table 59.Lock DSFID response format when Error_flag is set
time is equal to
Request
EOF
Response
EOF
Response
SOF
Response_flagsError codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–03h: the option is not supported
–0Fh: error with no information given
–11h: the specified block is already locked and thus cannot be locked again
–14h: the specified block was not successfully locked
Doc ID 15336 Rev 1171/100
Response
EOF
Commands codesLRIS64K
Figure 50. Lock DSFID frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Lock DSFID
request
EOF
-> SOF
1
Lock DSFID
response
EOF
LRIS64K<--------------- Wt ---------------> SOF
Lock sequence
when error
Lock DSFID
response
EOF
72/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.12 Get System Info
When receiving the Get System Info command, the LRIS64K sends back its information
data in the response.The Option_flag is supported and must be reset to 0. The Get System
Info can be issued in both Addressed and Non Addressed modes.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
Table 60.Get System Info request format
Request
SOF
Request
_flags
Get System
Info
UID
(1)
CRC16
Request
EOF
8 bits2Bh64 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
Table 61.Get System Info response format when Error_flag is NOT set
Response
SOF
Response
_flags
Information
flags
UIDDSFID AFI
Memory
size
IC
reference
CRC16
Response
EOF
00h0Fh64 bits 8 bits 8 bits 0307FFh44h16 bits
Response parameters:
●Information flags set to 0Fh. DSFID, AFI, Memory Size and IC reference fields are
present
●UID code on 64 bits
●DSFID value
●AFI value
●Memory size. The LRIS64K provides 2048 blocks (07FFh) of 4 byte (03h)
●IC reference. Only the 6 MSB are significant.
Table 62.Get System Info response format when Error_flag is set
Response
SOF
Response_flagsError codeCRC16
01h8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–03h: Option not supported
–0Fh: other error
Doc ID 15336 Rev 1173/100
Response
EOF
Commands codesLRIS64K
Figure 51. Get System Info frame exchange between VCD and LRIS64K
VCDSOF Get System Info request EOF
LRIS64K<-t
-> SOF Get System Info response EOF
1
74/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.13 Get Multiple Block Security Status
When receiving the Get Multiple Block Security Status command, the LRIS64K sends back
the sector security status. The blocks are numbered from '00h to '07FFh' in the request and
the value is minus one (–1) in the field. For example, a value of '06' in the “Number of blocks”
field requests to return the security status of 7 blocks.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
During the LRIS64K response, if the internal block address counter reaches 07FFh, it rolls
over to 0000h and the Sector Security Status bytes for that location are sent back to the
reader.
Table 63.Get Multiple Block Security Status request format
Get
Request
SOF
Request
_flags
Multiple
Block
Security
Status
UID
(1)
First
block
number
Number
of blocks
CRC16
Request
EOF
8 bits2Ch
1. Gray means that the field is optional.
64 bits16 bits16 bits16 bits
Request parameter:
●UID (optional)
●First block number
●Number of blocks
Table 64.Get Multiple Block Security Status response format when Error_flag is
NOT set
Response
SOF
1. Repeated as needed.
Response_
Sector security
flags
8 bits8 bits
status
(1)
CRC16
16 bits
Response
EOF
Response parameters:
●Sector security status (see Table 65: Sector security status)
Table 65.Sector security status
b
7
Reserved for future use. All
b
at 0
6
b
5
b
4
b
3
password control
bits
b
2
b
1
Read / Write
protection bits
b
0
0: Current sector not locked
1: Current sector locked
Doc ID 15336 Rev 1175/100
Commands codesLRIS64K
Table 66.Get Multiple Block Security Status response format when Error_flag is
set
Response
SOF
Response_
flags
Error codeCRC16
Response
EOF
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
Figure 52. Get Multiple Block Security Status frame exchange between VCD and
LRIS64K
VCDSOF
LRIS64K<-t
Get Multiple Block
Security Status
EOF
-> SOF
1
Get Multiple Block
Security Status
EOF
76/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.14 Write-sector Password
On receiving the Write-sector Password command, the LRIS64K uses the data contained in
the request to write the password and reports whether the operation was successful in the
response. The Option_flag is supported.
During write cycle time W
Otherwise, the LRIS64K may not correctly program the data into the memory. The W
equal to t
+ 18 × 302 µs. After a successful write, the new value of the selected
1nom
, there must be no modulation at all (neither 100% nor 10%).
t
t
time is
password is automatically activated. It is not required to present the new password value
until LRIS64K power-down.
Table 67.Write-sector Password request format
Request
SOF
Request
_flags
Writesector
Password
IC Mfg
code
UID
(1)
Password
number
DataCRC16
Request
EOF
8 bitsB1h02h64 bits8 bits32 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
●Password number (01h = Pswd1, 02h = Pswd2, 03h = Pswd3, other = Error)
●Data
Table 68.Write-sector Password response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
Response
EOF
8 bits16 bits
Response parameter:
●32-bit password value. The response is sent back after the write cycle.
Table 69.Write-sector Password response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–02h: the command is not recognized, for example: a format error occurred
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
–12h: the specified block is locked and its contents cannot be changed.
–13h: the specified block was not successfully programmed
Response
EOF
Doc ID 15336 Rev 1177/100
Commands codesLRIS64K
Figure 53. Write-sector Password frame exchange between VCD and LRIS64K
Write-
VCDSOF
LRIS64K<-t
LRIS64K<--------------- Wt ---------------> SOF
sector
Password
request
EOF
-> SOF
1
Write-sector
Password
response
EOF
Write sequence
when error
Write-
sector
Password
EOF
response
78/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.15 Lock-sector Password
On receiving the Lock-sector Password command, the LRIS64K sets the access rights and
permanently locks the selected sector. The Option_flag is supported.
A sector is selected by giving the address of one of its blocks in the Lock-sector Password
request (Sector number field). For example, addresses 0 to 31 are used to select sector 0
and addresses 32 to 63 are used to select sector 1. Care must be taken when issuing the
Lock-sector Password command as all the blocks belonging to the same sector are
automatically locked by a single command.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
During write cycle W
, there should be no modulation (neither 100% nor 10%) otherwise, the
t
LRIS64K may not correctly lock the memory block.
The W
Table 70.Lock-sector Password request format
1. Gray means that the field is optional.
time is equal to t
t
Request
SOF
+ 18 × 302 µs.
1nom
Request
_flags
Lock-
sector
Password
8 bitsB2h02h
IC
Mfg
code
Sector
security
status
CRC16
UID
(1)
Sector
number
64 bits16 bits8 bits16 bits
Request
Request parameters:
●(optional) UID
●Sector number
●Sector security status (refer to Ta bl e 7 1 )
Table 71.Sector security status
b
7
000password control bits
Table 72.Lock-sector Password response format when Error_flag is NOT set
b
6
b
5
b
4
b
3
b
2
b
1
Read / Write protection
bits
EOF
b
0
1
Response
SOF
Response_flagsCRC16
8 bits16 bits
Response parameter:
●No parameter.
Table 73.Lock-sector Password response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Doc ID 15336 Rev 1179/100
Response
EOF
Response
EOF
Commands codesLRIS64K
Response parameter:
●Error code as Error_flag is set:
–02h: the command is not recognized, for example: a format error occurred
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
–11h: the specified block is already locked and thus cannot be locked again
–14h: the specified block was not successfully locked
Figure 54. Lock-sector Password frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Lock-sector
Password
EOF
request
-> SOF
1
Lock-sector
Password
response
EOF
Lock sequence when
error
LRIS64K<--------------- W
--------------->SOF
t
Lock-sector
Password
response
EOF
80/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.16 Present-sector Password
On receiving the Present-sector Password command, the LRIS64K compares the requested
password with the data contained in the request and reports whether the operation has
been successful in the response. The Option_flag is supported.
During the W
10%) otherwise, the LRIS64K Password value may not be correctly compared.
The W
time is equal to t
t
After a successful command, the access to all the memory blocks linked to the password is
changed as described in Section 3.1: LRIS64K RF block security.
Table 74.Present-sector Password request format
comparison cycle time, there should be no modulation (neither 100% nor
t
+ 18 × 302 µs.
1nom
Request
SOF
Request
_flags
Present-
sector
Password
IC
Mfg
code
UID
(1)
Password
number
DataCRC16
Request
EOF
8 bitsB3h02h64 bits8 bits32 bits16 bits
1. Gray means that the field is optional.
Request parameter:
●UID (optional)
●Password Number (0x01 = Pswd1, 0x02 = Pswd2, 0x03 = Pswd3, other = Error)
●Data
Table 75.Present-sector Password response format when Error_flag is NOT set
Response
SOF
Response_flagsCRC16
Response
EOF
8 bits16 bits
Response parameter:
●No parameter. The response is send back after the writing cycle
Table 76.Present-sector Password response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
Response
EOF
8 bits8 bits16 bits
Response parameter:
●Error code as Error_flag is set:
–02h: the command is not recognized, for example: a format error occurred
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
Doc ID 15336 Rev 1181/100
Commands codesLRIS64K
Figure 55. Present-sector Password frame exchange between VCD and LRIS64K
Present-
VCDSOF
LRIS64K<-t
LRIS64K<-------------- W
sector
Password
request
EOF
-> SOF
1
Present-
sector
Password
EOF sequence when error
response
--------------> SOF
t
Present-
sector
Password
response
EOF
82/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.17 Fast Read Single Block
On receiving the Fast Read Single Block command, the LRIS64K reads the requested block
and sends back its 32-bit value in the response. The Option_flag is supported. The data rate
of the response is multiplied by 2.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
Table 77.Fast Read Single Block request format
Request
SOF
Request_
flags
Fast Read
Single
Block
IC Mfg
code
UID
(1)
Block
number
CRC16
Request
8 bitsC0h02h64 bits16 bits16 bits
1. Gray means that the field is optional.
Request parameters:
●Option_flag
●UID (optional)
●Block number
Table 78.Fast Read Single Block response format when Error_flag is NOT set
Response
SOF
Response
_flags
8 bits
1. Gray means that the field is optional.
Sector
security
(1)
status
DataCRC16
8 bits32 bits16 bits
Response
EOF
Response parameters:
●Sector security status if Option_flag is set (see Tabl e 79)
●4 bytes of block data
Table 79.Sector security status
b
7
Reserved for future used. All
b
at 0
6
b
5
b
4
b
3
password control
bits
b
2
b
1
Read / Write
protection bits
b
0
0: Current sector not locked
1: Current sector locked
EOF
Table 80.Fast Read Single Block response format when Error_flag is set
Response
SOF
Response_
flags
Error codeCRC16
8 bits8 bits16 bits
Doc ID 15336 Rev 1183/100
Response
EOF
Commands codesLRIS64K
Response parameter:
●Error code as Error_flag is set:
–02h: the command is not recognized, for example: a format error occurred
–03h: the option is not supported
–0Fh: error with no information given
–10h: the specified block is not available
–15h: the specified block is read protected
Figure 56. Fast Read Single Block frame exchange between VCD and LRIS64K
VCDSOF
Fast Read Single Block
request
EOF
LRIS64K<-t
-> SOF
1
Fast Read Single
Block response
EOF
84/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.18 Fast Inventory Initiated
Before receiving the Fast Inventory Initiated command, the LRIS64K must have received an
Initiate or a Fast Initiate command in order to set the Initiate_ flag. If not, the LRIS64K does
not answer to the Fast Inventory Initiated command.
On receiving the Fast Inventory Initiated request, the LRIS64K runs the anticollision
sequence. The Inventory_flag must be set to 1. The meaning of flags 5 to 8 is shown in
Table 20: Request flags 5 to 8 when Bit 3 = 1. The data rate of the response is multiplied by
2.
The request contains:
●the flags,
●the Inventory command code
●the AFI if the AFI flag is set
●the mask length
●the mask value
●the CRC
The LRIS64K does not generate any answer in case of error.
Table 81.Fast Inventory Initiated request format
Request
SOF
Request
_flags
8 bitsC1h02h
1. Gray means that the field is optional.
Fast
Inventory
Initiated
IC Mfg
code
Optional
AFI
(1)
Mask
length
Mask valueCRC16
8 bits8 bits0 - 64 bits16 bits
Request
EOF
The Response contains:
●the flags
●the Unique ID
Table 82.Fast Inventory Initiated response format
Response
SOF
Response
_flags
DSFIDUIDCRC16
Response
EOF
8 bits8 bits64 bits16 bits
During an Inventory process, if the VCD does not receive an RF LRIS64K response, it waits
a time t
before sending an EOF to switch to the next slot. t3 starts from the rising edge of
3
the request EOF sent by the VCD.
●If the VCD sends a 100% modulated EOF, the minimum value of t
t
min = 4384/fC (323.3µs) + t
3
●
If the VCD sends a 10% modulated EOF, the minimum value of t3 is:
t
min = 4384/fC (323.3µs) + t
3
SOF
NRT
is:
3
where:
●t
●t
is the time required by the LRIS64K to transmit an SOF to the VCD
SOF
is the nominal response time of the LRIS64K
NRT
Doc ID 15336 Rev 1185/100
Commands codesLRIS64K
t
NRT
and t
are dependent on the LRIS64K-to-VCD data rate and subcarrier modulation
SOF
mode.
24.19 Fast Initiate
On receiving the Fast Initiate command, the LRIS64K will set the internal Initiate_flag and
send back a response only if it is in the Ready state. The command has to be issued in the
Non Addressed mode only (Select_flag is reset to 0 and Address_flag is reset to 0). If an
error occurs, the LRIS64K does not generate any answer. The Initiate_flag is reset after a
power off of the LRIS64K. The data rate of the response is multiplied by 2.
The request contains:
●No data
Table 83.Fast Initiate request format
Request
SOF
Request_flags
Fast
Initiate
IC Mfg
Code
CRC16
8 bitsC2h02h16 bits
The response contains:
●the flags
●the Unique ID
Table 84.Fast Initiate response format
Response
SOF
Figure 57. Fast Initiate frame exchange between VCD and LRIS64K
VCDSOFFast Initiate request EOF
LRIS64K<-t
Response
_flags
DSFIDUIDCRC16
8 bits8 bits64 bits16 bits
-> SOF Fast Initiate response EOF
1
Request
EOF
Response
EOF
86/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.20 Fast Read Multiple Block
On receiving the Fast Read Multiple Block command, the LRIS64K reads the selected
blocks and sends back their value in multiples of 32 bits in the response. The blocks are
numbered from '00h to '7FFh' in the request and the value is minus one (–1) in the field. For
example, if the “number of blocks” field contains the value 06h, 7 blocks are read. The
maximum number of blocks is fixed to 32 assuming that they are all located in the same
sector. If the number of blocks overlaps sectors, the LRIS64K returns an error code.
The Protocol_extention_flag should be set to 1 for the LRIS64K to operate correctly. If the
Protocol_extention_flag is at 0, the LRIS64K answers with an error code.
The Option_flag is supported. The data rate of the response is multiplied by 2.
Table 85.Fast Read Multiple Block request format
Fast
Request
SOF
Request_
flags
Read
Multiple
Block
8 bitsC3h02h
1. Gray means that the field is optional.
IC Mfg
code
(1)
UID
64 bits16 bits8 bits16 bits
First
block
number
Number
of
blocks
CRC16
Request
EOF
Request parameters:
●Option_flag
●UID (Optional)
●First block number
●Number of blocks
Table 86.Fast Read Multiple Block response format when Error_flag is NOT set
Response
SOF
Response_
flags
8 bits
1. Gray means that the field is optional.
2. Repeated as needed.
Sector
security
(1)
status
(2)
8 bits
DataCRC16
(2)
32 bits
16 bits
Response
EOF
Response parameters:
●Sector security status if Option_flag is set (see Table 87: Sector security status if
Option_flag is set)
●N block of data
Table 87.Sector security status if Option_flag is set
b
7
Reserved for future use.
b
6
All at 0
b
5
b
b
4
password
control bits
3
Read / Write
protection bits
b
b
2
1
b
0
0: Current sector not locked
1: Current sector locked
Doc ID 15336 Rev 1187/100
Commands codesLRIS64K
Table 88.Fast Read Multiple Block response format when Error_flag is set
Figure 58. Fast Read Multiple Block frame exchange between VCD and LRIS64K
Fast Read
VCDSOF
LRIS64K<-t
Multiple Block
request
EOF
-> SOF
1
Fast Read
Multiple Block
response
EOF
88/100Doc ID 15336 Rev 11
LRIS64KCommands codes
24.21 Inventory Initiated
Before receiving the Inventory Initiated command, the LRIS64K must have received an
Initiate or a Fast Initiate command in order to set the Initiate_ flag. If not, the LRIS64K does
not answer to the Inventory Initiated command.
On receiving the Inventory Initiated request, the LRIS64K runs the anticollision sequence.
The Inventory_flag must be set to 1. The meaning of flags 5 to 8 is given in Ta bl e 2 0 :
Request flags 5 to 8 when Bit 3 = 1.
The request contains:
●the flags,
●the Inventory Command code
●the AFI if the AFI flag is set
●the mask length
●the mask value
●the CRC
The LRIS64K does not generate any answer in case of error.
Table 89.Inventory Initiated request format
Request
SOF
Request
_flags
Inventory
Initiated
IC
Mfg
code
Optional
AFI
Mask
length
Mask valueCRC16
Request
EOF
8 bitsD1h02h8 bits8 bits0 - 64 bits16 bits
The response contains:
●the flags
●the Unique ID
Table 90.Inventory Initiated response format
Response
SOF
Response
_flags
DSFIDUIDCRC16
Response
EOF
8 bits8 bits64 bits16 bits
During an Inventory process, if the VCD does not receive an RF LRIS64K response, it waits
a time t
before sending an EOF to switch to the next slot. t3 starts from the rising edge of
3
the request EOF sent by the VCD.
●If the VCD sends a 100% modulated EOF, the minimum value of t
t
min = 4384/fC (323.3µs) + t
3
●
If the VCD sends a 10% modulated EOF, the minimum value of t3 is:
t
min = 4384/fC (323.3µs) + t
3
SOF
NRT
is:
3
where:
●t
●t
t
NRT
is the time required by the LRIS64K to transmit an SOF to the VCD
SOF
is the nominal response time of the LRIS64K
NRT
and t
are dependent on the LRIS64K-to-VCD data rate and subcarrier modulation
SOF
mode.
Doc ID 15336 Rev 1189/100
Commands codesLRIS64K
24.22 Initiate
On receiving the Initiate command, the LRIS64K will set the internal Initiate_flag and send
back a response only if it is in the ready state. The command has to be issued in the Non
Addressed mode only (Select_flag is reset to 0 and Address_flag is reset to 0). If an error
occurs, the LRIS64K does not generate any answer. The Initiate_flag is reset after a power
off of the LRIS64K.
The request contains:
●No data
Table 91.Initiate request format
Request
SOF
Request_flagsInitiate
IC Mfg
code
CRC16
8 bitsD2h02h16 bits
The response contains:
●the flags
●the Unique ID
Table 92.Initiate Initiated response format
Response
SOF
Figure 59. Initiate frame exchange between VCD and LRIS64K
VCDSOF
LRIS64K<-t
Response
_flags
DSFIDUIDCRC16
8 bits8 bits64 bits16 bits
Initiate
request
EOF
-> SOF
1
Initiate
response
EOF
Request
EOF
Response
EOF
90/100Doc ID 15336 Rev 11
LRIS64KMaximum rating
25 Maximum rating
Stressing the device above the rating listed in the absolute maximum ratings table may
cause permanent damage to the device. These are stress ratings only and operation of the
device at these or any other conditions above those indicated in the operating sections of
this specification is not implied. Exposure to absolute maximum rating conditions for
extended periods may affect device reliability. Refer also to the STMicroelectronics SURE
Program and other relevant quality documents.
This section summarizes the operating and measurement conditions, and the DC and AC
characteristics of the device in RF mode. The parameters in the DC and AC Characteristic
tables that follow are derived from tests performed under the Measurement Conditions
summarized in the relevant tables. Designers should check that the operating conditions in
their circuit match the measurement conditions when relying on the quoted parameters.
Table 94.RF AC characteristics
SymbolParameterConditionMinTypMaxUnit
(1) (2)
f
CC
H_ISOOperating field according to ISOT
H_Extended
MI
CARRIER
t
RFR,tRFF
t
RFSBL
MI
CARRIER
t
RFR,tRFF
t
RFSBL
t
JIT
t
MIN CD
f
SH
f
SL
t
1
t
2
W
1. TA = –40 to 85 °C.
2. All timing measurements were performed between 0 °C and 50 °C on a reference antenna with the following
characteristics:
External size: 75 mm x 48 mm
Number of turns: 5
Width of conductor: 0.5 mm
Space between 2 conductors: 0.3 mm
Value of the tuning capacitor in SO8: 27.5 pF (LRIS64K)
Value of the coil: 5 µH
Tuning frequency: 13.56 MHz.
3. Characterized only, not 100% tested
4. 15% (or more) carrier modulation index offers a better signal/noise ratio and therefore a wider operating range with a better
noise immunity
External RF signal frequency13.55313.5613.567MHz
= 0 °C to 50 °C1505000mA/m
A
Operating field in extended
temperature range
10% carrier modulation index
MI=(A-B)/(A+B)
(3) (4)
TA = –40 °C to 85 °C1503500mA/m
150 mA/m > H_ISO >
1000 mA/m
1530
H_ISO > 1000 mA/m1030
10% rise and fall time0.53.0µs
10% minimum pulse width for bit7.19.44µs
100% carrier modulation indexMI=(A-B)/(A+B)95100%
100% rise and fall time0.53.5µs
100% minimum pulse width for bit7.19.44µs
Bit pulse jitter-2+2µs
Minimum time from carrier
generation to first data
From H-field min0.11ms
Subcarrier frequency highfCC/32423.75kHz
Subcarrier frequency lowfCC/28484.28kHz
Time for LRIS64K response4224/f
Time between commands4224/f
RF write time (including internal
t
Verify )
S
S
318.6320.9323.3µs
309311.5314µs
5.75ms
%
92/100Doc ID 15336 Rev 11
LRIS64KRF DC and AC parameters
AI06680
AB
t
RFF
t
RFR
t
RFSBL
t
MAXt
MIN CD
f
CC
Table 95.RF DC characteristics
(1)
SymbolParameterTest conditionsMin.Typ.Max.Unit
V
V
Limited voltage2.0V
CC
Backscattered level as defined
BACK
by ISO test
ISO/IEC 10373-710mV
ReadVCC= 2.0 V50µA
I
Supply current
CC
C
1. T
2. Characterised only, at room temperature only, measured at V
Table 96.Operating conditions
Internal tuning capacitor
TUN
= –40 to 85 °C.
A
WriteV
(2)
= 2.0 V150µA
CC
f = 13.56 MHz24.827.530.2pF
= 0.5 V peak.
AC0-AC1
SymbolParameterMin.Max.Unit
T
A
Ambient operating temperature–4085°C
Figure 60 shows an ASK modulated signal, from the VCD to the LRIS64K. The test
condition for the AC/DC parameters are:
●Close coupling condition with tester antenna (1mm)
●LRIS64K performance measured at the tag antenna
Figure 60. LRIS64K synchronous timing, transmit and receive
Doc ID 15336 Rev 1193/100
Part numberingLRIS64K
27 Part numbering
Table 97.Ordering information scheme
Example:LRIS64K - SBN18/ 2
Device type
LRIS64K (long-range tag with 64 Kbit EEPROM)
Package
SBN18 = 180 µm ± 15 µm bumped and sawn wafer on 8-inch frame
Tuning capacitance
2= 27.5 pF
For a list of available options (speed, package, etc.) or for further information on any aspect
of this device, please contact your nearest ST sales office.
94/100Doc ID 15336 Rev 11
LRIS64KAnticollision algorithm
Appendix A Anticollision algorithm
The following pseudocode describes how anticollision could be implemented on the VCD,
using recursivity.
A.1 Algorithm for pulsed slots
function push (mask, address); pushes on private stack
function pop (mask, address); pops from private stack
function pulse_next_pause; generates a power pulse
function store(LRIS64K_UID); stores LRIS64K_UID
function poll_loop (sub_address_size as integer)
pop (mask, address)
mask = address & mask; generates new mask
; send the request
mode = anticollision
send_Request (Request_cmd, mode, mask length, mask value)
for sub_address = 0 to (2^sub_address_size - 1)
pulse_next_pause
if no_collision_is_detected ; LRIS64K is inventoried
then
store (LRIS64K_UID)
else ; remember a collision was detected
push(mask,address)
endif
next sub_address
if stack_not_empty ; if some collisions have been detected and
then ; not yet processed, the function calls itself
poll_loop (sub_address_size); recursively to process the
The cyclic redundancy check (CRC) is calculated on all data contained in a message, from
the start of the flags through to the end of Data. The CRC is used from VCD to LRIS64K and
from LRIS64K to VCD.
To add extra protection against shifting errors, a further transformation on the calculated
CRC is made. The One’s Complement of the calculated CRC is the value attached to the
message for transmission.
To check received messages the 2 CRC bytes are often also included in the re-calculation,
for ease of use. In this case, the expected value for the generated CRC is the residue
F0B8h.
B.2 CRC calculation example
This example in C language illustrates one method of calculating the CRC on a given set of
bytes comprising a message.
C-example to calculate or check the CRC16 according to ISO/IEC 13239
#define NUMBER_OF_BYTES4// Example: 4 data bytes
#define CALC_CRC1
#define CHECK_CRC0
void main()
{
unsigned int current_crc_value;
unsigned char array_of_databytes[NUMBER_OF_BYTES + 2] = {1, 2, 3,
4, 0x91, 0x39};
int number_of_databytes = NUMBER_OF_BYTES;
int calculate_or_check_crc;
int i, j;
calculate_or_check_crc = CALC_CRC;
// calculate_or_check_crc = CHECK_CRC;// This could be an other
example
if (calculate_or_check_crc == CALC_CRC)
{
if (calculate_or_check_crc == CALC_CRC)
{
current_crc_value = ~current_crc_value;
printf ("Generated CRC is 0x%04X\n", current_crc_value);
// current_crc_value is now ready to be appended to the data
stream
// (first LSByte, then MSByte)
}
else // check CRC
{
if (current_crc_value == CHECK_VALUE)
{
printf ("Checked CRC is ok (0x%04X)\n",
current_crc_value);
}
else
{
printf ("Checked CRC is NOT ok (0x%04X)\n",
current_crc_value);
}
}
}
Doc ID 15336 Rev 1197/100
Application family identifier (AFI)LRIS64K
Appendix C Application family identifier (AFI)
The AFI (application family identifier) represents the type of application targeted by the VCD
and is used to extract from all the LRIS64K present only the LRIS64K meeting the required
application criteria.
It is programmed by the LRIS64K issuer (the purchaser of the LRIS64K). Once locked, it
cannot be modified.
The most significant nibble of the AFI is used to code one specific or all application families,
as defined in Ta b le 9 9 .
The least significant nibble of the AFI is used to code one specific or all application
subfamilies. Subfamily codes different from 0 are proprietary.
Table 99.AFI coding
(1)
AFI
Most
significant
nibble
‘0’‘0’All families and subfamilies No applicative preselection
‘X’'0'All subfamilies of family X Wide applicative preselection
'X'‘Y’Only the Yth subfamily of family X
‘0’ ‘Y’Proprietary subfamily Y only
‘1'‘0’, ‘Y’Transport Mass transit, bus, airline, etc.
'2'‘0’, ‘Y’FinancialIEP, banking, retail, etc.
'3'‘0’, ‘Y’IdentificationAccess control, etc.
'4'‘0’, ‘Y’TelecommunicationPublic telephony, GSM, etc.
‘5’‘0’, ‘Y’Medical
'6'‘0’, ‘Y’MultimediaInternet services, etc.
'7'‘0’, ‘Y’Gaming
8'‘0’, ‘Y’Data storagePortable files, etc.
'9'‘0’, ‘Y’Item management
'A'‘0’, ‘Y’Express parcels
'B'‘0’, ‘Y’Postal services
'C'‘0’, ‘Y’Airline bags
AFI
Least
significant
nibble
Meaning
VICCs respond from
Examples / Note
'D'‘0’, ‘Y’RFU
'E'‘0’, ‘Y’RFU
‘F’‘0’, ‘Y’RFU
1. X = '1' to 'F', Y = '1' to 'F'
98/100Doc ID 15336 Rev 11
LRIS64KRevision history
Revision history
Table 100. Document revision history
DateRevisionChanges
26-Jan-20091Initial release.
05-Feb-20092TSSOP8 package removed. Wafer silhouette added on page 1.
13-Feb-20093Device programming time corrected.
02-Apr-20094
16-Jul-20095
17-Sep-20096V
25-Aug-20107
05-Oct-20108
08-Nov-20109Updated document status from preliminary status to public.
Document status promoted from Target specification to Preliminary
data.
modified in Table 93: Absolute maximum ratings.
V
ESD
modified in Table 93: Absolute maximum ratings.
ESD
Updated Features on page 1.
Removed all references to packages.
Removed Figure 2: UFDFPN8 connections.
Updated Section 4: Initial delivery state on page 18.
Updated Figure 3, Figure 4, Ta ble 9 4 , and Tabl e 9 5.
Updated storage time (t
) in Table 93: Absolute maximum ratings
STG
on page 91.
Document classification changed to public.
Updated DSFID value in Section 4: Initial delivery state
19-Sep-201110
Modified Section 1: Description
Updated disclaimer on last page.
27-Oct-201111Updated footnote
(2)
of Table 94: RF AC characteristics.
Doc ID 15336 Rev 1199/100
LRIS64K
Please Read Carefully:
Information in this document is provided solely in connection with ST products. STMicroelectronics NV and its subsidiaries (“ST”) reserve the
right to make changes, corrections, modifications or improvements, to this document, and the products and services described herein at any
time, without notice.
All ST products are sold pursuant to ST’s terms and conditions of sale.
Purchasers are solely responsible for the choice, selection and use of the ST products and services described herein, and ST assumes no
liability whatsoever relating to the choice, selection or use of the ST products and services described herein.
No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted under this document. If any part of this
document refers to any third party products or services it shall not be deemed a license grant by ST for the use of such third party products
or services, or any intellectual property contained therein or considered as a warranty covering the use in any manner whatsoever of such
third party products or services or any intellectual property contained therein.
UNLESS OTHERWISE SET FORTH IN ST’S TERMS AND CONDITIONS OF SALE ST DISCLAIMS ANY EXPRESS OR IMPLIED
WARRANTY WITH RESPECT TO THE USE AND/OR SALE OF ST PRODUCTS INCLUDING WITHOUT LIMITATION IMPLIED
WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE (AND THEIR EQUIVALENTS UNDER THE LAWS
OF ANY JURISDICTION), OR INFRINGEMENT OF ANY PATENT, COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT.
UNLESS EXPRESSLY APPROVED IN WRITING BY TWO AUTHORIZED ST REPRESENTATIVES, ST PRODUCTS ARE NOT
RECOMMENDED, AUTHORIZED OR WARRANTED FOR USE IN MILITARY, AIR CRAFT, SPACE, LIFE SAVING, OR LIFE SUSTAINING
APPLICATIONS, NOR IN PRODUCTS OR SYSTEMS WHERE FAILURE OR MALFUNCTION MAY RESULT IN PERSONAL INJURY,
DEATH, OR SEVERE PROPERTY OR ENVIRONMENTAL DAMAGE. ST PRODUCTS WHICH ARE NOT SPECIFIED AS "AUTOMOTIVE
GRADE" MAY ONLY BE USED IN AUTOMOTIVE APPLICATIONS AT USER’S OWN RISK.
Resale of ST products with provisions different from the statements and/or technical features set forth in this document shall immediately void
any warranty granted by ST for the ST product or service described herein and shall not create or extend in any manner whatsoever, any
liability of ST.
ST and the ST logo are trademarks or registered trademarks of ST in various countries.
Information in this document supersedes and replaces all information previously supplied.
The ST logo is a registered trademark of STMicroelectronics. All other names are the property of their respective owners.